FIR2024-0080_Fire_Alarm_Equipment_Specification_Sheets_9.10.2024_3.26.46_PM_4491986Fire Alarm System Secondary Battery -set Calculation Worksheet Standby Total Alarm Total Standby Alarm/Transmit AES Product Current QTY CITY Current Current (Amps) Current (Amps) (Amps) (Amps) '707P-88-ULP-10.4000 X 1 = 0.400 1.5500 X 1 = 1.550 Total System Total System Standyby Current (Amps) 0.400 Alarm Current (Amps) 1.550 ## Hour Standby Required Required Standby Time Current Standby Capacity Required Alarm Time Alarm/Transmit Alarm (Amps) (Amp -Hours) (Hours) Current (Amps) Capacity (Amp -Hours 24 X 0.400 = 9.600 1 X 1.5500 = 1.550 Required Required Standby Alarm Capacity Total Capacity Capacity (Amp -Hours) (Amp -Hours) (Amp -Hours) 9.60 + 1.550 = 11.150