APPROVED BLD2024-0032+Mechanical_Plan+1.8.2024_12.26.27_PM+3988196
0 (4m) C410.2.2 Refrigerated display cases. Site -assembled or site -constructed refrigerated display cases shall comply with the following- QFC 851 EDMONDS MINOR REMODE 1 Lighting and glass doors in refrigerated display cases shall be controlled by one of the following: V 1.1. Time switch controls to turn off lights during nonbusiness hours. Timed overrides for display cases • F* shall turn the lights on for up to 1 hour and shall automatically time out to turn the lights off. 1.2. Motion sensor controls on each display case section that reduce lighting power by at least 50 percent within 3 minutes after the area within the sensor range is vacated. 2 Low -temperature display cases shall incorporate temperature -based defrost termination control with a time -limit default. The defrost cycle shall terminate first on an upper temperature limit breach and22828 1 OOTH AVE W (� second upon a time limit breach. PROJECT DATA 3 Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the 1. JURISDICTION: CITY OF EDMONDS relative humidity in the air outside the door or to the condensation on the inner glass pane. 2. PARCEL NUMBER: 00610600300201 EDMONDS, WA 98020 3. TENANT NAME: QFC 4. PRESENT USE: GROCERY STORE 5. LEGAL DESCRIPTION: WESTGATE PARK DIV 1 BLK 003 D-01 LOTS 2, 3, 4 & 6 LESS E 1 OFT OF LOTS 4 & 6 FOR CITY ST PER QCD41/616 & LESS ST HWY SR 104 ST HWY 1 TH IS 2OOFT WLY ALG SD R/W FR SE COR SD LOT 2 TH ELY ALG SD R/W TO POB LESS S/HY SCOPE OF WORK IMF — rill. A It _ R MIN '' or -�,r � ,f 4 �'� 'i •o'r! 3'. `�� e�*"may rJ ! .� '+f�`1 � +1 WIVE, 9 t _ �t4 OP N A SATELLITE MAP RO"0 NOT TO SCALE Q" 15th St SW 3 m Edmonds -Westgate .'eterinary Hospital PS N t --� 0 Gi zze,h Pi Svr 226th PI SW `g T, n, Ec:moncs memorial © emetery _ - - _ - - - - -..,, , _ p•. Rosewood Courteg 0 2270, PI SW o N _ MTh a Sunrise t06 of Edmonds Q � D 227th PI SW D D L o• 7 a `n St SW - 0 Belle 8aoiI v ces __, Great Clips 3 IR Grear Cops€ Q r Pagliaccu Pizza 9e� 2281h PI SW _ o PCC Community Markets T Edmonds Co-op - f McDonald's Q .� Fc.-tl•S o Walgreens Pharmacy ® 6 fli Save"walg'e _ Certainty" o Thrive ® as Kids Dentistry - n --, Westgate Substation I Sherwood Elementary School ° Ono Authentic Hawaiian Poke ® Tropical Tan n° Edm ^ds ;s Bucatini Pony Mailbox & Business Center > —=232ndiP.ISW,= -- — - 232K&Pl sw — OThe Trike Stop- Child Care and Preschool =t st 5vr 3 i Google o; , P N B VICINITY MAP RO"0 NOT TO SCALE 1. REFRIGERATION EQUIPMENT INSTALL 1.1. INSTALL (24) REFRIGERATED CASES 1.2. INSTALL CONDENSATE CASE DRAINS TO EXISTING CONDENSATE DRAINS 1.3. COORDINATE WITH GC ELECTRICAL CONTRACTOR, FOR HOOK UP OF REFRIGERATION EQUIPMENT DRAWING INDEX R0.0 TITLE SHEET R1.0 FLOOR PLAN R2.0 EQUIPMENT SCHEDULE R6.0 CUT SHEETS 1 R6.1 CUT SHEETS 2 R6.2 CUT SHEETS 3 R6.3 CUT SHEETS 4 R6.4 CUT SHEETS 5 PROJECT NOTES Separate Plumbing Permit Required. Please apply via MyBuildingPermit.com All New Cases shall be anchored to prevent seismic displacement. City Of Edmonds Building Department Work MECHANICAL Address 22828 100TH AVE W Owner--------------------QFC_ Approved Date 01 M/2024 Building Official Erg Permit Number BLD2024-0032 ALL WORK SHALL COMPLY WITH THE 2018 WASHINGTON STATE ENERGY CODE AND THE 2018 INTERNATIONAL MECHANICAL CODE INCLUDING ALL AMENDMENTS MADE BY THE STATE OF WASHINGTON AND THE CITY OF EDMONDS SITE PLAN SCALE: 1 /64" = V-0" ALL WORK SUBJECT FIELD INSPECTION FOR N STAMP: m Cn = N Z) O O00 U) M Z W O Z � W > Z_ Q = = 07 � >a O c") Z � W V__ V REVISIONS 0 DATE DESCRIPTION M RECEIVED Jan 08 2024 v / CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z o O LLI 00 Cj) 11L Q a 0 W a w = O V ) O Cl) W w U 00 O 0 0 a N N W z z O _ cn cn Q o Q� N O cY) w C G 11 r oz 0 N a_ LU 00 N Q o o W Z Lid N �o w �N 9) � oO w� m Lnw00 _z UL �v~ w _cw O zN g -_ w ¢ LP m > U a o Q m N+ Y 011 SHEET NUMBERIN-: R0.0 --l-I TITLE SHEET WATER HEA7B ABOVE COOLER ■ 1 rN 7 1, IN EM I`+Iry 1 I ■I■. ; II.II II,II II.II FIRE SPRINKLER MAIN SPRINKLER VALVE MAIN WATER SHJT OFF EXTERIOR STAQBUCKS ACCESSIBLE ELECTRICAL SHUT OFF IN COMPRESSOR ROOM ABOVE PREP O MEAT COOLER 20'-3 1/2' L 19'-0' W 10,-O" H 104-6" PER 589 SO. FT. o-2 \0V V RECEIVING DOCK PICKLP FREE7J92 PI" 1 (8LF) COOLER EXTENT OF (16LF) MEZZANINE ABOVE I GROCERY DAIRY FREEZER COOLER 12'-0' L 12-2 L 28'-O' W 28'-O' W 10'-O' H 10'-O" H 336 SOPF . 1 341 SO. FfR / 1 7!II m I MEAT PREP T� EBGMB \ 5-DECK SEAFOOD 12' SERVICE SEAFOOD 32 5-DECK FRESH MEAT SEAFOOD 10 �F 4ZEN FOOD MEAT 36' DUAL FRESH MEAT TOTAL:64' TEMP MEAT 16' MDLP FRESH MEAT PwD(°» MIOA-axa MIDA-4%4 � o E-11 E-11 0 � G4 C-12B C-12A 8' 1-D E-11 E-11 'ICE CREAM ECK MOBILE Mks Cz%%LEP MXLEP GROCERY 16' MDLP FRESH MEAT 6' 5-DECK R ® � ® ❑ MIDA-4%4 ❑ � FLORAL O i � PREP O VICE CREAM GROCERY (2 DOORS) DEFROST PANEL, CPC DOOR TO ROC ENCLOSURE, LOADING ELEC PANEL DOCK I G I I — — — J TRANSFORMER k —ELECTRICAL METER MEZZANINE V ICE CREAM GROCERY (2 DOORS) �"- J\ LT'\\ 0 G1 C8 \ 0 \` 0 LTIC \ Jo 0\\ \ 0 0 O J\ co 02 a00\\G2 Cd \ a � -LL8\` \ \Z.\\ O 0 \ G2 3 ♦ C) \ ` LIL AL\. \ G2 C-8 0 0 LD 0 w U U J KR (:REAM GROCERY 2 DOORS) VENDOR COOLER BANKS COLOR LEGEND: ❑ NEW LOCATION OF CASES ❑ RELOCATION OF CASES )R LS 400 LS SFORMER LS .� Ir r■■T- • mint 1611161 0 0 LD 0 w U U J KR (:REAM GROCERY 2 DOORS) VENDOR COOLER BANKS COLOR LEGEND: ❑ NEW LOCATION OF CASES ❑ RELOCATION OF CASES )R LS 400 LS SFORMER LS .� Ir r■■T- • mint 1611161 l I 1 � � � __ 1� ■�1 r1 FLORAL CNECKSTAND 0 TIBULE�j u 00 OUTDO FLORAL 0 LOCKING LIQUOR 36' VESTIBULE 0 111 111 111 111 111 111 111 111 111 111 111 111 111 111 011 • III 0 III DELI COOLER 16'-6 L D3 0-0" W ro0' H 165 SS PER 65O. FT, Key Mechanical 19430 681h Ave South - Kent WA 98032 phone: 253.872.7392 fax: 253.872.7398 01/08/2024 To Whom it May Concern, WA: KEYMEW*240NZ OR: 0093479 CA:813609 NV:0065396 AK: 20901 AZ: ROC298672 The scope for this QFC 851 Edmonds case installs permit application is to install (24) new store provided refrigeration cases and run new refrigeration lines to GC provided floor hubs and sinks. Refrigeration cases are made to meet or exceed energy code requirements in C410.3 of the 2018 WSEC by the manufacturer. The WSEC compliance forms do not seem to be applicable to this project scope. If there are any questions about this application, please email Wayne Cornell, Alexander Thorson and Brandon Canedo at wcornell(a»lceymechanical.com, athorson(a-),keymechanical.com and bcanedoAkeymechanical.com Thank you, Brandon Canedo (206) 809-4928 bcanedo@keymechanical.com WSEC COMPLIANCE NOT TO SCALE KeymechanicaLcom • O W Vco ~ = Z) N O O M V o LJ Z Z W � > Z_ Q = � 00 Q 0 � Z LU d� STAMP: REVISIONS I0 DATE DESCRIPTION RECEIVED Jan 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z o O o C w co Q Ill Q w ~ Cn LO O 0 100 Z L U N � N 0 C� N w O z 0 2 _ U) Cl)w 0 GO Q CN M w CO C O Q N a W W N J LL a 0 C.,00 O 00 Z N -- W � w N u 1 w O LU 0] (� 2, Lo a 2 w U w o v F- UQ O-) z N LU LL_ �� a �o Uw �� LLo Lnm MO �LU > C� O Q m N + Y SHEET NUMBER: R1.0 FLOOR PLAN SCALE: 1/16" = V-0" N FLOOR PLAN Store No.: QFC851 DESIGN AMBIENT: 85 ALTITUDE: 100 DATE F1 DATE KMA: QFC VOLTAGE: 460V BY: KDG 5/12/23 4/27/23 DISTRIBUTED UNIT INFORMATION CASE/COIL ePRO EVAP LOAD CON- TOTAL DEFROST SUCT PERCENT UNIT CKT L W H MODEL DESCRIPTION DEPT STAT ITEM TEMP (MBH) TROL REFRIG LOAD COMPRESSOR HP TEMP CAPACITY THR LOADED #/DAY TYPE D R404A EXISTING DISTRIBUTED UNIT 1 12'-2" 28 10 EXIST COIL(S) COOLER DAIRY EX 26 23.0 Configuration: Vertical 2 589 SQ FT 10 EXIST COIL(S) COOLER MEAT EX 20 33.3 Reclaim: Air 3 1 QTY M5NXEP-12 MEAT EX 26 18.9 Controller: CPC Einstein II RX400; Serving Units 'D' & 'E' 4 2 QTY DD5X ULP-12 (DAIRY) 12' FIVE DECK WITH DOORS DAIRY MOD. 32 7.1 1 OT/TIME Control Voltage: 208V 5 ABANDON Control Valve Voltage: 208V 6 2 QTY ESBDS-8 & SERVICE DELI. EX 20 5.7 2 OT/TEMP Compressor Voltage: 460V 1 QTY ESBDS-12 12' SERVICE DELI. EX 20 4.3 2 OT/TEMP Modify existing distributed unit electric as required to accomplish remodel 7 1 QTY PT-6R-RRS-60-SU & SELF SERVICE W/R.R. STOR. (SUSHI) DELI. EX 24 5.3 6 OT/TIME 8 1 QTY 05DMM(BEV)-6 & MULTIDECK W/ SYNERG-E COIL - 84" HIGH BEV. EX 34 7.0 6 OT/TEMP ZB45KCE 18 51.1 67.8 9 1 QTY IM5SL-6 6' FIVE DECK SEAF. NEW 27 6.3 EVR 4 OT/TIME ZB45KCE 18 51.1 67.8 1 QTY IM5SL-4 4' FIVE DECK SEAF. NEW 27 4.2 4 OT/TIME ZB45KCE 18 51.1 67.8 10 1 QTY DSFM-12 12' SERVICE SEAF. NEW 24 3.6 EVR 3 OT/TIME ZB45KCE 18 51.1 67.8 11 1 QTY ESGMS-12 12' SERVICE MEAT EX 22 3.2 1 OT/TIME ZB45KCE 18 51.1 67.8 12 3 QTY 05DMM-12 12' MULTIDECK W/ SYNERG-E COIL - 84" HIGH PROD. EX 28 49.5 6 OT/TEMP ZB45KCE 18 51.1 67.8 13 442 SQ FT 10 EXIST COIL(S) COOLER PROD. EX 26 27.7 14 2 QTY BLF-59SR SELF SERVICE BAK. NEW 20 11.3 EVR 4 OT/TIME 212.3 306.4 406.7 69.3% 15 1 QTY Q4-BV-05 5' SERVICE CASE BAK. NEW 22 2.0 EVR 3 OT/TIME EXISTING Air Cooled Condenser: HUSSMANN LAVF-22310, 29.54 mbh/deg td capacity, 68 circuits, 13.8 TD Setpoint E R404A EXISTING DISTRIBUTED UNIT 1 3 QTY DD5X ULP-12 (DAIRY) 12' FIVE DECK WITH DOORS DAIRY MOD. 32 10.6 1 OT/TIME Configuration: Vertical 2 1 QTY D5XULEP-12 12' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 17.5 4 OT/TIME Reclaim: