Loading...
kim retail stamped letterLSC Ludwig Structural Consulting September 19, 2024 Mr. Karl Christensen Legacy One Heating 4403 Russell Rd., Suite 110 Mukilteo, WA 98275 karl@legacyoneheating.net Subject: Rooftop Mechanical Unit Anchorage 23805 Highway 99, Edmonds, WA 98026 Dear Karl: Ludwig Structural Consulting (LSC) has performed an analysis of the wind and seismic forces and determined anchorage connection requirements for the proposed rooftop 5-ton Trane 4WCC4060 rooftop mechanical unit at 23805 Highway 99. Wind and seismic forces were determined using ASCE 7-16 and design parameters determined from the ASCE design hazards website. LSC has determined that the following minimum connections are required to 1) secure the mechanical unit to the curb adapter, and 2) secure the curb adapter to the existing curb. LSC understands that the curb adapter, existing curb, and mechanical unit housing are built with minimum 16-gauge metal. Required anchorage of the mechanical unit to the curb adapter shall meet the following requirements: Connection straps, including hold-down brackets, shall be 16-gauge minimum. A minimum of (4) connection straps shall be used. Connection straps shall be located within 4-inches of the mechanical unit corners. Connection straps shall be secured to the mechanical unit with a minimum of (2) #10 or larger sheet metal screws at each strap. Connection straps shall be secured to the curb adapter with a minimum of (2) #10 or larger sheet metal screws at each strap. Required anchorage of the curb adapter to the existing curb shall meet the following requirements: 1. A minimum of (3) #10 or larger sheet metal screws are required on each side to anchor the curb adapter to the existing curb. Ludwig Structural Consulting, L L C 4701 SW Admiral Way • Suite 325 • Seattle, WA 98116 ( 2 0 6 ) 4 0 2 - 4 2 9 0 2. Locate one screw within 2-inches of each corner. Remaining screws shall be evenly spaced along each edge. An installation of the mechanical unit and adapter curb in accordance with the requirements noted above will be able to withstand code -required wind and seismic forces. Sincerely; Jeff Baerwald PE, SE Exp: 4/8/2025 Ludwig Structural Consulting, L L C 4701 SW Admiral Way • Suite 325 • Seattle, WA 98116 ( 2 0 6 ) 4 0 2 - 4 2 9 0 L Li S 1►�-!I Ludwig Structural Consulting Legacy One Heating Rooftop Mechanical Unit 23 805 Highway 99. Edmonds, WA 98026 Structural Calculations —Equipment Anchorage Submittal: For Review Date: September 19, 2024 Prepared for: Legacy One Heatin€ Exp: 4/8/2025 1/ 11 / 2,02 Ludwig Structural Consulting, L L C 4701 SW Admiral Way • Suite 325 9 Seattle, WA 98116 ( 2 0 6 ) 4 0 2 - 4 2 9 0 Project: Legacy One Heating Location: 23805 Highway 99, Edmonds, WA Date: 9/19/2024 Engineer: JEB LSC Ludwig Structural Consulting Review of structure to support rooftop mechanical loads. Allowable stress design used for load check of framing. Unit locations are approximated based on locations shown on the mechanical drawings. Lateral Loads: Wind: Design per: ASCE 7-16 Section 30.10 