BLD2024-1135_Manufacturer_Specifications_and_Installation_Instructions_8.29.2024_8.43.10_AM_4469993Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
HVAC Guide Specifications
Inverter Driven, Direct Expansion (DX), Air -Cooled Heat Pump Split System
Section 15700 — Mechanical HVAC
Size Range:
1.5 tons nominal
Daikin North America LLC Model Number:
IDU: FTXR09TVJU(W/S), FTXR12TVJU(W/S), FVXS09NVJU, FVXS12NVJU,
FVXS15NVJU, CTXS07LVJU, FTXS09LVJU, FTXS12LVJU, FTXS15LVJU,
FDXS09LVJU, FDXS12LVJU, CDXS15LVJU, FDMQ09RVJU, FDMQ12RVJU,
FDMQ15RVJU, FFQ09Q2VJU, FFQ12Q2VJU, FFQ15Q2VJU
ODU: 2MXS18NMVJUA
Part 1 — General
MULTI -SPLIT AIR CONDITIONING
SPECIFICATION — Heat Pump
1.01 SYSTEM DESCRIPTION
The variable capacity, heat pump air conditioning system shall be a Daikin Inverter
Driven series (heat/cool model) multi -split system. The system shall consist of two (2)
evaporator models exclusively matched to outdoor model 2MXS18NMVJUA direct
expansion (DX), air-cooled, Daikin swing, variable speed, inverter driven compressor
using R-410A adequate for 98.4 feet of total length. The system shall have automatic
restart capability after a power failure has occurred and a low voltage cut-off feature to
prevent stalling during power supply issues. The system shall include a priority room
setting for operation mode, powerful operation and quiet operation.
1.02 QUALITY ASSURANCE
A. The units shall be tested by a Nationally Recognized Testing Laboratory (NRTL), in
accordance with ANSI/UL 1995 — Heating and Cooling Equipment and bear the listed
Mark.
B. All wiring shall be in accordance with the National Electric Code (NEC).
C. Each combination shall be rated in accordance with Air Conditioning Refrigeration
Institute's (ARI) Standard 210/240 and bear the ARI label.
D. The system will be produced in an ISO 9001 and ISO 14001 facility, which are
standards set by the International Standard Organization (ISO). The system shall be
factory tested for safety and function.
E. The outdoor unit will be factory charged for a line set length of 98.4 feet of refrigerant
with R-410A refrigerant.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
F. A holding charge of dry nitrogen shall be provided in the evaporator.
G. System Efficiency shall meet or exceed 14 SEER, 9.5 EER and 8.2 HSPF.
1.03 DELIVERY, STORAGE, AND HANDLING
A. Unit shall be stored and handled according to the manufacturer's recommendations.
2.01 LIMITED WARRANTY
This warranty is provided to you by Daikin North America LLC ("Daikin"), which warrants
all parts of this heating or air conditioning unit, as described below.
A. Owner -Occupied Residential Installations: This warranty applies to heating and air
conditioning units installed in owner -occupied residences and covers defects in
materials and workmanship that appear under normal use and maintenance.
Warranty coverage begins on the "installation date". The installation date is one of
three dates depending on the circumstances of purchase: (1) For units installed in a
newly constructed residence, the installation date is the date the owner purchases
the residence from the builder. (2) For units installed in existing residences, the
installation date is the date that the unit is originally installed. (3) If the date the
owner purchases the residence from the builder or the date the unit is originally
installed cannot be verified, the installation date is three months after the
manufacture date noted on the unit. Registration is not required to obtain warranty
coverage, but registration entitles the owner to the Registered Additional Term
Warranty described in the following paragraph. If the unit is not registered, the
warranty lasts for a period up to 5 YEARS (the "Initial Term Warranty"). California
and Quebec residents do not need to register the product in order to get all of the
rights and remedies of registered owners under this warranty, but Registered
Additional Term Warranty coverage is only available to the original owner of this unit
and his or her spouse.
B. Non -Owner Occupied Residential Installations: This warranty applies to heating and
air conditioning units installed in residences not occupied by the owner and covers
defects in material and workmanship that appear under normal use and
maintenance. Warranty coverage begins on the "installation date". The installation
date is one of two dates: (1) The installation date is the date that the unit is originally
installed. (2) If the date the unit is originally installed cannot be verified, the
installation date is three months after the manufacture date. Registration is not
required to obtain warranty coverage, but registration entitles the owner to the
Registered Additional Term Warranty described in the following paragraph, If the unit
is not registered, the warranty lasts for a period up to 5 YEARS (the "Initial Term
Warranty").
