APPROVED BLD RESUB 1-BLD2024-0955+Mechanical_Plan+8.7.2024_7.24.52_AM+4425505I A I B I � I D I E I F I G I H HVAC GENERAL NOTES - 2018 WA STATE L HVAC SYMBOL LEGEND DESCRIPTION SYMBOL DESCRIPTION SYMBOL BARE RECTANGULAR SHEETMETAL 14x12 SA FLEX DUCT �, SOUNDLINE SHEETMETAL (GENERAL NOTES) 14x12 SA-SL _ EQUIPMENT FLEX ROUND CONNECTOR _ 24� SHEETMETAL W/INSULATION (GENERAL NOTES) 14x12 SA_ W EQUIPMENT FLEX RECTANGULAR CONNECTOR �24x24 BARE ROUND SHEETMETAL 120 SA SUPPLY DUCT UP/DOWN F�__i� iT�iT` ;1 �\ I �^;•� ,� ��"x_ ,y ROUND SHEETMETAL W/INSULATION (GENERAL NOTES) 120 SA-W EXHAUST DUCT UP/DOWN F� ---, �-`� -� �"`� � I I >, 1 1 ;', ; Imo'_ ��I `J_... BARE OVAL SHEETMETAL 14x120 SA RETURN DUCT UP/DOWN '�, ;1 � I ; ��, ; OVAL SHEETMETAL W/INSULATION (GENERAL NOTES) 14x120 SA-W ----------------- SUPPLY AIR TERMINAL RECTANGULAR AND SQUARE EXAMPLE OF EXISTING 14x12 SA RETURN AIR TERMINAL RECTANGULAR AND SQUARE EXAMPLE OF DEMO XXXXXXXXX �°,r EXHAUST AIR TERMINAL RECTANGULAR AND SQUARE EXAMPLE OF NEW 14x12 SA RADIAL AIR TERMINAL O EXAMPLE OF FUTURE (N.I.C.) 14x12 SA SUPPLY AIR SLOT DIFFUSER EXPOSED QUALITY SHEETMETAL 14x12 SA-Q RETURN AIR SLOT DIFFUSER CLEANROOM QUALITY DUCTWORK 14x12 SA-C EXHAUST AIR SLOT DIFFUSER DUCTBOARD (1"FIBERGLASS) 14x12 SA-DB POINT OF CONNECTION CONTINUATION OF ROUND DUCT � CENTER LINE CL CONTINUATION OF RECTANGULAR DUCT �� THERMOSTAT O AIR FLOW IN SYMBOL � CARBON MONOXIDE SENSOR CO AIR FLOW OUT SYMBOL ter-► NITROGEN DIOXIDE SENSOR �0 MECHANICAL EQUIPMENT TAG AHU-001 OTHER SENSOR �$ KEYED NOTE 1O ELECTRICAL SWITCH ACCESS DOORS � � MITERED ELBOW WITH TURNING VANES RATED ENCLOSURE _ - - --444---- - - NOTE: SIZE REFLECTS ACTUAL SHEET METAL DIMENSION AND DOES NOT ACCOUNT FOR INSULATION OR LINING PIPING GENERAL NOTES PIPING MATERIAL SCHEDULE: PIPING SIZE MATERIAL JOINT INDIRECT DRAIN 1/2" - 2-1/2" 1/8" - 4-1/8" COPPER/DWV/TYPE M LEAD FREE SOLDER REFRIGERATION COPPER TUBE, ACR BRAZED PIPING INSULATION SCHEDULE PIPING PIPE INSULATION INSULATION CONDUCTIVITY TYPE SIZE TYPE THICKNESS RANGE 1/8" - 1" ELASTOMERIC FOAM 1/2" 0.21 - 0.27 REFRIGERATION SUCTION 1-1/8" + ELASTOMERIC FOAM 1" 0.21 - 0.27 REFRIGERATION MIXED (DOWNSTREAM OF TXV) 1/8" - 7/8" ELASTOMERIC FOAM 1" 0.21 - 0.27 - ALL PIPING INSULATION AND COVERINGS SHALL HAVE AN ASTM FLAME SPREAD RATING OF 25 OR LESS AND AN ASTM SMOKE DEVELOPED RATING OF 50 OR LESS. - ELASTOMERIC INSULATIONS SHALL BE CLOSED CELL. - ELASTOMERIC INSULATIONS WHICH MEET THESE RATINGS MAY BE USED AS A SUBSTITUTE FOR FIBERGLASS. - PROVIDE A VAPOR BARRIER COVERING ON ALL CHILLED WATER PIPING AND COIL CONDENSATE PIPING INSULATION. - PROVIDE A COVERING FOR ALL FIBERGLASS INSULATION WITHIN THE BUILDING. - PROVIDE A VINYL JACKET FOR ALL INSULATION EXPOSED TO SIGHT WITHIN THE BUILDING EXCEPT MECHANICAL ROOMS. - PROVIDE REMOVABLE LACED INSULATION PAD OVER ALL CONTROL VALVES, WHERE NOT LOCATED WITHIN A MECHANICAL ROOM. - PROVIDE ALUMINUM JACKET ON ALL INSULATED PIPING OUTSIDE BUILDING. - AT PIPE HANGERS PROVIDE RIGID INSULATION BETWEEN PIPE AND HANGER. 1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAYBE REQUIRED. THE MECHANICAL CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. 