RFI 24 Decay at unit 2A deck_MHPACIFIC
❑ BUILDING
ENVELOPE,INC.
❑ EXTERIOR RENOVATIONS 8 REPAIRS
❑
REQUEST FOR INFORMATION
PROJECT: Breakwater Edmonds Condominiums
REFERENCE CONTRACT DOCUMENTS
R.F.I. NO: 24
DATE: 7/11/2023
SUBJECT: Decay at unit 2A deck cantilevered beam, rim & metal strap
SPEC. SECTION: 06 1053
PLAN PAGE NO:
ATTACHMENTS: Photos
INFORMATION REQUESTED
We have uncovered decay at unit deck 2A rim, joist and both beams. North beam has 1 /211 of
decay at the face and top. South beam has decay 311 from the top 1 /2° deep and runs back 7°
at the tip of beam. How would you like us to proceed with repairs to the beams, rim and straps?
BY: Ashley Hogan FIRM: Pacific Building Envelope, Inc.
NOTE: 7/1 2/2023 is the date by which an answer is needed.
Time Impact
Yes
P1
No
❑
Possible ❑
Cost Impact
Yes
0
No
❑
Possible ❑
Site Visit Required
Yes
0
No
❑
Possible ❑
INFORMATION RESPONSE
Repair deteriorated deck beams (cantilevered 4x12 typ.), and edge deck joist, and rim
joist per the attached detail sketch. Replace rusty existing straps at joists to match
existing, or use Simpson LSTA12.
Shawn Stevenson, PE, SE
Morrison Hershfield
7/13/2023