Air 1 QTY D5XULEP-8 8' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 11.6 4 OT/TIME Controller: SEE UNIT'D' 3 1 QTY D5XULEP-12 12' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 17.5 4 OT/TIME Control Voltage: 208V 1 QTY D5XULEP-8 8' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 11.6 4 OT/TIME Control Valve Voltage: 208V 4 3 QTY D5XULEP-12 12' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 52.4 4 OT/TIME Compressor Voltage: 460V 5 3 QTY D5XULEP-12 12' FIVE DECK, ULTRA LOW FRONT BEV. EX 26 52.4 4 OT/TIME Modify existing distributed unit electric as required to accomplish remodel 6 3 QTY DD5X ULP-12 (DAIRY) 12' FIVE DECK WITH DOORS DAIRY MOD. 32 10.6 1 OT/TIME 7 1 QTY D5NXLEP-8 8' FIVE DECK, LOW FRONT, NARROW BEV. EX 26 10.9 3 OT/TIME ZB45KCE 24 57.5 74.3 8 1 QTY NFD-3R 3 DOOR WINE MERCHANDISER BEV. EX 45 4.7 0 NONE ZB45KCE 24 57.5 74.3 9 16'-6" 10 10 EXIST COIL(S) COOLER DELI. EX 26 13.3 ZB45KCE 24 57.5 74.3 10 1 QTY Q3-SS-6 SELF SERVICE MULTI -DECK DELI. NEW 20 5.1 EVR 4 OT/TIME ZB45KCE 24 57.5 74.3 1 QTY Q3-SS-8 SELF SERVICE MULTI -DECK DELI. NEW 20 6.8 4 OT/TIME ZB45KCE 24 57.5 74.3 11 4 QTY C2XXLE P-8 8' MULTI -DECK, 55" HIGH BACK, LOW FRONT DE Ll. EX 26 30.0 2 OT/TIM E ZB45KCE 24 57.5 74.3 NEW 12 1 QTY IDD5SL-6 6' FIVE DECK WITH DOORS BEV. NEW 33 1.2 1 OT/TIME 256.3 345.1 445.5 74.2% EXISTING Air Cooled Condenser: HUSSMANN LAVF-22310, 29.61 mbh/deg td capacity, 68 circuits, 15.0 TD Setpoint F R404A EXISTING DISTRIBUTED UNIT 1 2 QTY C2XXLEP-8 8' MULTI -DECK, 55" HIGH BACK, LOW FRONT DELI. EX 26 15.0 2 OT/TIME Configuration: Vertical 2 1 QTY IM-05-C12-R(DELI) 12' UNITIZED MULTI -DECK ISLAND DELI. NEW 26 25.8 EVR 6 OT/TIME Reclaim: Air 2 QTY IM-05-E5(DELI) MULTI -DECK SELF SERVICE END DELI. NEW 26 10.8 6 OT/TIME Controller: SEE RACK 'C' 3 2 QTY IM-05-C8-R(DELI) 8' UNITIZED MULTI -DECK ISLAND DELI. NEW 26 34.4 EVR 6 OT/TIME Control Voltage: 208V 2 QTY IM-05-E5(DELI) MULTI -DECK SELF SERVICE END DELI. NEW 26 10.8 6 OT/TIME Control Valve Voltage: 208V 4 1 QTY IM5SL-12 12' FIVE DECK MEAT NEW 27 12.5 EVR 4 OT/TIME Compressor Voltage: 460V 1 QTY IM5SL-8 8' FIVE DECK MEAT NEW 27 8.4 4 OT/TIME Modify existing distributed unit electric as required to accomplish remodel 5 1 QTY P4XEP-12 12' FIVE DECK PROD. EX 28 14.7 4 OT/TIME 2 QTY P4XEP-8 8' FIVE DECK PROD. EX 28 19.7 4 OT/TIME ZB45KCE 18 51.1 67.8 6 1 QTY ON5DM(FL)-12 12' NARROW MULTIDECK W/ SYNERG-E COIL - 84" HIGH FLOR. EX 34 12.7 2 OT/TEMP ZB45KCE 18 51.1 67.8 7 SPARE ZB45KCE 18 51.1 67.8 8 2 QTY D5XLEP-12 12' FIVE DECK, LOW FRONT DELI. EX 26 30.3 3 OT/TIME ZB45KCE 18 51.1 67.8 1 QTY D5XLEP-8 8' FIVE DECK, LOW FRONT DELI. EX 26 10.1 3 OT/TIME ZB45KCE 18 51.1 67.8 9 2 QTY D5XLEP-12 12' FIVE DECK, LOW FRONT DELI. EX 26 30.3 3 OT/TIME ZB45KCE 18 51.1 67.8 10 1 QTY 05DMM-6 & MULTIDECK W/ SYNERG-E COIL - 84" HIGH PROD. EX 28 8.3 6 OT/TEMP 11 3 QTY P4XEP-12 12' FIVE DECK PROD. EX 28 44.2 4 OT/TIME 290.5 306.4 406.7 94.8% NEW 12 1 QTY IM-04-E4-FR MURRAY'S 4 FT FOOD COUNTER (3 WELLS) DELI NEW 20 2.6 EVR 6 OT/TIME EXISTING Air Cooled Condenser: HUSSMANN LAVF-22310, 29.54 mbh/deg td capacity, 68 circuits, 13.8 TD Setpoint PARALLEL RACK INFORMATION CASE/COIL ePRO EVAP LOAD CON- TOTAL DEFROST SUCT PERCENT RACK CKT L W H MODEL DESCRIPTION DEPT STAT ITEM TEMP (MBH) TROL REFRIG LOAD COMPRESSOR HP TEMP CAPACITY THR LOADED #/DAY TYPE C R404A EXISTING DISTRIBUTED UNIT 1 1 QTY RLNI(LT-G-LED)-5 5 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 4.9 1 GAS/TIME Configuration: Vertical 1 QTY RLNI(LT-G-LED)-4 4 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 3.9 1 GAS/TIME Reclaim: Water 2 3 QTY RLNI(LT-G-LED)-5 5 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 14.6 1 GAS/TIME Controller: CPC Einstein II RX400; Serving Rack 'C' & Unit'F' 3 12 28 10 EXIST COIL(S) FREEZER GROC. EX -22 27.1 GAS/TIME Control Voltage: 208V 4 1 QTY FWG(DT-G)-12 12' WIDE ISLAND, DUAL TEMP, W/G MEAT EX -20 7.3 1 GAS/TIME Control Valve Voltage: 208V 1 QTY FWEG(DT-G) WIDE ISLAND END, DUAL TEMP, W/G MEAT EX -20 2.5 1 GAS/TIME Compressor Voltage: 460V 1 QTY FWEG(DT-G) WIDE ISLAND END, DUAL TEMP, W/G MEAT NEW -20 2.5 EVR 1 GAS/TIME 5 3 QTY RLNI(LT-G-LED)-5 5 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 14.6 1 GAS/TIME Modify existing distributed unit electric as required to accomplish remodel 6 1 QTY RLNI(LT-G-LED)-5 5 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 4.9 1 GAS/TIME 1 QTY RLNI(LT-G-LED)-4 4 DOOR G.D., LOW TEMP, NARROW, BACK-TO-BACK GROC. EX -11 3.9 1 GAS/TIME 2DF 3 -25 18.3 29.5 7 2 QTY RLN(IC-G-LED)-5 5 DOOR G.D., ICE CREAM TEMP, NARROW GROC. EX -19 11.6 1 GAS/TIME 3DB 7.5 -25 36.1 56.8 2 QTY RLN(IC-G-LED)-2 2 DOOR G.D., ICE CREAM TEMP, NARROW GROC. EX -19 4.6 1 GAS/TIME 4DA 10 -25 51.8 81.5 8 2 QTY RLN(IC-G-LED)-5 5 DOOR G.D., ICE CREAM TEMP, NARROW GROC. EX -19 11.6 1 GAS/TIME 4DL 15 -25 69.1 108.1 1 QTY RLN(IC-G-LED)-4 4 DOOR G.D., ICE CREAM TEMP, NARROW GROC. EX -19 4.7 1 GAS/TIME 2 QTY RLN(IC-G-LED)-2 2 DOOR G.D., ICE CREAM TEMP, NARROW GROC. EX -19 4.6 1 GAS/TIME 134.9 175.2 275.9 77.0% 9 1 QTY RLN(IC-G-LED)-2 2 DOOR G.D., ICE CREAM TEMP, NARROW BAK. EX -19 2.3 1 GAS/TIME 10 SPARE EXISTING Air Cooled Condenser: 11 SPARE HUSSMANN LAVF-22310, 29.61 mbh/deg td capacity, 68 circuits, 9.3 TD Setpoint 12A 1 QTY FWEG(DT-G) WIDE ISLAND END, DUAL TEMP, W/G MEAT EX -20 2.5 1 GAS/TIME 12B 1 QTY FWEG(DT-G) WIDE ISLAND END, DUAL TEMP, W/G MEAT EX -20 2.5 1 GAS/TIME 13 1 QTY RLN(LT-G-LED)-4 4 DOOR G.D., LOW TEMP, NARROW SEAF. EX -11 4.4 1 GAS/TIME • LU V ~ U) = Z) N O O 00 V o LLJ Z Z LLJ � > Z00 Q = � Q O � Z LU a7 STAMP: REVISIONS 0 DATE DESCRIPTION P _ RECEIVED Jan 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z o O U LLJ 00 Lu 0 Q Q 0 L L1 �j a w � = ~ C/ � Z LU U �� � � � a N N LLJ O z_ 2i w W z LU LU O� Q o rn O c'') w C G � Z O Q N a W LU 0oQ r LL (V Q C)w Q Q' U Z Lf) OO Z N � w LU C) N i m CY) Lf ) x U U o� w U LU Q U LL � co_ > LU Y 0a 0� Q� m0 No + SHEET NUMBER: R2.0 __/ EQUIPMENT SCHEDULE Hussmwnn° H,Xcel (Z FWEG Technical Data Sheet P/N 0465903_J NSF® Certified March 2017 Item Part # Description Wiring Item # Item Part # Description Wiring Item # FAN ASSEMBLIES, AND THERMOSTATS HEATERS A. 4W Standard Energy Efficient Fan Assembly (1) E. 208V Evaporator Defrost Heaters (5) 0477653 Fan Motor, Evaporator 3016522 End case (HE.4850620) (MO.4410544) 0464847 Fan Blade (FB.4780649) F. 208V Drip Pan Defrost Heaters, Electric (6) 0444300 End case (HE.4850609) B. Optional Adjustable Refrigeration Thermostat (2) 120V Drip Pan Defrost Heaters, Koolgas (7) C. 0398557 Defrost Termination Thermostat (3) 0465906 End case (HE.4850628) (Electric Defrost only) (CT.4440611) G. Nosing Anti -sweat Heaters (8) 0495006 End case (HE.4850684) D. 0481370 Heater Switch (4) (Koolgas Defrost only) H. Return Grille Anti -sweat Heaters (9) (CT.4440738) 0495010 End case (HE.4850688) I. Return Glass Anti -sweat Heaters (10) 0474775 End case, Front (GL.4977903) 0474776 End case, Left Side (GL.4978388) 0474777 End case, Right Side (GL.4977997) Data she-F.xcel FW .G Note: Revision J: Added high glide refrigerant note. Other changes marked by bar, underline or circle. ©2017 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 • WWW.HUSSMANN.COM Spanish P/N 0538927 Excel F W E G Low / Medium Temperature Electrical Data Number of Fans - 4W Evaporator Standard End 1 Optional Equipment Amperes Watts Amperes Watts End End End End Evaporator Fans 120V 50/60Hz Standard Energy Efficient 0.12 8 230V 50/6011z Standard Energy Efficient 0.06 8 230V 60Hz Export 0.15 24 230V 50Hz Export 0.18 27 Anti -sweat Heaters (on fan circuit) 120V 50/60Hz Standard 0.65 78 230V 50/60Hz Export 0.34 78 Joining Kit Anti -sweat Heaters 120V 50/6011z Standard 0.40 48 230V 50/6011z Export 0.21 48 Minimum Circuit Ampacity 120V 50/60Hz Standard Energy Efficient 0.97 1.37 230V 50/60Hz Standard Energy Efficient 0.60 0.81 230V 6011z Export 0.69 0.90 230V 5011z Export 0.72 0.93 Maximum Over Current Protection 120V 20 20 Maximum Over Current Protection 230V 15 15 Return Glass Anti -sweat Heaters 120V 50/6011z Standard 0.13 16 230V 50/6011z Export 0.07 16 208V Electric Defrost 6.54 1360 230V Export Electric Defrost 5.91 1360 120V Koolgas Defrost 1.33 160 208V Koolgas Defrost 0.77 160 230V Koolgas Defrost 0.85 196 Standard Lighting None 4 of 7 HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A. I FWEG Technical Data Sheet Engineering Plan Views Low / Medium Temperature Wide Island End Case 10-2004 -4 80 % (2048) 11 % (283) 8'/2 (217) -1 49 7/e (1267) PHYSICAL DATA Merchandiser Drip Pipe (in.) 1 1/4 Merchandiser Liquid Line (in.) 3/8 Merchandiser Suction Line (in.) 5/8 Dimensions shown as Inches & (mm). 