2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2015 EDITIONS OF THE SEATTLE ENERGY CODE (SEC), SEATTLE BUILDING CODE (SBC), SEATTLE MECHANICAL CODE (SMC), AND SEATTLE PLUMBING CODE (SPC). 3. ALL PIPE SIZES NOTED ON DRAWINGS ARE MINIMUMS. 4. SLOPE ALL INDIRECT DRAINS AT 2%UNLESS OTHERWISE NOTED ON DRAWINGS. OBTAIN APPROVAL FROM THE CODE AUTHORITY BEFORE INSTALLING PIPING AT LESS THAN 2% (EVEN IF LESSER SLOPE IS INDICATED ON DRAWINGS). 5. HANGERS AND SUPPORTS FOR PIPING SHALL BE IN ACCORDANCE WITH THE SMC AND SBC. 6. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. 7. PROVIDE CHROME PLATE ESCUTCHEON PLATES AT ALL EXPOSED WALL AND CEILING PENETRATIONS. 8. PROVIDE SHUT-OFF VALVES AT ALL EQUIPMENT CONNECTIONS. 9. PROVIDE UNION, GROOVED OR FLANGED CONNECTION AT EQUIPMENT FOR FUTURE REMOVAL AND SERVICING. 10. FOR CONDENSATE PIPING PROVIDE TRAPS WITH A MINIMUM SEAL 2"GREATER THAN THE FAN OPERATING STATIC PRESSURE AT ALL COOLING COIL... 11. PROVIDE MINIMUM 1"AIR BREAK FOR ALL CONDENSATE PIPE TERMINATIONS AT DRAINS. 12. PROVIDE DIELECTRIC CONNECTIONS BETWEEN DISSIMILAR METALS. 13. HEAT TRACING OF PIPING, WHERE INDICATED, SHALL BE PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR. COORDINATE ELECTRICAL SUPPLY FOR HEAT TRACE WITH ELECTRICAL CONTRACTOR. 14. TRENCHING, BACKFILLING AND COMPACTING FOR UNDERGROUND PIPING SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR UNLESS STATED OTHERWISE IN CONTRACT DOCUMENTS. SEQUENCE OF OPERATION HEAT PUMPS &FAN COIL UNITS SERVES: SUITE'S 204, 102, AND SUITE 213 CONTROLS: PROGRAMMABLE THERMOSTAT OCCUPIED HOURS: 7 AM TO 6 PM MONDAY - FRIDAY COOLING SETPOINT: 75°F (ADJ) HEATING SET POINT: 70°F (ADJ) FAN COIL UNITS SHALL OPERATE TO MAINTAIN ROOM TEMPERATURE SET POINT. HEAT PUMPS SHALL OPERATE T MAINTAIN REFRIGERANT FLOW AS DEMANDED BY ASSOCIATED FAN COIL UNITS. HEAT PUMPS SHALL PROVIDE PRIMARY HEAT SOURCE. ELECTRIC RESISTANCE HEAT TO ACT AS SUPPLEMENTAL HEAT. CONFIGURE THERMOSTATIC CONTROLS W/ AUTOMATIC SETBACK, MANUAL OVERRIDE, AUTOMATIC START AND STOP. PROVIDE WI/ 7-DAY PROGRAMMABLE CONTROLS UNIT ASSOCIATIONS: HP-01:FC-01 HP-11:FC-11 HP-30:FC-30 MECHANICAL GENERAL ABBREVIATIONS ABBV FULL NAME ABBV FULL NAME ABBV FULL NAME AC AIR CONDITIONING UNIT FCU FAN COIL UNIT NOM NOMINAL AFF ABOVE FINISHED FLOOR FD FIRE DAMPER NTS NOT TO SCALE AHU AIR HANDLING UNIT FLA FULL LOAD AMPS OBD OPPOSED BLADE DAMPER AL ALUMINUM FOB FLAT ON BOTTOM OD OUTSIDE DIMENSION BAS BUILDING AUTOMATION SYSTEM FOT FLAT ON TOP POC POINT OF CONNECTION BDD BACK DRAFT DAMPER FSD FIRE SMOKE DAMPER PRV PRESSURE REDUCING VALVE BI BLACK IRON GALV GALVANIZED PVC POLYVINYL CHLORIDE BOD BOTTOM OF DUCT GC GENERAL CONTRACTOR REQ'D REQUIRED BOTT BOTTOM GENX GENERATOR EXHAUST RPBA REDUCED PRESSURE BACKFLOW ASSY BTU BRITISH THERMAL UNITS GLVNL GALVANNEAL RTU ROOFTOP UNIT BTUH BRITISH THERMAL UNITS PER HOUR GPM GALLONS PER MINUTE SA SUPPLY AIR CAT1 CATEGORY ONE VENT GREASE GREASE DUCT SD SMOKE DAMPER CAT4 CATEGORY FOUR VENT GWB GYPSUM WALL BOARD SL SOUND LINED CFM CUBIC FEET PER MINUTE HP HORSE POWER, HEAT PUMP SM SHEET METAL CPVC CPVC MATERIAL HVAC HEATING, VENTILATION AND AIR COND. SP STATIC PRESSURE DB DUCTBOARD HX HEAT