FIR2024-0051+Fire_Alarm_Plan+7.1.2024_1.19.00_PM+4352685w Q I FAWALN
Ligle -AL 4w
FIRE ALARM TENANT IMPROVEMENT
SHEET # SHEET TITLE
FA01 SYSTEM INFORMATION
FA-02 TYPICAL WIRING, MOUNTING DETAILS & CALCULATIONS
FA-03 PARTIAL FIRST FLOOR FIRE ALARM T.I. LAYOUT
SHEET INDEX
TYPE
OF
WORK: BUILDING FIRE ALARM
SYSTEM
INSTALL (1) SMOKE
& (2)
HORN/STROBES TO EXISTING CIRCUIT ON
EXISTING PAD-4 NAC.
SCOPE OF WORK
GUARDIAN SECURITY
1743 1ST AVE. S., SEATTLE, WA 98134
1 -(206) 622-6545
MONITORING COMPANY
WIRE SCHEDULE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION
NUMBER OF CONDUCTORS SIZE
TYPE COLOR CODE
D DATA LINE - ADDRESSABLE LOOP
TWISTED PAIR WITH SHIELD #16
FPL/FPLR RED (JACKET)
S SIGNALING CIRCUIT - FEED
TWO #14
FPL/FPLR RED (JACKET)
S$ SIGNALING CIRCUIT - RETURN
TWO #14
FPL/FPLR RED (JACKET)
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS
WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V
#12 AWG THHN/THWN .244
O.D. .0467
TWO 600V
#14 AWG THHN/THWN TWISTED .210
O.D. .0346
TWO CONDUCTOR 300V
#18 AWG FPL TW CABLE .156
O.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT
FROM THE TABLE
ABOVE. CHOOSE THE SIZE
OF CONDUIT BASED ON THE MAXIMUM FILL
DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE
WIRE.
CONDUIT
SIZE MAXIMUM FILL
1 /2"
.12 SQUARE INCH
3/4"
.21 SQUARE INCH
1"
.34 SQUARE INCH
1-1/4"
.60 SQUARE INCH
1-1/2"
.82 SQUARE INCH
2"
1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED
THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
WIRE DESIGNATION
DMONDS, WASHINGTON
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED
WITH DEVICES ADDRESS.
I. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
24. LOCKOUT SHALL BE INSTALLED ON THE MAIN POWER DISCONNECT
CIRCUIT BREAKER. NFPA 72.10.6.5.4
25. THE MAIN POWER DISCONNECT CIRCUIT BREAKER SHALL HAVE A
RED MARKING. NFPA 72.10.6.2.3
26. MOUNT A SIGN STATING "FIRE ALARM CONTROL ROOM" ON OUTSIDE
OF DOOR LEADING TO FIRE PANEL. IFC 509-1
GENERAL NOTES
QUANTITY
E
E
E
E
1
1
2
SYMBOL
DESCRIPTION
MODEL
MANUFACTURER
BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
CONTROL PANEL
FS-250
SIEMENS
FS-250-ENCL
66" A.F.F.
E
(EXISTING)
TO TOP
Ed
REMOTE BOOSTER
POWER SUPPLY
PAD-4
SIEMENS
PAD-4-ENCL
66" A.F.F.
E
(EXISTING)
TO TOP
(DE
SMOKE DETECTOR
EXISTING
SIEMENS
4S
DEEP
CEILING
(EXISTING)
W/
1 G RING
o
FIRE ALARM
HORN STROBE
EXISTING
-
4S
DEEP
80" A.F.F.
TO BOTTOM
E
(EXISTING)
SMOKE DETECTOR
HFP-11 W/
SIEMENS
4S
DEEP
CEILING
(ADDRESSABLE -PHOTO)
DB-1 1 BASE
W/
1 G RING
FIRE ALARM
LHSW
WHEELOCK
4S
BOX
80" A.F.F.
