APPROVED PLN BLD BLD2024-0758+Mechanical_Plan+6.7.2024_9.02.48_AM+4307496238TH ST SW - %: 40 C!r VICINITY MAP NOT TO SCALE APPROVED BY PLANNING Jun 21 2024 Noise generated by mechanical equipment must meet the standards in ECC 5.30 DUCT INSULATION TABLE PER TABLEC403.10.1.2 2021 WSEC REQUIRED DUCT SYSTEM DUCT LOCATION AND USE TYPICAL EXAMPLE INSULATION R-VALUES OUTSIDE BUILDING ATTIC VENTED TO AMBIENT/ROOFTOP SUPPLY/RETURN EXPOSED TO WEATHER/AMBIENT CONDITIONS R 8 DUCT SUPPLY/RETURN UNCONDITIONED SPACE R-6 ENCLOSED ATTIC W/O VENT SUPPLY/RETURN UNCONDITIONED SPACE W/ AMBIENT CONDITIONS R-3.3 DUCT WITHIN CEILING PLENUM WITHIN 15OF OF DESIGN AIRFLOW TEMPERATURE SPIRAL DUCT IN OPEN CEILING SUPPLY/RETURN EXPOSED DUCT WITHIN THE ZONE IT'S SERVING NONE TERMINATING IN SAME SPACE DUCT WITHIN CONDITIONED SPACE, DOWNSTREAM OF DUCT THROUGH CEILING RETURN PLENUM RETURN/EXHAUST ERV, UPSTREAM OF ISOLATION DAMPER R-8 BETWEEN ERV AND MOTORIZED DAMPER AT ENVELOPE PENETRATION DUCT WITHIN CONDITIONED SPACE, DUCT THROUGH CEILING RETURN PLENUM RELIEF/EXHAUST R-16 BETWEEN MOTORIZED DAMPER AND UPSTREAM OF ISOLATION DAMPER ENVELOPE PENETRATION OUTDOOR AIR LESS THAN 2800 CFM DUCT WITHIN CONDITIONED SPACE R-7 DUCT THROUGH CEILING RETURN PLENUM OUTDOOR AIR GREATER THAN 2800 CFM INSIDE CONDITIONED SPACE, R 8 DUCT FROM MOTORIZED DAMPER AT DOWNSTREAM OF MOTORIZED DAMPER ENVELOPE PENETRATION TO HVAC UNIT DUCT FROM MOTORIZED DAMPER AT HVAC OUTDOOR AIR GREATER THAN 2800 CFM INSIDE CONDITIONED SPACE, R-16 UNIT (LOCATED INSIDE BUILDING) TO DOWNSTREAM OF MOTORIZED DAMPER ENVELOPE PENETRATION POINT SITE MAP NOT TO SCALE EXISTING GAS PACKAGED EQUIPMENT SCHEDULE FAN COOLING HEATING ELECTRICAL FILTER WEIGHT MARK MANF. MODEL TONS AIRFLOW ESP MOTOR DRIVE TOTAL OUTPUT M.C.A. MOCP SIZE (Ib) NOTES (CFM) (IN -WC) HP STYLE (BTU/h) SEER2 EER2 (BTU/h) HSPF2 V 0 (A) (A) (SQ.FT) (E)RTU-I TRANE 4WCC4060EI000A 5 1835 .1 1 DID 57,000 1 13.4 II 55,000 7 208 39 1 60 5.3 490 1 NOTES: I. PROVIDED AND INSTALLED BY OTHERS. AIR TERMINAL UNIT SCHEDULE ITEM MARK MANF. MODEL MATERIAL FINISH SIZE NOTES CEILING DIFFUSER CD-1 PRICE SMCD STEEL WHITE SEE SCHEDULE BORDER TYPE 36 = T-BAR BORDER TYPE 6 = HARD LID CEILING GRILLE CG-I PRICE 80 ALUMINUM WHITE NECK SIZE SQ. BORDER TYPE 3 = T-BAR NOTES: I. ADD MANUAL VOLUME DAMPER TO EACH SUPPLY DIFFUSER BRANCH. 2. ADD MANUAL VOLUME DAMPER TO EACH EXHAUST RETURN GRILLE BRANCH. SUPPLY DIFFUSER SIZE SIZE RANGE 6"X6" 0-100CFM 8" X 8" 101 - 250 CFM 101, X 101, 251 - 425 CFM 12" X 12" 426 - 650 CFM 238TH ST SW GOVERNING CODE INFORMATION 2021 INTERNATIONAL BUILDING CODE WITH STATEWIDE AMENDMENTS 2021 INTERNATIONAL MECHANICAL CODE WITH STATEWIDE AMENDMENTS 2021 INTERNATIONAL FIRE CODE WITH STATEWIDE AMENDMENTS 2021 INTERNATIONAL ENERGY CONSERVATION CODE/WASHINGTON STATE ENERGY CODE 2021 INTERNATIONAL EXISTING BUILDING CODE WITH STATEWIDE AMENDMENTS FOUND IN THE IBC COMMISSIONING PLAN ALL COMMISSIONING OF HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS AS REQUIRED BY SECTION C408 "SYSTEM COMMISSIONING" OF THE 2021 WASHINGTON STATE ENERGY CODE (WSEC) SHALL BE PERFORMED BY EVERGREEN REFRIGERATION, LLC. THE ACTIVITIES TO BE ACCOMPLISHED ARE PER THE SECTIONS LISTED IN THE "COMMISSIONING COMPLIANCE CHECKLIST" SHOWN BELOW. AT THE COMPLETION OF THE SCOPE ACTIVITIES REQUIRED FOR COMMISSIONING AS DEFINED