FIR2024-0051+Fire_Alarm_Equipment_Specification_Sheets+7.1.2024_1.18.21_PM+4352678SIEMENS Fire Safety HFFx11 FireFirxier' Detector Intelligent Fire Detector for FireFinder XLS and FS-250 Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS Model HFP-11 • Most Sophisticated "Detector Intelligence" available today • Multi -Criteria fire detection for the price of a photoelectric detector • FirePrint1mTechnology to discriminate between deceptive phenomena and an actual fire • Easily programmed to match specific hazard profiles from the control panel • Polarity Insensitive with SureWireTmTechnology • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability • System logic activation based on any of three inputs from detector (smoke, heat or neural network) • Detectors are self -testing, completing diagnostics every 4 seconds • Field cleanable chamber with replaceable chamber parts available • Multi -color detector status LED • Two -wire operation • Compatible Model DPU field device programmer/tester unit • Supports software based automatic environmental compensation • Optional fully programmable relay base, audible base, and duct housing • UL ULC Listed, CSFM, FM, NYMEAApproved Introduction The Siemens Building Technologies, Fire Safety Divi- sion HFP-11 Intelligent Fire Detector provides the life safety industry with the most highly evolved detection system available today. The HFP-11 utilizes advanced detection technology that allows the detector to distinguish non -threatening deceptive phenomena, such as cigarette smoke, from actual fire hazards, while optimizing detection for the area in which it is installed. No other detection system available today offers a higher level of protection or nuisance alarm immunity. The HFP-11 uses state-of-the-art micropro- cessor circuitry with error check, detector self -diagnos- tics and supervision programs. It • The HFP-11 intelligent fire detector is compatible with the Fire Safety Model DPU field device programmer/ tester unit, which is a compact, portable, menu -driven accessory for electronically programming and testing detectors, easily and reliably. The DPU eliminates the need for cumbersome, unreliable mechanical program- ming methods, such as dials or switches and reduces installation and service costs by electronically pro- gramming and testing the detector prior to installation. The HFP-11 fire detector is compatible with the Fire Finder XLS series of control panels. CATALOG NUMBER 6301 Description The HFP-11 is a plug-in, two -wire, multi -sensor detector with both photoelectric and thermal inputs and is compat- ible with Fire Finder XLS and FS-250 series of control panel systems. Each detector consists of a dust resis- tant, field -cleanable photoelectric chamber, a solid state non -mechanical thermal sensor, and microprocessor based electronics with a low -profile plastic housing.The HFP-11 utilizes state-of-the-artASIC circuitry and surface mount technology for maximum reliability. Every HFP-11 fire detector is shipped with a protective dust cover.The HFP-11 fire detector utilizes an infrared light emitting diode (IRLED), and light sensing photodiode. Under normal conditions, light transmitted by the LED is directed away from the photodiode and scattered through the smoke chamber in a controlled pattern.The smoke chamber is designed to manage light dissipation and extraneous reflections from dust particles or other non - smoke airborne contaminants in such a way as to main- tain stable, consistent detector operation. When smoke enters the detector chamber, light emitted from the IRLED is scattered by the smoke particles and is received by the photodiode. The HFP-11 also utilizes a modern, accurate, shock - resistant thermistor to sense temperature changes. The "on -board" FirePrint technology allows the detec- tor to gather smoke and thermal data, and to analyze this information in the detector's "neural network" By comparing data received with the common characteris- tics of fires, or fire fingerprints, the HFP-11 can com- pare these "Fire Prints" to those of deceptive phe- nomena that cause other detectors to false alarm. The advanced FirePrint technology allows the HFP-11 to accurately determine a true fire hazard from a non- threatening deceptive phenomena WITHOUT needing to use alarm delaying verification and confirmation techniques, which can increase the probability of losses due to fire. The HFP-11 provides the highest level of detector intelligence available today with a detector/control panel link that allows the user to program the detector for the specific hazard profile using a simple software menu selection. Detectors are