Seismic Wind speed: 85 MPH Exposure: C Importance Factor, I: 1.00 Roof height, h: 20 Feet Zone: 5 Effective Wind Area: 10 Ft KZt = 1.00 Kh = 0.90 qh = 18.85 PSF GCr = 1.9 Fh = gn(GCr)Af = 35.8 Af (psf) Design per: ASCE 7-16 Section 13.6 FP 0.4a pSns Wp (1 + 2(z/h)) Sys = 1.022 R /I IP = 1.00 p p Z= 1.00 x h Supports: aP = 2.5 RP = 3.0 Connections: aP = 2.5 RP = 3.0 Fp = 1.022 WP Fp = 1.022 WP Design Summary Page 1 ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS Address: 23805 Highway 99 Edmonds, Washington 98026 ASCE Hazards Report Standard: ASCE/SE17-16 Latitude: 47.782991 Risk Category: II Longitude:-122.343251 Soil Class: D - Default (see Elevation: 443.9473732253444 ft Section 11.4.3) (NAVD 88) a� glerance will r' '- _s2,rJ F15'A' 3 'l 233H F1 _ O0 %JMr, ,it ti'.S' a' — 2 23 G1h 51 SW 23Gth St SN 4 i.J. -3: ` v� Alax: m °9 2391h S: SYi 23Bth St SN 4 ds. L Sy L 240111 S15Vi 240th St 5rV } 791t i 24Zfid tit Sl'! 21Z''0 Sl bAl ;y -- 9�N. - .•II',m r441'Ia SW —._--_--__-- 14dlh1St'SVV S1101ICi J's Kltt,- 7 - Aurora C\'1� Aurora Volge. r Aero Wind wine I FUM s Ma ki1Rn _ _ I ,A !i 'b6 { t.Bll Fr-ek Eamon es l.Ir.+i nl ek. it E� *h. wmn Botl ell 4of K-fin CIUE �Sh6lEInF �"' 4 •rvJnrilk IMk+ml� 4 Lre F i P.iA C,q,em Rh - Kh V Wa 16 I L-W Kllk.l;�lld _ RF!1 links 1 rl Sew —•—,-:a.rant B.yLidye Inb n'1 — Results: Wind Speed 98 Vmph 10-year MRI 67 Vmph 25-year MRI 74 Vmph 50-year MRI 78 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1 B and Figs. CC.2-1—CC.2-4, and Section 26.5.2 Date Accessed: Wed Sep 18 2024 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is not in a hurricane -prone region as defined in ASCE/SEI 7-16 Section 26.2. https://ascehazardtool.org/ Page 1 of 3 Wed Sep 18 2024 ASCE® AMERICAN SOCIETY OF CIVIL ENGINEERS Seismic Site Soil Class: D - Default (see Section 11.4.3) Results: SS 1.277 Sol N/A S, 0.448 T L 6 Fa 1.2 PGA: 0.542 F N/A PGA M : 0.651 SMS 1.533 FPGA 1.2 SM1 N/A le : 1 SIDS 1.022 C : 1.355 Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Data Accessed: Wed Sep 18 2024 Date Source: USGS Seismic Design Maps https://ascehazardtool.org/ Page 2 of 3 Wed Sep 18 2024 ASCE® AMERICAN SOCIETY OF CIVIL ENGINEERS The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided "as is" and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third -party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third -party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool. https://ascehazardtool.org/ Page 3 of 3 Wed Sep 18 2024 Based on ASCE 7-16 Wind for Components and Cladding, Method 2 Design Factors V = 98 mph Basic wind speed (3-sec gust) Exposure: C I = 1.00 Importance Factor Kzt = 1.00 Topographic factor Kd = 0.85 Wind directionality Factor Level z (ft) Kz Kh qz Penthouse 0.85 0.90 17.7 Roof 20.0 0.90 0.90 18.8 L8 0.85 0.90 17.7 L7 0.85 0.90 17.7 L6 0.85 0.90 17.7 L5 0.85 0.90 17.7 L4 0.85 0.90 17.7 L3 0.85 0.90 17.7 L2 0.85 0.90 17.7 Base 0.0 0.85 0.90 17.7 GCpi = 0 (Figure 6-5) Span 4.0 Ft Zone 5 Zone 3 Zone 4 qh GCp+ GCp- p+ p- pmax GCp- p- GCp+ GCp- p- p+ p para 