18 'Y2 (470) 4'/4 (108) H 8'/2 (217) 10 % AP T 26 '/4 I 24 Refrigeration I (2t) (665) r Outlet I r -1 - - - 30 '/4 (612) lL Jl I Electrical I (767) Waste I Stub Up Area I a Outlet I 6 x 16 I 4 /4 31 /a (152 x 406) I (120) (804) 33'/2 - - Electrical I (851) Field Concection Wirewa Splashguard Y j Waste I Outlet 26'% FRONT 15'/2 (673) � (393) 52 % (1330) a 65 (1653) 69 (1755) General Case Length - Outside Inside Length Maximum O/S dimension of case back to front (includes bumper) Back of case to front of splashguard Back of case to O/S edge of front leg Distance between edges of external legs and center legs Distance between edges of center legs Distance between front legs and splashguard Electrical Service ® (Electrical Field Wiring connection point) RH End of case to center of stub up area Back of case to center of stub up area Length of electrical wireway I Wireway RH End of case to LH end of wireway Waste Outlets (One each end) El RH End of case to the center of LH waste outlet RH End of case to the center of RH waste outlet Back O/S of case to center of waste outlets Schedule 40 PVC drip pipe Refrigeration Outlet 0 Back of case to center of refrigeration outlet RH end of case to center of refrigeration outlet 42 (1064) 1 End Case 80 5/8 (2048) 73 5/8 (1870) 42 (1064) 33 1/2 (851) 301/4 (767) 48 1/2(1234) NA 31/s (82) 52 3/8 (1653) 24 (612) 261h (673) 69 (1755) 65 (1653) 151h (393) 31 5/8 (804) 1 1/4 (32) 26 1/4 (665) 18 1/2 (470) I 2 of 7 HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A. FWEG Technical Data Sheet Excel FW E G Low /Medium Temperature Product Data Recommended Usable Cube 1(Cu Ft/Ft) 3.69 ft3 /ft (0.34 m3 /m) AHRI Total Display Area 2 (Sq FtIFt) 3.34 ft2 /ft (1.02 m2 /m) Shelf Area 3 (Sq FtlFt) 2.79 ft2 /ft (0.85 m2 /m) 1 AHRI Refrigerated Volume less shelving and other unusable space: Refrigerated Volume/Unit of Length, ft3/ft [m3/m] 2 Computed using AHRI 1200 standard methodology: Total Display Area, ft2 [m2]/Unit of Length, ft [m] 3 Shelf surface area is composed of bottom deck plus standard shelf complement, as shown in the Hussmann Product Reference Guide. The standard shelf complement for this model is NONE. ESTIMATED SHIPPING WEIGHT 4 Can End lb (kg) NA (NA) NA (NA) NA (NA) NA (NA) NA (NA) 500 (227) 4 Actual weights will vary according to optional kits included. P/N 0465903 J HUSSMANN CORPORATION • BRIDGETON MO 63044-2483 U.S.A. • WWWAUSSMANN.COM 5 of 7 Single Level End Display with Glass Front Excel FW E G roe 2017 Hussmann refrigerated merchandisers configured for sale for use in the United States Energy Efficiency Low / Medium Temperature Compliant meet or surpass the requirements of the DOE 2017 energy efficiency standards. REFRIGERATION DATA*§ Note: This data is based on store temperature and humidity that does not exceed 75*F and 551/6 R.H. MED FF IC Discharge Air (OF) +24 -12= 22 Evaporator (OF) +19 -20= 30 Unit Sizing (OF) +17 -23 33 Dimensions shown as Inches & (mm). F W E G Btu/hrlcase MED FF IC Parallel 1555 2505 2675 Conventional 1625 2615 2795 35 % 9 vs *Dual temperature operation kits are not suitable for (910) (251) 35 '/4 ice cream temperature applications. (893) � 1 15 %a § Average evaporator temperature shown. Use dew T(404) point for high glide refrigerants for unit sizing. Care 24 % a (848) should be taken to use the dew point in PT tables (618) for measuring and adjusting superheat. Adjust Li evaporator pressure as needed to maintain discharge 3 % Fan Coil air temperature shown. (79) 5 '/2 (140) Case -to -Case Y 26'/4 (ss5) Connection 19 %a (503) Refrigeration Outlet 31 a/e (804) 33 %z (851) 42 (1064) Estimated Charge *** End 1.5 lb 24 oz 0.7 kg ***This is an average for all refrigerant types. Actual refrigerant charge may vary by approximately half a pound (8 oz/0.2 kg). Length Added to Lineup: 42 (1064) This End Case is used in place of an End Assembly. Partitions do not apply. NSF Certification This merchandiser model is manufactured to meet NSF/ANSI (National Sanitation Foundation) Standard #7 requirements for construction, materials & cleanability. DEFROST DATA MED FF IC Frequency(hr) 24 24 24 Defrost Water (lb/case/day) 6.6 6.3 5.4 (± 15% based on case configuration and product loading). ELECTRIC MED FF 1C Temp Term (*F) 48 48 48 Failsafe (minutes) 60 60 60 GAS Duration (minutes) NA 15 18 OFFTIME Not Recommended Standard Defrost Thermostat Close on rise: close 48°F - open 33°F CONVENTIONAL CONTROLS Low Pressure Backup Control - Cl/CO MED +22°F / +10°F FF -17OF / 29°F IC 27°F /-39°F Indoor Unit Only, Pressure Defrost Termination* Not Recommended **Use a Temperature Pressure Chart to determine PSIG conversions. P/N 0465903 J HUSSMANN CORPORATION • BRIDGETON MO 63044-2483 U.S.A. a WWW.HUSSMANN.COM 3 of 7 Electric Defrost - Standard 120V Neutral 1 AA e� Brown Band GV Y� O O O I Fan Nosing Return Grille Anti -Sweat Anti -Sweat Heater Heater Refrigeration Thermostat (Optional) 0 Light Blue To L - - - - - Condensing Unit Defrost Termination Thermostat O Dark Blue To } Condensing Unit L1 oO 208V Power From Defrost Contactors ► L2 I I O I �- Red Red Drip Pan Heater 0 Electric Defrost Heaters Return Class Anti -Sweat Heater 10 Purple White #--��PurleWhite 120V 120V Power Neutral WARNING All components must have mechanical ground, and the merchandiser must be grounded. Circled Number = Parts List Item Numbers 6 of 7 HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A. FWEG Technical Data Sheet 0 (40) m LU F____ 7) = N O �O 00 v) 0) LU z 50 Z � LLI >z Q = 2 () 00 CO Z STAMP: REVISIONS DATE DESCRIPTION RECEIVED Jan 08 2024 U) CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z O O cn W Q Q Q 0 W Q W = ~ i) O 0 U) Z W04 U 00O 0 LL oo 0 C� N N LU O Z_ 2 W U) Z LU LU 0 a Z co rn O M w rl� o Q N a W J w N a � oo Z Lr) OO CD Z N ~ 00 W 0 N O � m co _ U W o� CC CO UQ � if) z N U LU L.Lo UwLL I{)m _> LU 0 d 60 Q� m� N� + Y SHEET NUMBER: R&0 CUT SHEETS 1 Insight I M 5S L Meat & Delicatessen Refrigeration Data 1 IM5SL Optimal Shelf Life Energy Comparison Application Meat NSF Type 2 AHRI 1200 Ambient' Rating Points Discharge Air °F (°C) 32 (0) 31 (-0.55) 33 (0.55) Unlit Average Evaporator °F (°C) 2,1 28 (-2.22) 27 (-2.77) 29 (-1.66) Shelves Parallel Btu/hr/ft (Watts/m) 6 1030 (990) 1345 (1294) 965 (928) Conventional Btu/hr/ft (Watts/m) 6 1125 (1082) 1470 (1414) 1055 (1014) Discharge Air °F (°C) 31 (-0.55) 30 (-1.11) 32 (0) Lit Average Evaporator °F (°C) 2,3 27 (-2.77) 26 (-3.33) 28 (-2.22) Shelves Parallel Btu/hr/ft (Watts/m) 6,7 1045 (1005) 1365 (1313) 980 (942) Conventional Btu/hr/ft (Watts/m) 6•' 1140 (1096) 1490 (1433) 1070 (1029) IM5SL6 (8.25") 14008 16008 14008 Fan Speed" IM5SL4, 8, 12 (10.3") 1050 13008 1050 Notes: 1. All data based on store temperature and humidity that does not exceed NSF Type 1 ambient conditions of 75°F and 55 % relative humidity except where noted. 2. Average evaporator temperature shown. Use dew point for high glide refrigerants for unit sizing. Care should be taken to use the dew point in PT tables for measuring and adjusting superheat. Adjust evaporator pressure as needed to maintain discharge air temperature shown. 3. For DX CO2 applications the average evaporator temperature may be lowered b 2°F but not more than 5°F. An EPR valve should be used if the system suction temperature PP 9 P P Y Y Y P is more than 5 degrees below the published case evaporator temperature. A 31 °F flash tank temperature with a 24°F evaporator temperature is used when sizing default EEV selections to provide a minimum pressure drop across the valve of approximately 50 psig. For operating conditions that provide a pressure drop across the valve above 65 psig or below 35 psig, the electronic expansion valve size should be determined using the valve vendor sizing program and selected from the pull down list in the Hussman Product Configurator (HPC). 4. Data for operation in NSF Type 2 ambient of 80°F and 55 % relative humidity. 5. AHRI 1200 Rating Point for energy consumption comparison only. 6. Subtract 120 Btu/hr/ft (115.4 Watts/m) for front glass (on applicable models). 7. Add 10 Btu/hr/ft (9.6 Watts/m) per shelf row for LED shelf light fixtures. 8. Some lengths and/or applications require optional fan motor kits applied by the Hussmann Product Configurator (HPC). Defrost Data Conventional Controls Estimated Charge " IM5SL OFFTIME IM5SL IM5SL 4 ft 0.6 lb 10 oz 0.3 kg Time (minutes) 20 Low Pressure Backup 6 ft 1.1 lb 18 oz 0.5 kg Control Cl/CO 10 8 ft 1.5 lb 24 oz 0.7 kg ELECTRIC OR GAS Not Available 20°F / 10°F -6.67°C /-12.2°C 12 ft 2.9 lb 46 oz 1.3 kg Frequency (hours between defrost) 4 Defrost Water (lb/ft/day) 9 7.8 lb/ft/day Indoor Unit Only, 1 This is an average for all refrigerant (11.6 kg/m) Pressure Defrost types. Actual refrigerant charge may vary by Termination 10 approximately half a pound. 