optimized by selecting one of the following eleven applications: • Office/Retail • Lobby • Computer Room • Dormitory • Healthcare • Parking Garage • Utility/Transformer Room • Hostile Environment • Precious Storage • Air Duct • Warehouse/Light Manufacturing The software does the rest; no guessing on detector sensitivities or alarm verification; the control panel programs the HFP-11 detector for the protected area without hassle and without confirmation delays. Once optimized for the hazards in the protected area, the HFP-11 provides the best detection you can buy. Should the operator or installer forget to program the detector, the HFP-11 will revert to a default setting that allows it to operate as an office environment detector. The HFP-11's FirePrint technology monitors input from both the photo chamber and the thermal sensor, evaluating this information with sophisticated math- ematical formulas, or algorithms, comparing this input to characteristics of both threatening fires and decep- tive phenomena that would "fool" any ordinary detec- tor. This technology was developed over years of research and reviewing the results of over 20 years of fire test data in one of the world's most advanced fire research centers. The results of this research are the mathematical models that form the algorithms used in FirePrint. No other fire detector has this level of intelligence or this amount of research and development supporting it's design. The microprocessor's software can identify and disregard false input caused by radio frequency (RFI) and electromagnetic (EMI) interference, and validates all trouble conditions before annunciating or reporting to the control panel. The HFP-11 detector's microprocessor uses an integral EEPROM to store the detector's address and other critical operating param- eters which include the assigned program values for alarm and trouble thresholds. Communications within the detector itself and be- tween the HFP-11 and the control panel, or with the DPU field device programmer/tester unit, are super- vised and safe -guarded against disruption by reliable, microprocessor based error checking routines. Addi- tionally, the micro -processor supervises all EEPROM memory locations and provides a high degree of EEPROM failure fault tolerance. The HFP-11 determines its operating status to be normal, in alarm, or in trouble depending on the difference between the alarm threshold values stored in the detector's memory and the detector's latest analog measurement. The detector then communicates changes in its status to the control panel. In addition, the FireFinder XLS control panel will sample the value of the HFP-11's analog signal over a period of time in order to determine if those values indicate excessive buildup in the photo chamber; if so, the FireFinderXLS control panel will indicate that the particular detector requires maintenance. The HFP-11 is listed as a self -testing device.The HFP-11's visible light emitting diode (LED) flashes green every 4 seconds to indicate it is communicating with the control panel and that it has passed its internal self -test. Should the detector sense a fault or failure within its systems, the LED will flash amber and the detector will transmit that information to the control panel. A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the Fire Finder XLS panel indicating the status and settings assigned to each individual detector. When the HFP-11 moves to the alarm mode, it will flash red and to continue flashing until the system is reset at the control panel. At that same time, any user defined system alarm functions programmed into the system are activated. Detector sensitivity, calibration, and identification are dynamically supervised by the control panel. Detector sensitivity and pre -alarm levels are a function of the application chosen at the control panel and are controlled by the panel. If an alternate, non-FirePrint mode is selected, then the sensitivity can be changed from the control panel. The DPU Device Program/Test Unit accessory is used to program and verify the detector's address. The technician selects the accessory's program mode to enter the desired address. The DPU automatically sets and verifies the address and tests the detector. The DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment almost anywhere. When in the test mode, the DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. The HFP-11 fire detector may be installed on the same initiating circuit with HMS series manual stations, HTRI series interfaces, HCP output control devices, or HZM series of addressable, conventional zone modules. All HFP-11 detectors