Loading...
FIR2024-0018+Manufacturer_Equipment_Sheets+2.26.2024_4.03.31_PM+4083845FIR2024-0018 RECEIVED Feb 28 2024 CHAPTER 1 GENERAL INFORMATION 1 1 INTRODUCTION General Information The R uigv (,hard Wct (- licuucal System provides fire protection for ceummnercial kitchen applications such as appliances and ventilation. The Wet Chemical systrmt holds UL amid ULC listings as a pre-etlghterred system. Systems stall be designed and lttipletneuted according to the following; • NFPA Standard 17A, -Standard for Wet Chemical Systems' • NFPA Standard 96. "Standard for Ventilation Control and Ft re Protection of Commercial Cooking o pera do n_ti" • Other applicable NFPA standards as required for a particular application and design. Including, but not limited to. NFPA 701NEC). and NFPA 72. Fire Alarm Standard and CSA • This Design. litslallation, Operation, and Maintenance Manual IDIOM) • Any other standards enforced by a local Authority Having .lurLsdlctlon (AKJ ) Configurations In Chapter 3, System lksign, are tested and Wated to Underwriters l.ahoratorles I lJL) Standard 300, 1994 Edition, unless otherwise noted, and lhidet-writers l,aboratorles of Canada ORD 12_5A.6. 1-2 CLASSIFICATION OF FIRE 1-9 The classification of fire Is defined In NFPA 1, Sectlon 3.3. 102 as the following: • Claask Surface Type Fire%; wood or other cellulose-tyl-pe material lordltialy combustibles) • Claw B: Flantunable liquid.-, • Class C: Energized electrIcal equipment • Class D: Combustible metals I such as magnesium, sodium, zirconium. potassium, and titanium) • ClassK: Combustible cooking media Ivegetable or aultual oils and fats) Note: Range Guard Wet Cheiidcal systems is suited ter Class K type of fire. IThis system does wit supersede the requIretnents for portable fire extinguishers as defined lit NFPA 10.) GENERAL CILARACTEU611111CS OF THE BADGER SYSTEM The Range Guard System is a wart chemical fire suppression systrin with one type of agent. Thor system is capable of encompassing a wide variety of application requirements. The system utilizes stored pressure agent cylinders. Stored pressure cylinders; • Remain free of conlanthatlon • Provide a slnooth flow throughout the discharge The cyllndem are powder —coated, wrhded tnlld-steel shell conforming to DOTmC specification 4BW/4RA con -struts lolt and NFPA standards. The valve Is forged brass With nickel plating. The plating and cylinder coating makes It corrosion resistant. R'N 60.9127100.000 111 AVI 11 lip✓ General Information The system can be activated utechanicadly Irotu inan al release. thermo-bulb links. and fusible links. The system can be activated electrically with a 24 Vdc compatible alarm control panel that is tested and listed with the Range Guard system. Both automatic detection and manual release devices are used on control panels. Refer to Paragraph 2-2.1.5 for power requirements. Cylinders are actiimted from stored high-pressure gas. Automatic and manual actuation are available for the Range Guard System. Other actuations are available, such as, Mechanical gas valve closure • Drycontacts for annunciation and electrical slu ldouuu SY 1MM DESCR1pT1ON The Range Guard Wet Chemical '; sWem consists of a supply of wet chanlcal stored In one or more Cylinder and Valve Assemblies — Each cylinder is pressure activated by a System Valve Actuator. The system can be actuated dther autonatically attcl,to' manually, using mechanical, electrical, or pressure actuation devlce_4. Upon actuation, the wet chemical Is discharged through agent distribution piping and specially designed nozzles positioned throughout the protected area. Figitty 1 -1. Typical Range Guard Wet Chentical System Ali i I tWIP 11 PIN 6&91271 OOOOO Component Deacript ion CHAPTER 2 COMPONENT DESCRIPTION The Range Guard Wet Chemical Fire Suppression System consists of the lollowWg components; • Suppression — Agent storage cylinders distribution piping. nozzles. and detection Imechanical and electrical) • Controls • Auxiliary Components Cylinder and Valve Assembly The Wet Chemical Fire Suppression System utilizes five sizes of cylinders. The cylinders consist of a factory -filled wet chemical agent and valve assembly. The cylinders conform to DOTM specification 46V1!r4BA and NFPA standards. Distribution Piping The