ELECTRICAL Voltage Drop Calculation for Edway Taphouse
SUPPORT COMPANY
We utilized the formula method for calculating voltage drop and took direct readings of load
on the lighting circuit.
Breaker size:
Voltage measured at breaker:
Measured amperage under load
Length of wire to furthest load:
Conductor Size:
K constant for copper wire:
Formula:
VD=2*K*I*D/CM
Single pole 20 amp
120.0 V
2.4 amps
140 feet (estimated maximum)
AWG #12 (6.53 kcmil)
12.9 ohms
VD = (2 * 12.9 * 2.4 * 140)/(6530 cmil) = 1.32 Volts
VD for lighting circuit:
1.10%
The overall voltage drop for the lighting circuit is 1.1%, well within the 5% maximum allowed
by the Washington Energy Code.