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 18.85 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 18.85 35.81 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 18.8 1.00 -1.80 17.74 -33.93 33.93 -1.80 -33.93 1.00 -0.90 -16.96 17.74 34.70 Trib 2.5 Ft Figure 30.3-: Area 10.0 Sq Ft Pressure at z=h, 1.0 0.61-1 12 ft 0.6W 0.2H 4 ft 10 500 -1.8 VQ 1.6 5 1.4 �. .12 4 E 1.0 Z3 0.8 0.6 U 0.4 _) 0.2 0 +02 ri +0.4 is +0.6 c y +0.8 W +1.0 +12 -1.4 •1.1 -0-8 +0.7 +1.0 1 10 20 50 100 200 5001000 (0.1 ! (0.9) (1.9) (4.6) (9.3) (18.6) (46.5) (92.9) Effective Wind Area, ft2 (M2 ) GCp+ GCp+ GCp- 4 5 All roof 1 2 2' 3 3' 4 5 1.00 1.00 0.27 1.10 1.30 -1.60 -1.80 -2.60 -0.90 -1.80 18.8 18.8 5.1 -20.7 -24.5 -30.2 -33.9 -49.0 -17.0 -33.9 113 113 31 -19A -1d7 -1R1 -9n11 -9QA _1n9 -9nd IV IVV -3.0 .23 n 46 � -2a -- 22 c -2.0 U � t.6 o .t.4 � �ts 3 -1A OJ a6 Ta 44 42 w 0 02 .0.4 46 ae a6 t.5 i� tt .03 .o3 1 10 20 50 100 200 5001000 loll 1091 091 14.61 19.31 1196) (46.5) W-9) Effective Wind Area, it2 (n? ) Project: Kim Mechanical Unit Location: Edmonds, WA Date: 9/19/2024 Engineer: JEB Mechanical Unit Corner Loads Unit # 4WCC4060E Location: Weight: 490 Lbs H = 41 3/8 In B = 41 7/8 In L = 56 1/8 In Wind: Short Dir: Long Dir: Uplift: Fv = Seismic: Fp = 1.022 Fp = 501 Ev = 11sa ASD Dasinn fnr anchorana of unit to curly Center of Gravity: XH = 22 12/16 In (Assumed) XB = 15 10/16 In from Corner A XL = 24 3/16 In from Corner A Fh (psf) Af (sq ft) Fh (lb) Mot (lb -in) 35.8 12.0 431 8915 35.8 16.1 578 11948 20.7 16.3 338 Mot (lb -in) Wp Short Dir: 11396 Seismic Controls Ibs Long Dir: 11396 Wind Controls 0.204 Wp = 100 Ibs Mot, Load Direction Mr, Load Direction Mot - Mr (lb -in) V (Ibs) N (Ibs) Load Combination Short Long Short Long Short Long Short Long Short Long D 0 0 11842 7663 0 0 490 490 W 8915 11948 0 0 431 578 0 0 W uplift 0 0 -8165 -5284 0 0 -338 -338 E 11396 11396 0 0 501 501 0 0 Ev 0 0 2421 1566 0 0 100 100 D + 0.6W 5349 7169 11842 7663 -6494 -494 259 347 490 490 D - 0.6W 5349 7169 15659 12856 10310 -5687 -259 -347 490 490 0.6D + 0.6W +0.6Wu 5349 7169 2206 1428 3142 5741 259 347 91 91 0.6D - 0.6W +0.6Wu 5349 7169 4496 4543 853 2626 -259 -347 91 91 D + 0.7E+Ev 7977 7977 13537 8760 -5560 -782 351 351 590 590 D-0.7E+Ev 7977 7977 17899 14695 -9922 -6718 -351 -351 590 590 0.61) + 0.7E-Ev 7977 7977 10148 6567 -2171 1410 351 351 194 194 0.6D-0.7E-Ev 1 7977 7977 13418 11016 -5441 -3039 -351 -351 194 1 194 MAX 7977 7977 17899 14695 3142 5741 351 351 590 590 MIN 5349 7169 2206 1428 -10310 -6718 -351 -351 91 91 orces at connection of unit to the curb adapter: Short: Mot - Mr = 3142 lb -in Long: Mot - Mr = 5741 lb -in d = 56.13 in d = 41.88 in T = 56 Ibs T = 137 Ibs n = 2 screws n = 2 screws T = 28 lb/screw T = 69 lb/screw V = 88 lb/screw V = 88 lb/screw Use #10 screws to fasten unit to 16 ga curb: Va = 370 Ibs/screw DCR = 0.24 Ta = 137 Ibs/screw DCR = 0.50 Use (2) #10 TEK screws on each long side, (2) on each short side. Anchorage of curb to support: Curb height He = 10 in Curb width, Bc = 32 in Curb Length, Lc = 70 in Per curb adapter