distribution piping Inot supplied by Badger Fire Protection) is designed to distribute the wrt chemical agent to the hazard areas, In the Mige Guard pre-engineered system, pipe sizes, udillu►um and maximum pipe lengths and number of pipe fitlhlgs are predetermined. S Chapter 3 for more delalls. Nozzles There are seven types of nozzles for the Wet Chemical Fire Suppression System. Each type nozzle has been designed and tested for specific applications and areas of eaverage. The nozz are: • ADP • R • LPF • LPR • GRW • F • DM Detection Devioes There are two met hod% of detection that call be employed In the system: mechanical or electrical. Mechanical detection uses fusible -link or thermo-bulb link detectors to provide reliable performance. The detectors are designed to separate at a specific temperature and release tension on the detection cable which causes the release mechanism to activate. Fusible -link detectors are available in four temperature ratings. and the tlermo-bulb detectors are available In six temperature ratings. Electrical detection uses heat detectors that are equipped with self -restoring, uormnally-of)el coulacts which close when a predetermined temperature Is reached. Heat detectors are avidlabl In six set points, P'N W) 91271(c) 000 2 1 Apr 11 2(X)9 Component Description A Top OF OB1W OF CYLINDER W%LVE OMGMRQPORT I~ C -I 4amNAL CYU NUM OtAWTER Hgure 2-1. (Nniensions of Cylinder and Valve Assembly. PM B-12XXXX Refer to Figure 5-26 for Cylinder Valve details. Table 2-1. C`rltttder and Valve Assembly Siv-eiflrat lofts Ddltoraabtr Amy Put Number Mwel Maximum A B C (Ob P/N) Flow Number 60-120001-001 Rt3-1.25(t 1 I S-1 /4 in. 13,34 in. 8 in. I13120001) 1387 nun) 1349 mm) 1203 mm) 60-120002-001 Ra-2.5G 21 in. 19-5/8 in. 9 in. I13120002) 1534 nun) 1498 mm) 4230 mm) 60-120003-001 Ra-408 12 19 in. 17-1/2 in. 12-1/4 to. 1131200031 1483 mm) 1444 nun 4311 mm1 60-120006-001 RG-40M 12 24-3A in. 23 in. 10 in. IB120006) 1619 non) 1584 nun) 1254 mm) 60-120005-001 Rd-6a 18 35-1 6 to, 33-34 In. 10 in. I13120005) 1802 mm) 1857 nun) 1254 mm) Nate: It is perinisible to use old amteor stew cylinders included In thm manual on a Range Guard systelu. PM 6&9127100.000 23 Alu 112009 System Design 3-7 CYLINDER FLOWS Aller 1hitWtg ttuw tttatty nuzzles d' each type are retlttlred for a system, the sutra of all the nuzzle flow utunbers Ls nsed to detenniue the utunber and size of the cylhiders required, in amord<uice with the cylinder flaw ntunber tissue given below. Table 330. Cyttivicr Elam Nuluhrr Llntlts Maximum Flow Numbers of Cylinders C A irxier flow Number liG.1.25G 4 — Sbigor Cyltmier Systetn+t clash, ica timl nvotifoki) RG•2.5G a — st"gor CylUuier SN-orn" CM4, ttt:otifoki) RG-4G&RG4GM Can manlfoid ttp to 4 tvllnderst 1 Cyltixier 12 2 Cylimlers 24 It Cylindm 36 4 Cylinders 48 I1C1 GCI Can utanifold up to 2 cyllnderat I Cull» der 36 UvIlix1cr., thth, Illce c0indrr!6 can br ttztnifoldrd O.e., four RG•44118 or RG-4CiM: two RG-OG) Ai=11 2(K) + 342 AN 60•9127100000 Component Description 2-1.1.3 1 DISCHARGE NOZZLES There are essentially seven tees (A'nozzles in the Range Guard wet chemical system. They are: • ADP DM A 1® • LPR t:ach nozzle has: • Stainleaq steel Internal strainer and nickel-chronx• plated brava body Special foil seal over the discharge orifice to prevent grease from depositing In the orifice and plugging the nozzle • Grooved rhlgs on the body define the nozzle type I Refer to Table 2-5) • F ,(ly Is stamped with nozzle type said Kldde/RG as shown in Figure 2-6. IN S Figure 2-6. Example of Nozzle Stamped with Nozzle Type and. Kidde/RG Nate: Refer m Table 2-5 for a Ust of old and new Range Guard nozzle part numbers listed with this system. It is permissible to use older andbr newer nozzles included hi Table 2-5 in the same Range Guard system. For example. all old ADP nozzle I PIN B120011) marked "Range Guard" can be used in the same system wlth new nozzles marked "KIDDE/RG". R'N 60 9127100 0W 2.7 Aprf12009 Component Description Table 2-5. RaiW Guard Nozzles NOZ"c Type Part Number IOId Part Number; How Number (honv" ADP Ncw.le 87.12001 1.001 1 1 I D12001 1) F NoMv 87.120012.001 2 2 I ft 1200121 GRW Narnle 87.12001."Ol 1 3 Ili 120013) R Nozzle 87-120014-001 1 4 IB120014) DM Noaale 87-120015.001 3 0 18120015) LI'F