APPROVED BLD PLN BLD2024-1006+Site_Plan+8.2.2024_8.39.51_AM+4417706APPROVED LEGEND ACU AIR CONDITIONING UNIT AFF ABOVE FINISHED FLOOR AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT BDD BACKDRAFT DAMPER BHP BRAKE HORSEPOWER BTUH BRITISH THERMAL UNIT PER HOUR C COMMON CAP CAPACITY CC COOLING COIL CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CLG CEILING, COOLING CO CLEANOUT COMB COMBUSTION CONT CONTINUE, CONTROL CONTR CONTRACTOR COP COEFFICIENT OF PERFORMANCE CWS CHILLED WATER SUPPLY CWR CHILLED WATER RETURN D DIAMETER DB DRY BULB, DECIBEL DEG DEGREE DIM DIMENSION DISCH DISCHARGE DN DOWN EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN EFF EFFICIENCY EG EXHAUST GRILLE, ENGINE GENERATOR ELEC ELECTRIC EQUIV EQUIVALENT ESP EXTERNAL STATIC PRESSURE EXH EXHAUST EXT EXTERIOR, EXTERNAL F FAHRENHEIT FD FIRE DAMPER FCU FAN COIL UNIT FLR FLOOR FPM FEET PER MINUTE FPS FEET PER SECOND FSD FIRE/SMOKE DAMPER G GAS GRD GRILLES, REGISTERS, AND DIFFUSERS GWB GYPSUM WALLBOARD HORIZ HORIZONTAL HP HORSEPOWER, HEAT PUMP HRU HEAT RECOVERY UNIT HVAC HEATING, VENTILATING, AND AIR CONDITIONING HVU HEATING AND VENTILATION UNIT HWR HIGH WALL RETURN, HOT WATER RETURN HWS HIGH WALL SUPPLY, HOT WATER SUPPLY HX HEAT EXCHANGER ID INDIRECT DRAIN, INSIDE DIAMETER IN INCH KW KILOWATT L LONG, LENGTH LB POUND LWR LOW WALL RETURN LWS LOW WALL SUPPLY MBH THOUSAND BTU PER HOUR MECH MECHANICAL MCA MINIMUM CIRCUIT AMPACITY MOCP MAXIMUM OVER CURRENT PROTECTION MTD MOUNTED OSA OUTDOOR AIR OBD OPPOSED BLADE DAMPER OD OUTSIDE DIMENSION OR DIAMETER OPNG OPENING P PUMP PD PRESSURE DROP POC POINT OF CONNECTION PRV PRESSURE REDUCING VALVE PSIG POUNDS PER SQUARE INCH GAUGE RA RETURN AIR REF REFERENCE RF RELIEF FAN RG RETURN GRILLE RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR SCH SCHEDULE SF SUPPLY FAN, SQUARE FOOT SENS SENSIBLE SG SUPPLY GRILLE SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION SO SCREENED OPENING SP STATIC PRESSURE SS STAINLESS STEEL, SANITARY SEWER SQ SQUARE TG TRANSFER GRILLE TYP TYPICAL UH UNIT HEATER UON UNLESS OTHERWISE NOTED V VENT VENT VENTILATION, VENTILATOR VTR VENT THRU ROOF W WASTE, WATT, WIDE WB WET BULB (TEMPERATURE) EQUIPMENT EF-1 TYPICAL EQUIPMENT DESIGNATION (EXHAUST FAN SHOWN) DSD DUCT SMOKE DETECTOR O ROOM THERMOSTAT OR TEMPERATURE TRANSMITTER O ROOM HUMIDISTAT OR HUMIDITY TRANSMITTER co CARBON MONOXIDE SENSOR s� SMOKE DETECTOR TERMINALS CD-12x12 CD-1�DIFFUSER/GRILLE TYPE, AND OR NUMBER OR SIZE 400 400DESIGN CFM (WHERE APPLICABLE) CEILING DIFFUSER (FLOW ARROWS X � SHOWN FOR NON