can be cleaned in the field, when required, by simply removing the detector cover and unsnapping the photo chamber. There is also the option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and bug screen included in the detector maintenance kit, model D M K-11. The HFP-11 uses the low -profile surface mounting base, model DB-11. This base mounts on a 4-inch octagon, square, or a single gang electrical box. The base utilizes screw clamp contacts for electrical connections and self -wiping contacts for increased reliability. The base can be used with the optional LK-11 detector locking kit which contains 50 detector locks and an installation tool, to prevent unauthorized removal of the detector head. The DB-11 base has integral decorative plugs to cover the outer mounting screw holes. All HFP-11 detectors are approved for operation within the UL specified temperature range of 32 to 100 degrees F (0 to 38 degrees Q. Application Data Installation of the HFP-11 series of fire detectors requires a two -wire circuit. In many retrofit cases, existing wiring may be used. 7-tapping" is permitted only for Style 4 (Class B) wiring. The HFP-11 is polarity insensitive. This feature can greatly reduce installation an debugging time. HFP-11 fire detectors can be applied within the maximum 30 foot center spacing (900 sq. ft. areas) as referenced in NFPA 72. This applications guideline is based on ideal conditions, specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Fire Safety distributor or sales office whenever you need assistance applying FirePrint in unusual applications. Be sure to follow NFPA guidelines and UL/ULC approved installation instructions, which are included with every Fire Safety detector, and local codes as for all fire protection equipment. Dimensions Technical Specifications Operating Temperature: +32°F (0°C) to 100°F (38°C) per UL 268/268A Humidity: 0-93% Relative Humidity Non -Condensing Maximum spacing: 30 foot centers (900 sq. ft.) per NFPA 72 Chapter 5 and CAN/ULC-S524 Morsel Description Part Namur HFRII Addressable FirePrint Fire Detector 5001133290 DB-11 Detegor Mounting Base for Sores I 50D•094151 DBAIE Detector Ban Ismaili 500-094151E AD• 11 P I Apr Duct Housing for Series 11 500-099556 AD-HR Air Duct Housing wlRelay for H-Series Intelligent Detector 500-033280 DB-HR Relay Base for H-Series Intelligent Detectors 500-033220 ADBH, ll Audible base 5OD MIO RL-HC Remote Iredl alarm indicator. 4' on box mount 5OD-033230 RL14W Remote Iredl alarm indicator- single gang box mount 500-033310 LK-11 Base Locking Yit for Series 11 detectors 500-6900 DMK-11 Series 11 Maint Kit Ireplacernent labyrinth and bug bug screen) 50D-695338 In Canada Order. HFP-11C Addressable FirePrint Fire DetectoflUl.Q 50aD95112C DBA I C Detector Mountin Base `or Series 111ULC1 50C_D9%87 AD-11 PC Air Duct Housing {ULC} 50C-D95%4 DB-HRC Relay Base for Series 11 Intelligent Detectors (ULC) SOG03321CC. ADBH-11C Audible Base for Series 11 Intelligent Detector (ULC) St1C-11332-r.1C NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems. Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Siemens BuildingTechnologies Tel: (973) 5593-600 Thll 9 FAX: (973) 93-6670 Fire Safety Website: www.sbt.siemens.com/fis 10/05 5M SFS-IG Printed in U.S.A. Fire Safety 2 Kenview Boulevard Brampton, Ontario Canada L6T 5E4 Tel: (905) 799-9937 FAX: (905) 799-9858 October2005 Supersedes sheet dated 7103 Exceder LED Horn Strobes, Strobes & Horns Description The Wheelock Exceder TM Series expands to include the industry's first LED notification appliances in one of the smallest, most compact single gang designs in the world. The LED patented technology by Eaton's Cooper Notification's business provides the industry's lowest current draw. Ideal for Green Buildings, it's the pinnacle of life safety, performance and energy -efficiency. As the first notification appliances in the industry to utilize Light FIRE Emitting Diode (LED) as the light source, this breakthrough and patented optical design, resulting in best -in -class efficiency, enables material and system cost savings, allowing for a greater number of appliances on the notification appliance circuit and fewer power supplies. All strobe models feature a wide -range of candela settings (15, 30, 75, 110cd) on a single appliance. Models with an audible feature 2 sound settings (90 & 95 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. ,6A _ Wheelock ExcederTm LED strobes, horn strobes and horns feature the industry's smallest footprint and a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including lowest current draw, single -gang design, no tools needed for setting