shop drawings, the unit is centered on the existing curb so no additional eccentricity results. T/curb B/curb V (Ibs) N (Ibs) T (Ibs) Mot - Mr Mot - Mr Short Dir 3142 7046 351 91 101 Long Dir 5741 10117 351 91 316 Use #10 screws to fasten curb adapter to existing curb: n = 3 screws each short side n = 2 screws each long side Va = 370 Ibs/screw DCR = 0.24 Ta = 137 Ibs/screw DCR = 0.77 Use (2) #10 TEK screws on each long side, (3) on each short side Submittal Single Packaged Heat Pump 13.4 SEER2 Convertible 4WCC406OE 1000A Note: "Graphics in this document are for representation only. Actual model may differ in appearance. " August 2022 4WCC4060E-SUB-1 A-E N Product Specifications MODEL 4WCC406OE1000A RATED Volts/PH/Hz 208-230/1/60 Performance Cooling BTUH (a) 57000 Indoor Airflow (CFM) 1835 Power Input (KW) 4.85 EER2/SEER2 (BTU/Watt-Hr.) (b) 11.00 / 13.40 Sound Power Rating [dB(A)] (c) 77.3 PERFORMANCE HEATING (High Temp.) BTUH 55000 Power Input (KW) 4.71 (Low Temp.) BTUH 35400 Power Input (KW) 4.34 HSPF2 (BTUH/Watt-Hr) 7.0 POWER CONN. — V/Ph/Hz 208-230/1/60 Min. Brch. Cir. Ampacity (d) 39.0 Fuse Size — Max. (amps) 60 Fuse Size — Recmd. (amps) 60 COMPRESSOR SCROLL VOLTS/PH/HZ 208-230/1/60 R.L. Amps — L.R. Amps 24.4/ 144.2 OUTDOOR COIL — TYPE SPINE FIN Rows/F.P.I 2 / 24 Face Area (sq. ft.) 22.99 Tube Size (in.) 3/8 Refrigerant Control EXPANSION VALVE INDOOR COIL — TYPE PLATE FIN Rows/F.P.I 4/ 15 Face Area (sq. ft.) 5.0 Tube Size (in.) 3/8 Refrigeration Control EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT OUTDOOR FAN — TYPE SWEPT DIA.(IN.) 28.3 DRIVE/NO. SPEEDS DIRECT/ 1 CFM @ 0.0 in. w.g. (e) 5500 Motor— HP/R.P.M 1/3 / 825 Volts/Ph/Hz 208-230/1/60 F.L. Amps/L.R Amps 1.7 / 3.5 INDOOR FAN — TYPE CONSTANTTORQUE ECM Dia. x Width (in.) 11.87 X 10.68 Drive/No. Speeds DIRECT/ 4 CFM @ 0.0 in. w.g. M SEE FAN PERF TABLE Motor— HP/R.P.M. 1 / 1050 Volts/Ph/Hz 208-230/1/60 F.L. Amps 6.9 FILTER / FURNISHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft) (9) 5.3 REFRIGERANT R-410A Charge (lbs.) 11.0 CHARGING SPECIFICATIONS Subcooling 6° DIMENSIONS H X D X W Crated (in.) 52 X 47 X 62 WEIGHT Shipping (lbs.) / Net (lbs.) 594 / 490 (a) Rated in accordance with AHRI Standard 210/240. (b) Rated in accordance with D.O.E. test procedure. W Sound Power values are not adjusted forAHRI 270-95 tonal corrections. (d) Calculated in accordance with currently prevailing Nat'l Electrical Code. (e) Standard Air — Dry Coil — Outdoor. (f) Standard Air — Dry Coil — Indoor (9) Filters must be installed in return airstream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. 4WCC4060E-SUB-1A-EN Outline Drawings Figure 1. 