Planet Fitness Edmonds TAB Preliminary Report�n H i i�0 A. A dp \` Y Project Name: Planet Fitness Address: 22515 Highway 99, Edmonds WA, 98026 Project Number: 24-1120 This is to certify that Farrington Air Quality Services, LLC has Tested, Adjusted, and Balanced the systems described herein to their best possible performance capabilities. Data presented is a record of measurements and adjustments at the time the work was performed. This test and the associated balancing was performed in accordance with the TABB Procedural Guide (2003) and other industry standards. The air system testing and balancing report contained here in is true and factual based on actual field measurements and adjustments. I have personally performed or witnessed a minimum of 5% of the airflow tests. Submitted and certified by: Daniel Farrington, TABB Supervisor Date: 9/11/2024 \o�a�Certificaf�o 0 Daniel S Farrington Farrington Air Quality Services LLC TABB Supervisor #TB11516555 Expires 0980/2024 e�r�fied SupeN�� TESTING, ADJUSTING AND BALANCING BUREAU THE PROFESSIONAL'S CHOICE'" PARRINGTON AIR QUALITY SERVICES Abbreviations AC or ACU Air Conditioning Unit EAT Entering Air Temperature AP Pressure Drop. AHU Air Handling Unit EF Exhaust Fan PH Phase Ak The area of an opening in sq./ft. EG/ED Exhaust Grille/Diffuser PSI Pounds per Square Inch ATM Atmosphere EMS Energy Management System RA Return Air AVG Average ERU Energy Recovery Unit RAT Return Air Temperature BHP Brake Horsepower FHT Fume Hood Test RF Return Fan CAV Constant Air Volume FPB Fan Powered Box RH Relative Humidity CBV Cal. Balance Valve FIRM Feet per Minute RHC Reheat Coil CC Cooling Coil FT Foot, Feet RPM Revolutions per Minute CD Ceiling Diffuser GPM Gallons per Minute RTU Roof Top Unit CFM Cubic Feet per Minute HC Heating Coil SA Supply Air CH Chiller TDH Total Dynamic Head - Pump SAT Supply Air Temperature CHWS Chilled Water Supply HEPA High Efficiency Particulate Arrentance S.F. Service Factor CHWR Chilled Water Return HP Horsepower SF Smoke/Fire Damper CP Circulating Pump HVAC Heating Ventilation and AC SWG Sidewall Grille CD/CR Ceiling Diffuser/Register HWS Heating Water Supply TAB Test, Adjust & Balance CRAC Computer Room AC HWR Heating Water Return TEMP Temperature CRU Computer Room Unit HX Heat Exchanger TON 12,000 BTUH (Cooling CT Cooling Tower HZ Hertz, cycle/second of current TSTAT Thermostat (T) CU Condenser Unit in.w.g. inches of water gauge TSP Total Static Pressure CUH Cabinet Unit Heater K-factor Correction factor to the free area needed to calculate CFM UH Unit Heater CWS Condenser Water Supply KW Kilowatts V Volt — Either AC or DC CWR Condenser Water Return LAT Leaving Air Temperature VAV Variable Air Volume bo) D Discharge LWT Leaving Water Temperature VD Volume Damper DAT Discharge Air Temperature MAU Make-up Air Handling Unit VEL Velocity (usually in FPM) DB Dry Bulb MBH 1,000 BTUH VFD Variable Frequency Driv DDC Direct Digital Controls NT Not Tested VVT Variable Volume Termin DP Differential Pressure OSA Outside Air W.G. Water Gauge DNA Data not available or given OBD Opposed Blade Damper WB Wet Bulb DNV Data Not Visible OD Outside Diameter 1) TAB —Test the quantitative performance of a system then regulate it to a specific rate and to the proportion the flow according to the design 2) Flowhood — Instrument used by a Balancer to capture air and measures and reports in CFM 3) Total Static Pressure - Difference in pressure from the