EXCHANGER SS STAINLESS STEEL DDC DIRECT DIGITAL CONTROLS ID INSIDE DIMENSION SUSP SUSPENDED DEMO DEMOLISH LAT LEAVING AIR TEMPERATURE T THERMOSTAT DIFF DIFFUSER LBS POUNDS TOD TOP OF DUCT DMPR DAMPER LWT LEAVING WATER TEMPERATURE TV TURNING VANES DN DOWN MAT MIXED AIR TEMPERATURE TYP TYPICAL E EXISTING MBH ONE THOUSAND BTUH UNO UNLESS NOTED OTHERWISE EAT ENTERING AIR TEMPERATURE MCA MINIMUM CIRCUIT AMPACITY VAV VARIABLE AIR VOLUME EC EGGCRATE MD MOTORIZED DAMPER VD VOLUME DAMPER EER ENERGY EFFICIENCY RATIO MIN MINIMUM VFD VARIABLE FREQUENCY DRIVE EF EXHAUST FAN M-M MACDONALD-MILLER W DUCT INSULATION WRAP ELEV ELEVATION NC NORMALLY CLOSED W/ WITH ESP EXTERNAL STATIC PRESSURE NIC NOT IN CONTRACT WELD WELDED EWT ENTERING WATER TEMPERATURE NO NORMALLY OPEN f6 VOLTAGE PHASE &DUCT DIAMETER HVAC SYSTEM ABBREVIATIONS ABBV FULL NAME ABBV FULL NAME ABBV FULL NAME COMB-GALV COMBUSTION AIR EA AL EXHAUST ALUMINUM OA OUTSIDE AIR SA SUPPLY AIR LP EA SS EXHAUST SS 304 OA-KOOL OUTSIDE AIR KOOLDUCT SA-KOOL SUPPLY AIR LP KOOLDUCT EA AL WELD EXHAUST ALUMINUM WELDED RLF RELIEF AIR SA AL SUPPLY AIR LP ALUMINUM EA GALV WELD EXHAUST GALV WELDED RA RETURN AIR SA SS SUPPLY AIR LP SS 304 2B EA GLVNL WELD EXHAUST GALVANNEAL WELDED DB DUCTBOARD SA AL WELD SUPPLY AIR LP ALUMINUM WELDED EA SS WELD EXHAUST SS 304 WELDED FLU-CAT1 FLUE VENT -CATEGORY 1 SA GALV WELD SUPPLY AIR MP GALV WELDED EA BI GREASE EXHAUST GREASE BLACK IRON WELD FLU-CAT4 FLUE VENT -CATEGORY 4 SA GLVNL WELD SUPPLY AIR MP GALVANNEAL WELD EA GALV GREASE EXHAUST GREASE GALV WELDED FLU-CPVC FLUE VENT -CPVC MATERIAL SA SS WELD WELDED SUPPLY AIR LP SS 304 2B EA GALV GREASE EXHAUST GREASE SS 304 WELDED FLU -SS FLUE VENT -SHOP BUILT SS 304 EA EXHAUST AIR MUA MAKE-UP AIR FLU-GALV FLUE VENT -SHOP BUILT GALV PIPING SYSTEM ABBREVIATIONS ABBV FULL NAME ABBV FULL NAME ABBV FULL NAME C CONDENSATE INDIRECT DRAIN HHWR HEATING HOT WATER RETURN NGV NATURAL GAS VENT CA AIR COMPRESSED HHWS HEATING HOT WATER SUPPLY PA AIR PNEUMATIC CDWR CONDENSER WATER RETURN HPC STEAM CONDENSATE HIGH PRESS PC CONDENSATE PUMPED CDWS CONDENSER WATER SUPPLY HPS STEAM HIGH PRESS PCHR CHILLED WATER (PROCESS) RETURN CHRV CHILLER RELIEF VENT HRR HEAT RECOVERY RETURN PCHS CHILLED WATER (PROCESS) SUPPLY CHWR CHILLED WATER RETURN HRS HEAT RECOVERY SUPPLY RGAS REFRIGERANT HOT GAS CHWS CHILLED WATER SUPPLY LPC STEAM CONDENSATE LOW PRESS RLIQ REFRIGERANT LIQUID CLN STM STEAM CLEAN LPG LIQUID PROPANE RSUC REFRIGERANT SUCTION CLR CLOSED LOOP WATER RETURN LPS STEAM LOW PRESS SCHR CHILLED WATER (SECONDARY) RETURN CLS CLOSED LOOP WATER SUPPLY LTCR CHILLED WATER (LOW TEMP) RETURN SCHS CHILLED WATER (SECONDARY) SUPPLY COMB -PVC AIR COMBUSTION PVC LTCS CHILLED WATER LOW TEMP SUPPLY ( ) SCV STEAM CONDENSATE VENT CRYV CRYO VENT MPC STEAM CONDENSATE MEDIUM PRESS SPC STEAM CONDENSATE PUMPED FOC FUEL OIL SECONDARY CONTAINMENT MPS STEAM MEDIUM PRESS SV STEAM VENT FOF FUEL OIL FILL MUW MAKE-UP WATER VAC VACUUM FOR FUEL OIL RETURN NG-2PSI NATURAL GAS 2PSI VAC-E VACUUM EXHAUST FOS FUEL OIL SUPPLY NG-5PSI NATURAL GAS 5PSI VRFG VRF HOT GAS FOV FUEL OIL VENTS NG-CONDUIT NATURAL GAS CONDUIT VRFL VRF HIGH PRESS LIQUID GENX GENERATOR EXHAUST NG-H NATURAL GAS