changes, and three convenient mounting options for both new and retrofit construction. These products are suitable for indoor wall - mount applications. The LST Strobe, LHS Horn Strobe, and the LHN Horn are for 24V operation. LHN is suitable for 12V applications. The ExcederTm LED notification appliances are listed under UL Standards 1971 and 464 and under CAN/ULC-S525 and CAN/ULC- S526. Exceder LED Strobes and Horn Strobes may be synchronized when used in conjunction with the Wheelock DSM Sync Modules, Wheelock Power Supplies, SAFEPATH family of products or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. FM,TON Powering Business Worldwide Technical Data TDO01003EN Effective May 2014 Exceder LED Horn Strobes, Strobes & Horns Features • Energy Efficient • Patented LED technology provides industry's lowest current draw • Fewer power supplies required, smaller wire gage, reduced wire runs • Low -Profile Design • One of the smallest, most compact single -gang designs • Sleek, modern aesthetics with no visible mounting screws • Special Lettering Available • 4 Field Selectable Settings in 1 Device • Select 15, 30, 75, 110 cd • 2 Audible Settings • Select 90 or 95 dB • Select temporal or steady horn output • Easy -to -Install • Finger slide switches —No tools needed for setting changes • IN/OUT screw terminals using #12 to #18 AWG wires • Mounting Options include Exceder LSBB, any single -gang back - box and to 4" square with adapter kit • Strobe Synchronization Components • Meet synchronizing standards with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies or SAFEPATH products • Compliance • U L 1971, U L 464, U LC-S525, U LC-S526 • Factory Mutual (FM) • California State Fire Marshal (CSFM) • FCC Part 15, ICES Note: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range:' Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL 1971. Drawings Figure 1. Wall Strobe Figure 2. Wall Horn Strobe 2 EATON www.eaton.com Exceder LED Horn Strobes, Strobes & Horns Technical Data TDO01003EN Effective May 2014 Table 1. Strobe Ratings Table 2. Horn Ratings UUULC Max Current O Exceder LED Strobes 24VDC Exceder LED Horns Regulated Voltage Regulated Voltage Model Range VDC 15 30 75 110 Model Range VDC 95 dB 90 dB LST 16.0-33.0 0.030 0.040 0.115 0.200 LHN 8.0 -17.5 0.024 0.018 LHN 16.0 - 33.0 0.030 0.022 Table 3. Code 3 Horn Strobe Ratings UUULC Max Current O at Anechoic 95 dBA UL/ULC Max Current O at Anechoic 90 dBA Model Voltage (1) 15 30 75 110 VoltageOO 15 30 75 110 LHS 16.0 -33.0 0.040 0.046 0.125 0.219 16.0 -33.0 0.038 0.042 0.122 0.209 Table 4. Specification & Ordering Information Sync w/ DSM or Model Order Code Strobe Candela Red White Lettering Wheelock Power Supplies Horn Strobes LHSR 0526 15/30/75/110 X FIRE X LHSW 0527 15/30/75/110 X FIRE X LHSR-A 0740 15/30/75/110 X AGENT X LHSR-N 0741 15/30/75/110 X No Lettering X LHSW-A 0742 15/30/75/110 X AGENT X LHSW-AL 0743 15/30/75/110 X ALERT X LHSW-N 0744 15/30/75/110 X No Lettering X Strobes LSTR 0528 15/30/75/110 X FIRE X LSTW 0529 15/30/75/110 X FIRE X LSTR-A 0747 15/30/75/110 X AGENT X LSTR-AL 0748 15/30/75/110 X ALERT X LSTW-A 0749 15/30/75/110 X AGENT X LSTW-AL 0750 15/30/75/110 X ALERT X LSTW-N 0751 15/30/75/110 X No Lettering X LSTR-N 0754 15/30/75/110 X No Lettering X Horns LHNR 0530 X X LHNW 0531 X X Accessories LSBB-R 2420 Exceder LED Backbox X LSBB-W 2403 Exceder LED Backbox X ESB-KIT-R 0533 Exceder LED Trim Plate X ESB-KIT-W 0534 Exceder LED Trim Plate X Table 5. Specifications Physical Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating Weight .035 lbs. Lens Light Emitting Diode (LED) in a rugged Lexan lens Dimensions 4.53"H x 2.76 W x 1.27" D; Trimplate: 5.25" H x 4.58W x 0.32 D Operating Temperature Indoor: 33.8°F to 120.2°F (0°C to 49°C) and maximum humidity of 93% Mounting & Wire Connections Mounting (indoor only) Wall -mount applications only. Single -gang, Exceder LSBB backboxes or to 4" square with adapter kit Wire Connections #12 through #18 AWG Power & General Operating voltage 12 VDC: 8 - 17.5 VDC; 24 VDC: 16 - 33 VDC (12 VDC LHN models only) Strobe Output Rating UL 1971, ULC S526: Selectable 15, 30, 75, 110 candela output Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes can be synchronized with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies or SAFEPATH products, using Wheelock patented sync protocol Temporal Audible Pattern Selectable Continuous or Code 3 Horn tone: The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 sec- ond off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. ,O RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. (2) Regulated Voltage Range- VDC EATON www.eaton.com 3 Technical Data TDO01003EN Effective May 2014 Exceder LED Horn Strobes, Strobes & Horns Architects and Engineers Specifications The LED notification appliances shall be Wheelock(D ExcederTM Series LHS Audible Strobe appliances, Series LST Visual Strobe appli- ances and Series LHN Audible appliances for wall -mount applica- tions with a low -profile design or approved equals. The Series LHS and LST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing -Impaired) for Indoor Fire Protection Service. The Series LHS and LHN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the require- ments of FCC Part 15. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 16 to 33 VDC. The Series LHS Audible Strobe and LST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Light Emitting Diode (LED) as the light source with a rugged Lexan@ lens. The Series shall be of low current design. Where Multi -Candela appliances are specified, the strobe intensity shall have 4 field selectable settings at 15, 30, 75, 110, candela for wall mount applications. The selector switch for selecting the candela shall be tamper resistant. Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of two (2) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series LHS Audible Strobe, LST Strobe and Series LHN Audible mounting options shall include LED backboxes, single -gang backbox and to 4" square with adapter kit. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). All notification appliances shall be backwards compatible. The Series LHS, LHN and LST wall models shall have a low profile measuring 4.53"H x 2.76"W x 1.27"D. When synchronization is required, the appliance shall be compat- ible with Wheelock8's DSM Sync Modules, PS 6/8 Power Supplies, SAFEPATH products or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non -synchronized flash - rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible sig- nal may be silenced while maintaining strobe activation when used with Wheelock@ patented sync protocol.. UL 1971, UL 464 ULC-S525, ULC-S526, CSFM, FM, FCC, ICES Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. I WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Cooper Notification 273 Branchport Ave. Long Branch, NJ 07740 C oo p e r N of if i cation . co m © 2014 Eaton All Rights Reserved _ Printed in USA Publication No.TD001003EN Powering Business Worldwide May 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners. Exceder LED Horn Strobes, Strobes & Horns <<' Description I I I I Eaton's Cooper Notification business has designed the Wheelock Excederrm LED Horn Strobes, Strobes and Horn Series with the industry's lowest current draw and an aesthestically-pleasing low - profile design for indoor ceiling -mount applications. Ideal for Green Buildings, it's the pinnacle of life safety, performance and energy - efficiency. l � rn As the first notification appliances in the industry to utilize Light Emitting Diode (LED) as the light source, this breakthrough and patented optical design, resulting in best -in -class efficiency, enables material and system cost savings, allowing for a greater number of appliances on the notification appliance circuit and fewer power supplies. All strobe models feature a wide -range of candela settings (15, 30, 75, 95 cd) on a single appliance. Models with an audible feature 2 sound settings (90 & 95 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wheelock ExcederTm LED strobes, horn strobes and horns feature the industry's smallest footprint and a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including lowest current draw, no tools needed for setting changes, and convenient mounting options for both new and retrofit construction. These products are suitable for indoor ceiling -mount applications. The LSTC Strobe, LHSC Horn/Strobe, and the LHNC Horn are for 24V operation. _HNC is also suitable for 12V applications. The ExcederTm LED notification appliances are listed under UL Standards 1971 and 464 and under CAN/ULC-S525 and CAN/ULC- �� S526. The appliances are Restriction of Hazardous Substances (RoHS) compliant and contain no mercury or other hazardous substances. Exceder LED Strobes and Horn Strobes may be synchronized when used in conjunction with the Wheelock DSM Sync Modules, Wheelock Power Supplies, SAFEPATH family of products or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. FM,T*N Powering Business Worldwide Technical Data TDO01004EN Effective July 2014 Exceder LED Horn Strobes, Strobes & Horns Features • Energy Efficient • Patented LED provides industry's lowest current draw • Fewer power supplies required, smaller wire gauge, reduced wire runs Restriction of