9 (± 15% based on case configuration and product 10 48°F (8.89°C) loading). Use a Temperature Pressure Chart to determine PSG conversions. vroauci uata Gross Refrigerated Volume 12 (Cu FtlFt) 8.9 ft8/ft (0.83 m4nn) AHRI Total Display Area 13(Sq Ft/Ft) 3.97 ftz /ft (1.21 mom) Shelf Area 14 (Sq FtlFt) 8.35 ftZ /ft (2.54 mom) 12 AHRI Gross Refrigerated Volume: Refrigerated Volume/Unit of Length, ft3/ft [m3/m] 18 Computed using AHRI 1200 standard methodology: Total Display Area, ft2 [m2]/Unit of Length, ft [m] 14 Shelf surface area is composed of bottom deck plus standard shelf complement for this model: (4) rows of shelves: 14-in., 16-in., 18-in., 18-in. 2 Of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IM5SL Merchandiser Data Sheet Insight IM5SL Meat & Delicatessen Electrical Data Number of Fans 4 ft 6 ft 8 ft 12 ft 8.25-in. - 2 - - 10.3-in. 1 - 2 3 Amperes Watts Evaporator Fan 4 ft 6 ft 8 ft 12 ft 4 ft 6 ft 8 ft 12 ft 120V 601-lz Energy Efficient 0.40 0.60 0.80 1.20 24 36 48 72 230V 50/60Hz Energy Efficient 0.21 0.31 0.42 0.62 24 36 48 72 Minimum Circuit Ampacity 120V 601-lz Energy Efficient 0.60 0.80 1.00 1.40 230V 50/601-lz Energy Efficient 0.41 0.51 0.62 0.82 Maximum Over Current Protection 120V 20 20 20 20 Maximum Over Current Protection 230V 15 15 15 15 Lighting ONLY LIGHTING CONFIGURATIONS THAT ARE COMPLIANT WITH THE U.S. DEPT. OF ENERGY (DOE) 2017 REGULATION ARE AVAILABLE FOR SALE FOR USE IN THE U.S.A. Amperes Watts 4ft 6ft 8ft 12ft 4ft 6ft 8ft 12 ft STANDARD LED LIGHTING LED Canopy Lights 1 Row 0.16 0.22 0.31 0.47 19 27 38 57 OPTIONAL LED LIGHTING 2 Rows of Canopy Lights 0.32 0.44 0.62 0.94 38 54 76 114 LED SHELF LIGHTING 1 Row of Shelves 0.06 0.07 0.11 0.17 7 9 13 20 2 Rows of Shelves 0.11 0.15 0.22 0.33 13 18 27 40 3 Rows of Shelves 0.17 0.22 0.33 0.50 20 27 40 60 4 Rows of Shelves 0.22 0.30 0.44 0.67 27 36 53 80 5 Rows of Shelves 0.28 0.37 0.56 0.83 33 44 67 100 LED Rail Light 1 Row 0.06 0.07 0.11 0.17 7 9 13 20 120V Lighting Circuit Total = Standard Lighting + Total Optional Lighting + Optional Shelf Lighting 230V Lighting Circuit Total = Multiply 120V Lighting Circuit Total by 0.52 P/N 0535983 L HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 5of10 Insight Multideck Merchandiser, 5 Display Levels, Insight IM5SL Standard Bottom, Low Height Front Meat &Delicatessen DOE 2017 Hussmann refrigerated merchandisers configured for sale for use in the United States Energy Efficiency Compliant meet or surpass the requirements of the DOE 2017 energy efficiency standards. There is a mimimum of 1.5-in. clearance required to remove the raceway cover, 6.5 ft for full Dimensions shown as in. and (mm). access. See Installation manual for instructions. A -in hatwaan hark to hank r_asas IM5$L 1 1/2 In. (38 mm) Shelf complement shown as tested: Four rows of shelves (14-in., 16-in., 18- in.,18-in.), spacing between each row of shelves is 9-in., all down -tilted at 15' with a 12-in. mirror installed in the top, rear corner of the case. 91/4 (235) 36 112 (927) Required Air Gap Other optional kits (for example, top piping and vent fans) add to the i overall case height. 47114 (1200) Shown with Ellipse Option Canopy 797/8 i I (2028) and Bumper. Ft OPTIONAL RAIL LIGHT 21 I � 51718 (1318) (s2i) c W O A I L 301/8 L L / (765) 22314 (s7e) 18 314 Srl8n (476) 4 3/8 Rail light cannot be used j with glass front option. OPTIONAL GLASS FRONT 29 I (737) 33112 (8 1) (851) 7 1/4 (184) 35 s/8 (905) 43 s/e (1108) NSF Certification This merchandiser model is manufactured to meet NSF/ANSI (National Sanitation Glass front cannot be used Foundation) Standard #7 requirements for with rail light option. construction, materials and cleanability. P/N 0535983 L HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 3 of 10 Insight 1 M 5S L Meat & Delicatessen ENDS or PARTITIONS PHYSICAL DATA Each standard end and each insulated partition Merchandiser Drip Pipe (in.) 1 1/4 adds 1 112 in. (38 mm) to case line up. Optional Schedule 40 PVC view end with end bumper adds 3 3/4 in. (95 mm). Merchandiser Liquid Line (in.) 3/8 Merchandiser Suction Line (in.) 1/8 ESTIMATED SHIPPING WEIGHT t Case Solid End 4 ft 6 ft 8 ft 12 ft (each) I (kg) 700 (318) 850 (386) 950 (431) 1200 (544) 70 (32) t Actual weights will vary according to optional kits included. Shelf Options Approved shelf sizes for standard (horizontal, 2-3 position brackets) displays: 14-inch 16-inch 18-inch 20-inch 22-inch Contact engineering for non-standard (4 position brackets or other) display recommendations. Minimum number of Shelves: 3 Optimal number of Shelves: 4 Maximum number of Shelves: 6 Maximum number of Lighted Shelves: 5 Standard shelf complement for test purposes: (4) rows of shelves (14-in., 16-in., 18-in., 18-in.), all down -tilted at 150 with a 12-in. mirror, spacing between each row of shelves is 9-in. 6 of 1 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IM5SL Merchandiser Data Sheet Engineering Plan View IM3SL/IM4SL/ IM5SL/IP2SL/ INSL A G - 1 112 Inch F mm) 7 _I 7 Required Re ( 178 (178 Air Gap 13 I B =I I C ---------------1 I� (330) ID I I Refrigeration 8112 = Outlet (216) Field Electrical Waste Outlet I Connection voreway in can J n J at TOP-----------------�'--------- of Case D E FRONT (12 Foot Model shown above) Dimensions shown as in. and (mm). 3 518 (92) BSI 35 s/8 43 5/8 (29) 33112 (905) (1108) Refrigeration (851) 361/2 Outlet- ! I (927) General 4 ft 6 ft 8 ft 12 ft (A) Case Length (without ends or partitions) (Each end and insulated 481/8(1222) 721/4(1835) 96 1/4 (2445) 144 3/a (3668) partition adds 1 '12 in. (38 mm) to case line up.) Maximum O/S dimension of case back to front (includes bumper) 43 5/s(1108) 43 5/8(1108) 43 5/a(1108) 43 5/8(1108) Back of case to front of splashguard 35 5/s (905) 35 5/8 (905) 35 5/a (905) 35 5/8 (905) (B) Distance between edges of external legs and center legs NA 29 (737) 41 (1041) 41 (1041) (C) Distance between edges of center legs 41 '/8(1045) NA NA 41 '/8(1045) Distance between front legs and splashguard 8 (203) 8 (203) 8 (203) 8 (203) Electrical Service (Field Electrical Wiring Connection) (D) RH End of case to center of Field Electrical Wiring Connection 39 3/s (1000) 63 '/2 (1613) 87 '/2 (2223) 135 '/2 (3442) (top of case) Back of case to center of Field Electrical Wiring Connection 13 (330) 13 (330) 13 (330) 13 (330) Length of electrical wireway 445/8(1133) 331/2(851) 45'/8(1191) 45'/8(1191) (E) RH end of case to LH end of electrical wireway (top ofcase) 461/2(1181) 701/2(1791) 94 1/2(2400) 142 5/8(3623) Waste Outlets (F) RH End of case to the center of waste outlet 241/8(613) 241/8(613) 24'/8(613) 72'/4(1835) Back O/S of case to center of waste outlet(s) 33 '/2 (851) 33 '/2 (851) 33 '/2 (851) 33 '/2 (851) Schedule 40 PVC drip pipe 1 '/4 (32) 1 1/4 (32) 1 1/4 (32) 1 1/4 (32) Refrigeration Outlet (G) Back of case to center of refrigeration outlet 29 (737) 29 (737) 29 (737) 29 (737) End of case to center of refrigeration outlet 81/2 (216) 81/2 (216) 8 1/2 (216) 81/2 (216) 4 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IM5SL Merchandiser Data Sheet Fan Wiring Insight IM5SL Offtime Defrost Meat & Delicatessen I I I I 120VAC BK BK W W Field GND Connection = GND Connector i Connector i Connector I I I I Fan I Fan I Fan Motor I Motor I Motor 4-Ft 6-Ft & 8-Ft 12-Ft LED Canopy Light Circuits LED Canopy Lighting - 2 Rows 1 1 �BIK I 1 0-W 1 1 BK-BL rG Case Ground Bar I I Power _ W Supply R - Orange or Tan Band 1 1 R I 1 4-Ft Case 6-Ft or 8-Ft Case 12-Ft Case R 1 I I I BL I R I BL I I I 1 BBL R LED Canopy Fixture i BL LED Canopy Fixture I R LED Canopy Fixture R I Optional LED Lighting - LED Rail - 1 Row r- - - - - - - - - - - - - - r - - - - - - - - - - -I - - - - - - - - - - - - - - - - I I I I I R I I I BL I I R I R I R I 4-Ft Case I 6-Ft or 8-Ft Case I 12-Ft Case BL BL BL I I I I �-BL LED Rail Fixture I BL LED Canopy Fixture I BL LED Canopy Fixture I R I R I R I L- - - - - - - - - - - - - - - L - - - - - - - - - - - - - - -1 - - - - - - - - - - - - - - - - J WARNING All components must have mechanical ground, and the merchandiser must be grounded. R = Red Y = Yellow G = Green BL = Blue BK = Black W = White = 120V POWER O = 120V NEUTRAL ; = FIELD GROUND -�n = CASE GROUND 0 (40) m LIJ V J = N O 000 U) 0) LU z 50 Z � Lu \7 / Z 2 00 CO Z STAMP: REVISIONS DATE DESCRIPTION RECEIVED Jan 08 2024 U) CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z o O o /'S1 (n W 0 Q > Q 0 W Q W ~ U) U Lr)O 0 Z W04 U 00O 0 LL ob 0 C� N N LU O Z 2 W Z Q 0 Z O co CN O M w Il� o Q N a W J w N a O 00 00 CD Z N - -- W 0 N O L [ifz Lu on <'�_ C o K V) w Lu U 2 o ULl7NUW � LLm q _Y > Lu O 0- OQ �� C0 N + SHEET NUMBER. P/N 0535983_L HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 7 Of 10 �1- R 6. 1 -1� CUT SHEETS 2 SERVICE/SELF-SERVICE SEAFOOD DEEP SERVICE FISH MEAT REVISION DATE 02/02/17 BLF-SR Self -Service Open Multi -Deck Merchandiser BLF S R 48", 59", 77", 96", 120", 132" & 144" (Bakery) Self -Service Open Multi -Deck Merchandiser 48", 59", 77", 96", 120", 132" & 144" (Bakery) n HUSSMANN - DSFM REMOTE (CHINO) C \�I US a=e DOE 2017 dusr,uannlehige)ate9me)chandlsestnnfiguredtaSalE Intertek Intertek Energy Efficiency tot use in the United States meet or surpass the lequi(ements compbam of the 00E F017 energy efficiency standards. DSFM with Straight glass DSFM with Curved glass 583a (1483) DSFM 45' US wedge -Ill(32 ) -tar 14p 41. .4) R." 1 DSFM 45• os wwp DSFM rvµ� � 2EIsv waalrawaMAm 1 fill 42em per) 13s6 27 2 (348) (27 12 42- (1083) 13ma (346) 425m (1083) '27 27 (2 �2) 3"3'(1 66tn- 0.) �1wa)rxvax 1tnr��ev.. �� N. Contact your aeles representative lorinlonnrtion on possible availability of atltlnional case lengths. REFRIGERATION DATA: CAPACITY (BTU/HR/FT) (TOTAL TEMPERATURE (°F) VELOCITY CASE LENGTHS/ CASE USAGE FOR WEDGES) (FT/MIN ) RATING EVAPORATOR DISCHARGE WEDGES CONDITION AIR ** °F NSF 7 AHRI 1200 NSF 7 AHRI 1200 NSF 7 NSF 7 4' 6' 8' 10' 12' IFRESHSEAFOOD 300 300 24 24 31-33 1 350-500 45* IS I FRESH SEAFOOD 1800 1800 24 24 31-33 1 350-500 45'OS I FRESH SEAFOOD 1800 1800 24 24 31--33 1 350-500 **FRONT DISCHARGE AIR MEASURED INSIDE AIR CURTAIN HONEYCOMB *-REFRIGERATION NOTES: 1) AHRI 1200 RATING POINT FOR ENERGY CONSUMPTION COMPARISON ONLY 2) USE DEW POINT FOR HIGH GLIDE REFRIGERANTS. CARE SHOULD BE TAKEN TO USE THE DEW POINT IN P/T TABLES FOR MEASURING AND ADJUSTING SUPERHEAT. ADJUST EVAPORATOR PRESSURE AS NEEDED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SHOWN. 