SYMMETRICAL AIRFLOW) / F� CEILING RETURN/EXHAUST GRILLE LINEAR DIFFUSER, CEILING OR WALL MOUNTED (FLOW ARROWS SHOWN y y FOR NON SYMMETRICAL AIRFLOW) � WALL SUPPLY GRILLE (SG) �� WALL RETURN/EXHAUST GRILLE (RG, EG) TRANSFER GRILLE (TG), DUCT �� CONNECTED, WALL MOUNTED W/ 50 OPTIONAL CFM SHOWN TRANSFER GRILLE, CEILING �� � I I � � MOUNTED WITH FULL-SIZED LINED DUCT CONNECTION GENERAL ARCHITECTURAL BACKGROUND (THIN LINE) NEW MECHANICAL WORK (HEAVY LINE) - - MATCHLINE OR PROPERTY LINE SECTION INDENTIFICATION iDETAIL SIMILAR INDICATES DIRECTION OF CUTTING PLANE A LETTER INDICATES SECTION M-3 M-3 (N0. INDICATES DETAIL) SHEET #WHERE SECTION IS DRAWN SHEET #WHERE SECTION IS TAKEN DUCTWORK DUCT (1ST FIGURE = SIDE SHOWN, 18x12 2ND FIGURE = SIDE NOT SHOWN) UP DOWN � i i� DUCT SECTION, POSITIVE PRESSURE UP DOWN � � DUCT SECTION, NEGATIVE PRESSURE UP DOWN ROUND DUCT SECTION UP UP UP XOR DUCT PENETRATION THRU FLOOR ROOF FSD FSD FIRE/SMOKE DAMPER (--� _ HORIZ DUCT, --♦ = VERT DUCT), 2-HR RATED, UON VOLUME DAMPER FD �FD FIRE DAMPER (--� = HORIZ DUCT, --♦ = VERT DUCT), 2-HR RATED, UON 90° ELBOW, R/D OR R/W=1.5 SQUARE CORNER ELBOW WITH TURNING VANES 90° TAKE -OFF OR TEE 90° CONICAL TAKE -OFF 45° LATERAL TAKE -OFF TRANSITION OR REDUCER (FOT = � FLAT ON TOP, FOB = FLAT ON BOTTOM) WYE FI TTI N G 90° RECTANGULAR TAKE -OFF WITH 45° TAPER 90° DIVERGING RECTANGULAR TEE, ,{ EITHER RADIUS OR TURNING VANES FLEXIBLE DUCT � ROUND DUCT INDICATOR PLANS MUST BE GEN-P%�,� N�'TE`� ON JOB SITE GENERAL NOTES -MECHANICAL 1. REFERENCE TO RELATED WORK: "REF" INDICATIONS DENOTE WORK COVERED ELSEWHERE (ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL, LANDSCAPE, OR KITCHEN), OR ITEM BASED ON A SPECIFIC MANUFACTURER'S DIMENSIONS (VERIFY). 2. ELECTRICAL CHARACTERISTICS: REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS (VOLTAGES, ETC.) OF MECHANICAL EQUIPMENT, UNLESS OTHERWISE INDICATED. 3. CODES: COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE PER THE APPLICABLE BUILDING, MECHANICAL, ENERGY, PLUMBING, FIRE, AND HEALTH CODES AND REGULATIONS AS ADOPTED BY THE LOCAL AHJ. 4. PREPARE AND SUBMIT FOR REVIEW A SHOP DRAWING BASED ON FINAL STRUCTURAL SHOP DRAWINGS FOR LOCATING AND ROUTING ALL DUCTWORK, DAMPERS, EQUIPMENT, PIPING, ETC. A. COORDINATE FLOOR AND BEAM PENETRATIONS WITH STRUCTURAL. B. COORDINATE FINAL LOCATION AND ROUTING WITH CEILING, LIGHTS, WALLS, FIRE SPRINKLER PIPING, AND OTHER TRADES WORK C. INCLUDE ADDITIONAL OFFSETS, ELBOWS, ROUTING, EQUIVALENT DUCT SIZING EXCHANGE, RELOCATING, ETC. AS REQUIRED FOR A COMPLETE OPERATING MECHANICAL SYSTEM. D. PROVIDE SHOP DRAWINGS AT NO ADDITIONAL COST TO THE OWNER. 