Nozzle 87-120022-001 2 1 & 4 1 B 12Ut122) LPR Nozzle 87.12002"01 1 Disc & Com IBI200241 Note: It is perutlsslble to use old and/or new nozzles included in this tuanutaI in a Range Guard systeltt. AFF0 2009 2.8 PRd 60.9127100OW ('i)itiI w)nrnt Irr•:r rtptii)n 1 1. CONTROLS 2-2.1 UNIVERSAL CONTROL HEAD (UCH) Control System, P. N B120099 The UCH Control System. PM B120099. is used far actuating the Range Guard Cylinder and Valve Assembly, The UCH Control System can be attached to the System Valve Actuator, PIN B12O042 for direct cylinder mounting, or to a wall for remote mounting. Knockouts are provided to accommodate either type of mounting. The controller can be operated with: • Automatic mechanical detection Ifusible-links and thermo-bulb links). • Automatic electrical operation, and Remote and local manual operation. AJ 3-3/4 in. (95 mm) 8-3116 in. (208 n11) Figure 2-15, lCN Cutttrul tiystetu, Pr'N B1200fi9 �I 9-7116 in. (240 corn) P,N W-9127100 OW 2 13 Apr9 2("J Component Description 2-2. .1 SY81MM NITROGEN CARTRIDGE. PIN 87-12004"01 (OLD PAY B120043) The UCH Control System uses a nitrogen cartridge for actuating the wet chemical cylinders and Ls charged with dry nitrogen (see Figtu*e 2.16). Tle cartridge 6s mounted inside the UCH Control Svsteur to protect It from tampering and provides the date cA ntanufacturhig and space (gray band) for recording the installation date. cRar BAND I Figure 2-16. System Nitrogen Cartridge. PIN 87-1200434001 Note: New system cartridges (PM 87-120043-001) are marked "PiN 87-120043-001". Old system cartridges WeN B120043) are not marked with a part number. It is permissible to use old and/or new system cartridges included tit this manual in a Range Guard system. 2-2. 1.2 TEST CARTRIDGE, PIN 87-120044-001 (OLD P,W B120044) The Test Cartridge is used for tesUug of the Badger Wet Chemical System. The cartridge has a red band and Is labeled -TEST CARTRIDGE- as shown tit Figure 2-17. Note: The System NltroWn Cartridge PM 87-120043-001 is required for actuation and full discharge or" puff' tests. Q The Teat Cartridge (P;'N 87.120044-001) must be removed and the System Nitrogen Cartridge (P;'N 87-120043-001) must be installed at the completion of any work done on CAUTION the system. [failure to do so will result in malfunction of the system. I 4tn 'I � (t04mm1 Figure 2-17. Test Cartridge, P/N 87-120044-001 NOW New test cartridges (PM 87-120044-001) are marked "PM 87-120044-001". Old test cartridges WIN B120044) are not marked whit a part number. It is permissible to use old attdlor new test cartridges included in this manual In a Range Guard system. Ap il2009 2 14 PrN 60.91271004W 2-11.3 SYSTEM VALVE ACTUATOR (SVA►. PIN 0120042 A Svsterrt Vatic Actuator IWA) Is mounted to c%rnv wet chemical Lvllnder t,ahe assemble Ikcr Flg1re 2-18►. TheSVA has ports for bwprollk• lubbignins, aid is alsoegtdpprd with a sprtltgloaded plintgrr that kx,k� the piston in tlx (1lvc•hargM poxitlon, rimuring complete.(bmlvirgr of tlw cyllnderls) contewt s. SA4Ll WC �T1499)k QM MOLE (1r I QiIOT tWOAM) IN►T PWrT � , / _ -7L ,y4h %, ,n N►T PL ua Of APPLICAOLE) sv►PISTON N 5ogN6 �DArrn SET ►OOWN P STON N ACTLATLD ► W NGtR POSITDN(TOWAOM CO M *A VALVE) Ftjorrr 2-18. S,.sirj" Valk Achs3tor ISVA), P;N n 120042 I' V C091271004U00 2-15 hpT.� <-IrI Component Ueseripthom 2-4.1.6 hDCWGWITCH KIT. P W 8120039. 8120039-801 [YOR UCH) The Microswitch Kit is a Shale pole, double -throw switch late Figure 2-21 and Table 2-7►. Included to the kit Is the microswitch, plgtall assenifbly and four mounting screws ltwo short aid two long) Notes Microswltch Kit RN B120039.501 includes p1giall aawnnbly with white stripers. The wire leads are 24-bnches J610 ni m) in lenob. Four Mlcroswltcln Kits can be remounted in tlnc U(II Control System. There are tvio mounting locations to accontmotfate the four Micraswltch kits (two stacked at each mxnnntlnng locatksntl, with EMT ports far each motintinglot,.dlcun. This allm" for the use of two electrical rnmctionn boxes for seperatloun of sliptal Ibtes and AC lUneas. These are used when It Is uecessaiy to open or close electrical circuits. The following are exarttples. but not Ifni Ited to; • Electric appliance shutdown • Make up air shutdown • Electric gas wahr shutdown • Shnnthreaker,tvby