Hazardous Substances (RoHS) • Low -Profile Design • One of the smallest, most compact ceiling designs • Sleek, modern aesthetics with no visible mounting screws • Special Lettering Available • 4 Field Selectable Settings in 1 Device • Select 15, 30, 75, 95 cd • 2 Audible Settings • Select 90 or 95 dB • Select temporal or steady horn output • Easy -to -Install • Finger slide switches —No tools needed for setting changes • IN/OUT screw terminals using #12 to #18 AWG wires • Mounting Options include Exceder LSPKBB-C backboxes, 4" square, 1 1/2 or 2 1/8"deep and 4" Octagonal, 1 1/2" or 2 1/8"deep • Strobe Synchronization Components • Meet synchronizing standards with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies or SAFEPATH products • Compliance • UL 1971, UL 464, ULC-S525, ULC-S526 • California State Fire Marshal (CSFM) • Factory Mutual (FM) • RoHS • FCC Part 15, ICES Note: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range:' Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL 1971. Drawings Figure 1. Ceiling Horn Strobe - Top View 1.50 1.87 — Figure 2. Ceiling Horn Strobe - Side View 2 EATON www.eaton.com Exceder LED Horn Strobes, Strobes & Horns Technical Data TDO01004EN Effective July 2014 Table 1. Strobe Ratings Table 2. Horn Ratings UUULC Max Current a Exceder LED Strobes 24VDC Exceder LED Horns Regulated Voltage Regulated Voltage Model Range VDC 15 30 75 95 Model Range VDC 95 dB 90 dB LSTC 16.0-33.0 0.040 0.058 0.155 0.258 LHNC 8.0 - 17.5 0.025 0.020 LH N C 16.0 - 33.0 0.037 0.026 Table 3. Code 3 Horn Strobe Ratings UUULC Max Current a at Anechoic 95 dBA UUULC Max Current a at Anechoic 90 dBA Model Voltage b 15 30 75 95 Voltageb 15 30 75 95 LHSC 16.0 -33.0 0.049 0.063 0.174 0.273 16.0 -33.0 0.042 0.062 0.170 0.270 Table 1. Table 4. Specification & Ordering Information Sync w/ DSM or Model Strobe Candela Red White Lettering Wheelock Power Supplies Horn Strobes LHSRC 15/30/75/95 X FIRE X LHTWC 15/30/75/95 X FIRE X Strobes LSTRC 15/30/75/95 X FIRE X LSTWC 15/30/75/95 X FIRE X LSTRC-AL 15/30/75/95 X ALERT X LSTWC-AL 15/30/75/95 X ALERT X Horns LHNWC X No Lettering X LHNWC X No Lettering X Accessories LSPKBB-CR Exceder LED Backbox X LSPKBB-CW Exceder LED Backbox X Table 5. Specifications Physical Material Red or white textured UV stabilized, colored impregnated engineered plastic. Exceeds 94V-0 UL flammability rating Weight .035 lbs. Lens Light Emitting Diode (LED) in a rugged Lexan lens Dimensions 6.26" Diameter x 1.5" D Operating Temperature Indoor: 33.8°F to 120.2°F (0°C to 49°C) and maximum humidity of 93% Mounting & Wire Connections Mounting (indoor only) Ceiling -mount applications only. Exceder LSPKBB-C backboxes or to 4" square, 1 1/2 or 2 1/8"and Octagonal, 1 %2" or 2 1/8"deep Wire Connections #12 through #18 AWG Power & General Operating voltage 12 VDC: 8 - 17.5 VDC; 24 VDC: 16 - 33 VDC (12 VDC LHN models only) Strobe Output Rating UL 1971, ULC S526: Selectable 15, 30, 75, 95 candela output Strobe Flash Rate Strobes are designed to flash at 1 flash per second Synchronization Models Strobes and horns can be synchronized with Wheelock's DSM Sync Modules, PS-6/8 Power Supplies or SAFEPATH products, using Wheelock patented sync protocol Temporal Audible Pattern Selectable Continuous or Code 3 Horn tone: The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. a RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. b Regulated Voltage Range-VDC EATON www.eaton.com 3 Technical Data TDO01004 EN Effective July 2014 Exceder LED Horn Strobes, Strobes & Horns Architects and Engineers Specifications The LED notification appliances shall be Wheelock@ ExcederTM Series LHSC Audible Strobe appliances, Series LSTC Visual Strobe appliances and Series LHN Audible appliances for ceiling -mount applications with a low -profile design or approved equals. The Series LHSC and LSTC Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing -Impaired) for Indoor Fire Protection Service. The Series LHSC and LHNC Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). The Series shall be Restriction of Hazardous Substances (RoHS) compliant and contain no mercury or other hazardous substances. All Series shall meet the requirements of FCC Part 15. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 16 to 33 VDC. The Series LHSC Audible Strobe and LSTC Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Light Emitting Diode (LED) as the light source with a rugged Lexan@ lens. The Series shall be of low current design. Where Multi -Candela appliances are specified, the strobe intensity shall have 4 field selectable settings at 15, 30, 75, 95 candela for ceiling -mount applications. The selector switch for selecting the candela shall be tamper resistant. Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of two (2) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series LHSC Audible Strobe, LSTC Strobe and Series LHNC mounting options shall include LED Ceiling backboxes, 4" square, 1 1/2 or 2 1/8"deep and 4" Octagonal, 1 1/2" or 2 1/8"deep. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). All notification appliances shall be back- wards compatible. The Series LHSC, LHNC and LSTC ceiling models shall have a low profile measuring 6.26" Diameter with 1.5"D. When synchronization is required, the appliance shall be compat- ible with Wheelock®'s DSM Sync Modules, PS 6/8 Power Supplies, SAFEPATH products or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non -synchronized flash - rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible sig- nal may be silenced while maintaining strobe activation when used with Wheelock@ patented sync protocol.. UL 1971, UL 464 ULC-S525, ULC-S526, CSFM, FM, FCC, ICES, RoHS Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton Cooper Notification 273 Branchport Ave. Long Branch, NJ 07740 C oo p e r N of if i cation . co m © 2014 Eaton All Rights Reserved _ Printed in USA Publication No.TDO01004EN PoweringBusiness Worldwide July 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners. SIEMENS Data sheet Fire Safety & Security Products Specialized Detection Devices `DB' Series Detector Bases Models D132-HR, DB-11 and DB-11 E ARCHITECT AND ENGINEER SPECIFICATIONS • Each detector base is compatible with Model 'H',"11" and "121" series of conventional detectors - All bases compatible with the optional Model LK-11 detector -locking kit • Each detector base also functions with the addressable Model'H'series, as well as Models FD0421, FDOT421, FDOOT441, FDOOTC441 and FDT421 intelligent devices Model DB2-HR is also compatible with ASAtechnology"' detectors Model D132-HR has backwards compatibility with Siemens Model'H'-series intelligent detectors • Models D13-11 and D13-11 E mount on a 4-inch square, octagon or single -gang electrical box - Model D13-11 has plugs to cover the outer -mounting screw holes • Model D132-HR mounts on a 4"-square, double - gang electrical box Product Overview The detector bases are low -profile, surface -mounting bases used on various Siemens— Fire Safety conventional and addressable detectors. Model D132-HR, which is a redesign of Model DB-HR, is compatible with the standard, addressable type of intelligent detectors, as well as those detection devices that operate with ASAtechnologyTM. Additionally, Model D132-HR is backward compatible with the Siemens Model 'H'-series intelligent detectors and detector -assigned FACPs. Model D132-HR can also operate with Siemens' 252-point addressable, 504-point addressable and FireFinde&XLS fire systems. A relay output from the fire detector base for signaling other devices is provided by Model D132-HR. The detector bases use screw -clamp contacts for electrical connections and self -wiping contacts for better reliability. Further, the bases can be used with the optional Model LK- 11 detector locking kit, which contains 50 detector locks and an installation tool, to prevent unauthorized removal of the detector head. Specifications Models D13-11 and D13-11 E are the standard bases for Model 'H'-series 11" and Model 121 "-series conventional detectors, as well as the Model'H'-series addressable detectors. Model D13-11 has a 6-inch (15.2 cm) diameter. The diameter for Model D13-11 E is 4.5 inches (11.4 cm). A& Model DB-11 E Model D13-11 • OUL 268 Listed, ©ULC-S529 Listed; FM, CSFM and NYC Fire Department Approved Specifications — (continued) Moreover, Models D13-11 and D13-11 E mount on a 4"-square, (10.2 cm) octagon or single -gang box. Model D13-11 has integral, decorative plugs to cover the outer screw holes. However, Model D132-HR mounts on a double -gang, 4-inch (10.2 cm.) square electrical box. Dimensions 1 r-----6" (11.4 cm.) Diameter I 7/2" {t _27 cm) E C4� l ie' Diameter 4-1/8" rio_5 cm.I Diameter Note: Model D13-11 E base detector has a diameter dimension of 4.5" (11.4 cm.). Mounting Diagram O„BLE-GANG BOX Model DB2-HR 34 -INCHES DEEP 4-INCH SQUA E BO o 0 2-118-INCHES DEEPo o' r��o�� • Q o 0 o d o 0 BREAK OFF THIS SECTION WHEN USING A DOUBLE - GANG BOX NOWS: The Module Barrier (shown to the right) must be used when Model DB2-HR relay contacts are connected to non -power -limited circuits. Break apart the barrier to the correct size and shape 6161 C for either the 4-inch square or double -gang box. Install the barrier diagonally into the back box Detector Bases ['DEI' Series to create two (2), separate compartments with the back box, in order to separate the wires. SIEMENS Canada Limited Wiring Diagrams 1n0REiIDTEDI lC9 1b (RelaDif REIA TO enn.. REsrDTE D RUC O GETNLS r.