3) THE PRINCIPAL COOLING EFFECT IN FISH CASES IS ACCOMPLISHED WITH A TRADITIONAL ICE BED. THE REFRIGERATION PRESERVES THE ICE AND MAINTAINS A COLD PROTECTIVE LAYER OVER THE PRODUCT. 4) RATING CONDITION IS NSF TYPE I, 75°F/55% RH RFCRIr.FRATInN l rnkITIN11Fn• ELEC. THERMOSTAT / AIR TERM. SENSOR SETTINGS DEFROST TIME DEFROST FREQUENCY TEMP l DRIP DEFROST WATER USAGE CUT IN CUTOUT TYPE (MIN) (#/DAY) COIL TIME (LBS/DAY/FT) (,F) (,F) ONLY FRESH SEAFOOD 33 30 OFF TIME 46 3 48 N/A N/A ELECTRICAL DATA: STANDARD FANS, HEATERS, LED LIGHTS 1115 VOLT) EST. GLYCOL (20°F CASE REFG. INLET, 6° RISE) LENGTHS CHRG. GPM PSI 404A (LBS) 4' 0.9 0.4 0.7 6' 1.3 0.6 0.3 8' 1.8 0.8 0.5 10, 2.3 1.0 0.9 12' 2.8 1.2 1.2 45° IS 0.8 0.6 1.0 450OS 0.8 0.6 0.4 END PANEL WIDTH KEY # OF END END PNL TOTAL ADDED PNLS WIDTH LENGTH (IN.) (IN.) 1 1.125 1 1.125 2 1.125 1 2.25 OPTIONAL HUMIDITY SYSTEM OPTIONAL LED MAX. LED LOAD ANTI -SWEAT CONVENIENCE EVAPORATOR FANS BOOM LIGHTS FANS (OPTIONAL) SHELF LIGHTS (W/ALL OPTIONS) HEATERS OUTLETS (OPTIONAL) CASE LED 3" AXIAL FAN LENGTH # A EVP BLADE BLADE AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS # VOLTS AMPS # OF AMPS WATT FANS DIA. (IN.) PITCH (°) OUTLETS FANS 4' 1 1 8 10 0.6 50 0.2 27 N/A N/A 0.2 27 0.2 23 1 115 15 1 0.1 8 6' 2 8 10 1.2 100 0.3 39 N/A N/A 0.3 39 0.3 34 1 115 15 1 0.1 8 8' 2 8 10 1.2 100 0.5 54 N/A N/A 0.5 54 0.4 46 1 115 15 1 0.1 8 10, 3 8 10 1.9 150 0.6 68 N/A N/A 0.6 68 0.5 57 1 115 15 1 0.1 8 12' 3 8 10 1.9 150 0.7 81 N/A N/A 0.7 81 0.6 68 1 115 15 2 0.2 16 45° OS 1 8 10 0.6 50 N/A I N/A I N/A I N/A I N/A I N/A 1 0.1 1 11 1 1 1 115 1 15 1 1 1 0.1 8 45' IS 1 1 8 1 10 1 0.6 1 50 1 N/A I N/A I N/A I N/A I N/A I N/A 1 0.2 1 29 1 1 1 115 1 15 1 1 1 0.1 8 OPTIONAL HIGH OUTPUT LED LIGHTS 115 VOLT) CASE LENGTH BOOM LIGHTS H.O. LED (OPTIONAL) OPTIONAL SHELF MAX. H.O. LED LOAD AMPS WATTS AMPS WATTS AMPS WATTS 4' 0.3 32 N/A N/A 0.3 32 6' 0.4 47 1 N/A N/A 1 0.4 47 8' 0.6 64 N/A N/A 1 0.6 64 10, 0.7 81 N/A N/A I .7 81 12' 0.8 96 i 96 45° OS N/A N/A N/A N/A N/A N/A 45' IS N/A N/A N/A N/A N/A N/A BLF-SR Self -Service Open Multi -Deck Merchandiser 48", 59", 77", 96", 120", 132" & 144" (Bakery) GENERAL NOTES: • --" Indicates that the feature is not an option on this case model and/or the data is not yet available at this time. SHIPPING WEIGHT Case Weight BLF-SR --- o Etl► Eta . COMPLIANT 1 Intertek Intertek ENGINEERED FOR STORES WITH AMBIENT CONDITIONS NOT TO EXCEED 75° AND 55% RELATIVE HUMIDITY. DUE TO ENGINEERING IMPROVEMENTS SPECIFICATIONS MAY CHANGE WITHOUT NOTICE. ALL MEASUREMENTS ARE TAKEN PER ASHRAE-72-2005 SPECIFICATIONS. HILLPHOENIX REFRIGERATED DISPLAY CASES FOR SALE IN THE UNITED STATES MEET OR EXCEED DEPARTMENT OF ENERGY 2017 REQUIREMENTS. NUMBERS ARE BASED ON STANDARD CASE SIZES. CONSULT ENGINEERING. BLF-SR, BLF-S Rev. Date Rev. # Rev. Title 10-02-20 2 ENDVIEW UPDATE 05-14-20 1 NEW STANDARDS Clearv, yant' Hi//p/`soersix a a company Self -Service Open Multi -Deck Merchandiser 48", 59", 77", 96", 120", 132" & 144" (Bakery) DEFROST CONTROLS Electric Defrost Timed -Off Defrost Hot Gas Defrost Run -Off Termination Termination Termination Defrosts Time Fail -Safe Temp Fail -Safe Temp Fail -Safe Temp LOAD LIMIT Per Day (Min) (Min) (°F) (Min) (°F) (Min) (°F) 1sj 3/a" [ao.o m] 4 --- --- --- 30/*17 --- --- I I i _ �G9 d� cEi Q 10" s E ~ _ = c6LU n O \ 141 'L IL U) c')F Z 25 7/8" [65.8 an o U 2017 _ ETA DOE E11► ua COMPLIANT Intertek Intertek ENGINEERED FOR STORES WITH AMBIENT CONDITIONS NOT TO EXCEED 75° AND 55% RELATIVE HUMIDITY. DUE TO ENGINEERING IMPROVEMENTS SPECIFICATIONS MAY CHANGE WITHOUT NOTICE. ALL MEASUREMENTS ARE TAKEN PER ASHRAE-72-2005 SPECIFICATIONS. HILLPHOENIX REFRIGERATED DISPLAY CASES FOR SALE IN THE UNITED STATES MEET OR EXCEED DEPARTMENT OF ENERGY 2017 REQUIREMENTS. NUMBERS ARE BASED ON STANDARD CASE SIZES. CONSULT ENGINEERING. BLF-SR Rev. Date Rev. # Rev. Title 10-02-20 2 ENDVIEW UPDATE 05-14-20 1 NEW STANDARDS Clearv,• yant �i7lplSoe�x a company POWER SUPPL E N E �° E U E ui � F pp N <n r 8 5/8" 72.7 cm 7 5/8" 95.5 cm f K3 Rli [�i I I B1•X�Z? i t1 " 15.2 cm 15" X 13" MECHANICAL ACCES 2017 DOE ETV Etl► ua COMPLIANT Intertek Intertek ENGINEERED FOR STORES WITH AMBIENT CONDITIONS NOT TO EXCEED 75° AND 55% RELATIVE HUMIDITY. DUE TO ENGINEERING IMPROVEMENTS SPECIFICATIONS MAY CHANGE WITHOUT NOTICE. ALL MEASUREMENTS ARE TAKEN PER ASHRAE-72-2005 SPECIFICATIONS. HILLPHOENIX REFRIGERATED DISPLAY CASES FOR SALE IN THE UNITED STATES MEET OR EXCEED DEPARTMENT OF ENERGY 2017 REQUIREMENTS. NUMBERS ARE BASED ON STANDARD CASE SIZE CONSULT ENGINEERING. FRONT OF CAS 48 1/2" [123.2 cm] {48" c 56 1/2" [143.5 cm] {59" c 74 5/8" [189.5 cm] (77" c -96 1/2" [245.1 cm] {96" c 120 1/2" [306.1 cm] (120" 130 1/2" [331.5 cm] {132" BLF-SR Rev. Date Rev. # Rev. Title 10-02-20 2 ENDVIEW UPDATE 05-14-20 1 NEW STANDARDS OEKIC OEKICK Cleary• yant a := company ELECTRICAL DATA Fans High Efficiency Fans Anti -Condensate Fans Drain Heaters Optional Defrost Heaters Case Per 120 Volts 120 Volts 120 Volts 208 Volts Length Case Amps Watts Amps Watts Amps Watts Amps Wafts 48" 2 0.60 72 --- --- - -- - -- 59" 2 0.60 72 -- -- -- -- - --- 77" 2 0.60 72 -- -- -- -- - -- 96" 3 0.90 108 -- -- -- -- - -- 120" 4 1.20 144 -- -- -- -- - -- 132" 1 4 1 1.20 1 144 -- -- --- --- --- --- 144" 1 4 1.20 1 144 -- -- --- --- - --- LIGHTING DATA Case Length Lights Per Row Light Length Clearvoyant 4 LED Lighting (Per Light Row) Standard Power (Cornice or Shelf) High Power (Cornice) 120 Volts 120 Volts Amps Watts Amps Watts 48" 1 4' 0.05 5.9 0.12 14.9 5911 1 4' 0.05 5.9 0.12 14.9 77" 2 3' 0.08 9.4 0.20 23.8 9611 2 4' 0.10 11.8 0.24 29.8 120" 2 5' 0.12 15.0 0.30 37.0 132" 2 1 5' 0.12 1 15.0 0.30 37.0 144" 3 4' 0.15 1 17.7 0.36 44.7 GUIDELINES AND CONTROL SETTINGS (DX) BTUH/ft Superheat Set Point @ Bulb (*F) Evaporator ("F) Discharge Air (°F) Discharge Air Velocity (FPM) Conventional Parallel 1201 1150 10 -14 20 31 580 - 600 NOTES: • --" Indicates that the feature is not an option on this case model and/or the data is not yet • Listed BTUH indicates unlighted shelves. Add the following for lighted shelves: I 4' Shelf LED: 36 BTUH I 4' Canopy LED: 72 BTUH I 3' Shelf LED: 27 BTUH 3' Hi -Output LED: 54 BTUH • Listed discharge air velocity represents the average velocity at the peak of defrost. Time -off duration for defrost with no termination control. -2017 DOE % Suff COMPLIANT Intertek Intertek ENGINEERED FOR STORES WITH AMBIENT CONDITIONS NOT TO EXCEED 75° AND 55% RELATIVE HUMIDITY. DUE TO ENGINEERING IMPROVEMENTS SPECIFICATIONS MAY CHANGE WITHOUT NOTICE. ALL MEASUREMENTS ARE TAKEN PER ASHRAE-72-2005 SPECIFICATIONS. HILLPHOENIX REFRIGERATED DISPLAY CASES FOR SALE IN THE UNITED STATES MEET OR EXCEED DEPARTMENT OF ENERGY 2017 REQUIREMENTS. NUMBERS ARE BASED ON STANDARD CASE SIZES. CONSULT ENGINEERING. BLF-SR Rev. Date Rev. # Rev. Title 10-02-20 2 ENDVIEW UPDATE 05-14-20 1 NEW STANDARDS C410.2.2 Refrigerated display cases. Site -assembled or site -constructed refrigerated display cases shall comply with the following: 1. Lighting and glass doors In refrigerated display cases shall be controlled by one of the following: 1.1. Time switch controls to turn off lights during nonbusiness hours. Timed overrides for display cases shall turn the lights on for up to 1 hour and shall automatically time out to turn the lights off. 1.2. Motion sensor controls on each display case section that reduce lighting power by at least 50 percent within 3 minutes after the area within the sensor range is vacated. 2. Low -temperature display cases shall incorporate temperature -based defrost termination control with a time -limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach. 3. Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane. Hi//phoenix,. a company E I C ��I uS DELI / BAKERY SERVICE CASE REVISION DATE 03/24/17 HUSSMANN - 04-DVIBV (CHINO) 4'A" .