motel Not for aU nn Initiation. Elex•trlculapplian t-exijm)allphavc ahlght-r:in►p ratings lumthe.witrhrs. In thisca.w. ssx•happltsncrs shall trod be wired directly to the nmicroewltch. A naIpnetic contactor or relay mutt be used. To wire the mticroswltch for LICH. refer to Figure 4-30. dEC11rGY Ot1�MEGlOQ K •G MG•O S W TCN Figure 2 21 . %butuvwitch Kit, PeN 0120039 Table 2-7. Microswitch Electrical Rath #p 12!VJ-1II 1Ac W-5 Anlp: 2S0 Yar I -1 l2 HP 125 NW- 1; 2 HP Apr9 IMM 2.1 d PM 111" IV IOD-Cluo ('.omponcnt tN-wrlptlon 2-2.3.2 UNIVERSAL -LINK HOUSING KIT, P.,W 120064 The Unimi sul-L11)k I-lcswshig Kit, ti jovAj to Flgtltv 2.29. oo»slsts of the following: Table 2-12, 1Inwrrxal Ltnk I Imming Ktt. RN 120064 stem Qu " 11- 112 tn. R'Yl tt►ml Dtt"Ior W114hig I t?trnp titee» 't -'S' Hooks 2 Tlne Items above are used to attach the Fluslble-LUnk or T'lienw•Bulb Links to the 06•lnch cable leading todw UCH Control System or A+ Control Hoot. The Llnhrraal-Link Housingcainbeconflgnrod as an Fnd•of-Une or InAlne bracket. V 16 at C ABL E TO CONTROL SYSTEM (NOT 9UPPUEol S' NOOKS �� \ _ r Z THERMO-OUL8 LINK 11.1RM LOCKNUT OR F U348L I! L W - �� M OT SUPPU ® I IN OT SiaPL IE01 T l�RSI O 0 L MM( OR FUSIBLE-LNt (NOT SUPPM01 C FAMP SLEEVE 112 n EMT t10USM4 E1U PLI Of ENDOflM! CONNECTOR EXAMPLE OF Ou5* IS1114"SALNO11Sr WT S. HOOK (NOT SUPPl,lDI UNIVERSAL aKi7 Figire 2.29. Example of Fnd-of-line. and In -line Univer-ml Link I Icnaing Kit, P,N 120064 PM M9127100000 2-35 April 20M IAmponeni fJewripTlon 2-2.3.4 IfUS®LGLINKS, TYPE ML. P11%WK-282fifiI AX111, WK.282062-000, WK-282664 M and WK-282666.000 (OLD PIN B282661. 8282662, U282664 AND B282661f) Fusible -Links are available In %%rlous temperature ratings with a minimummadmum load rating of 10 MAC) lb. 15 kW 18 kg) (sex Tablr 2.14). Figure 2-3 1. Fusible -Link, KEN WK-28266X-000 Table 2-14, Fusible -Link Temperature Ratings >rm"-Unk latlft Ahsimum Expo& re Color Pan Nwabar Temperature ICXd Part NU labor) IWiT (74'C1 1001p(3811 Yellow UW281xwi I -(XX) 1112A26611 212°F (1 OWC 1 150' F (65C I W lrte 1174 282662.000 (82A26621 ]6( P 4182-C 1 30" (149`0 Unpainted A'K.2A2664.000 (B2826641 iW-F 1260T 1 440T f22WICI Orang• W14282B".000 482826661 Motet New type Mi. fusible Links IP1N WK-28 MX,000) are marked"K". (Ad type ML fusible I.Inks (PrN [328266X1) are u>atked "B." It Its permissible to use old m)dou new type ML lusible Links included In this manual in a Range Guard system, The rating temperature. which is stamped on the Fusible-Wnk. is the temperature at which the link will separate when nrw. I lowever, ccntitnual exix)sure to cycling ambient te)nperatureuc may cause a degradatlon of the link omer tlnw. PM fi 9127100000 2.27 Apra ZOM Component Description 1- 3.7 CORM)CR PULLEY. " WK-844648-900 The Corner Pulley Is used to chsuW the direction of the control cable runs. Tly —dAe-s protecthe conduit I la -Inch EMT) Is attached to the Corner Pulleys with thecouphngnuts provided. The Corner Pulley Is ecptlpprd with a hill-txaring pulley for minbnism reslalance to the cable travel. 3R (m2 mm l 31n 1762 mrM Figure 2-33, Corner Mr0ey. PAN WK-844648-900 Pew M912710"00 2-29 Aprf 2W-4 C ompon e 2-2.4.2 I VF-MOTF MANUAL RELEASE PULL STATION, P;'M 60-120110-001 lx• kt•uwtc SlAnual Release Pull Station. shown ith F1Wtr 2.35, Is ptcAyitled as a uteat,.-s ul t,..u, k. i actuatingthe Mtxtn from a remote location, The Remote Manual Release is attached to the Unl%rt I i Control I leadlUCHlor the A+ Control lox. with 1116•inch control cable. The Revitote Manetal Release Pull Station is available for use in both the "unt-tensioned' Pull-to•Ttip and "tensioned' Releaw-to- Trip lines. To actuate Or system at the Renate Manual Release full Staton, pull out the safety pin and pull hard on the handle. In the Pull -to -Trip node (UCH ONLY). tension will be applied to the cable, allowing One UCH to activate the Cylinder and Vale Assembh'. In the Release -to -Trip nwxde, trtn wMg the xafrh• pin will teleaxe tensient from the cable., all(mitig the UCH or A+ Control Boot to act Wage Or Cylinder and Valve Assembly. The Remote Manual Release Pull Station maybe mounted in recess orsutiam mount amtfiguratlon. The assembly is packaWd with all ucoessaty components needed to install in either condoit*aton. Mounting hardware is not included. 