HIGH PRESS VRFS VRF LOW PRESS SUCTION GLWR GLYCOL WATER RETURN NG-L NATURAL GAS LOW PRESS GLWS GLYCOL WATER SUPPLY NG-M NATURAL GAS MEDIUM PRESS PIPING SYMBOL LEGEND SYMBOL DESCRIPTION ABBV SYMBOL DESCRIPTION ABBV D4 BALANCING VALVE GATE VALVE BALV GV Q HORIZONTAL EXPANSION TANK HET � VERTICAL EXPANSION TANK VET �Q GLOBE VALVE GLV `� AIR SEPARATOR AIR SEP D�4 BALL VALVE -FULL PORTED BV ,�, AIR PURGER AP `jLJ SILENT CHECK VALVE CV � END SUCTION CENTRIFUGAL PUMP ES PUMP BUTTERFLY VALVE BFV � VERTICAL IN -LINE CENTRIFUGAL PUMP VI PUMP BUTTERFLY VALVE W/MEMORY STOP BFVM � SUCTION DIFFUSER SUC DIFF i"i..l FLEXIBLE CONNECTION i TEMPERATURE GAUGE TG ® REDUCED PRESS. BACKFLOW PREVENTER RPBP Q THERMOMETER THERM BACKFLOW PREVENTER BFP � BALL VALVE W/ 3/4" HOSE ADAPTOR BV W/ HA UNION UNION p CONCENTRIC REDUCER CR STRAINER STRN � ECCENTRIC REDUCER ER �- PRESSURE RELIEF VALVE RV �Q TWO-WAY CONTROL VAVLE 2WAY PRESSURE REDUCING VALVE PRV � THREE-WAY CONTROL VALVE 3WAY PRESSURE /TEMPERATURE PORT P&T � POINT OF CONNECTION P.O.C. �T BULB WELL BW r1.r PIPE BREAK -PIG TAIL MANUAL AIR VENT MAV s° cFlws s° cFlws PIPE -SIZE &ABBREVIATION PIPE -SIZE &ABBREVIATION WITH INSULATION 4 AUTOMATIC AIR VENT AV PRESSURE GAUGE PG ® PUMP p�j SOLENOID VALVE SV �`+ FLEX PIPE rt� PIPE -HEAT TRACE � EXPANSION THERMAL EXP --� HOSE BIB HB 4 SUB -METER WATER FLOW MTR eru METER BTU BTU MTR 4 WATER HAMMER ARRESTOR WHA Po SENSOR PRESSURE DIFFERENTIAL PDIF CT� GAS COCK GC TiT CIRCUIT SETTER VALVE CS DRAWING SHEET INDEX -MECHANICAL NUMBER TITLE TM0.01 HVAC SCHEDULES TM0.02 HVAC SCHEDULES TM0.10 SITE PLAN TM2.01 FIRST FLOOR PLAN -SHEETMETAL TM2.02 SECOND FLOOR PLAN -SHEETMETAL TMP2.01 FIRST FLOOR PLAN -PIPING TMP2.02 SECOND FLOOR PLAN -PIPING TMP2.03 ROOF PLAN -PIPING TM3.01 ELEVATIONS TM6.01 MECHANICAL DETAILS 1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. 2. MATERIALS METHODS AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2018 EDITIONS OF THE INTERNATIONAL MECHANICAL CODE INTERNATIONAL BUILDING CODE, INTERNATIONAL FIRE CODE 2018 WSEC, AND LOCAL CODES AND ORDINANCES. 3. DUCT CONSTRUCTION AND HANGING SHALL COMPLY WITH CHAPTER 6 OF THE 2018 IMC AND WITH CURRENT SMACNA STANDARDS. EARTHQUAKE BRACE ALL DUCTS 28" DIA AND LARGER WHICH ARE SUSPENDED MORE THAN 12" BELOW STRUCTURAL SYSTEM. 4. JOINTS OF MEDIUM AND HIGH VELOCITY DUCT SYSTEMS SHALL BE SEALED WITH GASKETS OR LISTED MASTIC TYPE DUCT SEALANT. 5. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS, PER 2018 WASHINGTON STATE ENERGY CODE, COMMERCIAL PROVISIONS - DUCT WRAP, WHERE INDICATED, SHALL BE 0.75 LB/CU FT FIBERGLASS DUCT INSULATION WITH A FACTORY APPLIED REINFORCED ALUM. FOIL VAPOR BARRIER. - SOUND LINING, WHERE INDICATED, SHALL BE 1" 1.5 LB/CU FT FIBERGLASS DUCT LINING COATED TO PREVENT FIBER EROSION AT VELOCITIES UP TO 6000 FPM. - DUCT BOARD, WHERE INDICATED, SHALL BE 1" RIGID FRK FACED EI 475 FIBERGLASS DUCT BOARD SYSTEM, UL 181 LISTED AS A CLASS 1 AIR DUCT. - SUPPLY DUCT WHICH CONVEYS SUPPLY AIR AT TEMPERATURES LESS THAN 55 DEG F OR GREATER THAN 105 DEG F WHEN LOCATED IN CONDITIONED SPAC SHALL BE INSULATED WITH A MINIMUM OF R-3.3 ,WHEN LOCATED IN UNCONDITIONED SPACE R-6 AND WHEN LOCATED OUTSIDE