5. MECHANICAL CONTRACTOR SHALL LOCATE AND COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITHIN THE STRUCTURE. 6. ACCESS DOORS: COORDINATE WITH ARCHITECT AND LOCATE ALL ACCESS DOORS ON SHOP DRAWINGS PRIOR TO BEGINNING OF CONSTRUCTION. ACCESS DOORS IN FIRE RATED STRUCTURE SHALL BE FIRE RATED. VERIFY ACCESS DOOR LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO BIDDING. 7. RATED PENETRATION: DUCT PENETRATIONS THROUGH RATED ENCLOSURES SHALL BE FIRE/SMOKE DAMPERED PER THE LATEST EDITION OF THE UNDERWRITERS LABORATORIES(UL) FIRE RESISTANCE WITH HOURLY RATINGS FOR THROUGH -PENETRATION FIRE STOPS SYSTEM VOLUME #2, OR SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S UL LISTINGS (3M OR EQUIVALENT). DETERMINE REQUIREMENTS WITH GENERAL CONTRACTOR PRIOR TO BID. 8. EXHAUST OUTLETS/DRYER VENTS: SOURCE -SPECIFIC FANS SHALL BE VENTED TO OUTDOORS WITH A MINIMUM 3' CLEARANCE BETWEEN VENT OUTLETS AND BUILDING OPENINGS, AND 10' MINIMUM BETWEEN VENT OUTLETS AND MECHANICAL AIR INTAKES. 9. SHAFT AND PLENUM CONNECTIONS: SEAL CONNECTIONS TO AIR SHAFTS AIRTIGHT. PROVIDE AIRTIGHT SEAL AROUND PENETRATIONS IN AIR PLENUMS. 10. LIGHT FIXTURE CLEARANCE: COORDINATE LOCATIONS OF MECHANICAL WORK TO PROVIDE CLEARANCES OVER LIGHTING FIXTURES FOR REMOVAL AND REPLACEMENT. 11. MOTORS: COMPLY WITH ENERGY CODE ENFORCED BY AHJ FOR MINIMUM EFFICIENCIES UNDER FULL LOAD. 12. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT: VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF MECHANICAL WORK AND WORK OF OTHER TRADES TO PROVIDE ACCESS CLEARANCES FOR SERVICE AND MAINTENANCE. COORDINATION REQUIREMENTS 1. DUCTWORK: LOCATE AND COORDINATE THE EXACT LOCATION OF DUCTWORK WITH STRUCTURAL PLANS AND WITH THE GENERAL CONTRACTOR PRIOR TO INSTALLATION OF ANY STRUCTURE OR EQUIPMENT. COORDINATE WITH FRAMING CONTRACTOR TO ASSURE JOIST SPACES LINE UP WHEN DUCTWORK MUST PASS THROUGH DIFFERENT JOIST SPACES. 2. ADJUSTMENTS: ALL EQUIPMENT, MOTORS, FANS GAS BURNERS, IGNITION DEVICES, DRIVES, ETC. SHALL BE ADJUSTED AND BALANCED TO OPERATE AT SPECIFIED RATINGS AS REQUIRED FOR THIS PROJECT SITE AND ACCOUNTING FOR ELEVATION ABOVE SEA LEVEL. 