1 irb Remote Manual Rrlraxr Pull Station ix xupplird with a chot(x of labels. The proper label muat w attached to the faceplate so as to be easily read alter Installation. Applyltg the libel diet Installation allows forverttcal or horizontal mounting of the Remote Manual Release Pull Station 4.7M in (125mm) ,,$) PULL PIN, PULL a! HANDLE HARD i 2.1r16 en. 182 mml 34116 in 121 mend Fp�ure 2�'Lf;. Rrtnotr Manual Rrlriw� Fhill Stattcnt, P;'N 6Q•120110•Q01 ,4 D r4 : - r r # I 1 L PAY OOxt 1'1; PAP 0,111 Component Damn on 2-&4 91ectrlc Gas Valve, P-Tf 9197XXX Electric GasValm (FIgw)e 2-43)operates on 1120V. 60 Hz) which powers a solenold holdingthe mlve open. This valve is controlled by a pressure switch or micro®wltclu and the Manual Reset Relay Boot, See Parapaph 2-35. UP(m m'Xtem ac uati m. the ckmtm, x1opping the lma flow to the ;qrl8l:o mix). A locs of rImtrlcal power will also cause the Electric Gas Vake to close. See Table 2-18 fora list of the electric ips valve sizes. All Electric Gas Valves must be installed horizontally with the solenoid up. Note: The electric Km valve and the Manual Reset Relay must be specifically UL listed br use with the Ran®r Guard system, t10.�100 Flfpnre 2.43. Electric Gas Valve. WN 9197XXX Table 2-18, Electric t Valve Sizes tiles IhR xme.r L2 Itt t 13 rural 9197017 304 1n 1 19 enrol 9197018 1 tit. (23 rnn I 919,7019 1 • I1 4 on. 432 Turn 1 9197t12D 1.1;'2in. 1 38 run f 9197021 2 bt. t51 Waal 40197rr11 2•Ir1 on, 164 nml 91417444 3 in, 1 76 rrsu I 9197445 t5'DI eln•e127100400o t..stI Ayrr1 P 0 , Component Description 2-3.5 1 Manual Reset Rely for Electric the Valve. P;N 910173Ii The Manual Reset Relay Box WiMire 2.44 and FlgJre 2.451pr(Mdes DPDTcontacts rated for 6 amps it 115 Vac and prewnts Immediate reopening of the Electric Gas Valve WN 9197XXX), Figure 2-45 .h(rwia thr hlanttal Reran Rrky Anne taaml Wwr 2006, Mote: Thr Electric Gas Valve and the Manual Reset Relay must be specifically LIL listed for use with ihr Radar Guard systrtn. I� IM! tltfTirJl [ucnec a►a verve wt*T O u� Figure 2-44. Manual Reset Relay hoot. PM 9 10 1735 f RESET BUTTON ON TOP OF BOX i I CAUTION I GAS BURNERS MUST BE IN'OFF POSITION BEFORE RESETTINRELAY ( TURN OFF POWER SOURCE BEFORF REMM' NG THIS COVER � I MANUAL RESET RELAY i TYPE RB-2 Q F AAIR 115 VAC - F'1LOT DUTY 125 VA l� i `o Ftkurr 2-45. M:iint:d Rrvrt Relay riox, P;N 9101735 (lived BHorr 2006) Apr! 20M l -10 A'N 6" 1271OU iKIO System tff.lgn 3-4 APPLI AIr W Table 3-1 lists the varlous appliances and nozzle type used to protect that appllatoe. Table 3-1. Appliance References Appltatim Norsk Flan Number rmeP Vat "r yutgle Wt Deep Fryer wiAt Di Ip Bu�u d� F'magraplt 3-4.1 F , IS- L2 In. x 24- V2 ht. Deep Fat Freer I magratplt 34.2 421 F t Split WI Deep Fat Fryer Pumosplt 3-4.3 F , 14 In. x 14 in. (356 iron x 356 iron I lJ rp Fat Fryer Paragraph 34A F Shtgle IPyt Deep Fryer with Drip Boards less that I in. (25 mml Paragraph 345 F ' Split Vat Deep Fat Fryer ILos Proxtuttyl Paragraph 3.4jS ADP I De*cp Fat Fryer (Los Proxhattyl Paragraph 34.7 LPF _ Kr>sp►' Kreme Model 270 Wh Dou0mut Fryer Paragraph 3.4.8 ADP Raedes Farr -Horner Raw t'ar age spit 349 R Two-Hurner Hange Paragraph V4.10 k Shtgle Bunter Range Pmagmph 3-4.11 R Four-Bwnet Raiff Para6raph3-4.12 LPR Brollem Upateltt Drotlrrs Ana`roph 3.4.13 ADP Otatbrotkrs (Lsaa. Ptmlee. Ceramic. cc Sptttheitc Ruckl Paragraph 3.4.14 F _ Gas RadaivElemic Cltarbro0er FOragral* 3.4.15 GRW I Natival or Mexquhe Owcoal l7taarbrotkr Paragraph 3-4. IG ADP Mc%quhe I.og>` CharbmUer Paragraph 3-4.17 13M <7uht Broiler lClowd-Topl Paragraph 3-4. IA A13P Cluaht Btalkr IOpert-Topl F%mprph 3-4.19 ADP Odd&e - Flat Cookhtg Surface ParrKt.iph 3.4.20 ADP Suit Pm egra plt 3-4.21 GRW Tilt Udllets Ittrafdng Pansl Paapaph3.4.22 F _ BIN M91271000ct0 .315 AprilLUUJ .1.4, 1 single Vat Deep Fat Fryer With Drip Boards Table 3-2. F Noaale Coverage Area fesss �stasars Maxtmum Kinard Area 18 1n. x 18 in. µ57 mm x 457 mml Mn xhmun AppU NI[r A mA (1i►'ll ll dj i p bKm rd i 18 IIt. x 231n. 4457 nnn x 584 mtn l Nozde Ahn Midpoint ofharard area Nozzk L Icatton (from top d sMltaece at sit atge of 450 w mcre imm the horizontal I 27 bl. 16816 tnlnl M SI. 45 in. It 143 mml Max. tl R.1143 Tr,► AN / NOM E UJV aE l OCR m ANVVISS[At VMfMV