HORN/STROBE
TO BOTTOM
FIRE ALARM
LHSWC
WHEELOCK
4S
BOX
CEILING
HORN/STROBE
SYMBOLS LEGEND
OUTPUT
U)
z
O
Q
U
J
a_
a_
J
Q
Q
z
z
Q
Q
��-,0
wo
U
Q
J
m Q
o
o )
O
Q J
� J
LJJ
of
I— w
j
zw
zw
Q U
Q U
INPUT
Q
� O
o
ANY SMOKE/HEAT/PULL/WATERF LOW
X
X
ANY SYSTEM TROUBLE
X
SEQUENCE OF OPERATIONS MATRIX
Proprietary & Confidential, Copyright 2013
STEVE SENDLAKOWSKI
NICET LEVEL III
CERT. #115442 EXP. 01 /01 /2027
z
0
Vn
w
W
V)
Q
W
J
LU
-.3
o
ro
011
0-
wft0
00
z
N
o
�D
~
\0
z
o
N
W
C/)
x
a
3:
LL
yw
Z~
w
Q��
LO
Mimi
o
LO
0��
N
1>
\0
:
Q
I_o
\0
�
w
m
w
J
U
w
z
0
I -
EL
U
V)
W
0
W
0
Z
a
0
0
N
W
Q
It
N
\
o
o
\
0
0aaaaa
0
z
z
Ow
�w
>
�(D
U)o
�LU
wrn
LL1 Q
z
�F_
3:
O
Q
��
Z
W
=�
NZ
Q
C
G
�
TO
N
Ln
CMO LU
t'
_
zw
Q
�
o
01:
LL
SCALE: NOT TO SCALE
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE:06/26/2024
BACKROUND PLAN PROVIDED BY:
%JOB NUMBER:75790-1
SHEET
FA- 01
Guardian Security Systems, Inc. All Rights Reserved
CEILIN
TI LE
NEXT DEVICE
-NDED
INATED CEILING
J lvl\J r \ L- LJL I Lv l VI\
SMOKE DETECTOR MOUNTING DETAIL
STROBE MOUNTING (DROP CEILING
s
FROM PAD -
u
HARD LID -
CEILING
STROBE MOUNTING (HARD LID)
X
5 1a
DB-11
6 1b
HFP-11 SMOKE
DETECTOR
TO FS250 TO NEXT
FACP ADDRESSABLE
DEVICE
TYPICAL DATA LOOP WIRING DETAIL
I
HORN
STROBE
HORN
STROBE
TYPICAL NAC WIRING DETAIL
HORN
STROBE
EOL
TYPICAL WIRING AND MOUNTNG DETAILS
FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION
Project: VIRGINIA MASON - EDMONDS T.I.
Panel: EXISTING SIEMENS PAD-4-9A BOOSTER POWER SUPPLY
Date: June 26, 2024
Module/Device Qty Standby Total Standby Alarm Total Alarm
(mA) (mA) (mA) (mA)
Power Module
1
78
78
0
174
174
0
A TOTAL FIRE ALARM POWER SUPPLY 78 174
B Auxiliary Device Current 0 0
C Notification Appliance Load (Max. Total / mA) 0 153
Total(A)= 78 Total(B)= 327
CALCULATION
D
Total current ratings of all devices in system (line A + line B + line C)
78
327
E
Total current ratings converted to amperes (line D x .001)
0.078
0.327
F
Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5).
24
G
Multiply lines E and F Total Standby AH
1.872
H
Alarm sounding period in hours (15 mins= 0.25 hours)
0.25
1
Multiply lines E and H Total Alarm AH
0.08175
J
Add lines G and I Total Standby and Alarm AH
1.95375
K
Multiply line J by 1.2 (20% extra insurance to meet desired performance)
2.3445
12-V DC BATTERYSIZE RECOMMENDED (AMPERE -HOUR) 7
Notification Appliance Circuit Detail
PROJECT: VIRGINIA MASON - EDMONDS T.I.