3. APPROVALS: MECHANICAL AND PLUMBING EQUIPMENT SHALL BE APPROVED FOR INSTALLATION IN THE PROJECT LOCATION AND SHALL HAVE ALL CERTIFICATIONS AND RATINGS TO MEET ALL ENERGY, POLLUTION, ENVIRONMENTAL, SEISMIC, ETC. CODES AND REGULATIONS. THE CONTRACTOR SHALL COORDINATE WITH HIS MANUFACTURE SUPPLIERS AND SHALL INCLUDE ALL COSTS REQUIRED TO MEET THESE REQUIREMENTS IN HIS BID. HVAC NOTES 1. ATTACHMENTS: AIR DISTRIBUTION OUTLETS AND LOUVERS SHALL HAVE ALL REQUIRED ACCESSORIES AND ATTACHMENTS FOR A COMPLETE CONNECTION TO THE SPECIFIC TYPE OF STRUCTURE THAT THEY ARE BEING ATTACHED T0. THIS INCLUDES, BUT IS NOT LIMITED T0, EXTERIOR BRICKS, GWB WALLS, GWB CEILING, ETC. 2. FIRE RATINGS: RATED FLOOR/CEILING JOINT SPACES HAVING DUCTWORK INSIDE THEM SHALL BE FIRE/SMOKE PROTECTED TO MAINTAIN THE 1-HOUR FLOOR/CEILING RATING PER LOCAL JURISDICTIONS. EXHAUST DUCTWORK PENETRATING THE 1-HOUR ROOF/CEILING OR FLOOR/CEILING ASSEMBLY SHALL HAVE ACCESSIBLE CEILING FIRE DAMPERS. ALTERNATIVELY, THE EXHAUST DUCTWORK SHALL BE ROUTED INSIDE A RATED SHAFT TO PROTECT THE CEILING/ROOF RATING PER THE LOCAL JURISDICTIONS. 3. FIRESTOP: PIPE, DUCT, AND CONDUIT PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE FIRE AND SMOKE STOPPED PER CODE. 4. DUCTWORK: DUCTWORK SHALL BE SMOOTH SHEET METAL (CLASS-1). DUCTWORK THROUGH FIRE RATED STRUCTURE AND FLOOR SHALL BE MIN. 26 GA. STEEL. MAXIMUM LENGTH OF FLEXIBLE DUCTS SHALL BE 5'-0", UNLESS OTHERWISE NOTED ON DRAWINGS. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. 5. DUCTWORK AND PIPING OUTSIDE OF MECHANICAL ROOMS SHALL BE CONCEALED. COORDINATE WITH THE GENERAL CONTRACTOR TO FUR -OUT AS REQUIRED. 6. VOLUME DAMPERS: PROVIDE AN ACCESSIBLE MANUAL VOLUME DAMPER FOR EACH SUPPLY, RETURN, OSA, AND EXHAUST OPENING, LOCATED AS FAR UPSTREAM AS POSSIBLE FROM THE OPENING. PROVIDE A MANUAL VOLUME DAMPER FOR BRANCH MAINS SERVING MORE THAN ONE OPENING. VOLUME DAMPERS IN NON -ACCESSIBLE CEILINGS SHALL HAVE A CONTROL ARM EXTENDED TO AN ACCESSIBLE LOCATION. PROVIDE "YOUNG" REGULATOR OR EQUAL. EXACT LOCATION OF CONTROL DEVICES VISIBLE IN FINISHED SPACES SHALL BE COORDINATED WITH THE ARCHITECT. 7. SEISMIC: PROVIDE SEISMIC RESTRAINTS FOR MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK PER SMACNA AND LOCAL REGULATIONS. 8. FILTER CLEARANCE: PROVIDE ADEQUATE CLEARANCE FOR CHANGING AIR FILTERS SHEET METAL NOTES 1. REFERENCE: SMACNA HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE, CURRENT EDITION. 2. CLEARANCE: COORDINATE DUCTWORK WITH MISCELLANEOUS OBSTRUCTIONS IN CEILING SPACE. 3. ROUND ELBOWS AND OFFSETS: FULL RADIUS (R/D = 1.5), 5-PIECE SEGMENTED OR STAMPED. REFER TO SMACNA HVACDCS FIG 2-7, 3-3. DO NOT USE ANGLED OFFSET (TYPE 1). MITERED OFFSET (TYPE 2) MAY BE USED UP TO 30 DEGREE OFFSET ANGLE. 4. ROUND TEES AND LATERALS: CONICAL TEE PER SMACNA HVACDCS FIG 3-5; DO NOT USE STRAIGHT TEE; DO NOT USE CONICAL SADDLE TAP FOR EXPOSED DUCTWORK IN FINISHED SPACES. 