•° DOE 2017 HbssTaRn retrigeratedmerchandisers canfgurRdfor sale �- Energy Elficia!ncy for use in the United States meet or surpass the requirements • t - Intertek Intertek Compliant nlthe DOE. A191mlefficiency standards, ll Multi -Deck Service Deli Case Q4-BV Multi -Deck Service Bakery Case i- 21 26),4,6m) 04-DV, BV 1413w) 16406) 63111 � 16406 31 v4 3Q3/s 18(457) 3 1/4 22va 251/e 281/e O 51 (]�) (76S) (562) (638) (714) 5 t 4 18ws7) S2 v4 221ss9) 8 T (1 2u (132n a (2oa) (1�\ ll 41 (156) (1051) 273/4 v0s) 273 a vos) I Dmin ReM- 167/a 1 ChB 107/8 (429) 93/4 (429) 93/4 (24a) y24ft) (276) I 107/8 1 24v416161 63/8 love w customerslde 12761 (162) (276j 241/4I616) I63B 11848 %2 98 144 411/200S41 411/2110SAI (1�) (20) (1219) (1829) (2438) (3658) REFRIGERATION DATA• CAPACITY *** TEMPERATURE (°F) (BTU/HR/FT) VELOCITY CASE CASE USAGE (FT/MIN) RATING DISCHARGE LENGTHS CONDITION EVAPORATOR AIR ** (°F) /12001 NSF 7 7200I NSF 7 NSF 7 NSF 7 4' 5' 6' 8' 12' 1 DELI / BAKERY 400 400 1 22 25-27 i250-400 **FRONT DISCHARGE AIR MEASURED INSIDE AIR CURTAIN HONEYCOMB ***REFRIGERATION NOTES: 1) BTU'S INCLUDE TWO ROWS OF CANOPY LIGHTS. ADD 10 BTUS PER FOOT, PER SHELF FOR OPTIONAL LED LIGHTS 2) AHRI 1200 RATING POINT FOR ENERGY CONSUMPTION COMPARISON ONLY 3) RATING CONDITION IS NSF TYPE I, 75°F/55% RH REFRIGERATION DATA CONTINUED: ELEC. THERMOSTAT / AIR TERM. SENSOR SETTINGS DEFROST TYPE TIME (MIN) DEFROST FREQUENCY (#/DAY) TEMP (•F) COIL DRIP TIME DEFROST WATER (LBS/DAY/FT) USAGE CUT IN CUT OUT (°F) (°F) ONLY DELI / BAKERY 27 24 OFF TIME 30 3 45 N/A 1.0 ELECTRICAL DATA: STANDARD FANS. HEATERS. LED LIGHTS (115 VOLT) EST. 20°F GLYCOL CASE REFG. 6° RISE LENGTHS CHRG. 404a (LBS) GPM PSI 4' 0.2 0.6 1.4 5' 0.3 0.8 2.3 6' 0.3 0.9 0.9 8' 0.4 1.2 1.7 12' 0.6 1.7 2.0 END PANEL WIDTH KEY # OF END END PNL TOTAL ADDED PNLS WIDTH LENGTH (IN.) (IN.) 1 1.125 1.125 2 1.125 2.25 ANTI -SWEAT EVAPORATOR FANS AIRSWEEP FANS CANOPY OPTIONAL LED MAX. LED LOAD ALL OPTIONS) HEATERS (ON CONVENIENCE CASE LENGTH LIGHTS LED SHELF LIGHTS (W/ FAN CIRCUIT OUTLETS (OPTIONAL) EVAP BLADEI AMPS WATTS A/S AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS VOLTS AMPS FANS N) PITCH CH () FANS OUTLETS 4' 2 6.7 20 0.24 16 1 0.04 5 0.30 35 0.27 31 0.57 66 1.30 150 1 115 15 5' 2 6.7 20 0.24 16 1 0.04 44 0.34 39 0.72 83 1.65 190 1 115 15 6' 4 6.7 20 0.48 32 2 0.08 �140.920 49 0.26 30 0.69 79 1.96 225 1 115 15 8' 4 6.7 20 0.48 32 2 0.08 69 0.54 62 1.14 131 2.61 300 1 115 15 12' 6 6.7 20 0.72 48 3 0.12 104 1 0.81 1 93 1 1.71 1 197 1 3.91 1450 2 115 30 OPTIONAL HIGH OUTPUT LED LIGHTS 115 VOLT) CASE LENGTH CANOPY LIGHTS H.O. LED OPTIONAL SHELF MAX. H.O. LED LOAD AMPS WATTS AMPS WATTS AMPS WATTS 4' 0.39 45 0.40 46 0.79 91 5' N/A N/A N/A N/A N/A N/A 6' N/A N/A N/A 8' 0.78 90 0.79 91 1 1.57 181 12' 1.171351.19 137 1 2.36 1272 0 U m Uj D U) = N M 0 OCC) U) 0) wz Z)0 Z � W z Q = co TCOT VJ W STAMP: REVISIONS 0 DATE DESCRIPTION RECEIVED Jan 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z o 0 0 co Q i0 W Q W ~ U) C) W I- Z W Ca) 0 LL ONO 0 0 Lu O Z W U) Z Z O 0') O co w o 0 a W LL w N a o 00 C) 00 Ol N� 0(n of Z U w CO C) ~ UQ w O� L()U z N LU o o� Uw U a 0 o Q 100 INo + Y 00- SHEET NUMBER: R6.2 CUT SHEETS 3 Hussmnnn" Insight standard field electrical connections are at the top left of the merchandiser Field Electrical *Coils, fans and TXVs are modular with one per 3 or 4 foot section. Portion of parts removed for clarity. 12 foot merchandiser shown. INSF Certification This merchandiser model is manufactured to meet NSF/ANSI (National Sanitation Foundation) Standard #7 requirements for construction, materials and cleanability. Performance Data Product Data (AHRI Statistics) Cross Section Plan View Electrical Loads Insight° IDD5SL Dairy / Delicatessen / Beverage with EcoVision Doors Merchandiser Data Sheet P/N 0535995_P NSF -Certified November 2023 DOE 2017 Energy Efficiency Compliant (OSTF9 NT ERTFk Canopy LED Lights C us Shelf LED Lights 0 Insight standard electrical field connections are at the top of the merchandiser Page 2 Estimated Shipping Weights Page 2 Shelf Options Page 3 Wiring Diagrams Page 4 QR Code for Parts and Product Information Page 5 Revision History Page 6 Page 6 Page 7 Page 10 Page 10 We reserve the right to change or revise specifications and product design in connection with any feature of our products. Such changes do not entitle the buyer to corresponding changes, improvements, additions or replacements for equipment previously sold or shipped. Data sheet -Insight IDD5SL ©2023 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 • WWW.HUSSMANN.COM Engineering Plan View Spanish PIN 0535996 Dimensions shown as in. and (mm). IDD5SL A _ F G 1 1/21nch (38 mm) Required 7 7 3 5/8 Air Gap1111111 (1.. (178) (92) 1#8 I B C B Wi (457) I I 43 5/8 8 112 29 (1108) 37 > Refrigeration 17 Outlet i i i i (216) I Refrigeration Waste Outlet 1 1 Outlet (737) 33 v2 35 5/8 (851) (905) 43 7/8 it `_r j WO -ay m canopy -% -------------------Lj---------- (1114) Splashguard Field Electrical --- --------- -------------------------------------------------------- D Connection 1 221/2 at TOP IF (572) of Case ---------------------------------------------------------------------- Door Swing Clearance-- FRONT (12 Foot Model shown above) General 4 ft 6 ft 8 ft 12 ft (A) Case Length (without ends or partitions) (Each end and insulated 48'/8 (1222) 721/4 (1835) 961/4 (2445) 144 3/8 (3668) partition adds 1 '12 in. (38 mm) to case line up.) Maximum O/S dimension of case back to front (includes bumper) 43 1/8(1108) 43'/8(1108) 43'/8(1108) 43'/8(1108) Back of case to front of splashguard 35'/8 (905) 35'/8 (905) 35'/8 (905) 35'/8 (905) (B) Distance between edges of external legs and center legs NA 29 (737) 41 (1041) 41 (1041) (C) Distance between edges of center legs 41 1/8 (1045) NA NA 41 '/8 (1045) Distance between front legs and splashguard 8 (203) 8 (203) 8 (203) 8 (203) Electrical Service (Field Electrical Wiring Connection) (D) RH End of case to center of Field Electrical Wiring Connection 39 3/8 (1000) 63 '/2 (1613) 87 1/2 (2223) 135 '/2 (3442) (top of case) Back of case to center of Field Electrical Wiring Connection 18 (457) 18 (457) 18 (457) 18 (457) Length of electrical wireway 44'/8 (1133) 33 '/2 (851) 45 7/8 (1165) 45 '/8 (1165) (E) RH end of case to LH end of electrical wireway (top ofcase) 461/2 (1181) 701/2 (1791) 941/2 (2400) 1421/8 (3630) Waste Outlets (F) RH End of case to the center of waste outlet 24'/8(613) 24'/8(613) 24'/8(613) 72'/4(1835) Back O/S of case to center of waste outlet(s) 33 '/2 (851) 33 '/2 (851) 33 '/2 (851) 33 '/2 (851) Schedule 40 PVC drip pipe 1 1/4 (32) 1 1/4 (32) 1 1/4 (32) 1 1/4 (32) Refrigeration Outlet (G) Back of case to center of refrigeration outlet 29 (737) 29 (737) 29 (737) 29 (737) End of case to center of refrigeration outlet 8 '/2 (216) 8 '/2 (216) 8 '/2 (216) 8 '/2 (216) 4 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 A IDD5SL Merchandiser Data Sheet Insight IDD5SL Dairy / Delicatessen Refrigeration Data IDD5SL Optimal Shelf Life Energy Comparison Door Option EcoVision EcoVision HA EcoVisi EcoVision HA+on Dairy/Deli/ Convertible/ NSF Type 2 Harsh AHRI 1200 Application Beverage/ Pegs' Meat Ambient s Environment Rating Produce point' Discharge Air OF (°C) 37 (2.77) 36 (2.22) 34 (1.11) 34 (1.11) 33 (0.55) 37 (2.77) Unlit Average Evaporator OF (°C) 2,1 34 (1.11) 33 (0.55) 31 (-0.55) 31 (-0.55) 30 (-1.11) 34 (1.11) Mullions Parallel Btu/hr/ft (Watts/m) 180 (173) 200 (192) 215 (207) 225 (216) 280 (269) 180 (173) Conventional Btu/hr/ft (Watts/m) 185 (178) 205 (197) 220 (212) 230 (221) 285 (274) 185 (178) Discharge Air OF (°C) 36 (2.22) 35 (1.66) 33 (0.55) 33 (0.55) 32 (0) 36 (2.22) Lit Average Evaporator OF (°C) 2,1 33 (0.55) 32 (0) 30 (-1.11) 30 (-1.11) 29 (-1.67) 33 (0.55) Mullions Parallel Btu/hr/ft (Watts/m) 194 (187) 214 (206) 228 (220) 238 (229) 292 (280) 194 (187) Conventional Btu/hr/ft (Watts/m) 200 (192) 220 (212) 235 (226) 245 (236) 300 (288) 200 (192) IDD5SL6 (8.25") 1300 1300 1300 1300 1300 1300 Fan Speed IDD5SL4, 8, 12 (8.25") 1300 1300 1300 1300 1300 1300 Notes: 1. All data based on store temperature and humidity that does not exceed NSF Type 1 ambient conditions of 75°F and 55% relative humidity except where noted. 2. Average evaporator temperature shown. Use dew point for high glide refrigerants for unit sizing. Care should be taken to use the dew point in PT tables for measuring and adjusting superheat. Adjust evaporator pressure as needed to maintain discharge air temperature shown. 3. For DX CO2 applications the average evaporator temperature may be lowered by 5°F but not more than 10°F. An EPR valve should be used if the system suction temperature is below 24°F. A 31 OF flash tank temperature with a 24°F evaporator temperature is used when sizing default EEV selections to provide a minimum pressure drop across the valve of approximately 50 psig. For operating conditions that provide a pressure drop across the valve above 65 psig or below 35 psig, the electronic expansion valve size should be determined using the valve vendor sizing program and selected from the pull down list in the Hussmann Product Configurator (HPC). 4. Hussmann Peg Shelves for Dairy/Deli applications only. 5. Data for operation in NSF Type 2 ambient of 80°F and 55% relative humidity. 6. AHRI 1200 Rating Point for energy consumption comparison only. Defrost Data Conventional Controls Estimated Charge a IDD5SL Type 1 Harsh IDD5SL 4 ft 0.6 lb 10 oz 0.3 kg Environment Low Pressure Backup 6 ft 1.1 lb 18 oz 0.5 kg Frequency (hours between defrost) Control Cl/CO a 8 ft 1.5 lb 24 oz 0.7 kg 24 12 26°F / 16°F -3.3°C / -8.9°C 12 ft 2.9 lb 46 oz 1.3 kg OFFTIME Time (minutes) 40 30 Indoor Unit Only, s This is an average for all refrigerant types. GAS Not Available Pressure Defrost Actual refrigerant charge may vary by Termination approximately half a pound. 