Panel: EXISTING SIEMENS PAD-4-9A BOOSTER POWER SUPPL`Wire Resistance 3.07
Date: April 6, 2023 CURRENT TOTAL= 153.00
SLHSCW @15Cd
SLHSCW @30Cd
3
Total Wire Resistance ( R )
Total Device Load, Amps (1)
Voltage Drop( E)
Fni vni+ana
(WL*2)*(R/ft)
(Total Cct Load)
(E=1*R)
SYSTEM CALCULATIONS
STEVE SENDLAKOWSKI
NICET LEVEL III
CERT. #115442 EXP. 01/01/2027
z
0
w
w
U)
Q
LLJ
J
W
�Ira
J
o
ON
l00
eft
00
ON
_
-I
00
z
N
0
�
c�
�
z
o
N
cn
Q
x
Q
yw
w
Ln
019-
c/
Q
N
W
N
Q
O
C�
N
�
W
m
w
J
U
LLJ
z
0
EL
U
U)
LLJ
0
N
0
z
Q
o
0-
0
CO
U-i
Q
N
\
o
o
\
r`
0
0aaaaa
0
0
Zz
OW
�w
o0
Ir
0
E
wa)
W Q
z
O
Q
�U)
Q
z
LLJ
2 p
C\1 z1—
r O
N
Q
LO T C)
�W
ZW
Q
c)
Ir
W
SCALE: NOT TO SCALE
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE:06/26/2024
BACKROUND PLAN PROVIDED BY:
JOB NUMBER:75790-1
Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Riqhts Reserved
SHEET
FA-02
WORK AREA
SITE MAP
SCALE: NTS
VICINITY MAP
SCALE: NTS
FLOOR 2 - FACP LOCATION
SITE LOCATION
SCALE: NTS
N
J
----------------------
FLOOR 2
FACP NACn 120 VAC, DEDICATED
E E ( BY OTHERS)
FAC P
---------------------------
FLOOR 1
S
OFFICE
O
SUPPLY
C
0
TO EXISTING
NAC CIRCUIT
RECEPTION
O
S
OM
S 1-4-? S 1-4-? S 1-4-?
15Cd 30Cd 15Cd
D
D'?
S
E
RISER DIAGRAM
-----1
SOILED
HOLDING
C
�t
SCALE: NTS
OE
* CREDIT
TO EXISTING
F
,) NAC CIRCUIT
`
Lw
l �J S 1-4-?
1
Qp
30Cd
1
1
LU
C
S 1-4-?
�J
L
Q
N
zn77
W
j 0
LU
WOF
TV U
WORK AREA
WAITING
COMP.
C�
DEXA FUTURE CLINI
518
>—D
!�E
PARTIAL FIRST FLOOR FIRE ALARM T.I. LAYOUT
SCALE: 3/16" = 1'0"
STEVE SENDLAKOWSKI
NICET LEVEL III
CERT. #115442 EXP. 01 /01 /2027
z
0
V)
w
o'
W
C/')
Q
W
J
LU
-.3
o
ro
0*1
0
0
z
N
o
�
z
o
N
W
Cn
x
a
3:
LL-
LU
w
U
Ln
Mimi
o
Ln
�
Q
N
LJ J
\0
Q
—
u
CD
ho
�
w
mw
J
U
LU
C�
z
0
EL
U
C/')
LU
0
0
0
Z_
a
0
0
W
Q
N
a
o
�
0
Oaaaaa
0
Z
z
COW
G
w
LU
0
�o
1
w�
WQ
Z
���
O
Q
`n cn
Cn
Z
W
2p
N z
Q
�
NO
Q
w
Lp
CW
ZW
Q
�
o
01:
LL
SCALE: AS NOTED
DRAWN BY:
C. ENGSTFELD
DESIGNED BY:
T. QUAALE
DATE:06/26/2024
BACKROUND PLAN PROVIDED BY:
JOB NUMBER:75790-1
Proprietary & Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Riqhts Reserved
SHEET
FA-03