inlet to the discharge of a fan added together 4) Economizer— Components and controls that allow an air handler to effectively use outside air instead of mechanical cooling to save energy and provide building pressurization 5) Total Dynamic Head - The difference between the pressure of a fluid entering a pump vs exiting added together 6) Design Tolerance — Specified by the designer or +/-10% 7) Ratio of Tolerance - Used to verify that terminals and/or the system are within Design Tolerance; Example 90%- 110% of design if design was 250 then .90/1.10=1.22 and flow between 275CFM-225CFM would be acceptable FARRINGTON Equipment List AIR QUALITY SERVICES Equipment Manufacturer Model/Serial Number Calibration Date Capture Hood Testo 420 /50612935/0523 8/22/2024 DP Manometer Fluke 922/49810227 10/25/2024 Water Meter TSI HM685/72232002 4/16/2024 FARRINGTON AIR QUALITY SERVICES 1) General Information Executive Summary a) This report is based on actual field readings taken during operation unless otherwise noted. Work was completed on: 9/11/2024 b) Equipment is inspected for proper and safe operation unless noted in this summary or the associated data contain herein. c) Work requiring adjustments will be performed to +/-10% of the design value unless other specifications require increased/decreased tolerances and approval by the Engineer of Record (EOR) or Authority Having Jurisdiction (AHJ). Flow rates were measured with calibrated instruments and are listed on the tool summary. d) All suggestions to further improve performance or function need to be fully vetted and verified by all interested parties (i.e. Engineer, Owner, Tenant, Contractor) e) Deficiencies noted throughout this report are the responsibility of the parties having an interest in them and are not to be corrected by the TAB team unless instructed in the contract documents. Notes are added for clarification as applicable. f) Design information is drawn from various sources to include, but not limited to: Drawings, specifications, user manuals, shop drawings, submittals, service history, legacy documents, and oral & photographic information. Additionally, unspecified values may be field determined as required in the absence of engineered values, based on current best practices. 2) Scope of the Project (Overview) ONE (1) Dedicated Outside Air System (DOAS) SIX (6) Roof Top Units (RTU) 3) Findings: a) DOAS unit to provide fresh outside air and exhaust to space. b) RTU's to provide conditioned air to space. Procedures Summarized: i. Total airflow was measured using the summation of applicable supply/exhaust diffusers, and/or, a pitot tube traverse for total airflow. ii. Fans were then adjusted, as needed, until design airflow was met. iii. Supply and Exhaust diffusers were then proportioned to engineered design values. iv. Unit nameplate and running data was then measured and recorded. Thank you for choosing Farrington Air Quality Services, please contact with any questions regarding the above report. Daniel Farrington, TABB CP Owner/Operator tel: 253-466-3000 cell: 253-225-5592 email: Daniel@farringtonair.com RLIRIN'TON AIR QUALITY SERVICES www.farringtonair.com FARRINGTON AIR QUALITY SERVICES Table of Contents PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT M 24-1120 AUTHOR: 1 Energy Recovery Unit ....................... 1.1 DOAS-1....................................... 2 Roof Top Unit .................................... 