M ONO {S �n �1IA1 mm� AN/ NOTES MAT aL IWU C"CPML I"= LOCATSOAMVV"► , AN PONE "T MN TV aft I as n A IAI mmy I MPAt 1 .uwaNf NOPdNTO/ TT n. IMlA/m A1lA iW noI MN IS n i SDT r..r Din rw.. OAI, aQAAD IS In ASTm NAA FIROOIT VEW NOTES IOCAncow air at NO Pt MTrM MOOMOMAI `�♦ Q AN PONT NO/ONI 0 M/d AAD AOMA MA&AD AV OPI I► a OA /O Fltotre 3.2. Sttgk Vat fkxp Fat Fnrr I EIn (SIT of NU D e. C2Hn"*UA)1. AP►UAAICSAASA sam me W April 2OUB 3tl Rod fl" IV IOU4WO 3-4.14, Two Sumter Ranges Table 3.14, R Mwir Cmvrag Arra — Two Bia-urr Ring lotus !"arametwe M.tdutnun hazard L vWh 28 at. 1711 unit I Nmzk Mm Midpoint of hatwd area Notzlr 1"w1na - An}wWr vathin the grew of a c Irde 20 In. Ia(*j nett I Mill. generated by a 9 in. 4229 tcun) radius about the tnld}wutl 42 ut. 11067 unit I Mm x4ft: SbApeof txwner not bnpa"Anl 20 Iv ism mm I MMI €ROM TOP OF RAN GE I If h J467 mm I DIA 42 on. 41067 mm1 MAIL (r1101111 TOP OF RAMGE 1 A R'NOZZLE MAY BE L OC AT E D ANYWHERE Y#TT1aN THE SHAM D AREA ANPalT hNOPaITOf KAZARD AREA ri an (711 R 0 MA% 14 in psa mm 1 MAX 9lJRNER NA7AR0AREA C> LENGTH 11TERLIE TOCFMTERUIE Figure 3.1 1. R Noulr Cvwrag for a 2-Huriwr Rang AyA 2" 3V 1 tt WN 6" Ill IOU (100 Sv%trni Dmi n A-4. IN (;ac Radiact,glodric Charbroller Table 3-21. GRIN Nozzle Umferagr Area A aW RIQUL! ON ae IOCARD ANY WI! R[ tM TMN T►! GRID as.,, i 1P7 nrtb CIAGOrAI ►ROM Mll. AIM fOYr A In It2t9 rNM ae A1tsmm. MAt MAl A<"POW Al MAVK IOCA 1! O ANY WF! a PYIt PN M O NO I r 24 n IetOmm'. AN fOM Mp4M MAL of KAAA/10 AA" s on IOCATON P� d O R MO1K f ROM J1 n iiil�m.+ + AIM►OMI YAX MOPONT Of IMiAPD AR[A R10M/YT urn OAfl K Af/ F� 71 n. fSD rrm;� t1W. A tl .n i010 Tti A/PUAWE AMA WAS FOCUT VIEW am VIEW 1110jie 3 t 7. Gab Radiant-Mectric Clarbroller Dlsar 19raa�etan Ns�lnntm ('clnAdt� tiurtxc 11 Ot x 14 ul ;.i{:( nun to (>10 rnml '�.rttk Attu Mklpuktl !,I! 111� lbac.vtcl arn� alkn� ..ntkmp Riot+� Ncttzk LctczlUutt (ixa�letl at :lII att�Je of �5' <tr tug u r f1• au Ur hclrtrctntwll �' i tlt 1610 uuu l Alin �.�+ 6t 11219 nut I Ma _',rrl 312 NodtfON117IOU QUO system um 3-4.20 (,riddle —Flat Cooking 'surface lWith or without Raised Ribs) Table 3-26. AD11 Nozzle Catrragr Area Mxrhnurn Ruard Area 30 in. x 42 In. (762 corn x IM7 mtnl Nozsk Ahu At a puhu 3 hi 176rund fruni Ili, null-iti t of hacvd At" No"-k 1"-arttrn - any point on the perimeter of 13 h1. CVO nm)l Mb►. apPAla WC 49 ht. 11219rural Mt% NoCot Rtsnton.Ing the nozzk dtrmily aver the applRoux tto l prr rIII l "I 30 Is, (M M MAX 42 in (Mi7 M"O M AX r ow (1219"w") VAX TOPOP A//ItANOE AN POWT J 1w (Tf ae" jAAOiUS MOM TM Ma CW4TOsMAZMOMEA Flgtae 3.22. Griddle - F!ffi Cooking Sur iam R'N M917710040OU AV Aprf 700I0 3-6 V CNTU ATION 3-6.1 1 Plenums Table 3.29. Plehntnt Protertbm System DMIgn ltettn Plara stem ADP Nozzle No F'11ter t 10 ft x 41t. 43 in x 12 ml &Ux. ,N- Ftl ter 10 ft. x 4 1. 43 to x 1.2 tal 20 ft. x 4 R. 0 to x 1.2 in) I - k► -Med at one etitd of Or pantwu 1 - k►cm led of end of paettttta painting iglu* v Stttfor frank Ftltr 10 11. x 4 *. 43 in x 1.2 ml 20 ft. x 4 ft. 05 in x 1.2 tn) t located at one end of the pannun 2 located at a ul of plenum pdntbig tuaw ds W frn no fibers are pre*e•ttt, lite, nook protec-ting the ple stun IF umd to thwit Ce the wart chetttcw out the unde-r- ide of the Itnod. In this c-a e. the hood matt• nag emceed a leigth d to ft l3 ml or a width of 4 ft 1 l 2 ml- Plen»n;�, larger than 10 ft. 0,0 m ) x 4 ft, 11,2 m) may be protected by add Mg add ft tonal ADI' nluxles for estch ackiblonal 10 ft, 11.0 in) of pirtntm length and each additional Oft. 0.2 m) of pkhrtutt wieftlt. N=Jes inay be Installed pobtUttg In the saute ditectlou. attcl.ix at tlw ends of the plenum pobttltW. toward each other Ixee Figtxm 3.28). Fach no¢zlr wig prcMde c%wrngr fora lnctxinnttrt Of 10 ft, 13 m` of pletrunt length and 41 ft. 11.2 in) of plenuial width. ADP nuzdes must be centrally boated In tiro plettunt with d rlf discharge directed alaM the length of the plenum and located in relatlon to the filters as shown in Figwe 3-28. Rrfer to Figtue 3-28 for filter hetfott. AIN 0 912J1uuUOJ 337 System Design DUCT 19Ot21[ lot -V' FILTER BANK COVERAGE 10 ft. 13 ml PLENUM 401 (12 onI 110Q21.E T I H Z "V " FILTE R RANK COVERAGE )ENDVIEW) DUCT • j.1 100 SINGLE FILTER BANK COVERAGE 10 ft.) 3 m ) P LE NUM DUCT low LE / 20 A / K TI W FILTER BANK COVER,', c E 20 R. (A n4 PLE W?M NwZLE 40 0 22 "1 200 (s on) 4A / (1 2 TI>IrJ SINGLE FILTER BANK COVERAGE 20 R. )e ml PLENUM •h,3 wl♦ I I SI NGL E BAN K FILTE R COVERAGE JENDVIEW) IKme 3-28. ADP Protection Nozzle. PIN B 120011 Aptf 20M "4 IM 60-0127100mo 3-6.1 . 