BY SECTION C408 OF WSEC THE "COMMISSIONING COMPLIANCE CHECKLIST" WILL BE REVIEWED WITH THE BUILDING OF WORK OWNER OR THE OWNER'S REPRESENTATIVE AND THIS CERTIFICATION WILL BE SIGNED AND DATED. THIS WILL SATISFY TO THE CODE OFFICIAL THAT THE REPORT HAS BEEN ACCEPTED AS REQUIRED BY SECTION C408.1.3 OF WSEC. GLOBE OR ROOFTOP GLOBE CAP NOT TO SCALE PROJECT INFORMATION SUPPORTING DOCUMENTS COMMISSIONING COMPLIANCE CHECKLIST Project Name: Project Address: Certified Commissioning Professional: Type of ISO Certification and Number: Manuals, record documents and training have been completed or are scheduled (SECTION C103. • BUILDING OPERATIONS AND MAINTENANCE INFORMATION (C103.62) HAVE BEEN SUBMITTED TO THE OWNER OR SCHEDULED DATE: • MANUALS (C103.6.2.1) HAVE BEEN SUBMITTED TO THE OWNER OR SCHEDULED DATE: • COMPLIANCE DOCUMENTATION (CIO3.6.3) HAS BEEN PROVIDED TO THE OWNER OR SCHEDULED DATE: • SYSTEM OPERATION TRAINING (C103.6.4) HAS BEEN PROVIDED TO THE OWNER OR SCHEDULED DATE: COMMISSIONING Commissioning Plan was used during construction (Section C408.1.2) PLAN COMMISSIONING Commissioning Report has been submitted (Section C408.1.3) REPORT COMMISSIONED SYSTEMS CERTIFICATION Mechanical Systems were included in the commissioning process (Section C408.2) Testing, adjusting and balancing is complete (Section C408.2.2) There are unresolved deficiencies with the mechanical system. These are described in the attached Commissioning Report submitted to the Owner Service Water Heating Systems were included in the commissioning process (Section C408.3) There are unresolved deficiencies with the service water heating system. These are described in the attached Commissioning Report submitted to the Owner. Controlled Receptacles and Lighting Control Systems were included in the commissioning process (Section C408.4) There are unresolved deficiencies with the electrical power and/or automatic lighting controls. These are described in the attached Commissioning Report submitted to the Owner. Additional Systems were included in the commissioning process (Section C408.5) There are unresolved deficiencies with systems required by C406 or C407. These are described in the attached Commissioning Report submitted to the Owner. Metering Systems were included in the commissioning process (Section C408.6) There are unresolved deficiencies with the metering system. These are described in the attached Commissioning Report submitted to the Owner. Refrigeration Systems were included in the commissioning process (Section C408.7) There are unresolved deficiencies with systems required by section C410. These are described in the attached Commissioning Report submitted to the Owner. I HEREBY CERTIFY THAT ALL REQUIREMENTS FOR SECTION C408 SYSTEM COMMISSIONING HAVE BEEN COMPLETED IN ACCORDANCE WITH THE WASHINGTON STATE ENERGY CODE, INCLUDING ALL THE ITEMS ABOVE. CERTIFIED COMMISSIONING PROFESSIONAL DATE OI HEREBY CERTIFY THAT ALL REQUIREMENTS FOR SECTION C408 SYSTEM COMMISSIONING HAVE BEEN COMPLETED IN ACCORDANCE WITH THE WASHINGTON STATE ENERGY CODE, INCLUDING ALL THE ITEMS ABOVE. BUILDING OWNER OR OWNERS REPRESENTATIVE DATE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE T STORM CAP CONE FLASHING FLAT OR PITCHED GENERAL NOTES DUCTWORK 1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4" TO EACH DIMENSION IF THE DUCTWORK IS ON THE INTERIOR OF THE BUILDING. 