2.1 RTU-01........................................ 2.2 RTU-02........................................ 2.3 RTU-03........................................ 2.4 RTU-04........................................ 2.5 RTU-04/Total Return ................... 2.6 RTU-04/Total Supply ................... 2.7 RTU-05........................................ 2.8 RTU-05/Total Return ................... 2.9 RTU-05/Total Supply ................... 2.10 RTU-06...................................... 2.11 RTU-06/Total Return ................. 2.12 RTU-06/Total Supply ................. 3 Planet Fitness Mech Drawings 3.pdf 4 Planet Fitness Mech Drawings 5.pdf 5 Planet Fitness Mech Drawings 2.pdf 1 1 2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Farrington Air Quality Services FARRINGTON AIR QUALITY SERVICES Energy Recovery Unit PROJECT: Planrt Fitness Edmonds LOCATION: Edmonds, WA PROJECT #: 24-1120 SYSTEM/UNIT: DOAS-1 Unit Data Unit Manufacturer Aaon Unit Model Number RN-014-2,3,4,8-!-GA!!-000:!!!!! Unit Serial Number 202408-BNCB26513 Unit Type Energy Wheel DOAS-1/SF Filter Filter Manufacturer Glassfloss Filter Type Pleated Actual MERV Rating 10 Filter Qty - S1 6 Filter Size - S1 16x20x2 Filter Qty - S2 6 Filer Size - S2 20x25x2 Filter Qty - S3 6 Filter Size - S3 20x25x4 DATE: 9/11 /2024 CONTACT: Chris Brittenham AUTHOR: Tested By: Chris Brittenham Date: 9/9/2024 Motor Data Motor Type Belt Drive Nameplate Motor Manufacturer Weg Nameplate Motor Frame 182/4T Nameplate Motor FL Amps 6.33 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.15 Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 DOAS-1/SF Motor Type Direct Drive Nameplate Motor Manufacturer Weg Nameplate Motor Frame 213/5T Nameplate Motor FL Amps 9.25 Amps Nameplate Motor Hertz 60 Hz Nameplate Motor Service Factor 1.15 Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data DOAS-1/EF Design Nameplate Motor HP 5.0 HP Motor Voltage 460 Volts Motor RPM 1760 RPM Motor Phase 3 DOAS-1/SF Desian Nameplate Motor HP 7.5 HP Motor Voltage 460 Volts Motor RPM 1770 RPM Motor Phase 3 Sheave Data DOAS-1/EF Number of Belts 1 Belt Size A51 Sheave Center Line Distance 20.00 in. Sheave Data DOAS-1/EF Motor Fan Sheave Manufacturer QB Dodge QB Dodge Sheave Model 1 VP44 BB AK-51 Sheave Diameter 4.4 in. 5.1 in. Sheave Bore 1 1/8 in. 1 in. DOAS-1/SF Motor Fan Sheave Manufacturer Sheave Model Sheave Diameter Sheave Bore Farrington Air Quality Services Page 1 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-01 Unit Manufacturer Unit Model Number Unit Serial Number Unit Discharge RTU-01/SF Filter Bank Filter Type Filter Qty - S1 Filter Size - S1 Unit Data 50FCQA04B2A6A8U2T0 2824C10013 Downblast Construction 2 16x25x2 RTU-01 Supply Outlet Summary Tested By: Chris Brittenham Date: 9/9/2024 Motor Data RTU-01/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 1.20 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-01/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 System/Unit Outlet Tvpe Size LxW / D Instrument AK Factor Design CFM Prelim CFM Final CFM % Final Outlet-01 CD 6 Flowhood 1.00 100 Outlet-02 CD 6 Flowhood 1.00 100 Outlet-03 CD 6 Flowhood 1.00 100 Outlet-04 CD 6 Flowhood 1.00 100 Outlet-05 CD 6 Flowhood 1.00 100 Outlet-06 CD 6 Flowhood 1.00 100 Outlet-07 CD 6 Flowhood 1.00 50 Outlet-08 CD 6 Flowhood 1.00 50 Outlet-09 CD 8 Flowhood 1.00 100 Outlet-10 CD 8 Flowhood 1.00 100 Outlet-11 CD 8 Flowhood 1.00 100 Outlet-12 CD 6 Flowhood 1.00 100 Outlet-13 CD 8 