90- DEGREE TEE WITH OVAL TO ROUND TAP, LATERAL, AND 45- DEGREE RECTANGULAR LEAD-IN PER SMACNA HVACDCS FIG 3-4. 5. RECTANGULAR ELBOWS AND OFFSETS: FULL RADIUS WHERE SPACE PERMITS, R/W = 1.5; OTHERWISE USE SQUARE CORNER ELBOW WITH TURNING VANES. 6. RECTANGULAR DIVIDED FLOW FITTINGS: USE GENERALLY, EXCEPT BRANCHES TO TERMINALS; SMACNA HVACDCS FIG 2-5, TYPES 1, 2, 4A, AND 4B. DO NOT USE TYPE 3. 7. TURNING VANES: H.E.P. MANUFACTURER OR APPROVED HIGH EFFICIENCY PROFILE AIRFOIL TYPE FOR RECTANGULAR SQUARE THROAT ELBOWS. 8. TAKEOFFS TO OPENINGS: CONICAL TYPE WITH VOLUME DAMPER FOR ROUND DUCT BRANCHES PER SMACNA HVACDCS FIG 2-6, MINIMUM INLET DIAMETER 2 INCHES LARGER THAN DUCT SIZE. 45 DEGREE ENTRY FITTING FOR RECTANGULAR DUCT BRANCHES PER SMACNA HVACDCS FIG 2-6. 9. FLEXIBLE CONNECTIONS: PROVIDE AT EACH DUCT CONNECTION TO FANS, PACKAGED HVAC EQUIPMENT, EXTERNALLY ISOLATED AIR HANDLING UNITS, FAN COIL UNITS, AND SIMILAR EQUIPMENT. EXCEPTION: EQUIPMENT IN CORRIDOR CEILING SPACES WHERE FIRE RATING IS REQUIRED. INSULATION/LINING NOTES 1. ENERGY CODE: AS A MINIMUM, COMPLY WITH THICKNESSES AND TYPES LISTED IN ENERGY CODE ENFORCED BY AHJ. 2. EXTENT OF INTERNAL DUCT LINING: A. GRILLE AND DIFFUSER BOXES AND BOOTS. B. TRANSFER DUCTS. 3. EXTENT OF EXTERNAL DUCT INSULATION: A. SUPPLY AND RETURN AIR IN UNCONDITIONED SPACES, MECHANICAL ROOMS, ELECTRICAL ROOMS, AND EQUIPMENT ROOMS NOT SPECIFIED TO BE INTERNALLY LINED. B. SUPPLY AIR IN CONCEALED LOCATIONS NOT SPECIFIED TO BE INTERNALLY LINED. C. OUTDOOR AIR INTAKE. D. EXHAUST DUCT IN UNCONDITIONED SPACES. 4. MISCELLANEOUS DUCT FITTINGS (CONICAL TAKEOFFS, ETC.): WRAP WITH INSULATION FOR CONDENSATION CONTROL. PIPING NOTES 1. DISASSEMBLY PROVISIONS: PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE. 2. REDUCERS: PROVIDE AS REQUIRED FROM LINE PIPE SIZE TO EQUIPMENT, TRAP, COIL, AND CONTROL VALVE CONNECTION SIZES. 3. OFFSETS: PROVIDE FOR BRANCH LINES TO EQUIPMENT. 4. DIELECTRIC UNIONS: PROVIDE AT CONNECTIONS OF DISSIMILAR PIPE. DRAWINGS ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, LAYOUT, AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENT. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS. REFER TO MANUFACTURER'S STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION REQUIREMENTS. PROVIDE DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS, AND MATERIALS NECESSARY FOR A COMPLETE SYSTEM. ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE APPROVED BY PLANNING C SC Aug 02 2024 Noise generated by mechanical equipment must meet the standards in ECC 5.30 City Of Edmonds Building Department Work MECHANICAL- RTU Address 50 PINE ST UNIT 515 Owner GASPER Approved Date 08/06/2024 Building Official Permit Number BLD2024-1006 PROJECT HOC �,TI ON AP P CAB E COD E� THESE DRAWINGS ARE BASED ON THE FOLLOWING CODES: -2021 INTERNATIONAL BUILDING CODE (WITH WASHINGTON STATE AMENDMENTS) -2021 INTERNATIONAL MECHANICAL CODE (WITH WASHINGTON STATE AMENDMENTS) -2021 WASHINGTON STATE ENERGY CODE DRAW C DES DWG DESCRIPTION M0.0 LEGEND, NOTES &INDEX M0.1 SCHEDULES /DETAILS M1.0 HVAC PLANS P S � � N � � F r �FCHAN�GP Gasline Mechanical Inc. 9926 Elliot Rd. Snohomish WA 98296 �pvQ�,,ER TI<<M-`�< � �o.••.••••W •••. qti .';��cF Asy��c• ; z: v�o �sr'ER�°��� �oov ��Op`�'�ONAL ENGp �� - I%-�-� �000000 i" EXPIRES: 10/25/24 ISSUE: 0 RECEIVED Aug 02 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET NO. LEGEND, NOTES, & INDEX O o O PROJECT NO. COPIRIGHT 2024, PINEHURST ENGINEERING / GASLINE MECHANICAL 7/ 17/24 PERMIT SET SPL T SYSTEM HEAT PUMP SCHEDULE - NDOOR UN T EQUIP N0. SERVICE MOUNTING/ DISCHARGE FAN ELECTRICAL BASIS OF DESIGN (1)(2)(3) CONNECTED OUTDOOR UNIT AIRFLOW, CFM MOTOR HP VOLTAGE MOCP IHP-201 A UNIT 201 HIGH WALL 335 FHP 208V/1 P 15 BOSCH BMS500-AA0009-1 AHWXC OHP-201 IHP-201 B UNIT 201 HIGH WALL 523 FHP 208V/1 P 15 BOSCH BMS500-AAU018-1 AHWXC OHP-201 IHP-422A UNIT 422 HIGH WALL 335 FHP 208V/1 P 15 BOSCH BMS500-AA0009-1 AHWXC OHP-422 IHP-422B UNIT 422 HIGH WALL 523 FHP 208V/1 P 15 BOSCH BMS500-AAU018-1 AHWXC OHP-422 IHP-423A UNIT 423 HIGH WALL 335 FHP 208V/1 P 15 BOSCH BMS500-AA0009-1 AHWXC OHP-423 IHP-423B UNIT 423 HIGH WALL 523 FHP 208V/1 P 15 BOSCH BMS500-AAU018-1 AHWXC OHP-4231 IHP-515A UNIT 515 HIGH WALL 335 FHP 208V/1P 15 BOSCH BMS500-AA0009-1AHWXC OHP-515 IHP-5156 UNIT 515 HIGH WALL 523 FHP 208V/1P 15 BOSCH BMS500-AAU018-1AHWXC OHP-515 IHP-517A UNIT 517 HIGH WALL 335 FHP 208V/1P 15 BOSCH BMS500-AA0009-1AHWXC OHP-517 IHP-517B UNIT 517 HIGH WALL 523 FHP 208V/1P 15 BOSCH BMS500-AAU018-1AHWXC OHP-517 NOTES: (1) INSTALL UNITS AS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER IN COMPLIANCE WITH LOCAL CODES. (2) PROVIDE CONDENSATE PUMP IF REQUIRED. SPA T SYSTEM HEAT PUMP SCHEDULE - OUTDOOR UNIT EQUIP N0. SERVICE CAPACITY, TOTAL COOLING SEER TOTAL HEATING HSPF REFRIGERANT ELECTRICAL WEIGHT, LBS SOUND RATING BASIS OF DESIGN (1)(2)(3)(4) CONNECTED VOLTAGE MOCP TONS CAPACITY, BTUH CAPACITY, BTUH CHARGE, LBS (dB) IHP OHP-201 UNIT 201 2.5 30,776 25.5 13,000 12.3 5.73 208V/1 P 30 140 61 BOSCH IHP-210A/B BMS500-AAM027-1 