Loading...
NOT NEEDED RESUB1 BLD2023-0699+VOLTAGE Summary+9.21.2023_3.07.26_PM+37976899/20/2023 ELECTRICAL Voltage Drop Calculation for Edway Taphouse SUPPORT COMPANY We utilized the formula method for calculating voltage drop and took direct readings of load on the lighting circuit. Breaker size: Voltage measured at breaker: Measured amperage under load Length of wire to furthest load: Conductor Size: K constant for copper wire: Formula: VD=2*K*I*D/CM Single pole 20 amp 120.0 V 2.4 amps 140 feet (estimated maximum) AWG #12 (6.53 kcmil) 12.9 ohms VD = (2 * 12.9 * 2.4 * 140)/(6530 cmil) = 1.32 Volts VD for lighting circuit: 1.10% The overall voltage drop for the lighting circuit is 1.1%, well within the 5% maximum allowed by the Washington Energy Code.