2 - 5 Ton Models 11.18 [II/I6] SECTION X-X TYPICAL (8) SIDES OF SIDEFLOW DUCT OPENINGS 18.03 18.29 [23/321 123/321 14.2 (9/161 25.40 111 SECTION Y-Y TYPICAL (8) SIDES OF DOWNFLOW DUCT OPENINGS 19.0 [3/41 FEMALE NPT 2 - 3 TON Units 1 3.5 - 5 TON Units RECOMMENDED SERVICE CLEARANCE mm Inches W/ ECONOMIZER W/ ECONOMIZER BACKSIDE 305 [121 762 [301 305 [121 762 [301 LEFT SIDE 762 [301 914 [361 914 [361 1067 [421 RIGHT SIDE 610 [241 610 [241 - FRONT SIDE 1067 [421 762 [301 - CLEARANCE TO COMBUSTIBLE MATERIAL mm Inches BOTTOM 0 0 BACK SIDE 1 25 [11 25 [11 LEFT SIDE 152 [61 152 [61 RIGHT SIDE 152 [61 152 [61 FRONT SIDE 305 [121 305 [121 TOP 914 [361 914 [361 DIMENSIONS mm Inches A HEIGHT OF UNIT - TABLE NEXT PAGE BB I CENTER OF GRAVITY - TABLE NEXT PAGE CC CENTER OF GRAVITY - TABLE NEXT PAGE DD-De th 1049.02 [41-5/161 1125.22[44-5/161 EE-Width 1240.28 [48-27/321 1487.17[58-9/161 FF 497.8 [19-5/81 576.00 [22-11/161 connection strap 4" of each corner 1 Ur JIUC CENTER OF GRAVITY OUTLET FRONT SIDE BOTTOM SIDE 4VVCC406OE-SUB-1 A -EN 3 Outline Drawings Figure 2. 2 - 5 Ton Models E BOTTOM DUCT OPENINGS 24V ENTRY 359. 9 [14 �/32] 288.42 225.68 [II ICl/321 [8-7/81 I 17.73 J �0111' ENTRY [4-5/8] 28.5[I 1/81 DIA. KNOCKOUT 85.22 OWER ENTRY [3-1I/321 28.58 11-1/81 DIA. KNOCKOUT I28.08 50.01 [1-31%32D1DIAKN NOCKOUT [5-1/32] SINGLE POINT ENTRY RIGHT SIDE S0.01 [I-31%32D1DIA.N NOCKO OCKOUT 62.71 [2-15/321 DIA. KNOCKOUT BACK DUCT OPENINGS (SURFACE AREA) 321 [20-.7/81 Height mm[in] PHYSICAL DIMENSIONS mm[In] A -Height B C D E F G H I J K L M N 4WCC4024 898.53 [35.38] 304.80 [12] 75.41 [2.93] 75A1 [2.93] 406.40 [161 167.89 [6.61] 173.46 [16] 304.80 [6.8] 79.50 [3.13] 398.22 [15.681 176.07 [6.931 177.55 [6.99] 296.62 [11.681 1155.45 [45A91 4WCC4030 949.33 [37.38] 4WCC4036 4WCC4042 1000.13 [39.381 457.20 [181 75.41 [2.97] 75A1 [2.97] 381.00 1151 244.09 [9.61] 318.75 [12.551 381.00 [151 79.50 [3.13] 449.02 [17.681 176.07 [6.931 322.84 [12.711 372.82 [14.681 1402.34 [55.211 4WCC4048 4WCC4060 1050.93 [41.381 Corner Weights KG/LBS SHIPPINGWEIGHT KG/LBS UNIT WEIGHT KG/LBS Center Of Gravity mm[inch] W7 W2 W3 W4 BB CC 4WCC4024 52.9 [1171 33.3 [731 24.1 [531 38.3 [841 182.3 [4021 148.6 [3281 430 [16.91 565.3 [22.31 4WCC4030 55.3 [1221 50.3 [1101 16.6 [371 39.2 [861 195.0 [4301 161.3 [3551 413.5 [16.31 581 [22.91 4WCC4036 59.6 [1311 37.3 [821 26.6 [591 41.7 [921 199 [4391 165.3 [3641 430 [16.91 535 [21.11 4WCC4042 64A [1421 47.6 [1051 39.5 [871 49.9 [1101 248.6 [547.91 201.4 [4441 449.6 [17.71 641.8 [25.31 4WCC4048 68.9 [1521 40.8 [901 30.8 [681 52.2 [1151 240 [5291 192.8 [4251 414.0 [16.31 414.0 [16.31 4WCC4060 79.4 [1751 47.2 [1041 35.8 [791 59.9 [1321 269.5 [5941 222.3 [4901 414.0 [16.31 414.0 [16.31 4 4WCC4060E-SUB-1A-EN Indoor Fan Performance 4WCC4060E1 EXTERNAL STATIC PRESSURE (IN.WG) Horizontal Airflow [Down Airflow] Motor Speed 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 515 523 533 544 554 Watts [511] [521] [533] [546] [558] - - - - - LOW CFM 1857 1831 1800 1766 1737 - - - [1875] [1841] [1805] [1766] [1730] Watts - 632 644 655 666 677 689 699 714 728 741 [631] [643] [654] [665] [676] [687] [697] [712] [726] [739] MED-LOW 2059 2020 1990 1960 1928 1895 1871 1828 1786 1748 CFM - [2070] [2031] [2001] [1971] [1939] [1905] [1881] [1838] [1796] [1758] 759 769 779 788 803 816 830 845 860 874 Watts - [758] [771] [786] [801] [815] [829] [839] [849] [858] [872] MED-HIGH 2058 2032 2003 1974 1943 1911 1877 1843 1807 1771 CFM - [2063] [2034] [1999] [1965] [1931] [1894] [1869] [1846] [1795] [1759] 910 921 932 941 956 969 983 997 1010 1021 Watts - [908] [919] [930] [942] [960] [971] [988] [997] [1001] [1018] HIGH CFM - 2177 2152 2127 2105 2071 2041 2009 1975 1940 1903 [2184] [2150] [2104] [2073] [2027] [1998] [1961] [1937] [1905] [1890] Note: Airflow must not exceed 2250 CFM due to condensate blowoff. 