THE BUILDING R-8 (CLIMATE ZONE 4) OR R-12 (CLIMATE ZONE 5) PER WSEC C403.10.1 AND TABLE C403.10.1.2. DUCTWORK EXPOSED TO VIEW WITHIN A ZONE THAT SERVES THAT ZONE IS... - OUTSIDE AIR DUCT INSULATION INSIDE THE BUILDING SHALL BE INSULATED PER C403.10.1 AND TABLE C403.10.1.1 AS FOLLOWS: IF >= 2800 CFM INSULATE TO R-16 UPSTREAM OF AUTOMATIC SHUTOFF DAMPERS AND R-8 (CLIMATE ZONE 4C) OR R-12 (CLIMATE ZONE 56) DOWNSTREAM OF AUTOMATIC SHUTOFF DAMPERS. IF < 2800 CFM INSULATE TO R-7. 6. FLEX DUCTS SHALL CONSIST OF A REINFORCED VAPOR BARRIER, 1 1/2" FIBERGLASS INSULATION, AND NON -PERFORATED INTERIOR LINER WITH WIRE HELIX. DUCT SHALL BE A UL 181 LISTED CLASS 1 AIR DUCT. FLEX DUCTS SHALL ONLY BE USED WHERE SHOWN AND SHALL NOT EXCEED 12' IN LENGTH UNLESS NOTED OTHERWISE. 7. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH SECTION 1613 OF THE 2018 IBC. 8. PROVIDE FIRE DAMPERS, SMOKE DAMPERS AND FIRE/SMOKE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 717.5 OF THE 2018 IBC. PROVIDE CEILING FIRE DAMPERS WHERE INDICATED ON PLANS AND AS REQUIRED BY SECTION 717.6.2.1 OF THE 2018 IBC. INSTALL FIRE DAMPERS SMOKE DAMPERS AND FIRE/SMOKE DAMPERS IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS, THE TERMS OF THEIR LISTING, AND THE... 9. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. 10. PROVIDE RETURN DUCT SMOKE DETECTOR AUTOMATIC SHUT DOWN OF ALL NEW HEATING, COOLING, OR VENTILATION EQUIPMENT MOVING IN EXCESS OF 2000 CFM IN ACCORDANCE WITH SECTION 606 OF THE 2018 IMC. POWER AND INTERLOCK WIRING WITH THE BUILDING FIRE ALARM SYSTEM IS BY THE ELECTRICAL CONTRACTOR. BAS TO MONITOR FIRE ALARM CONTROL PANEL AND SHUT DOWN ALL FAN TERMINAL UNITS DURING ANY BUILDING FIRE ALARM EVENT, IN ACCORDANCE WITH 2O18 IMC 606.2.2. 11. HVAC EQUIPMENT, VALVES AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS. UNLESS SHOWN ON ARCHITECTURAL DRAWINGS, REQUIRED ACCESS PANELS SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MINIMUM ACCESS DOOR SIZE FOR VALVES AND DAMPERS TO BE 18" X 18". 12. HEAT TRACING OF PIPING, WHERE INDICATED, SHALL BE PROVIDED AND INSTALLED BY THE HVAC CONTRACTOR. THE HVAC CONTRACTOR IS TO COORDINATE THE HEAT TRACE POWER WIRING WITH ELECTRICAL CONTRACTOR. 13. MOTORS STARTERS NOT LISTED AS BEING PROVIDED IN THE HVAC EQUIPMENT SCHEDULES ARE TO BE PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. 14. WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION TO BE PROVIDED TO THE BUILDING OWNER. RECORD DRAWINGS SHALL INCLUDE AS A MINIMUM THE LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT, GENERAL CONFIGURATION OF DUCT AND PIPE DISTRIBUTION SYSTEM, INCLUDING SIZES, AND THE TERMINAL AIR AND WATER DESIGN FLOW RATES. 15. OPERATING AND MAINTENANCE MANUALS TO BE PROVIDED TO THE BUILDING OWNER THAT INCLUDE: SUBMITTAL DATA, NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY, HVAC CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION AND A COMPLETE OPERATIONAL NARRATIVE FOR EACH SYSTEM. 16. COMMISSIONING IS REQUIRED ON THIS PROJECT IN ACCORD WITH 2O18 WASHINGTON STATE ENERGY CODE (WSEC), COMMERCIAL PROVISIONS AND SECTION C408. 