1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND IS THE HEIGHT. 1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING LESS THAN 25 AND A FLAME SMOKE DEVELOPMENT LESS THEN 50, PER IMC 602.2.1. 1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETWEEN 112 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT PRESSURES ABOVE 112 WATER COLUMN SHALL BE SEALED IN ACCORDANCE WITH STANDARD RS-7. 1.5 ALL DUCT GAUGES PER SMACNA, IMC 603-4. 1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603-10. 1.7 ATTACH DIFFUSERS AND GRILLES TO T-BAR PER WA STATE & LOCAL CODES. 1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS. INSULATION 2.1 WHEN PRESENT, INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES. 2.2 WHEN PRESENT, INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGY CODES. GENERAL CONTRACTOR 3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP, CEILING, FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING AND FIRE PROOF LININGS PER IMC & IBC. 3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS WITH ERL BEFORE FRAMING OPENINGS. 3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING AS REQUIRED FOR MECHANICAL WORK. 3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS REQUIRED FOR MECHANICAL WORK. 3.5 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL MECHANICAL EQUIPMENT. 3.6 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE ALL CANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS. 3.7 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OR T-BAR CEILING AS REQUIRED FOR HVAC INSTALLATION. 3.8 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC. ELECTRICAL 4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED BY ELECTRICAL CONTRACTOR. 4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS, DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT. 4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS, WITH ERL MECHANICAL PLAN AND WITH FIELD LOCATIONS. 4.4 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER. IF APPLICABLE. 4.5 ELECTRICIAN TO PROVIDE APPURTENANCES IN ACCORDANCE WITH NEC 210.63, AND ALL OTHER APPLICABLE SECTIONS. PLUMBING 5.1 PLUMBING CONTRACTOR OFFSETS VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH AIR INTAKES OR 3' ABOVE HIGHEST POINT OF INTAKE, IMC 401.4 5.2 CONDENSATE DRAINS FOR AIR HANDLERS BY PLUMBER. ENERGY CODE COMPLIANCE 6.1 THE SUPPLY HEATING AND COOLING ENERGY TO EACH ZONE SHALL BE CONTROLLED BY INDIVIDUAL THERMOSTATIC CONTROLS CAPABLE OF RESPONDING TO TEMPERATURE WITHIN THE ZONE. AT MINIMUM, EACH FLOOR SHALL BE CONSIDERED A ZONE. 6.2 OUTDOOR AIR SUPPLY, EXHAUST OPENINGS AND RELIEF OUTLETS SHALL BE PROVIDED WITH CLASS IA MOTORIZED DAMPERS WHICH CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFF PER WSEC SECTION C403.7.8. MECHANICAL CODE COMPLIANCE 7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM. DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606. APPROVED PLANS MUST BE ON JOB SITE City Of Edmonds Building Department Work MECHANICAL Address 23805 HIGHWAY 99 #101 Owner CLUB PILATES Approved Date 06/12/2024 Building Official Erg ------------------------------- Permit Number BLD2024-0758 EXHAUST FAN SCHEDULE MARK MANF. MODEL AIRFLOW (CFM) ESP (IN -WC) ELECTRICAL WEIGHT (lb) NOTES V 0 MCA (A) EF-I