-0' .l]Erd to tb l�llltl\WigR • 5 pst-11 pM rA�rn� 11R Fl S c-m.il R9AGtL R_ pM 515 — CMRIORt ` 5 AD&tt 5 Ke REYDIEBENI'EA CAUTION: sNMneeeuma Ms.wroRes eyrnesuury awt...na.wore...m.y I. Do not use looped wire under base to rminel5. Breakwire wexrermemw.wmsr nle+RN mmBneume.�a nRrnve my u n to provide supervision of c,nn,,ti,n. 2 _ 2. When a re mote relay is used le c,na,l a critical system R&lt RLD-tt.RWFIt gee faAonx function,th—Nyenditsessocieted detectorendopbonal e.RWII 1xR--1 mod ulels) must be ee ONLY devices on the indiatin circuit. Note: The illustration above is typical wiring for Models DB-1land D13-11 E (using Models PE-11, PE-11T, DT-11, OP121, OH121, and HI121 detectors). UIS-11F11 e,(Nu KtIAVI e, u—) U15-1I-5(K-11E KGL/,T Ill IU-1WKUI + USE AN END OF TO NITIATIN6 LINE DEVICE CBiCUTOf 5 1a AL Or ,Sa 8 1b OINITACTS EaSIEMENS 1.I cDO rNaO�ie B3ie_ NdGTOR fr 1 v� CONTRA UNIT MOOg.4 131-1/RLI-2 DO NOT USE AN — are shown in Me Non-Alamt/Systent Reset -'-_ iddlon. TO TEXT END OF _� LINE BASE DEVICE _ 'The relay contacts Note: The illustration above is typical wiring for Models D13-11 and D13-11 E (using Models FP-11, FPT-11, FS-DP, FS-DPT, and FS-DT detectors). 06-11(NO REMOTE DEVICE) DB-HR (REMOTE RELAY` BASE', TO NEXT BASE DD NOT MJW'I-- To USE AN END OF LINE O DEVICE ORly' RELAvOPTICINVIL 5 a900 E(OI-NCNoICaDR raz 1 � }3n Nzo vnc ACTS 6 1b Ja_ (NcCOIAODELS 3A, :10 VNo DC DO NDT RL�MI/RLa1C TB3 USE AN EID LINE 'The relay contacts are shown n the Nori-AlarnllSystem Reset conditel To TEXT BASE DEVICE ^HFP-11/HFPT-11/HF Po.11/SFP-11/SFPT-11/SFPO-11 s a polarity irsensdive detector. Line 1 and Line 2can be enter Yne of thelocp. NOTE: SFP-11 Series detectors are approved for use in Canada only. Note: The illustration above is typical wiring for Models D13-11 and D13-11 E (using Models HFP-11 Series and SFP-11 Series detectors). s�NE 1 _ TO RE%T DEVICE DO NOT USE AN END (EMOTE RELAYBASE MOM CBZM Oc LrE CEV CE B WLRATN0.24%M 20%A m osmTNB W WT 6 BEIB6BpAIW BC. C011111�IMI8 //�� �pe1e } _ CONTACTS TIE RELAY COMALTB ARE SWIM N1FE L e/ lll�� J 1pV� x RN?1hlARWSYBTEM D ESET Q.p TON UE2 10=1 WFEB='I TOTBl'1B!NVST CONEDlE.T. TB,i F TBt.S ~ ENTER OR E%R BEGIPoCALBm(QJOiPOfi.IE USED iNMK PO OR NpNPOMR �! UMTED TO NEXT DENCE DO NOT UEANEFD Oe UNE DEV CE SDE OF'w RES APPLGTON Note: The illustration above is typical wiring for Model DB2-HR for polarity -insensitive detectors). Details for Ordering Model Number Part Number Description AD2-P 500-649706 Air -Duct Housing AD2-PR 500-649707 Air -Duct Housing with Relay D13-11 500-094151 Low -Profile Surface -Mount Base DB-11 C 500-095687 Low -Profile Surface -Mount Base [Canada] DB-11 E 500-094151 E Smaller -Diameter Detector Base DB-HR 500-033220 Relay Base for'H'-Series Intelligent Detector DB2-HR S54370-Fl2-A1 Relay base compatible with'S'-Line and 'C-line detectors; backwards compatible with Model'H'-series detectors DT-11 500-095430 135DF ]57.2DC]Low-Profile Thermal Detector DT-11 C 500-095983 Low -Profile Thermal Detector [Canada] FD0421 S54320-F4-A1 Photoelectric Smoke Detector FDOT421 S54320-F6-A1 Addressable Multi -Criteria Fire Detector FDT421 S54320-F5-A1 Thermal (Heat) Detector FDOOT441 554320-F7-A1 Multi -Criteria Fire Detector with ASAtechnolo TN FDOOTC441 S54320-F8-A1 Multi -Criteria Fire I CO Detector with ASAtechnolo TN LK-11 500-695350 Base Lockina Kit for Model I l'-series detectors Model Number Part Number Description FP-11 500-095112 FirePrint"m Intelligent Detector FP-11C 500-095112C FirePrintTNIntelligent Detector[Canada] FPT-11 500-095918 Thermal Detector FPT-11C 500-095918C Thermal Detector [Canada] HFPO-11 500-034800 FS-250 Addressable Detector HFP-11 500-033290 FirePrintTNDetector HFPT-11 500-033380 Thermal Detector H0 21 S54372-F3-A1 Heat Detector OH121 S54372-F2-A1 Multi -Sensor Smoke Detector OP121 S54372-Fl-Al Photoelectric Smoke Detector PE-11 500-094150 Conventional Photoelectric Smoke Detector PE-11 T 500-095150 Photoelectric Smoke Detector with 135DF f 57.2°C] Thermal Sensor SFP-11 500-33290C Photo / Thermal Detector [Canada] SFPO-11 500-34800C Photo Detector [Canada] SFPT-11 500-033380C Detector Package [Canada] Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product's installation instructions. Fire Safety SC, Ltd. 2 Kenview Boulevard SIEMENS Canada, Limited URL:www.USA.Siemens.com/Desigo-Fire-Safety Brampton, Ontario September2012 L6T 5E4 / Canada Supersedes sheet dated 4/12 Tel: (905) 799-9937 (Rev. 1) FAX: (905) 799-9858