48°F (8.89°C) ater' 1.0 Ib/ft/day 1.5 Ib/ft/day(1.5 LERR kg/m) (2.3 kg/m) 8 Use a Temperature Pressure Chart to ed on case confi uration and roduct loadin 9 P 9) determine PSIG conversions. Product Data Gross Refrigerated Volume 10 (Cu Ft/Ft) 11.6 ft3/ft (1.08 mom) AHRI Total Display Area11 (Sq FtlFt) 4.29 ftz /ft (1.31 m2/m) Shelf Area" (Sq Ffft) 9.85 ftz /ft (3.00 m2/m) '0 AHRI Gross Refrigerated Volume: Refrigerated Volume/Unit of Length, ft3/ft [m3/m] 11 Computed using AHRI 1200 standard methodology: Total Display Area, ft2 [m2]/Unit of Length, ft [m] t2 Shelf surface area is composed of bottom deck plus standard shelf complement for this model: (4) rows of 22-in. shelves 2 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IDD5SL Merchandiser Data Sheet Electrical Data Number of Fans 8.25-in. 4 ft 6 ft 8 ft 12 ft 1 2 2 3 Amperes Insight IDD5SL Dairy / Delicatessen Watts Evaporator Fan 4 ft 6 ft 8 ft 12 ft 4 ft 6 ft 8 ft 12 ft 120V 60Hz Energy Efficient 0.25 0.50 0.50 0.75 16 32 32 48 230V 50/6OHz Energy Efficient 0.13 0.26 0.26 0.39 16 32 32 48 Minimum Circuit Ampacity 120V 60Hz Energy Efficient 0.45 0.70 0.70 0.95 230V 50/6OHz Energy Efficient 0.33 0.46 0.46 0.59 Maximum Over Current Protection 120V 20 20 20 20 Maximum Over Current Protection 230V 15 15 15 15 Lighting ONLY LIGHTING CONFIGURATIONS THAT ARE COMPLIANT WITH THE U.S. DEPT. OF ENERGY (DOE) 2017 REGULATION ARE AVAILABLE FOR SALE FOR USE IN THE U.S.A. STANDARD LED LIGHTING LED Canopy Lights 1 Row 0.16 0.22 0.31 0.47 19 27 38 Shelf None Optional LED Mullion Lights 48-in. 0.22 0.39 0.39 0.56 27 47 47 120V Lighting Circuit Total = Standard Lighting + Total Optional Lighting 230V Lighting Circuit Total = Multiply 120V Lighting Circuit Total by 0.52 FRAME ANTI -CONDENSATE HEATERS (Only with EcoVision 0.39 0.59 0.64 0.88 46 69 74 HA+ Door Option) 57 CA 103 P/N 0535995 P HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 5 of 10 Insight Multideck Merchandiser, EcoVision Doors, 5 Display Levels, Standard Bottom, Low Height Front Insight Dairy ary IDD5SL /Delicatessen DOE 2017 Hussmann refrigerated merchandisers configured for sale for use in the United States Energy Efficiency Compliant meet or surpass the requirements of the DOE 2017 energy efficiency standards. Shelf complement shown as tested: Four rows of 22-in. shelves spaced equally between bottom display pan and interior top panel. Other optional kits (top piping and vent fans) add to the overall case height. Aminimum 1'h-in clearance required to remove raceway cover, 6 1/2-in for full access. See the Installation manual for instructions. 3-in. between back to back cases. Shown with Ellipse Option Canopy and Bumper. Dimensions shown as in. and (mm). IDD5SL 101/2 (2 7) I- - - - - - - I I I I I I Door 83 3/8 1 Opening (2118) 1 51 1/2 (1308) I I I I I I I I 211/2 (546) 151/2 (394) 51/2 (140) 221/2 (572) 43 7/8 (1114) 591 /4 (1505) FANS 1 1/2 In. (38 mm) Required Air Gap III - I I 29 (737) 331 /2 (851) 35 5/8 (905) 43 5/8 (1108) 841/2 (2146) W A L L NSF Certification This merchandiser model is manufactured to meet NSF/ANSI (National Sanitation Foundation) Standard #7 requirements for construction, materials and cleanability. L/N 0535995 P HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 3 of 10 Insight IDD5SL Dairy / Delicatessen ENDS or PARTITIONS PHYSICAL DATA Each standard end and each insulated partition Merchandiser Drip Pipe (in.) 1 1/4 adds 1 1/2 in. (38 mm) to case line up. Optional Schedule 40 PVC view end with end bumper adds 3 Y4 in. (95 mm). Merchandiser Liquid Line (in.) 3/8 Merchandiser Suction Line (in.) 5/8 ESTIMATED SHIPPING WEIGHT t Case Solid End 4 ft 6 ft 8 ft 12 ft (each) I (kg) 760 (345) 920 (417) 1110 (504) 1260 (572) 80 (36) t Actual weights will vary according to optional kits included. elf Options Approved shelf sizes for standard (horizontal, 2-3 position brackets) displays: 18-inch 20-inch 22-inch 24-inch Contact engineering for non-standard (4 position brackets or other) display recommendations. Minimum number of Shelves: 3 Optimal number of Shelves: 4 Maximum number of Shelves: 8 Maximum number of Lighted Shelves: 0 Standard shelf complement for test purposes: (4) 22-in. shelves, evenly distributed vertically 6 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IDD5SL Merchandiser Data Sheet • O UJ V ~ v! = � N O �Qnn vJ DD V o � LLJ 5O Z Z LIJ � z f_/ �/ ) co (D O CO Z .ram STAM P: REVISIONS DATE DESCRIPTION RECEIVED Jan 08 2024 ' A CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 0 Z O O to w 00 cn W Q Q Q 0 Q W ~ U) �C:)0 I- Z 0 W U co O � Cq 0 0 N N LJ O Z 2 W C) Z UJ 0 a Z ZZ co rn O co w 2 o 0 CV a W �J w N 0_0 z to OO CD ZaVw ~ ^ C) [if co mt� oU of Ucy)zNU wQ 2 U LU o LL .o > SHEET NUMBER: R6.3 CUT SHEETS 4 Fan Wiring Offtime Defrost Insight I D D 5 S L Dairy / Delicatessen BK BK I I I I 120VAC W IT I W Field GNDU� Connection = d�a GND Connector i Connector I i Connector I Fan I I Fan I I Fan Motor I Motor I Motor 4-Ft 6-Ft & 8-Ft 12-Ft LED Canopy Light Circuits LED Canopy Lighting - 1 Row r------------ - - - - -n r---------------------------------� I I I I I I I I • BK tt BK Power BL I I � BK BK POWer BL o-- W W Supply R I I o-w W Supply R I G Case Ground Bar i i G Case Ground Bar Orange or Orange or 6-Ft or 8-Ft Case Tan Band 4-Ft Case I I Tan Band I R I I R R I I I BIL BL I Lq,R BL LED Canopy Fixture I I R L LED Canopy Fixture L�tBL LED Canopy Fixture I I I R I L- - - - - - - - - - - - - - - - - J L - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - J r------------------------------------------------------- I I I I I I .BK �W r G Case Ground Bar BK Power BL (T fto I Orange or 12-Ft Case W Supply R I Tan Band I R I I BL I R BL R BL RBL LED Canopy FixtureR L LED Canopy Fixture BR LED Canopy Fixture L- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - J WARNING All components must have mechanical ground, and the merchandiser must be grounded. R = Red Y = Yellow G = Green BL = Blue BK = Black W = White • = 120V POWER O = 120V NEUTRAL 1 = FIELD GROUND n = CASE GROUND P/N 0535995 P HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 7 of 10 Insight I D D 5S L Dairy / Delicatessen Estimating Refrigeration and Electrical Load (for comparison purposes only) Case Btu To determine Btu for a case, refer to the performance data chart on Page 2. Select lit or unlit shelves, then select the type of remote refrigeration system (parallel or conventional), which will give Btu/hr/ft. Multiply this number by the length of the case to determine Btu per hour. Add 10 BTU/HR/FT for LED Mullion Lights. Case Electrical Refer to store legend to determine number of circuits. Lighting should be specified in store legend. Fan electrical load for a case is computed by selecting the case length and fan voltage on Page 6. For example, a 12 ft case uses 3 fans. The store legend specifies fans on a 230V circuit. In this instance, fans use 0.39 Amps and the MCA is 0.59. When applied, ambient fans, anti -sweat heaters, controllers, etc. must be included in the MCA. Include lights in the MCA if lights are on same circuit. Lights may be on a separate circuit. To estimate lighting load: select case length (12 ft), canopy lighting [standard or optional] (here 0.70 for standard), and mullion lighting [maximum for which case is wired] (0.57 for EcoShine II 48" mullion lights); then add together [0.48 + 0.57 = 1.05 amps for 120V] (for 230V, multiply 1.05 * 0.52 = 0.55). Line Sizing - Refer to store legend. Hussmann Line Sizing Charts are engineered for use with Hussmann refrigeration equipment. Scan the QR code with your mobile device to access additional product information or order parts. Parts may also be ordered at: parts. hussmann.com Call toll free: 1.855.487.7778 Revision History Revision A: August 2013: Original Issue Revision B: October 2015: Added coil, fan and fan speed selector callouts to cover image. Updated Refrigeration Data on Page 2. Added clearance, access notes and updated cross section image. Revision C: December 2015: Updated cross section and plan view. Revision D: April 2016: Updated cover image, updated application data, added Gross Refrigerated Volume and updated plan view. Revision E: June 2016: Updated cross section. Revision F: August 2016: Updated cross section and plan view. Revision G: January 2017: Removed EcoShine "Plus" references. Revision H: April 2017: Updated LED energy values. Revision J: April 2017: Updated LED energy values. Revision K: September 2017: Updated notes page. Revision L: May 2018: Updated lighting information. Revision M: February 2021: Removed replacement parts page, updated electrical data and updated cross section. Revision N: January 2023. Added CO2 note, Page 2. Revision P: November 2023: Updated fan and lighting information. 