C. Commercial Installations: This warranty applies to heating and air conditioning units
installed in buildings other than residences and covers defects in materials and
workmanship that appear under normal use and maintenance. Warranty coverage
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
begins on the "installation date". The installation date is one of two dates: (1) The
installation date is the date that the unit is originally installed (2) If the date the unit is
originally installed cannot be verified, the installation date is three months after the
manufacture date. The warranty lasts for a period up to 5 YEARS.
2.02 EXTENDED WARRANTY —
A. Owner -Occupied Residential Installations: If the unit is properly registered online
within 60 days after the installation date, an additional warranty (the "Registered
Additional Term Warranty") is provided and lasts for as long as the original registered
owner or his or her spouse ("registered owner") own and reside in the home in which
the unit was originally installed for a period up to 12 YEARS after the installation
date. To register, go to www.daikincomfort.com and click "PRODUCT Registration".
Some states and provinces do not allow limitation of warranty coverage to registered
owner, so the above limitation may not apply to you. Refer to the warranty certificate
for complete warranty details.
B. Non -Owner Occupied Residential Installations: If the unit is properly registered online
within 60 days after the installation date, an additional warranty (the "Registered
Additional Term Warranty") is provided and lasts for as long as the original registered
owner ("registered owner") owns the residence in which the unit was originally
installed, for a period up to 12 YEARS after the installation date. To register, go to
www.daikincomfort.com and click "PRODUCT Registration".
Neither the limited or extended warranties continue after the unit is removed from the
location where it was originally installed. The replacement of a part under this warranty
does not extend the warranty period. In other words, Daikin warrants a replacement part
only for the period remaining in the applicable warranty that commenced on the
installation date.
2.03 INSTALLATION REQUIREMENTS
Installation must comply with installation manual. It is recommended the system be
installed by a contractor/dealer who has been through Daikin training programs.
Part 3 — PERFORMANCE
3.01 The system performance shall be in accordance with AHRI 210/240 test conditions as
shown in the performance table below.
System
Configuration
Mode
Max
Connected
Max Cooling Capacity
Max Heating
Capacity
SEER
EER
HSPF
Non -Ducted
Heatpump
24,000
21,000
25,000
18.9
12.5
10.7
2MXS18NMVJUA
Ducted
Heatpump
24,000
21,000
25,000
14
9.5
8.2
Mixed
Heatpump
24,000
20,100
25,000
16.5
11.0
9.5
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
The cooling performance is based on 80OF DB / 670F WB for the indoor unit and 95OF
DB / 75OF WB for the outdoor unit and 25 feet of piping. The heating performance is
based on 70oF DB / 60°F WB for the indoor unit and 47°F DB / 43°F WB for the outdoor
unit and 25 feet of piping.
3.02 The operating range in cooling will be 14°F DB — 115°F DB.
3.03 The operating range in heating will be YF WB — 60°F WB.
3.04 The system shall be capable of maximum refrigerant piping of 164 feet (maximum 82
feet per indoor unit), with 49 feet maximum vertical difference between indoor unit and
outdoor unit (maximum 24 feet between indoor units), without any oil traps, BP boxes, or
additional components.
Part 4 — PRODUCTS
4.01 INDOOR UNIT— CTXS/FTXS
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Unit Cabinet:
1. The indoor unit shall have a white, "wipe -clean" finish.
2. The drain and refrigerant piping shall be accessible from six (6) positions for
flexible installation (right side, right back, and right bottom; and left side, left back,
and left bottom.
3. The cabinet shall be supplied with a mounting plate to be installed onto a wall for
securely mounting the cabinet.
4. The cabinet includes:
i. Indoor unit ON/OFF switch, capable of being used when the remote
controller is missing. When switch is used, the default setting is AUTO
mode, 770F temperature setting, and AUTO airflow rate.
ii. "Intelligent Eye" motion sensor capable of setting back the set point
temperature for energy savings. This feature may be disengaged on the
I/R remote controller.
iii. OPERATION lamp that turns green when activated
iv. TIMER lamp that turns orange when activated
V. A Signal Receiver that receives signals from the remote controller at a
maximum distance of 23 ft. When the unit receives a signal, you will hear
the following: 2 beeps — operation start, 1 beep — Setting changed, 1 long
beep — Operation stop.
B. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven fan by a
single motor.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. An auto -swing louver for adjustable air flow (both vertically and horizontally) is
standard via the wireless remote control furnished with each system.
4. The indoor fan shall offer a choice of five speeds, plus quiet and auto settings.
5. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
C. Filter:
1. The return air filter provided will be a mildew resistant, removable and washable
filter. Two titanium apatite photocatalytic air purifying filters are included for
additional air filtration.
D. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
E. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60
hertz power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz
power from the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
F. Control:
1. The unit shall have a backlit, wireless remote infra -red controller capable
to operate the system. It shall have Cooling Operation, Heating
Operation, Automatic Operation, Dry Operation and Fan Only Operation.
2. The controller shall consist of an On/Off Power switch, Mode Selector,
Quiet Button (for outdoor unit), Fan Setting, Swing Louver, On/Off Timer
Setting, Temperature Adjustment, °C or OF Temperature Display,
Intelligent Eye Sensor, Weekly Timer, Night Set Mode, Comfort Mode,
Econo Mode, and Powerful Operation.
i. On/Off switch powers the system on or off.
ii. Mode selector shall operate the system in auto, cool, heat, fan, or
dry operation.
iii. Quiet button for outdoor unit lowers the noise level by changing
frequency and fan speed of the outdoor unit.
iv. Fan setting shall provide five fan speeds, plus quiet and auto
settings.
V. Swing louver shall adjust the airflow (horizontal and vertical)
blades.
1. Vertical & horizontal positions can be manually
adjusted, or placed into auto swing or 3-D airflow
settings.
vi. On/Off timer is used for automatically switching the unit on or off.
1. Night Set mode automatically engaged with Off Timer
is set. This setting automatically adjusts the
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
temperature setting 0.9°F (0.5°C) up in COOL, 3.6°F
(2.0°C) down in HEAT to prevent excessive cooling or
heating during sleeping hours.
vii. Temperature adjustment allows for the increase or decrease of
the desired temperature.
viii. The Intelligent Eye sensor detects human movement. If no
movement is detected in the room for more than 20 minutes, the
operation automatically changes up or down 3.6°F to an energy
saving operation.
ix. Weekly timer allows for programming the temperature setting and
on/off times of up to four settings per day for each day of the
week.
X. Comfort Mode directs the airflow upwards while in COOL
operation and downward while in HEAT operation. This function
prevents air from blowing directly on the occupants in the room.
A. Econo operation is a function which enables efficient operation by
limiting the maximum power consumption value. This function will
also prevent the circuit breaker from tripping when the unit
operates alongside other appliances on the same circuit.
xii. Powerful operation allows quick cool down or heating up in the
desired space to achieve maximum desired temperature in the
shortest allowable time period.
3. The controller shall be able to display two -digit fault codes extracted from
the indoor unit to aid in troubleshooting.
4. Temperature range on the remote control shall be 640F to 90OF in COOL
mode, 50OF to 860F in HEAT mode, and 640F to 860F in AUTO mode.
The temperature shall be controlled in 1 ° increments.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor coil temperature sensors
enabled by commands from the remote control.
6. The unit shall also have the capability to connect to a smart -device app
via wireless adapter.
G. Sound:
1. Indoor unit sound levels shall not exceed:
Indoor Daikin Model
Cooling Mode Sound
Level (H/M/L/SL)
dB(A)
Heating Mode Sound
Level (H/M/L/SL)
dB(A)
CTXS07LVJU
38 / 32 / 25 / 22
38 / 33 / 28 / 25
FTXS09LVJU
41 / 33 / 25 / 22
42 / 35 / 28 / 25
FTXS12LVJU
45/37/29/23
45/39/29/26
FTXS15LVJU
45 / 40 / 35 / 32
43 / 38 / 33 / 30
*values are measured approximately 3 feet away with JIS standard
operating conditions.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
4.02 INDOOR UNIT — CTXG
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Unit Cabinet:
1. The indoor unit shall have a white or silver, "wipe -clean" finish.
2. The drain and refrigerant piping shall be accessible from six (6) positions for
flexible installation (right side, right back, and right bottom; and left side, left back,
and left bottom).
3. The cabinet shall be supplied with a mounting plate to be installed onto a wall for
securely mounting the cabinet.
4. The cabinet includes:
i. "Intelligent -eye" motion sensor capable of setting back the set point
temperature for energy savings. This feature may be disengaged on the
I/R remote controller.
ii. Multi -monitor lamp changes color according to the mode of operation
allowing the user to visually determine the mode of operation; Red/Blue
for Auto, Green for Dry, Blue for Cool, Red for Heat, White for Fan,
Orange for Timer.
iii. Indoor unit ON/OFF switch, capable of being used when the remote
controller is missing. When switch is used, the default setting is AUTO
mode, 77°F temperature setting, and AUTO airflow rate.
iv. A Signal Receiver that receives signals from the remote controller at a
maximum distance of 19-11/16 ft. When the unit receives a signal, you
will hear the following: 2 beeps — operation start, 1 beep- setting changed,
1 long beep — operation stop.
B. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven fan by a
single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. An auto -swing louver for adjustable airflow (both vertically and horizontally) is
standard via the I/R remote control furnished with each system.
4. The indoor fan shall offer a choice of five speeds, plus quiet and auto settings.
5. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
C. Filter:
1. The return air filter provided will be a mildew resistant, removable and washable
filter. Two titanium apatite photocatalytic air purifying filters are included for
additional air filtration.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
D. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
E. Electrical
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60 hertz
power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz power from
the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
F. Control:
1. The unit shall have a backlit, wireless remote infra -red controller capable to
operate the system. It shall have Cooling Operation, Heating Operation,
Automatic Operation, Dry Operation and Fan Only Operation.
2. The controller shall consist of an On/Off power switch, Mode selector, Quiet
Button (for outdoor unit), Fan Setting, Swing Louver, On/Off Timer Setting,
Temperature Adjustment, °C or °F Temperature Display, "Intelligent Eye" sensor,
Econo Mode, Weekly Timer, Night Set Mode, Comfort Airflow and Powerful
Operation.
i. On/Off switch powers the system on or off.
ii. Mode selector shall operate the system in auto, cool, heat, fan or dry
operation.
iii. Quiet button for outdoor unit lowers the noise level of the outdoor unit by
changing frequency and fan speed of the outdoor unit.
iv. Fan setting shall provide five fan speeds, plus quiet and auto settings.
V. Swing louver shall adjust the airflow (horizontal and vertical) blades.
1. Vertical & horizontal positions can be manually adjusted, or placed
into auto swing or 3-D airflow settings.
vi. On/Off timer is used for automatically switching the unit on or off.
1. Night Set mode automatically engaged when Off Timer is set. This
setting automatically adjusts the temperature setting 0.9°F (0.5°C)
up in COOL, 3.6°F (2.0°C) down in HEAT to prevent excessive
cooling or heating during sleeping hours.
vii. Temperature adjustment allows for the increase or decrease of the
desired temperature.
viii. The Intelligent Eye sensor detects human movement. If no movement is
detected in the room for more than 20 minutes, the operation
automatically changes up or down 3.6°F to an energy saving operation.
ix. Weekly timer allows for programming the temperature setting and on/off
times of up to four settings per day for each day of the week.
X. Comfort Mode directs the airflow upwards while in COOL operation and
downward while in HEAT operation. This function prevents air from
blowing directly on the occupants in the room.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
xi. Econo operation is a function which enables efficient operation by limiting
the maximum power consumption value. This function will also prevent
the circuit breaker from tripping when the unit operates alongside other
appliances on the same circuit.
xii. Powerful operation allows quick cool down or heating up in the desired
space to achieve maximum desired temperature in the shortest allowable
time period.
3. The controller shall be able to display two -digit fault codes extracted from the
indoor unit to aid in troubleshooting.
4. Temperature range on the remote control shall be 64°F to 90°F in COOL mode,
50' to 86°F in HEAT mode, and 64°F to 86°F in AUTO mode. The temperature
shall be controlled in 1 ° increments.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor foil temperature sensors
enabled by commands from the remote control.
6. The unit shall also have the capability to connect to a smart -device app via
wireless adapter.
G. Sound:
1. Indoor unit sound levels shall not exceed:
Cooling Mode Sound
Heating Mode Sound
Indoor Daikin Model
Level (H/M/L/SL)
Level (H/M/L/SL)
dB(A)
dB(A)
FTXR09TVJU(W/S)
38 / 32 / 25 / 19
41 / 34 / 28 / 19
FTXR12TVJU W/S
45 / 34 / 26 / 20
45 / 37 / 29 / 20
*values are measured approximately 3 feet away with JIS standard
operating conditions
4.02 INDOOR UNIT — FFQ
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Decor Panel
1. The indoor unit panel shall have a white finish or a white finish with a Silver trim.
2. Panel shall be a four-way air distribution type and be impact resistant.
3. The four air discharge outlet louvers shall be independently motorized and
controllable. Each louver shall have a visual indicator to easily identify the louver
and simplify the airflow configuration.
4. The air flow shall be capable of field modification to 3-way and 2-way airflow to
accommodate various installation configurations including corner installations.
5. The panel shall be a low profile design, extending 5/16" below the ceiling
6. The panel dimensions shall measure 24-7/16" x 24-7/16" and shall fit into a
standard 2x2 ceiling grid with no overlap of adjacent tiles.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
B. Unit Cabinet:
1. The indoor unit shall be located in the ceiling.
2. Fresh air intake shall be possible by way of direct duct installation to the side of
the indoor unit cabinet.