1 System L 4s ign DUCTS The ADP nozzle, WN 87-12001 1-001. is used for protection of the exhaust ductwork. The duct crass section can be am, shape. not including obstructions Me- round, square, or rectangular) and the duct Itself can be of tmllntited length. In ace.cmiance. with NFPA %. , the exhaust lan should be left running at the tine of system discharge. Tlls will help to rennove snLoke and other alrbornr materials and Mac's from the hazard area in the event of a fire. Check with the Authority I(avtng.Jurlscliction for local regtlrelltrnts. A damps, if prexent, should be left cyix.n at mstem diselvape. However. it the damper is obeyed. the system desllpter must Insure that additional nozzles are required. I Protection of Ducts O to 80 inches to Perimeter Chie ADP nozzle. WN 87-12001 1-001. is required for protection ad a duct with a perimeter up to 74) Inches Irefrr to Figure 3-291. Length of duct is unlimited. The nozzle Is located at the grometrlc meter of the crass -sectional area that It Is protecting, and is located In the duct wlhtn six inches of thr entrance. Notet All Range Guard systenis are listed by UL and ULC for use with the exhaust lan either on or off when the system is dbchargrd. DUCT HOOD DUCT PERIMETER UP TO AM rtte+e UMIN G S0 n (1 z» men) 11-79 w 13" ww) 16 (ll an MAX MAOOKAL (w+ ww) 1" n - 11 70 n 1300 mm 1 p14 I t MAX®OrAGOgAL VA X "A 90 UAR E O UC T R EC m WOU LAR D UCT 2 -'A' • 2 "B' - 6S n (16S1 wlwtl ROUND DUCT - ADP NO ZZ- L � 0.6.n y152mrni DUCT MTRANC£ t i i OF VMTte:AL DUCT I YE 1"1C Al.'NO ite20 NTAL O UC1 I AM POW I 4 I " rtMOLC IZLE F 10a= fTAL DLPCT 1101 rL 4S1 10 102 wnwr) P NOZZLE TV to DUCT HIP Flgtere 3.Z9. Diicf Pto1e-<tk>n I ktnv Sliwlr ADP Nort:.lr. PrN •57 1 --" I 1 (l01 WN M912710040OO .31M Aprti 20M system 3-6, 111.2 Ducts 50 to 100 inches to Perimeter Two ADP nozzles. WN 87-120011 4001. pohiting to tlw same dtrectlon are required br protection of ducts with perimeters greater than 50 inches and leas than or equal to 100 tnches, Ducts can be of unlimited lengh Irrfer to Figurr 3.30). for other option ofdux,tx ul] to 7:5 perimeter inchlx (Sex Figure 3.32). Notes AD Ranpe Guard systems are listed by UL and ULC for use with the eXhaust fan either oat or off when the system is dlschargrd. '/4u '/Ix I I 25 I.I.03Swnn) MAX ODE 4 MAX DIAGONAL TYP 11 Ten (300 mm I SO,U ARE SEE TRANSITIONAL DUCT PAGE FOR HEIGHT OF NOZZLES IN TRANSITION DUCTS DUCT '/ 1/4d 11A MAX DWAKM31A31tn.(/Mmm) WWZLFSTO BE ALONG ONE . CE NTE RL INE AT TH E 1 N POWT 3 NOZZLESTOBEO-On O.Mmml UP FROM ENTRANCE OF VERTICAL DUCT YAIL 0 AOONAL "-71 n pM mn I ADPNOZaf,, RECTAN OU LAR R OUN O C r AOPNOZZLE 1 DUCT ENT 4L Of VEWOCAL DUCT Ci Of NOt UNWAL DUCT 2 -4 an (51 rnrn • 102 mm) AD► "IM11 ��� Art POINT NOZZLE TIP TO Ol1CT NP VERMAW10RlZMAL DUCT Figure 3-30, Duct Protection l.lsingTwo ADP Nozzles, PiN 87-12001 1-001 Ap r9 1(ICF1 3.36 PM 6040127 IOU oUO tem lW.Al 3-d.1.2.21 T�Worl Dud The propowd protection for transitional duct applications should be approarod by IheAHJ (Authority Having Jurisdiction) prlor to startingthis system installation, Badgrrrecomnxnds that transitional ducts be Imotected as folknvx. Measure the dimenxicns at xtx inches Into the transition piece. Determine the nunther of mmiles reyulred by the perlmeter measured at the six-inch location. Place the tip of the nozzlefsl at six ineb s Into the transition piece. See Figure 3-36. ml Figure 3-34j. Transitional Duct INN W-91271000W S41 Aprf 2CM Dar 3-8 1 PIP'II40 Ric Q u Ot)v11 E flTTS RanW Guard systems do not requtrc balanced piping to achieve proper distribution ion of wrt che►nical to all nozzles, Balanced piping is not necessary because a liquid has no difficulty In turning corners or (hangingdtrecticnts. P--tnW Gtatxi nox4escomr exltutppexi with penu►anent prcdrtet tttliml orlflcvm. This n►eans that the liquid will be delhrered In the exact quantities necessary to the duct. plenum and appliance hazards as required, MI pipe shall be schedule 