17. A COMPLETE REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED AND FILED WITH THE OWNER 18. SHAFT WALLS CONSTRUCTED TO SUPPORT AIR MOVEMENT FOR RETURN AIR SYSTEMS AND STAIR &ELEVATOR PRESSSURIZATION SYSTEMS SHALL BE CONSTRUCTED TO THE FOLLOWING STANDARDS: A. SHAFTS (RATED FOR MAXIMIUM 2" WC) SHALL BE CONSTRUCTED TO WITHSTAND 15 PSF LOADING WITH A DEFLECTION OF L/360 (UNO). B. SHAFTS SHALL BE SEALED SUBSTANTIALLY AIR -TIGHT USING THE CRITERIA FROM THE 2018 INTERNATIONAL BUILDING CODE: 1. SECTION 715.E FIRE RESISTANT JOINT SYSTEMS IN SMOKE BARRIERS: LEAKAGE SHALL NOT EXCEED 5 CFM PER LINEAR FOOT OF JOINT AT 0.3" WC. 2. SECTION 909.5 SMOKE BARRIER CONSTRUCTION FOR INTERIOR EXIT STAIRWAYS AND EXIT PASSAGEWAYS: MAXIMUM ALLOWABLE LEAKAGE AREA PER SHAFT SHALL NOT EXCEED (0.00035 SF/SF) C. STAIR AND ELEVATOR PRESSURIZATION SHAFTS SHALL BE PRESSURE TESTED DURING COMMISIONING. CONTRACTOR SHALL MAKE MODIFCATIONS TO INSTALLATION UNTIL SHAFT IS IN COMPLIANCE. 19. DAMPERS USED FOR OUTDOOR AIR INTAKE, EXHAUST, OR RELIEF SHALL HAVE THE FOLLOWING MAXIMUM LEAKAGE RATES AT 1" W.G. (PER AMCA STANDARD 500D): MOTORIZED DAMPERS: 4CFM/S.F. GRAVITY DAMPERS: 20CFM/S.F. (40 CFM/S.F. FOR DAMPERS SMALLER THAN 24" IN EITHER DIMENSION) PER 2018 WSEC C403.7.8.3. 20. OUTSIDE AIR INTAKE, EXHAUST, AND RELIEF DAMPERS SERVING CONDITIONED SPACES MUST BE MOTORIZED (FAIL CLOSED) PER WSEC, COMMERCIAL PROVISIONS, 2018 WSEC SECTION C403.7.8. EXCEPT AS ALLOWED BY WSEC. 21. MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND ASMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723, EXCEPT AS NOTED IN SECTION 602.2.1 OF THE 2018 IMC. SCOPE OF WORK THIS PROJECT WILL REPLACE TWO (E) 1.5 TON SPLIT SYSTEMS (INDOOR AND OUTDOOR UNITS). THE UNITS TO BE REPLACED ARE HP-6 AND FC-6 SERVING SUITE 113 AND HP-22 AND FC-22 SERVING SUITE 212. THE NEW UNITS WILL BE HEAT PUMPS WITH COMPARABLE HEATING AND COOLING CAPACITIES. MIXING BOXES WILL BE REPLACED. DUCTWORK AND CONDENSATE DRAIN PIPING WILL BE REUSED AS MUCH AS POSSIBLE WITH MINOR MODIFICATIONS TO CONNECT TO NEW EQUIPMENT. THE REFRIGERANT PIPING WILL BE REPLACED. THIS PROJECT WILL REPLACE THREE (3) 1.5 TON SPLIT SYSTEMS (INDOOR AND OUTDOOR UNITS). THE UNITS TO BE REPLACED ARE HP-01 AND FC-01, SERVING SUITE 204 AND HP-11 AND FC-11 SERVING SUITE 102, AND HP-30 AND FC-30 SERVING SUITE 213. THE NEW UNITS WILL BE HEAT PUMPS WITH COMPARABLE HEATING AND COOLING CAPACITIES. MIXING BOXES WILL BE REPLACED. DUCTWORK AND CONDENSATE DRAIN PIPING WILL BE REUSED WHERE POSSIBLE WITH MINOR MODIFICATIONS TO CONNECT NEW EQUIPMENT. THE REFRIGERANT PIPING WILL BE REPLACED. LEGAL DESCRIPTION PARCEL NUMBER: 00738800010100 LEGAL DESCRIPTION: 7500 212TH ST SW SUITE 102 - 00738800010200, SUITE 204 - 00738800020400, SUITE 213 - 007388000213 o_ 2 H PROJECT SITE 7-ELEVEN �� � 0 0 BURGER KING Q mm L-U H- 0 212TH ST SW �� DAIRY QUEEN �EDMONDS- WOODWAY HIGH SCHOOL` � w Q 2 WORur ci rlQ�r�� � \�_� r TO FIELD SPECTION FOR DE COMPLIANCE ON JOB SITE W 212TH ST SW SV1 NORTH 1 `� = energy works Home Comfort Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw.com C Of Edmonds �uilding Department Work S Owner 3 RTU, LIKE FOR LIKE -------------------- 7500 212TH ST SW ------------------ STOY REALITY A oved Dat B ng Offici