Flowhood 1.00 100 Totals: - - - 1200 1 0 1 0 0 RTU-U1 Return Inlet Summary System/Unit Inlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Inlet-01 RG 8 Flowhood 100 Inlet-02 RG 6 Flowhood 100 Inlet-03 RG 8 Flowhood 200 Inlet-04 RG 10 Flowhood 245 Inlet-05 RG 6 Flowhood 50 Inlet-06 RG 8 Flowhood 100 Inlet-07 RG 8 Flowhood 100 Inlet-08 RG 8 Flowhood 100 Inlet-09 RG 6 Flowhood 100 Totals: - I - - 1095 0 0 0 Farrington Air Quality Services Page 2 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-02 Unit Manufacturer Unit Model Number Unit Serial Number Unit Discharge RTU-02/SF Filter Bank Filter Type Filter Qty - S1 Filter Size - S1 Unit Data 50FCQA04E2A6A8U2C0 2824C10014 Downblast Construction 2 16x25x2 RTU-02 Supply Outlet Summary Tested By: Chris Brittenham Date: 9/9/2024 Motor Data RTU-02/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 1.20 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-02/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 System/Unit Outlet Tvpe Size LxW / D Instrument AK Factor Design CFM Prelim CFM Final CFM % Final Outlet-01 CD 10 Flowhood 1.00 175 Outlet-02 CD 10 Flowhood 1.00 175 Outlet-03 CD 10 Flowhood 1.00 175 Outlet-04 CD 10 Flowhood 1.00 150 Outlet-05 CD 10 Flowhood 1.00 175 Outlet-06 CD 10 Flowhood 1.00 175 Outlet-07 CD 10 Flowhood 1.00 175 Totals: - - - 1200 0 0 0 RTU-02 Return Inlet Summary System/Unit Inlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Inlet-01 12 Flowhood 600 Inlet-02 12 Flowhood 600 Totals: - - 1200 0 0 0 Farrington Air Quality Services Page 3 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-03 Unit Data Unit Manufacturer Carrier Unit Model Number 50FCQM12B3A6A8U2C0 Unit Serial Number 3124P79666 Unit Discharge Downblast RTU-03/SF Filter Bank Filter Type Construction Filter Qty - S1 4 Filter Size - S1 20x2Ox2 Test Data Design Actual Supply Airflow 3900 CFM Return Airflow 3800 CFM RTU-03 Supply Outlet Summary Tested By: Chris Brittenham Date: 9/9/2024 Motor Data RTU-03/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 5.60 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-03/Supply Fan Design Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 System/Unit Outlet Tvpe Size LxW / D Instrument AK Factor Design CFM Prelim CFM Final CFM % Final Outlet-01 CD 8 Flowhood 1.00 150 Outlet-02 CD 10 Flowhood 1.00 200 Outlet-03 CD 6 Flowhood 1.00 75 Outlet-04 CD 6 Flowhood 1.00 75 Outlet-05 CD 10 Flowhood 1.00 250 Outlet-06 CD 10 Flowhood 1.00 300 Outlet-07 CD 6 Flowhood 1.00 75 Outlet-08 CD 10 Flowhood 1.00 400 Outlet-09 CD 10 Flowhood 1.00 400 Outlet-10 CD 10 Flowhood 1.00 300 Outlet-11 CD 10 Flowhood 1.00 400 Outlet-12 CD 6 Flowhood 1.00 75 Outlet-13 CD 10 Flowhood 1.00 400 Outlet-14 I CD 10 Flowhood 1.00 300 Outlet-15 CD 12 Flowhood 1 1.00 400 Outlet-16 CD 8 Flowhood 1.00 100 Totals: - - - 3900 0 0 0 RTU-03 Return Inlet Summary System/Unit Inlet Type Size LxW / D Instrument AK Factor Final FPM Design CFM Prelim CFM Final CFM % Final Inlet-01 RG 10 Flowhood 250 Inlet-02 RG 8 Flowhood 150 Inlet-03 RG 10 Flowhood 250 Inlet-04 RG 12 Flowhood 400 Inlet-05 RG 10 Flowhood 250 Inlet-06 RG 10 Flowhood 300 Inlet-07 RG 10 Flowhood 250 Inlet-08 RG 10 Flowhood 250 Inlet-09 RG 12 Flowhood 400 Inlet-10 RG 8 Flowhood 100 Inlet-11 RG 12 Flowhood 400 Inlet-12 RG 12 Flowhood 400 Inlet-13 RG 12 Flowhood 400 Totals: I - - - 3800 1 0 1 0 0 Farrington Air Quality Services Page 4 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-04 