3. The cabinet shall be constructed with sound absorbing foamed polystyrene and
polyethylene insulation.
C. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven fan by a
single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. The indoor fan shall offer a choice of three speeds.
4. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
D. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection and lift
mechanism. The lift mechanism provides up to 24-13/16" of lift, measured from
the drain outlet.
E. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60
hertz power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz
power from the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
F. Control:
1. The unit shall have either a Wired type remote controller or a backlit,
wireless remote infra -red controller capable to operate the system.
2. The unit shall be compatible with interfacing with a BMS system via
optional LonWorks or BACnet gateways.
3. The unit shall be compatible with a Daikin Intelligent Touch Manager
advanced multi -zone controller.
4. The controller shall be able to display two -digit fault codes extracted from
the indoor unit to aid in troubleshooting.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor coil temperature sensors
enabled by commands from the remote control.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
G. Sound:
1. Indoor unit sound levels are as follows:
Indoor Daikin Model
Cooling Mode Sound
Level (H/M/L) dB(A)
Heating Mode Sound
Level (H/M/L) dB(A)
FFQ09Q2VJU
38 / 35 / 29
38 / 35 / 29
FFQ12Q2VJU
39 / 36 / 30
39 / 36 / 30
FFQ15Q2VJU
40 / 37 / 31
40 / 37 / 31
*values are measured approximately 5 feet away with JIS standard
operating conditions.
4.04 INDOOR UNIT — FVXS
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Unit Cabinet:
1. The indoor unit shall have a white, "wipe -clean" finish.
2. The drain and refrigerant piping shall be accessible from six (6) positions for
flexible installation (right side, right back, and right bottom; and left side, left back,
and left bottom.
3. The cabinet shall be supplied with a mounting plate to be installed onto a wall for
securely mounting the cabinet.
4. The cabinet shall be able to be mounted in four (4) positions as shown in the
image below; Floor, wall, half concealed & concealed.
Exposed
Half concealed
Concealed
AO Mounting
plate
i
i
i
�77
Mjg_--
Grid (field supply)
Floor Installation
Wall Installation
5. The cabinet includes
i. Indoor unit ON/OFF switch, capable of being used when the remote
controller is missing. When switch is used, the default setting is AUTO
mode, 770F temperature setting, and AUTO airflow rate.
ii. OPERATION lamp that turns green when activated
iii. TIMER lamp that turns orange when activated
iv. A Signal Receiver that receives signals from the remote controller at a
maximum distance of 23 ft. When the unit receives a signal, you will hear
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
the following: 2 beeps — operation start, 1 beep — Setting changed, 1 long
beep — Operation stop.
V. Air outlet selection switch to select airflow from upper outlet only, or
automatic airflow pattern depending on mode and conditions.
1. When switch is set to upper outlet only, air will blow from top
vent regardless of operating mode or situation.
2. When switch is set to automatic airflow pattern, the blowing
patterns are as follows:
Mode
Situation
Blowing pattern
When the operation is activated or when the
Air is emitted from the upper and lower air
room is not fully cooled.
outlets in order to reach the set temperature
4
quickly.
COOL
()
When the room has become fully cool, or
Air is emitted only from the upper air outlet so
when 1 hour has passed since turning on the
that air does not come into direct contact with
air conditioner.
people and indoor temperature is equalized.
When the operation is activated or when air
Air is emitted only from the upper air outlet so
emitted is of low temperature.
that air does not come into direct contact with
people.
HEAT
At times other than the above situations.
Air is emitted from the upper and lower air
outlets so that warm air is spread throughout the
whole room.
Whenever in DRY mode.
Air is emitted only from the upper air outlet so
DRY
that air does not come into direct contact with
(0)
people.
Whenever in FAN mode.
FAN
AUTO
Operates in the actual operation mode of the air conditioner according to the descriptions in this table. (COOL or HEAT)
(IA1)
B. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven fan by a
single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. An auto -swing louver for adjustable air flow (vertically) is standard via the
wireless remote control furnished with each system.
4. The indoor fan shall offer a choice of five speeds, plus quiet and auto settings.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
5. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
C. Filter:
1. The return air filters provided will be a mildew resistant, removable and washable
filter. Two titanium apatite photocatalytic air purifying filters are included for
additional air filtration.
D. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
E. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60
hertz power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz
power from the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
F. Control:
1. The unit shall have a backlit, wireless remote infra -red controller capable
to operate the system. It shall have Cooling Operation, Heating
Operation, Automatic Operation, Dry Operation and Fan Only Operation.
2. The controller shall consist of an On/Off Power switch, Mode Selector,
Fan Setting, Swing Louver, On/Off Timer Setting, Temperature
Adjustment, °C or OF Temperature Display, Econo Mode, Weekly Timer,
Outdoor Unit Quiet Operation, and Powerful Operation.
i. On/Off switch powers the system on or off.
ii. Mode selector shall operate the system in auto, cool, heat, fan, or
dry operation.
iii. Fan setting shall provide five fan speeds, plus quiet and auto
settings.
iv. Swing louver shall adjust the airflow (horizontal and vertical)
blades.
1. Vertical movement controlled via remote, horizontal
movement controlled manually.
V. On/Off timer is used for automatically switching the unit on or off.
1. Night Set mode automatically engaged with Off Timer
is set. This setting automatically adjusts the
temperature setting 0.9°F (0.5°C) up in COOL, 3.6°F
(2.0°C) down in HEAT to prevent excessive cooling or
heating during sleeping hours.
vi. Temperature adjustment allows for the increase or decrease of
the desired temperature.
vii. Econo operation is a function which enables efficient operation by
limiting the maximum power consumption value. This function will
also prevent the circuit breaker from tripping when the unit
operates alongside other appliances on the same circuit.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
viii. Weekly timer allows for up to four timer settings to be saved for
each day of the week.
ix. Outdoor Unit Quiet Operation lowers the noise level of the outdoor
unit by changing frequency and fan speed of the outdoor unit.
X. Powerful operation allows quick cool down or heating up in the
desired space to achieve maximum desired temperature in the
shortest allowable time period.
3. The controller shall be able to display two -digit fault codes extracted from
the indoor unit to aid in troubleshooting.
4. Temperature range on the remote control shall be 64°F to 90°F in COOL
mode, 50OF to 860F in HEAT mode, and 647 to 86°F in AUTO mode. The
temperature shall be controlled in 10 increments.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor coil temperature sensors
enabled by commands from the remote control.
6. The unit shall also have the capability to connect to a smart -device app
via wireless adapter
G. Sound:
1. Indoor unit sound levels shall not exceed:
Indoor Daikin Model
Cooling Mode Sound
Level (H/M/L/SL)
dB(A)
Heating Mode Sound
Level (H/M/L/SL)
dB(A)
FVXS09NVJU
38 / 32 / 26 / 23
38 / 32 / 26 / 23
FVXS12NVJU
39/33/27/24
39/33/27/24
FVXS15NVJU
44 / 40 / 36 /32
45 / 40 / 36 / 32
*values are measured approximately 3 feet away with JIS standard
operating conditions.
4.05 INDOOR UNIT — FDXS
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Unit Cabinet:
1. The indoor unit shall have an unfinished sheet metal cabinet.
2. The drain and refrigerant piping shall be accessible from the right side for flexible
installation.
3. The cabinet shall be supplied with suspension bracket for securely mounting the
cabinet to a threaded rod (field supplied).
4. The cabinet includes a receiver to accept signals from an infra -red remote
controller at a maximum distance of 13 ft. The receiver also includes:
i. Indoor unit ON/OFF switch, capable of being used when the remote
controller is missing. When switch is used, the default setting is AUTO
mode, 770F temperature setting, and AUTO airflow rate.
ii. OPERATION lamp that turns green when activated
iii. TIMER lamp that turns orange when activated
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
B. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven sirocco fan
by a single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. The indoor fan shall offer a choice of five speeds, plus quiet and auto settings
with an ESP of 0.12 in. WG at high speed for the rated capacity.
4. The return air shall be accessible by either bottom or factory standard rear return.
5. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
C. Filter:
1. The return air filter provided will be a mildew resistant, removable and washable
filter.
D. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
E. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60
hertz power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz
power from the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
F. Control:
1. The unit shall have a backlit, wireless remote infra -red controller capable
to operate the system. It shall have Cooling Operation, Heating
Operation, Automatic Operation, Dry Operation and Fan Only Operation.
2. The controller shall consist of an On/Off Power switch, Mode Selector,
Quiet Button (for outdoor unit), Fan Setting, On/Off Timer Setting,
Temperature Adjustment, °C or OF Temperature Display, Night Set Mode,
Econo Mode, and Powerful Operation.
i. On/Off switch powers the system on or off.
ii. Mode selector shall operate the system in auto, cool, heat, fan, or
dry operation.
iii. Quiet button for outdoor unit lowers the noise level by changing
frequency and fan speed of the outdoor unit.
iv. Fan setting shall provide five fan speeds, plus quiet and auto
settings.