BROAN LIOOE 100 .25 120 10 0.3 A 18.9 1 EF-2 BROAN AEI10 110 0.1 115 10 0.3 A 10 1 EF-3 BROAN AEI10 110 0.1 115 10 0.3 A 10 1 NOTES: I. SWITCHED TO RUN THROUGH LIGHT SWITCH BY ELECTRICAL CONTRACTOR. WA2021 SYMBOL LEGEND NOTE: NOT ALL SYMBOLS SHOWN ON THIS LEGEND MAY PERTAIN TO THIS PROJECT. NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS, DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS. N v M V w w O �a C1 •i o°Jc co CD w M z � E v~i 00 Z I UO M Z 2 "o � Y Q '� N O 6 � N 0 w Lu cn � z 3 1`10 r, LU U-) a 3 TA C)v WAS LU Ce LU I U) _. LU w 0052287 � z �FCitST w SSJONAL�G RECOWED 6/7/?024 I CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT z 0 � N w LU O 00 W o w W LL I --I = I0 w a z > m o 0 J ro U U 0 c\l w Z 0 a H� U V) w 0 w F- 0 w a PERMIT SET DATE: 6.7.24 ISSUED FOR CONSTRUCTION ❑ DATE: ---- AS BUILT ❑ DATE: ---- CLUB PILATES EDMONDS COVER SHEET DWG BY: JC CKD BY: KT/AF JOB NO.: 524141 SHEET: VENTILATION TABLE PEOPLE AREA OUTDOOR OUTDOOR OCCUPANT ROOM AIRFLOW RATE AIRFLOW ROOM DENSITY OCCUPANCY TOTAL REQ. DESIGN AREA IN BREATHING RATE IN NAME #/1000 SF (# PEOPLE) OSA CFM OSA CFM (SF) ZONE, BREATHING 11� CFM/PERSON ZONE, CFM/SF I1) III Customer Entry/Sign In 101 480 10 5 5 0.06 53.8 55 Club Pilates Studio 102 1,330 16 22 20 0.06 519.8 520 PT Area 105 and 106 393 10 4 5 0.06 43.58 45 Off ice 107 72 5 1 5 0.06 9.32 10 Hallway 108 63 0 0 5 0.06 3.78 5 Employee 109 355 10 4 5 0.06 41.3 45 Egress Hallway B200 52 0 0 1 5 1 0.06 1 3.12 1 5 BldgElect/Data B201 69 0 0 5 0.06 4.14 5 NOTES: 1. PER I MC TABLE 403.3.1.1 HVAC PLAN SCALE: 1 /4"=1' 0 1' 2 4' 8' KEY NOTES: I. DUCTWORK FROM EXISTING ROOFTOP UNIT TO REMAIN AS IS. 2. THERMOSTAT PROVIDED AND INSTALLED BY OTHERS. NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS, DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN REFRIGERATION U.C. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS. L0 V w w c O �a a v� �i OTC 00 w M i K z E p o z y O z=r\ � LU Q QT _ 3: Cr:,) o, H J LU > z r, r1j LU TA� J1 OF WASqI,j, � LU �� LU �o 0052287 � � z SSIDNATT LU RECOWED 6/7/?024 1 CITY OF DEVELOPMENT EDMONDS SERVICES DEPARTMENT z 0 z 0 0 2: cv o 0 0 00 M J LU LU a a = z LU > m J � 0 o � 0 U M 0 r*4 LU z 0 U U0 w 0 w I— Q Q w PERMIT SET DATE: 6.7.24 ISSUED FOR CONSTRUCTION ❑ DATE: ---- AS BUILT ❑ DATE: ---- CLUB PILATES EDMONDS OVERALL FLOOR PLAN DWG BY: JC CKD BY: KT/AF JOB NO.: 524141 SHEET: KEY NOTES: EXISTING ROOFTOP UNIT. ROOF PLAN SCALE: 1/8"=1' NOT PUBLISHED. ALL RIGHTS RESERVED. THE DRAWING AND SPECIFICATIONS, IDEAS, DESIGN AND ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN THE PROPERTY OF EVERGREEN REFRIGERATION LLC. NO PART THERE OF SHALL BE DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATION TO EVERGREEN REFRIGERATION U.C. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS. Lr) J c� V W W _� _C ice+ L �i 00 w Co i F- z E p o Z u p Z Y Q l0 QT _ 3: OTV H J Lu > O z a) cli Lu Tarp OF WASqI,1, � Lu co r!� In Lu 0052287 z O �FGLS'I�RG��� w Sto RECOWED 6/7/?024 1 CITY OF DEVELOPMENT EDMONDS SERVICES DEPARTMENT 0 z O o cl-j 2: o 0 00 m z w Lf) 0-) Q w 112L g LL a 0 = z O m Ln 0 o O i °0 0 DC U cv w z 0 U ul) w 0 w I— Q Q w PERMIT SET DATE: 6.7.24 ISSUED FOR CONSTRUCTION ❑ DATE: ---- AS BUILT ❑ DATE: ---- CLUB PILATES EDMONDS ROOF PLAN DWG BY: JC CKD BY: KT/AF JOB NO.: 524141 SHEET: M202