10 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IDD5SL Merchandiser Data Sheet Insight I D D 5S L Dairy / Delicatessen Mullion LED Lighting ------------- F- LED Power -1 F Lff Power - Supply 24VDC r J Supply 24VDC r l �GWrWRL l *GW WRL J { LJ r LJ Rl B� RH LED Light R BL R BL t BL LH LED Li ht BL LH LED Light BL CTR LED Light BL RH LED Light R R =L R L 4 Ft Case J L_ 6 Ft or 8 Ft Case J ------------------------------------ �BK C----; PLED Power ---tL W SuppLED lyower 24VDC 1 Supply 24VDC F LL W� R J K= RL J LJ LJ R BL BL BL BL LH LED Light LBL CTR LED Light BL CTR LED Light BL RH LED Light R R 7 R R L - 12 R Case Door Frame Heater EcoVision HA+ Only ______________ 1 RACE\\'AY I� 6DOOR (12M WARNING All components must have mechanical ground, and the merchandiser must be grounded. R = Red Y = Yellow G = Green BL = Blue BK = Black W = White • = 120V POWER O = 120V NEUTRAL 1 = FIELD GROUND -d- = CASE GROUND 8 of 10 U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-890-2900 IDD5SL Merchandiser Data Sheet C-P C oukUS Intertek Intertek 03-SS I^�o Self -Service Multil I�- SELF-SERVICE DELI REVISION DATE 01/31/17 HUSSMANN - 03SS (CHINO) Q3-81a8vOei w= DOE2017 Hussmann he United fed tertmeet of Suconfigured for sale Enegy Eehu.Rey for use in the 0nrted States meet or wrpass the requirements Cor„pl... of the DOI 7017 energy efficiency standards. ,Z 03-SS, -SC ------- -I'M 221. --- ----------- 18(o 51sn°h 24sn 72. n 27s% 303 low n1tn (625) (702) (7e1 - l6� 4wn9e) 33,a1es1 o1 Match 8 /Oom° �3-SS &wbe 22S Olb 0888swwas•oRi 03-SS Serbs zzS us 8,R s,A 30� �Ieni 45�4 ( ) Erse (127) (�) 44� L b Or„°I ° o g C 44 x 17 Leonrdo-on_ __ ____ Imp fE (nos) nee by a � 44J1:,-.,u arc .2l48vanawe,say °Isw"3 3. (1219) R°" . ni19 1 26 �-) 44sb (naa( 2: 47 -� rwv/� 1w1 0 RFFRI111FRATI/7N DATA• CASE LENGTHS/ WEDGES CASE USAGE CAPACITY ••• (BTU/HI (TOTAL FOR WEDGES) TEMPERATURE (OF) VELOCITY FT/MIN ( ) RATING CONDITION EVAPORATOR DISCHARGE AIR' °F NSF 7 AHRI 1200 NSF 7 AHRI 1200 NSF 7 NSF 7 4' 5' 6' 8' 10' 12' SS DELI 850 850 20 20 28-32 150-200 4' 5' 6' 8' 10' 12' MEAT 880 850 18 20 26-30 1 150-200 22.5° IS SS DELI 2700 2700 20 20 28-32 150-200 22.5' OS SS DELI 2600 2600 20 20 28_32 150-200 45°IS SS DELI 1610 1610 20 20 28-32 150-200 45° OS SS DEL 1376 1376 20 20 28-32 150-200 90- OS SS DELI 3200 3200 20 20 28-32 150-200 REAR STORAGE I SS DELI 100 90 20 1 26 30-34 380-600 **FRONT DISCHARGE AIR MEASURED INSIDE AIR CURTAIN HONEYCOMB -REFRIGERATION NOTES: 1) BTU'S INCLUDE CANOPY LIGHTS. ADD 10 BTUS/SHELF/FT FOR EACH SHELF (LIGHT) 2) AHRI 1200 RATING POINT FOR ENERGY CONSUMPTION COMPARISON ONLY 3) USE DEW POINT FOR HIGH GLIDE REFRIGERANTS. CARE SHOULD BE TAKEN TO USE THE DEW POINT IN Prr TABLES FOR MEASURING AND ADJUSTING SUPERHEAT. ADJUST EVAPORATOR PRESSURE AS NEEDED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SHOWN. 4) RATING CONDITION IS NSF TYPE I, 75°F/55% RH. 0000lr-oo ATlnu nATA r•nuTlw Ion• CASE LENGTHS EST. REFG. CHRG. 404A(LBS) GLYCOL(20°F INLET, 6° RISE) GLYCOL(201 INLET, 6° RISE) FRONT REAR STORAGE GPM PSI GPM PSI 4' 0.5 1.3 3.4 0.1 0.0 5' 0.7 1.6 5.4 0.2 0.1 6' 0.7 1.9 7.7 0.2 0.2 8' 1.0 2.5 3.5 0.3 0.4 10, 1.4 3.0 6.2 0.3 0.6 12' 1.5 3.6 7.1 0.4 0.8 22.5°IS 0.3 0.9 1.7 N/A N/A 22.5° OS 0.3 0.8 1.6 N/A N/A 45°IS 0.3 0.5 0.8 N/A N/A 45° OS 0.2 0.4 0.4 N/A N/A 90° OS 0.3 1.0 2.0 N/A N/A ELEC. THERMOSTAT /AIR TERM. SENSOR SETTINGS DEFROST TIME DEFROST TEMP DRIP DEFROST LOCATION FREQUENCY (°F) WATER USAGE CUT IN CUT OUT TYPE (MIN) (#/DAY) COIL TIME (LBS/DAY/FT) (,F) (°F) ONLY SELF SERVICE SS DELI 30 27 OFF TIME 30 4 48 N/A 9.1 SELF SERVICE MEAT 28 25 48 10.3 REAR STORAGE DELI 35 32 45 0.7 ELECTRICAL DATAc STANDARD FANS_ HFATERS_ LED LIGHTS /115 VOLT/ END PANEL WIDTH KEY END # OF END PNL TOTAL ADDED PNLS WIDTH LENGTH (IN.) (IN.) 1 1.125 1.125 2 1.125 2.25 EVAPORATOR FANS REFRIGERATED REAR STORAGE (OPTIONAL) EVAP FANS CANOPY LIGHTS LED OPTIONAL LED SHELF LIGHTS MAX. LED LOAD (W/ALL OPTIONS) ANTI -SWEAT HEATERS (ON FAN CIRCUIT CONVENIENCE OUTLETS OPTIONAL CASE LENGTH # OF EVAP FANS BLADE DIA. (IN.) BLADE PITCH (°) AMPS WATTS # OF EVAP FANS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS # OUTLE TS OLT P 4' 2 6.7 25 0.2 16 1 0.3 9 0.1 10 0.2 21 0.3 31 N/A N/A N/A N/A N/A 2 6.7 20 0.2 16 1 0.3 9 0.1 13 0.1 13 0.2 26 N/A N/A N/A N/A N/A 6' 3 6.7 25 0.4 24 1 0.3 9 0.1 15 0.1 15 0.3 31 N/A N/A N/A N/A N/A 8' 4 6.7 25 0.5 32 1 0.3 9 0.2 21 0.2 21 0.4 41 N/A N/A N/A N/A N/A 10, 4 6.7 20 0.5 32 1 0.3 9 0.2 26 0.2 26 0.5 52 N/A N/A N/A N/A N/A 12' 6 6.7 25 0.7 48 1 0.3 9 0.3 31 0.2 21 0.4 51 N/A N/A N/A N/A N/A 22.5°IS 1 6.7 15 0.1 8 N/A N/A N/A 0.1 8 0.0 4 0.1 12 N/A N/A N/A N/A N/A 22.5° OS 2 6.7 25 0.2 16 N/A N/A N/A 0.1 8 0.1 10 0.2 18 N/A N/A N/A N/A N/A 45° OS 1 6.7 25 0.1 8 N/A N/A N/A 0.0 4 0.0 4 0.1 8 N/A N/A N/A N/A N/A 45°IS 1 6.7 25 0.1 8 N/A N/A N/A 0.0 4 0.1 7 0.1 11 N/A N/A N/A N/A N/A 901OS 3 6.7 20 0.4 24 N/A N/A N/A 0.0 4 0.1 14 0.2 18 N/A N/A N/A N/A N/A OPTIONAL HIGH OUTPUT LED LIGHTS 115 VOLT) CASE LENGTH CANOPY LED OPTIONAL SHELF MAXLO�LED AMPS WATTS AMPS WATTS 4' 0.3 30 0.4 46 N/A N/A N/A N/A N/A 6' 0.2 26 0.5 52 8' 0.3 30 0.5 6110,N/A N/A N/A N/A N/A 12'46 fAWATTS 0.3 30 0.7 76 22.5°N/A N/A N/A N/A N/A 22.5° N/A N/A N/A N/A N/A 45° ON/A N/A N/A N/A N/A 45°IN/A N/A N/A N/A N/A 90° ON/A N/A N/A N/A N/A Door Frame Heater EcoVision HA+ Only COT ---------------------------------------------- 3 DOOR / 4 DOOR (6 FT / 8 FT) Insight I D D5S L Dairy / Delicatessen ------------------------- RACEWAY I I I I II T I h Noio I I j BK ppj I �01 I I�I I I I I I BK g L BK I -- I FIELD WT WIRING CONNECTIONS toil lob I I�H 17 �i I h �I h ul I If=I If=, I I I I I I i I I i I I I I I I I I I I I I I I I I I II MULLION LED MULLION LED W BL POWER SUPPLY MULLION BK WH RD BL �I ERsuwLr BK RDLIP CANOPY LED 2 DOOR (4 FT) WARNING All components must have mechanical ground, and the merchandiser must be grounded. R = Red Y = Yellow G = Green BL = Blue BK = Black W = White • = 120V POWER O = 120V NEUTRAL 1 = FIELD GROUND -#- = CASE GROUND P/N 0535995 P HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM 9 of 10 ETV Sk MEDIUM TEMP SELFSERVICE MULTI -DECK REVISION DATE 02/26/18 HUSSMANN - ISLA - IM-05-(E or C)-R (CHINO) US DO! 2017 hussmaun rehigelated merchandisers configured'm sale IM-CS-R Center Module IM-15-R In -line Module y th" use m the Ilmted States meet 91 surpass the repo cements Intertek Intertek J compliant of the BIIE ta17 ene(gy efrioenq standards. 19z•1as) f,52n IM-05-R Refrigerated Self -Service Module " 18am 11ns saz) 17 (073) 131rz(sas) B3as 3)a (aazt �p,1 35v4 Li !J' R." 55M 10 le. 254) 10 (sal) 6 3ra (2 Rnev 45 " Erie Noun° 37518 (171) (305) 1,A End ( > 6 3ra 14 (20) � �' (16224 �3� (171) (356) 58 6 374 16 (1473) (171) Ios IM-ES-R End Module 6 3/4 207a (Sao) L = 25 (sa5) is (171) 22559.- 101/8 (257) 1-1 677e (175) 33 sm 35318 (854) (899) Center Module (C) Inline and End Module (I. E) RFFRIGFRATII ri CAPACITY (BTU/HR/FT) TEMPERATURE (°F) VELOCITY CASE LENGTHS CASE USAGE (FT/MIN) RATING DISCHARGE EVAPORATOR CONDITION AIR ** °F NSF 7 NSF 7 AHRI 1200 NSF 7 NSF 7 DELI / DAIRY 1110 905 25 26 30•-32 225•-250 8' 10' 12' 3',4',5',6', 1 MEAT 1430 905 21 26 28-30 225-250 8' 10' 12' EST. 20°F GLYCOL CASE I ISO RISE LENGTHS CHRG. GPM PSI 404A (LBS) 3' 0.7 1.2 1.1 4' 1.0 1.6 2.0 5' 1.2 2.0 3.1 6' 1.4 2.4 1.8 8' 2.0 3.1 2.9 10' 2.5 3.8 4.2 12' 2.9 4.5 3.9 **FRONT DISCHARGE AIR MEASURED INSIDE AIR CURTAIN HONEYCOMB -REFRIGERATION NOTES: 1) BTU'S INCLUDE CANOPY LIGHTS ONLY. ADD 10 BTUS/SHELF/FT FOR EACH SHELF (LIGHT) 2) MEAT CASE SPECS ARE FOR PACKAGED MEAT. 3) AHRI 1200 RATING POINT FOR ENERGY CONSUMPTION COMPARISON ONLY. 4) USE DEW POINT FOR HIGH GLIDE REFRIGERANTS. CARE SHOULD BE TAKEN TO USE THE DEW POINT IN PIT TABLES FOR MEASURING AND ADJUSTING SUPERHEAT. ADJUST EVAPORATOR PRESSURE AS NEEDED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SHOWN. 5) RATING CONDITION IS NSF TYPE I, 75°F/55% RH RFFRIGFRATIll nATA r`1lNTIN1 IFD- ELEC.THERMOSTAT/AIR TERM. SENSOR SETTINGS TIME DEFROST FREQUENCY TEMP (°F) DRIP DEFROST WATER DEFROST USAGE culCUT OUT TYPE (MIN) (#/DAY) COIL TIME (LBS/DAY/FT) IN ( F) (OF) ONLY DELI / DAIRY 33 30 OFF TIME 20 6 52 N/A 7.5 MEAT 31 28 OFF TIME 20 6 52 N/A 9 ELECTRICAL DATA: STANDARD FANS HFATFRS I FD I IGHTS 111A Vnl Tl END PANEL WIDTH KEY # OF END END PNL TOTAL ADDED LENGTH IN. 1 1.125 1 1.125 2 1.125 2.25 CANOPY LIGHTS LED SHELF MAX. LED LOAD ANTI -SWEAT CONVENIENCE EVAPORATOR FANS (W/ ALL HEATERS (ON FAN CASE LED LIGHTS OPTIONS CIRCUIT OUTLETS (OPTIONAL) LENGTH *OF BLADE EVAP DUI. PIITCH;) AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS AMPS WATTS OUTLETS VOLTS AMPS FANS IN. 3' 1 8 1 25 0.3 8 0.17 19 0.27 31 0.44 50 N/A N/A 1 115 15 4' 1 8 1 25 0.3 8 0.23 27 1 0.36 41 0.59 68 N/A N/A 1 115 15 1 8 30 0.3 8 0.30 34 0.45 52 0.75 86 N/A N/A 1 115 15 6' 2 8 25 0.6 16 0.34 39 0.54 62 0.87 100 N/A N/A 1 115 15 8' 2 8 25 0.6 16 0.47 54 0.72 82 1.18 136 N/A N/A 1 115 15 10' 2 8 30 0.6 16 0.59 68 0.90 104 1.49 172 N/A N/A 1 115 15 12' 3 8 25 0.9 24 0.70 Al 1.11 124 1.78 204 N/A N/A 2 115 30 OPTIONAL HIGH OUTPUT LED LIGHTS 115 VOLT) CASE LENGTHH.0 LIGHTS LED SHELF LIGHTS H.O. LED MAX. H.O. LED LOAD AMPS WATTS AMPS WATTS AMPS WATTS 3' 0.21 24 0.45 52 0.66 76 4' 0.28 32 0.53 61 0.81 93 5' N/A N/A N/A N/A N/A N/A 6' 1 0.41 47 0.90 104 1.31 151 8' 0.56 64 1.06 122 1.61 186 10, N/A I N/A I N/A N/A I N/A 1 N/A 12' 1 0.83 1 96 1 1.59 183 1 2.42 1 278 0 U m D U) = N co D O O00 U) O) Wz �0 Z � W z co T�T VJ W STAMP: REVISIONS 0 DATE DESCRIPTION W W 0 Q W I- U) 1- W RECEIVED Jan 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES 0 Z O 2 W LO CO CU LL 0 �1 W a7 I- V) w Z 0o 0 Cl W Q N W O Z 2 W W Z z O � O M w 2 o 0 a LU v LL w N a o P CO Lr) CD O z N w O W Oi m co z = U U w COW Q' �w N UL w O rnZ L6 N2 U O UwLu a Ll�m Ce)O >- O a 0 Q� W 0 N + Y SHEET NUMBER: R6.4 _." CUT SHEETS 5