CSXRC OHP-422 UNIT 422 2.5 30,776 25.5 13,000 12.3 5.73 208V/1 P 30 140 61 BOSCH IHP-422A/B BMS500-AAM027-1 CSXRC OHP-423 UNIT 423 2.5 30,776 25.5 13,000 12.3 5.73 208V/1 P 30 140 61 BOSCH IHP-423A/B BMS500-AAM027-1 CSXRC OHP-515 UNIT 515 2.5 30,776 25.5 13,000 12.3 5.73 208V/1P 30 140 61 BOSCH IHP-515A/B BMS500-AAM027-1 CSXRC OHP-517 UNIT 517 2.5 30,776 25.5 13,000 12.3 5.73 208V/1P 30 140 61 BOSCH IHP-517A/B BMS500-AAM027-1 CSXRC NOTES: (1) ARI LISTED WITH ALL STANDARD FEATURES, INSTALLATION ACCESSORIES AND COMPRESSOR SHORT CYCLING PROTECTION. FILTER DRIER, REFRIGERANT LINE FILTER, LIQUID SOLENOID VALVE, AND SAFETY PRESSURE SWITCHES. INSTALL REFRIGERANT TUBING AND LENGTH IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. (2) PROVIDE ALL REQUIRED ACCESSORIES FOR LOW —AMBIENT AND LONG —LINE APPLICATIONS. (3) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO FIELD COORDINATE ROUTING. (4) REFRIGERANT SHALL BE R-410A. ISOLATION SPRING (TYP) SOLDERED CURB CAP (TYP)- OHP MOUNTNG W DETA SCALE: NONE OHP UNIT ROOFTOP CHASE SIZE PER PLANS 8" ROOF CURB PEA ROOFING AND FLASI INSTALLED PER MAf REQUIREMENTS PER PLANS CHASE PENETRAT ON THROUGH ROOF DETAIL SCALE: NONE nnr � �� TOP FOR GE JOUS SOLDERED -0 DUCT FOR -TIGHT 'UCTION 11N. CURB CAP P 5 � � N G � v �tcCNAN�GP Gasline Mechanical Inc. 9926 Elliot Rd. Snohomish WA 98296 v0�o oN000No��o �-1�-�� EXPIRES: 10/25/24 H U W ti O a IssuE 0 C7 Q Q d Q W H a 0 N 0 W� W� H� vl Q ZO �� aQ oW RECEIVED Aug 02 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET NO. SCHEDULES DET,4ILS 0 � PROJECT NO. 7/ 17/24 PERMIT SET CCPIRIGHT 2024, PINEHURST ENGINEERING / GASLINE MECHANICAL I I I I �o� boo �o WEST R00� HVAC SCALE: 1 /8" = 1'-0" N I I I I I I �� ��� 1 520' TO SHEETMETAL COVER FOR REFRIGERANT AND ELECTRICAL LINES (T1P) EAST R00� HVAC SCALE: 1 /8" = 1'-0" I I �o� �30� dog U f� TS 515 /51 � HVAC U f� TS 42 2 /42 � HVAC �j SCALE: 1 /8" = 1'-0" � I SCALE: 1 /8" = 1'-0" )HP-201 750' TO iPERTY LINE G55 dBA) / / �o� / � �o� � � � � � / � � � � � / N� ao I I _—� = � --� I �� ��� T --J �� O _� LINE SE TO ROOF I �� — � �,a � / �,� UNIT 201 HVAC SCALE: 1 /8" = 1'-0" N P 5 � � N G � F �tcCNAN�GP Gasline Mechanical Inc. 9926 Elliot Rd. Snohomish WA 98296 v0�o oN000No��� �"-1�_�-�t EXPIRES: 10/25/24 0 0 � N O 00 �T� rr'Tr'11 W .. �--I h--� v W WI� Z O O • ~^' �/ � I"�'1 Q H � � � W ISSUE: RECEIVED Aug 02 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET NO. UNIT PLANS �V� � � 0 PROJECT NO. 7/ 17/24 PERMIT SET COPIRIGHT 2024, PINEHURST ENGINEERING / GASLINE MECHANICAL