4WCC4060E-SUB-1 A -EN Full Perimeter Roof Mounting Curb Figure 3. 3.5 — 5.0 Ton Models BAYCURB051A Full Perimeter Roof Mounting Curb 10 7/8 14 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the \ items depicted in the drawings. The manufacturer \ is not responsible for the unauthorized use of these i \ \ drawings and expressly disclaims any liability for \ damages resulting from such unauthorized use. \ \ RETURN \ AIR \ SUPPLY D� i CHANNEL END— i 38 7. AIR ml'_19.1 HOLE IN ROOF 53 1/8 —CHANNEL SIDE WOOD NAILER i SERVICE CLEARANCE DIMENSIONS A B C D WC*/TC* 42.00 36.00 12.00** 24.00 DC*/YC* 42.00 36.00 12.00** 36.00 ** 42.00 WITH ECONOMIZER WITH 25% FRESH AIR ACCESSORY 6 1 4WCC4060E-SUB-1A-EN Supplementary Electric Heater Table 1. BAYHTRV — Supplementary Electric Heaters ELECTRIC RATED HEATER NO. KW/STAGE MAX. FUSE CANADA UNIT HEATER VOLT- PHASE AMPS CAPACITY OF MCA OR HACR ONLY MAX. MODEL MODEL AGE STAGES CKT BKR CKT BKR KW BTUH 1 2 SIZE SIZE 4024-4060 BAYHTRV105 208/240 1 18/21 3.76/5.0 00/ 1 3570/ - 23/26 25/30 25/30 178 4024-4060 BAYHTRV108 208/240 1 29/33 6.0/8.0 205 1 .8.0/ - 36/41 40/45 40/45 00/ 4024-4060 BAYHTRV110 208/240 1 36/42 7.5/10.0 1 - 45/52 45/60 45/60 34100/ 1050 4030-4060 BAYHTRV115 208/240 1 54/63 11.27/ 38500/ 2 7.5/ 3.76/ 68/78 70/80 70/80 15.0 51200 10.0 5.0 4048-4060 BAYHTRV120 208/240 1 72/83 15.0/ 51200/ 2 7.5/ 7.5/ 90/ 90/110 90/110 20.0 68300 10.0 10.0 104 4060 BAYHTRV125 208/240 1 90/ 18.78/ 64100/ 2 11.26/ 7.5/ 113/ 125/150 125/150 104 25.0 85300 15.0 10.0 130 Table 2. BAYSPEK — Single Power Entry Kit SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION UNIT MODEL SINGLE POWER ENTRY KIT HEATER MODEL MIN CKTAMP MAX OVER -CURRENT DEVICE 4WCC4060E BAYSPEK62 BAYHTRV105 65 80 BAYHTRV108 80 90 BAYHTRV110 91 100 BAYSPEK63 BAYHTRV115 117 125 BAYHTRV120 143 150 4WCC4060E-SUB-1 A-E N Optional Equipment — Filter Rack Figure 4. BAYFLTR101 Filter Rack (2.0 - 3.0 Ton Models) BAYFLTR201 (3.5 - 5.0 Ton Models) (Mounts in Filter/Coil Section) Figure 5. BAYACCDOR1A Hinged Filter Access Door (2.0 - 3.0 Ton Models) BAYACCDOR2A (3.5 - 5.0 Ton Models) Replaces Filter/Coil Access Panel Note: The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4WCC4060E-SUB-1A-EN Optional Equipment — Filter Rack Optional Equipment — Economizer Table 3. BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) HVAC Unit Economizer Unit Application Models Economizer eeeeeee�ee rain hood e�eeeeeeeee BAYECON101A 2.0 — 3.0 Ton Models Outside air dampers Return air dampers Required c filter kit, order Mist separately eliminator i� BAYECON102A 3.5 — 5.0 Ton Models Relief Return damper Duct Roofcurb Table 4. BAYCON200, 201A Horizontal Economizer and Rain Hood Economizer A 0 \ B Gaskets (2) Duct E r— Rain Hood Mixed Air Sensor Economizer Models A B C D E F BAYECON200A 2.0 — 3.0 Ton 22" 20" 16-7/8" 15-11/16" 11-11/16" 151, BAYECON201A 3.5 — 5.0 Ton 26" 22-21/32" 191, 17-11/16" 14-11/16" 21-3/8" Note. The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4WCC4060E-SUB-1 A -EN Optional Equipment — Filter Rack Optional Equipment — Outside Air Damper Table 5. BAYOSAH001 and 002A Outside Air Damper (Replaces Filter/Coil Access Panel A \ FULLY UPEW Manual Fresh Air Model Unit Application Models A B C D BAYOSAHOOIA 2.0 — 3.0 Ton 22-7/16" 20-11/16" 12-3/8" 9-3/16" � D / C 113 G B FULLY CLOSED BAYOSAH002A 3.5 — 5.0 Ton 25-3/16" 20-11/16" 12-3/8" 9-3/16" Table 6. BAYDMPR101 and 102A, 25% Motorized Outside Air Damper (Mounts Over Horizontal Return Air Opening) A r, � Manual Fresh Air Model Unit Application Models A B C D E BAYDM- PR101A 2.0 .o 3.0 Ton 15-13/16" 11-13/16" 10-1/4" 11-1/2" 12-1/4" C B E BAYDM- PR102A 3.5 — 5.0 Ton 18-3/16" 15-1/8" 10-1/4" 11-1/2" 12-1/4" D Note; The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 4WCC4060E-SUB-1A-EN Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 1151F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards. Unit Casing All components shall be mounted in a weather - resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff. Compressor The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise. Refrigeration System All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard. Evaporator Coil Internally enhanced 3/8" OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 — 650 psig. All units have TXV to control refrigerant flow. Condenser Coil The Spine Fin TM condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8" OD seamless aluminum tubing glued to a continuous aluminum fin Coils are lab tested to withstand 2.000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan Constant Torgue, forward -curved, centrifugal wheel in a Composite Vortica ® Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Outdoor Fan One direct -drive, statically and dynamically balanced propeller fan shall be used in a draw -through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. System Controls System controls include condenser fan, evaporator fan and compressor contactors. Accessories Roof Curb The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory installed wood nailer strips. Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. Single Source Power Entry This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut -to -length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes. 4WCC4060E-SUB-1 A -EN 11 Mechanical Specifications Fully Modulating Economizer This accessory shall be field installed and be composed of the following items: 0-100 % fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometric relief damper shall be standard with the economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment "off" cycle. Economizer requires BAYRLAY004A relay kit to interface the economizer to the heat pump. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Start Kit Extra compressor starting capacity for single phase equipment. Control Options Standard Indoor Thermostats Two stage heating/cooling or one stage heating/ cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setting Thermostat Programmable electronic thermostat shall provide heating setback and cooling setup with 7—day programming capability. 1H/1C or 21-1/2C models available. 12 4WCC4060E-SUB-1A-EN About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com. 0%-us Intertek The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org. The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. 4WCC4060E-SUB-1A-EN 31Au92022 Supersedes (New) ©2022 gMicroMetl Date: Weight: 3lbs (US) 1.36kg (Metric) rt N Paumber: ECMT-PC-TD RTU: Submitted to: Approved by: Notes: HVAC Unit Hold Down Brackets - Designed To Secure HVAC Unit To Curb. The Addition of Hold Down Brackets Do Not Provide Wind or Seismic Certification. Includes Self -Drilling Screws. For Use Only With MicroMetl Curb. Set of 6 brackets Hold down Brackets & 4 Corner Brackets Min (2) #10 screws per hold-down D0r 1 2.59 1 750 �i Min (2) #10 screws per hold-down to curb adapter ECMT UC-TD (CITY 6) CORNER CURB TO (Used with utility curb) UNIT BRACKET (QTY 4) 1W 'ate Min (2) #10 screws per hold-down to unit 1.0w 5 "41 1 8S6 301 I � 130" REF 2.000 391 i 37a J �..— Min (2) #10 screws per hold-down to curb adapter .260 �- ECMT PC-TD (QTY 6) (Used with standard curb) NOTE- Brackets are not certified and do not offer seismic rating This Document Is The Property Of MicroMetl Corporation And Is Delivered Upon The Express Condition That The Contents Will Not Be Disclosed Or Used Without Microldetl's Written Consent MicroMetl Reserves The Right To Discontinue, Or Change At Any Time, Specifications & Designs Without Any Notice Incurring Obligations. Master Revision 0001 A Page Revision 0001 A Indianapolis_3035 N. Shadeland Ave., Indianapolis, IN 46226_800.MMC.HVAC -- Sparks_905 Southern Way, Sparks, NV 89431_800.884.4MMC -- Longview_201 Kodak Blvd., Longview, TX 75602_903.248.4800 WEIGHT: 112 LBS. IN 1 '' EXISTING CU PLAN VIEW 72" 56 8 O.D. 72" 1 ' �► 71 16 " O. D. ►� FRONT VIEW NOTES: 1. 16 GA. GALV. STEEL CONSTRUCTION 2. INTERNALLY INSULATED WITH 1"-1.5 PCF DENSITY INSULATION 3. CONTINUOUS WELDED SEAMS AND CORNERS 4. 1/4" X 1 1 /4" GASKETING 5. SHIPPED FULLY ASSEMBLED 6. UNIT TO ADAPTER GASKET INCLUDED (3) #10 SCREWS EA SIDE ---\ 2" TYP. �tIP' 10' 70" O.D. �418"O.D.� 3� 4g" L 33 16' � 48 I� O.D. SIDE VIEW INSTALLATION INSTRUCTIONS: • REMOVE OLD A/C UNIT. • APPLY 1 /4" X 1 1 /4" GASKETING ON EXISTING CURB. • INSTALL & SECURE ADAPTER CURB ON EXISTING CURB AS REQUIRED BY LOCAL BUILDING CODES. • APPLY 1 /4" X 1 1 /4" GASKETING ON ADAPTER CURB. • INSTALL & SECURE NEW A/C UNIT ON ADAPTER CURB AS REQUIRED BY LOCAL BUILDING CODE. 00< 28'' 28" SIP 28" IN 32" O.D. ISOMETRIC VIEW FIELD CURB DIM. PROVIDED MAY HAVE BEEN MODIFIED.. PLEASE REVIEW EXISTING CURB THOROUGHLY QUOTE: JH1286-24RO TAG: JOB: Legacy One - Trina NEW UNIT: 4WCC4060 EXISTING UNIT: PC9052