r� Permit Numbe I� 5 C 7 024-0955- UNIT 102 024-0956- UNIT 204 024-0957 -UNIT 213 Q� � � � � U � T' U � � o Q = N � � � 2 � � N a> O L N >` � � � .. a--� � � I --I � (n � � 0 � �-' � � - - z z 'gin a� - � � °' � �' o (n U � i.L r, oC TM 0.01 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT C F G H I J K L HEAT PUMP SCHEDULE UNIT N0. ASSOCIATED FAN COIL UNIT LOCATION MFG & MODEL N0. NOMINAL COOL TONS RATED MBH COP SEER/SEER2 ELECTRICAL WT LBS NOTES COOL HEAT VOLT/PH/HZ MCA MOCP (E) HP-01 (E) FC-01 ROOF LENNOX HP-18-211V 1. 5 18 18 2. 7 8. 15/ - 208/1/60 - 20 - DEMOLISH (E) HP-11 (E) FC-11 ROOF LENNOX HP-18-211V 1. 5 18 18 2. 7 8. 15/ - 208/1/60 - 20 - DEMOLISH (E) HP-30 (E) FC-30 ROOF LENNOX HP-18-261V 2 24 24 2. 7 8. 15/ - 208/1/60 - 20 - DEMOLISH HP-01 FC-01 ROOF GOODMAN-GSZS602410A (INVERTER) (Commissioned as) 1. 5 16. 6 17. 4 3. 5 - /17. 3 208/1/60 18. 8 20 122 1, 2 HP-11 FC-11 ROOF GOODMAN-GSZS602410A (INVERTER) (Commissioned as) 1. 5 16. 6 17. 4 3. 5 - /17. 3 208/1/60 18. 8 20 122 1, 2 HP-30 FC-30 ROOF GOODMAN-GSZS602410A (INVERTER) 2 22. 2 23. 2 3. 5 - / 17. 3 208/ 1 /60 18. 8 20 122 1, 2 NOTES: 1. SYSTEMS ARE EXEMPT FROM 2021 WSEC ECONOMIZER REQUIREMENT WITH 10% HIGHER EFFICIENCY THAN MINIMUM EFFICIENCY LISTED ON TABLE C403 2. ELECTRICAL TO PROVIDE DISCONNECTS FAN COIL SCHEDULE UNIT N0. MFG & MODEL N0. ASSOCIATED HEAT PUMP COOLING MBH HEATING MBH FAN OA CFM ELECTRICAL WT LBS NOTES CFM ESP HP V/PH/HZ MCA MOCP (E)FC-01 LENNOX CBF16 21-00 (E)HP-01 18 18 650 0.3 1/8 - 208/1/60 - - - DEMOLISH (E)FC-11 LENNOX CBF16 21-00 (E)HP-11 18 18 650 0.3 1/8 - 208/1/60 - - - DEMOLISH (E)FC-30 LENNOX CBF16 26-05 (E)HP-30 24 24 850 0.3 1/4 - 208/1/60 - - - DEMOLISH FC-01 GOODMAN AHVE24BP1400A HP-01 16.6 17.4 610 0. 5 1/2 50 208/1/60 4.9 15 115 1, 2, 3, 4 FC-11 GOODMAN AHVE24BP1400A HP-11 16.6 17.4 610 0.5 1/2 50 208/1/60 4.9 15 115 FC-30 GOODMAN AHVE24BP1400A HP-30 22.2 23.2 800 0.5 1/2 50 208/1/60 4.9 15 115 NOTES 1. COOLING AND HEATING CAPACITIES ARE BASED ON TOTAL CAPACITIES CURRENTLY PROVIDED BY (3) EXISTING UNITS 2. ELECTRICAL T PROVIDE DISCONNECTS 3. PROVIDED WITH ECM MOTOR 4. NO ECONOMIZER NEEDED PER WSEC TABLE C503.4 UNIT TYPE 2 OPTION B. REPLACEMENT UNIT SAME SIZE AND GREATER THAN 10% PREMIUM EFFICIENT AND NOT DECREASING CURRENT AIRSIDE ECONOMIZER CAPACITY VENTILATION SCHEDULE ROOM 2018 IMC REQUIREMENTS DESIGN NAME SERVED BY CLASSIFICATION AREA OCC/1000SF OCC CFM/OCC CFM/SF OSA CFM REQ'D EXH CFM/SF EXH REQ'D OSA EXHAUST SUITE 204 HP-1 OFFICE SPACES 590 5 3 5 0.06 43 - - 50 - SUITE 102 HP-11 OFFICE SPACES 403 5 2 5 0.06 42 - - 50 - SUITE 213 HP-30 OFFICE SPACES 515 5 3 5 0.06 43 - - 50 - L 1 2 3 4 5 6 7 8 = energy works Home Comfort Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw.com �� �, U (/) � O� � � I Q = fV � O o � � _ � � fV O� -- O M L �_ m � ~ � � � � O O � � �-' � � - - z z 'gin a� - � � � � � o (n U � i.L r-, oC TM 0.02 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT A � B � C � D � E � F � G � H � I � J � K � L J H t` t` 212TH ST SW � SITE PLAN SCALE: 1" = 50'-0" )MONDS-WOODWAY HIGH SCHOOL B� w Q 7-ELEVEN 212TH ST SW DAIRY QUEEN C DR. BUFF CAR WASH & DETAI IL J PROJECT SITE 0 0 .. J M 212TH ST SW �i W Q 2 H ti 213TH PL SW L 1 2 3 4 5 6 8 -�.. � ® energy works Home Gamfart Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw. com z � Q a� °, rn � � ,__, � � W = CV pp O �_ O � � � � fV � O� .. •• O M L QJ � ,� � N �_ m � ~ �C � � � � O � C � � �' � � -- z z 'gin r� a� - � �' � °' � o (n U � i.L r-, oC I TM 0.10 I RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT I A I B I � I D I E I 1 1ST FLOOR DEMO PLAN -SHEETMETAL SCALE: 1 /2" = 1'-0" G H I 2 1ST FLOOR PLAN -SHEETMETAL SCALE: 1/2" = 1'-0" N 0 1 2 4 8 J K L L 1 2 3 5 6 8 -�.. � ® energy works Home Gamfart Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw. com w w w z Q � a � O � O ,--I = N 00 O � � � N � .. .. •• O M L QJ � ,� � N �_ m � ~ � � � � O � � � �' � � -- z z 'gin r� a� - � �' � °' � o (n U � i.L r-, oC TM 2.01 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT I A I B I � I D I E I F I G I H I I I J I K I a D 0 D 50 CFM OA �_ � (E)MIXING BOX 14�SA 100SA � 2ND FLOOR DEMO PLAN -SHEETMETAL SCALE: 1/2" = 1'-0" 50 CFM OA 2 2ND FLOOR PLAN -SHEETMETAL SCALE: 1 /2" = 1'-0" N 0 1 2 4 8 L L 1 2 3 5 6 8 -�.. � ® energy works Home Gamfart Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw. com J Q F- W w w z Q J a � � O � O � � IJi a1 rl � o z N = � N � 00 O o O � � � � N O� .. .. •• O M L QJ � ,� � N �_ m � ~ � � � � O � � � �' � � -- z z 'gin r� a� - � �' � °' � o (n U � i.L r-, oC TM 2.02 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 50 CFM OA� I A I B I � I D I E I F � 2ND FLOOR DEMO PLAN -SHEETMETAL SCALE: 1/2" = 1'-0" I G I H I I I J I K I L I A� 2 2ND FLOOR PLAN -SHEETMETAL SCALE: 1 /2" = 1'-0" N 0 1 2 4 8 ill 21 31 DI 51 �1 71 -�.. � ® energy works Home Gamfart Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw. com J Q F- W F- W W Z Q J a � � O � O � � IJi a1 rl � o z N = � N � 00 O o O � � � � N O� .. .. •• O M L QJ � ,� � N �_ m � ~ � � � � O � � � �' � � -- z z 'gin r� a� - � �' � °' � o (n U � i.L r-, oC �31 TM 2.03 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT A � B � C � D � E � F � G � H � I � J � K � L 3 O �� 2 O � 5 4 6 1O METERING DEVICE 02 DISTRIBUTION &CIRCUIT TUBES 03 SUCTION MAINFOLD 40 SATURATED SUCTION LINE WITH TRAP (FOLLOW MFG GUIDELINES) 05 CONDENSATE VENT (IF REQUIRED) 1 TM6.01 �� z TM6.01 �/ 9/16(15) � FC-X 60 CONDENSATE PUMP (MAY NOT BE REQUIRED) 70 FLEXIBLE CONNECTION PROVIDE ALL THREAD ROD. MOUNT UNIT FROM STRUCTURE TYPICAL 4 PLACES O NEOPRENE ISOLATOR OR SPRING ISOLATOR W/ MINIMUM 1" DEFLECTION TYPICAL 4 PLACES FAN COIL UNIT DETAIL N.T.S. 36-5/8(930; BRAND NAME LABEL ROOFTOP CONDENSING UNIT SUPPORT DETAIL N.T.S. 4 TM6.01 �� H P-X REUSE EXISTING EQUIPMENT PAD ROOF LRLIQ— INVERT TRAP MIN. 6" ABOVE INLET RSUC SPLIT SYSTEM PIPING DETAIL N.T.S. c+Tnl InTI mr l.rV I V L.J C I V J/'1 I C I V L.J flh I I V L 1 `� 3 5 C -�.. � ® energy works Home Gamfart Solutions Energy Works LLC 7034 220th St SW Mountlake,Terrace WA 98043 Phone: (425)409-5661 Info@energyworksnw. com J I —I W J a U � z a � ,� � ,� U 2 N 00 O w � � � O � fV .. •• O M L %� � I Q� � m � � vi E � � o o � O �' � � -- z z 'gin r� a� - � �' � °' � o (n U � i.L r-, oC TM 6.01 RESUB Aug 08 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT