APPROVED RESUB 1 FIR2024-0018+Drawings+2.26.2024_4.03.07_PM+4083844Information for system operator/owner
CLAIRE'S PANTRY
301 MAIN ST
EDMONDS, WA 98020
ICC CERT # 9917130
8„ X 8"
4 FT. F.D DUCT
HOOD E
P
6
I
42" — 48"
REMOTE PULL STATION
DOUBLE STACK
CONVECTION OVEN
SHALL BE INSTALLED 42"-48"
AVOVE THE FLOOR AT A DISTANCE
(ORIENTED TO THE LEFT)
> 10 FT FROM THE HAZARD BUT
NOT MORE THAN 20 FT. ITSHALL BE
SIDE VIEW
INSTALLED IN THE PATH OF EGRESS
AND REQUIRE A MAXIMUM FORCE
OF 40 LBS. AND A MAXIMUM
MOVEMENT OF 14" FOR
ACTUATION
PIPING SIZE
3/8" PIPING
1/2" PIPING
3/4" PIPING
INSTALLED BY
ALL - AMERICAN FIRE PROTECTION INC.
P.O. BOX 393 EVERETT, WA 98206
PHONE: 360 - 474 - 9773 FAX: 360 - 631 - 5146
14 FT.
HOOD
ADP
Contact your system manufacturer/distributor to ensure factory
trained and certified personnel perform repairs, maintenance, or
servicing of the suppression system. Failure to do so may
compromise the UL listing of the hood suppression system, void
the warranty and ieopardize insurance claims resulting from a fire.
/ (2) X ADP --- 36" X 8„
NOZZLES A* DUCT
F ♦ F + R IF GRW
NOZZLE NOZZLE NOZZLE NOZZLE
27" — 45" 27" — 45" 20"- 42" 24" — 48"
...........
IN -
Buzimill M
—
o I o
2 X GAS FRYERS
15" X 23"
8"x8„
ADP
DZZLE DUCT
ADP
F NOZZLE NOZZLE
27"-45" 13"-48"
ADP
NOZZLE
ADP P 11111, ADP ADP P ADP
NOZZLE NOZZLE NOZZLE 13"-48"
13"-48" 13"-48" 13"-48"
o 9 o -4—
BADGER
�
Badger
Fire Protection
in L&
2- GAS
BURNER CHARBROILER
GAS 24" X 24"
RANGE
12"X24"
GAS GAS GAS
GRIDDLE GRIDDLE GRIDDLE
24" X 24" 40" X 24" 36" X 24"
UL 300 COMPLIANT SYSTEM
SYSTEM MFG: BADGER FIRE PROTECTION UCH CONTROL HEAD
RANGE GUARD - 6 GALLON TANK
CAPABLE FLOW POINTS: 18 ACTUAL FLOW POINTS USED: 17
** SYSTEM SHALL BE SERVICED AND MAINTAINED TO UL300, NFPAI7A,
NFPA 96 AND MANUFACTURERS INSTRUCTIONS.
ELECTRICAL GAS
SHUTOFF VALVE
& RESET RELAY
• • ■
l
RANGJm—
GUARD 6
GALLON FIRE
SYSTEIM_
Audible Fire
/� Alarm & Strobe
Connection to
electrical shut down
mnn arrivarinn
:LASS K WET CHEMICAL EXTINGUISHER
SHALL BE INSTALLED 42' - 48' ABOVE
THE FINISHED FLOOR
Approved
DFM Chris Sort
South County Fire
Date: 03/06/2024
03-06-2024
RESUB 1 PLAN
REVIEW
NOTES: APPROVED
DFM BURT
FIR2024-0018
RECEIVED
Feb 28 2024
FIRE SYSTEM AND APPLIANCE DRAWING WILL BE DISPLAYED AT OR NEAR THE SYSTEM MANUAL PULL STATION