40 Istandard welo►t) black steel. Pipe may be chrome plated, Galhanized plpr shill not be tuned. All pipe atxi flt11n gx to ust be trade ttggtt wlthotut !ripe dunce or thread sealant. P11te fittings shall brr statatiarci weight steel. cast Iron, malleable trots or ductile tron. Galwanlaxd fittings shall not be used. Branch line connection and lu►ditldual nozzle connections n►ay be made by ttsingelther the outlet or the nm of a tee, 3-&1 Stainless Steel Tubing and FittingA 1 y r Stainless steel tubing may be used on all Range Guard systems. Flith►lgi inay be stainless steel compression or stainless steel flare types. Betldingof tubing using mandrels is permissible. Pipe sislug Pipe sues are detern►Ined by the total nunnber of flow winbers running through a particular piece of pipe, This is the flaw demand for that portion of the system, Note: It Is not permissible to drop pipe diameters below the required ►altx. For example. using 1,2- Inch pipe to flow 18 now numbers Is not permissible. il(rweter. Itcreaxing pipe diameter Is acceptable (ire.. using 1-Inch pipe to flow 18 !low nnn►bers) providing the systen complies with Internal pile volume llmitatlons. Table 3-31. Flaw Number Rangr and Pipe T)jlc now Mamber lllmp MittimIn" Tips Bim AM Wag Staietir" Sxrrl T11hing Size 1-2 I,V-itch 3-fuc11 1-8 344tufi NA 1 — 12 1124nch 5r8•ntwIt i — 24 344nch 7.9.atch 25 — 48 1 • Inch Itch 38.3 General Rules • A maximum of 100 equivalent ft.130.5 m) but not more than 40 linear ft, 412.2 m) of 1/4-In, pipe may be used from each hratw h line. • The h►1jo►est point of the system shall not exceed 121t. 13.7 in) above the cylinder outlet. • The vertical rise of a branch line above the supply line shall not exceed a u►axin►un► of 4 ft. 1.2 m1. • Maxlnnu»u discharge pipe voltnne Ittnnattotia sh:dl not be ew"Ard. • M;Wt num exluulwalent letugih binitatlons shall tu» hr rzrerdrd. • Maxltunutn fkrw lioints for a g)ven piltr shall nol he excvedeci. • There are to be no low points or "traps' }resent In dischuaige piping. PM M91271004000 3 -lr April VIM :3-HAA DiCMCT'OR L)etectors its big Range Guard apprmed fusible link detectors are required over cookbigapploij,cs and In the divix of kitchen cooking eluili nrnt per NFPA 1 7A :aid NFPA 96. For prote•tion oftfir duct. a drte•tor ttnast be (-entered rtIher (hash with the hoo d-dix•I open Ing_ or In the duct but not nwre than 12 feet (3.7 in) downstream bout whete the duct is connected to We hood. When mounted In the duct. the detector should be oriented so that the bracket does not shield the link from the hot air stre nn, and the fiaslhlr link Is centered In the duct. Maximum (1lntetasion per drtrctor is 54 in. x 54 in• (1372 iron x 1372 mint. Alipbatirm havi nga murt:icrarra Larger than 54 in. x .`t4 in. 11372 nun x 1372 nmt) nxltiirr mi(litional detectors. When a cooking appliance is under We hood•dtwt opetilnll, the appliance is protected by the detector mourned at the hood -duct opening or 12 In. 1305 Inc) mandmutn into the duct, An add It kinal drtectior Is not needed to lwotrct th:d aliltlianct. A trinlirratuirr %urvirvi umo be lierforaxsd at all kwationx where drtrctorm will be bnedaIled.Thr mirmy must becondtictedunde uiaxbiiuncooklivgorappliauoecleaniiigcotiditiousInordertodeteimine the optimum exhaust air flow locations and to record the peak temperatures that are expected to occur. Clhwv the %time1' lee completed: • select the iowest temperature rated detector dial can be used, • Make .sure the maxbnttm expostre temperature of the link exceeds the .Rln aim temlorr,t,tre ohtabied from thr survrv. • Make sure links are located In We exhaust air lbw. not In dead air r pacts. This will piovide Uw fastest detector response, Note. Care umst be taken not to install links db vedy In We exhaust flow of appliance Rue W-, 12 en (305 mmi MAX. IF APPUANCE IS UNDER HOOD DUCT OPENING rR-i r r� - am in i--X I X I x I IX I I X 1 x. in- A -4 -I-X- W4 -n (19 owmI 04C1 AOM P1P111110 LIQUID SEALADAPTERS STOVE jI FRYER IS1DYi HARB{tOsiER �*-24in. +f4-24in-01�0-24in-H10.24ect-0114-181n.4� 1*-30det-01 1*— 481ct---01 (610 mend (610 mml 4610 mmi (610 mmi 4457 mmi (762 mmi (1219 mmi 2(W- Flgire 3-40, Posltiming Uetectors 3oci ORIDIDLE UIPRIGt1T [0-- M R —► BROILER 114 Z2 mmi ♦Kin 11'%6f1 kiIjj 1-01,/1,1