V. On/Off timer is used for automatically switching the unit on or off.
1. Night Set mode automatically engaged with Off Timer
is set. This setting automatically adjusts the
temperature setting 0.9°F (0.5°C) up in COOL, 3.6°F
(2.0°C) down in HEAT to prevent excessive cooling or
heating during sleeping hours.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
vi. Temperature adjustment allows for the increase or decrease of
the desired temperature.
vii. Econo operation is a function which enables efficient operation by
limiting the maximum power consumption value. This function will
also prevent the circuit breaker from tripping when the unit
operates alongside other appliances on the same circuit.
viii. Powerful operation allows quick cool down or heating up in the
desired space to achieve maximum desired temperature in the
shortest allowable time period.
3. The controller shall be able to display two -digit fault codes extracted from
the indoor unit to aid in troubleshooting.
4. Temperature range on the remote control shall be 640F to 90OF in COOL
mode, 50°F to 86°F in HEAT mode, and 64°F to 86°F in AUTO mode.
The temperature shall be controlled in 1 ° increments.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor coil temperature sensors
enabled by commands from the remote control.
6. The unit shall also have the capability to connect to a smart -device app
via wireless adapter.
G. Sound:
1. Indoor unit sound levels are as follows:
Cooling Mode Sound
Heating Mode Sound
Indoor Daikin Model
Level (H/M/L) dB(A)
Level (H/M/L/SL)
dB(A)
FDXS09LVJU
35 / 33 / 31
35 / 33 / 31
FDXS12LVJU
35 / 33 / 31
35 / 33 / 31
CDXS15LVJU
37 / 35 / 33
37 / 35 / 33
* values are measured approximately 5 feet away with fan speed on high,
approximately 6.6 ft of supply duct, and 3.3 ft of return duct
4.06 INDOOR UNIT — FDMQ
General:
The indoor unit shall be factory assembled and pre -wired with all necessary electronic
and refrigerant controls. Both liquid and suction lines must be individually insulated
between the outdoor and indoor units.
A. Unit Cabinet:
1. The indoor unit shall be constructed of heavy gauge galvanized steel.
2. The unit shall be internally insulated and shall be capable of installation in indoor
environments up to 80% relative humidity without requiring additional field
installed insulation.
3. The drain and refrigerant piping shall be accessible from the right side.
4. The cabinet shall have a factory rear return air position with the ability to convert
to bottom return.
5. The cabinet shall include a drain pan inspection port on the right side to observe
drain pan conditions.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
B. Fan:
1. The evaporator fan shall be an assembly consisting of a direct -driven fan by a
single motor.
2. The fan shall be statically and dynamically balanced and operate on a motor with
permanent lubricated bearings.
3. The indoor fan shall offer a choice of three speeds, plus quiet setting.
4. The fan shall have a delayed start when initially put into HEAT operation, giving
time for the evaporator coil to heat up and preventing a cold draft from entering
the room.
5. The fan motor shall be capable of delivering the following:
Model Number
Fan ESP (in. w.g)
CFM Range
FDMQ09RVJU
0.12 — 0.60
240 - 343
FDMQ12RVJU
0.12 — 0.60
275 - 392
FDMQ15RVJU
0.20 — 0.60
360 - 516
6. The unit shall be equipped with internal controls to allow the fan motor to be
manually adjusted, via field setting, to deliver airflow at a variety of external static
pressures. Models FDMQ09RVJU through FDMQ12RVJU shall have 13
available fan curves. Model FDMQ15RVJU shall have 11 available fan curves.
C. Coil:
1. The evaporator coil shall be a nonferrous, aluminum fin on copper tube heat
exchanger.
2. All tube joints shall be brazed with silver alloy or phoscopper.
3. All coils will be factory pressure tested.
4. A condensate pan shall be provided under the coil with a drain connection.
i. The unit shall be equipped with a factory -integral condensate lift
mechanism capable of 26-9/16 inches of lift.
D. Electrical:
1. The outdoor unit shall be powered with 208-230 volts, 1 phase, and 60
hertz power. The indoor unit shall receive 208-230 volt, 1 phase, 60 hertz
power from the outdoor unit.
2. The allowable voltage range shall be 187 volts to 253 volts.
E. Control:
1. The unit shall have either a Wired type remote controller or a backlit,
wireless remote infra -red controller capable to operate the system.
2. The unit shall be compatible with interfacing with a BMS system via
optional LonWorks or BACnet gateways.
3. The unit shall be compatible with a Daikin Intelligent Touch Manager
advanced multi -zone controller.
4. The controller shall be able to display two -digit fault codes extracted from
the indoor unit to aid in troubleshooting.
5. The indoor unit microprocessor has the capability to receive and process
commands via return air temperature and indoor coil temperature sensors
enabled by commands from the remote control.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
F. Sound:
1. Indoor unit sound levels are as follows:
Indoor Daikin Model
Cooling Mode Sound
Level dB(A)
Heating Mode Sound
Level dB(A)
FDMQ09RVJU
32
32
FDMQ12RVJU
33
33
FDMQ15RVJU
34
34
*values are measured approximately 5 feet away with fan speed on high,
approximately 6.6 ft of supply duct, and 3.3 ft of return duct.
4.07 OUTDOOR UNIT
General:
The outdoor unit shall be specifically matched to corresponding indoor units while not
exceeding maximum connected capacity. The outdoor unit shall be completely factory
assembled and pre -wired with all necessary electronic and refrigerant controls. The outdoor unit
shall be controlled by a microprocessor and dedicated EEV's shall be provided for capacity
control during part load of the indoor unit.
A. Unit Cabinet:
1. The outdoor unit shall be completely weatherproof and corrosion resistant. The
unit shall be constructed from rust -proof mild steel panels coated with a baked
enamel finish.
2. The outdoor unit will come furnished with four (4) mounting feet, mounted across
the base pan, to allow bolting to a cement pad or optionally supplied mounting
bracket.
3. The assembly will be able to withstand a maximum rated wind pressure of 193psf
Lateral, 93psf Uplift. See document TER-16-3088.
B. Fan:
1. The fan shall be a direct drive, propeller type fan.
2. The motor shall be inverter driven, permanently lubricated type bearings,
inherent.
3. The fan shall be capable of operating in "Quiet Operation" which lowers the
outdoor fan speed in either COOL, HEAT, or AUTO modes.
4. A fan guard is provided on the outdoor unit to prevent contact with fan operation.
5. Airflow shall be horizontal discharge.
C. Coil:
1. The outdoor coil shall be nonferrous construction with corrugated fin tube.
2. The fins are to be covered with an anti -corrosion acrylic resin and hydrophilic film
type E1, rated for up to 1000 hours salt spray.
3. Refrigerant flow from the condenser will be controlled via a metering device.
4. Automatic defrost will remove any frost from the outdoor unit allowing the system
to maintain heating capacity.
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
D. Compressor:
1. The outdoor compressor shall be a patented, variable speed Daikin swing
inverter -driven compressor. The one piece action reduces noise, extends life,
boasts higher efficiency and reduces energy consumption.
2. The outdoor unit shall have an accumulator and four-way reversing valve.
3. PVE Refrigerant Oil shall be used to provide improved lubrication & better
chemical stability, and no hydrolysis, leading to higher product reliability.
4. The compressor shall have an internal thermal overload.
5. The outdoor unit can operate with a maximum refrigerant piping of 164 feet
(maximum 82 feet per indoor unit), with 49 feet maximum vertical difference
between indoor unit and outdoor unit (maximum 24 feet between indoor units),
without any oil traps, BP boxes, or additional components.
6. The compressor shall have a quick -warming function to prevent pumping liquid
refrigerant in low -ambient conditions.
E. Electrical:
1. The electrical power requirement is 208-230 volt, 1-phase, and 60 Hz power.
2. The voltage range limitations shall be a minimum of 187 volts and a maximum of
253 volts.
F. Sound:
1. Outdoor unit sound levels shall not exceed:
Outdoor Daikin Model
Cooling Mode
Heating Mode
Sound Level dB(A)
Sound Level dB(A)
2MXS18NMVJUA
50
51
*values are measured approximately 3 feet away with JIS standard
operating conditions.
2. Outdoor unit shall be equipped with optional Night Quiet Mode for COOL
operation. Night Quiet reduces the operation noise during night-time
hours and is engaged via dipswitch setting during installation.
i. Night Quiet mode shall be activated when temperature drops
10.8°F or more below the highest temperature recorded that day.
Function will be cancelled when the temperature difference
between the current outdoor temperature and the maximum
outdoor temperature becomes less than 7.2°F.
4.08 SYSTEM DIAGNOSTICS
General:
The system shall be capable of producing 2-digit fault codes:
A. Controls — compatibility varies by indoor unit model.
1. I/R controller
2. Wired Controller
3. Wi-fi module
Daikin North America LLC — RA Multi -Zone Heat Pump
WGS-2MXS18NMVJUA
B. D-Checker software: The D-Checker software has the ability to display error
codes and values for every sensor on the system through the outdoor unit.
The sensor data points shall be graphed or recorded for export to a
spreadsheet. The spreadsheet can then be analyzed to troubleshoot
operational issues or acknowledge proper operation.