Unit Manufacturer Unit Model Number Unit Serial Number Unit Discharge RTU-04/SF Filter Bank Filter Type Filter Qty - S1 Filter Size - S1 Unit Data 50FCQM07B2A6B8U2C0 2824C10077 Downblast Construction 4 16x16X2 Test Data O/A Damper Position 0 % R/A Damper Position 100 % Test Data Desian Actual Supply Airflow 2400 CFM 2282 CFM Return Airflow 2400 CFM Tested By: Chris Brittenham Date: 9/10/2024 Motor Data RTU-04/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 2.60 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-04/Supply Fan Desian Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 Farrington Air Quality Services Page 5 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-04/Total Return Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 11.00 in. Duct Width 29.00 in. Air Flow Area 2.22 sq. ft. Number Of Rows 5 Readings Per Row 4 Total Readings 20 Location of Holes 1 Left Row 1 Row 2 Row 3 Row 4 Row 5 Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 19627 Average Velocity 935 FPM Design Airflow 2400 CFM Actual Airflow 2076 CFM Traverse Data Points 71fi 1303 1202 789 889 1 98fi 1 907 7fi1 s75 1v3 ssa s81 1 919 1 F572 E919 I777 1192 976 1250 991 29 Farrington Air Quality Services Page 6 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-04/Total Supply Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 17.00 in. Duct Width 11.00 in. Air Flow Area 1.30 sq. ft. Number Of Rows 4 Readings Per Row 4 Total Readings 16 Location of Holes 1 Left Row 1 Row 2 Row 3 Row 4 Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 20718 Average Velocity 1299 FPM Design Airflow 2400 CFM Actual Airflow 1689 CFM Static Pressure at Traverse 0.243 in. we Location Traverse Data Points O O O O V U V V 1338 625 1159 144$ 708 I 1179 1468 11961519 1440 1777 F C-9 -81 198C 11 Farrington Air Quality Services Page 7 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-05 Unit Manufacturer Unit Model Number Unit Serial Number Unit Discharge RTU-05/SF Filter Bank Filter Type Filter Qty - S1 Filter Size - S1 Unit Data 50FCQM12BA6A8U2C0 3124P79664 Downblast Construction 4 20x2Ox2 Test Data O/A Damper Position 0 % R/A Damper Position 100 % Test Data Desian Actual Supply Airflow 4000 CFM 4360 CFM Return Airflow 4000 CFM 4047 CFM Tested By: Chris Brittenham Date: 9/10/2024 Motor Data RTU-05/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 3.00 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-05/Supply Fan Desian Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 Farrington Air Quality Services Page 8 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-05/Total Return Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 13.00 in. Duct Width 38.00 in. Air Flow Area 3.43 sq. ft. Number Of Rows 4 Readings Per Row 7 Total Readings 28 Location of Holes 1 Left Row 1 Row 2 Row 3 Row 4 Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 33032 Average Velocity 1180 FPM Design Airflow 4000 CFM Actual Airflow 4047 CFM Static Pressure at Traverse -0.222 in. we Location Traverse Data Points r N M Q N W A O O O 6 O O O U U U U U U U 525 1295 1429 1519 750 933 1-0 1301 14A4 1277 1462 1324 1336 111D 1"0 1053 1307 753 1318 990 I 462 1007 1372 1216 107D 1427 1344 1238 38 Farrington Air Quality Services Page 9 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-05/Total Supply Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 13.00 in. Duct Width 29.00 in. Air Flow Area 2.62 sq. ft. Number Of Rows 5 Readings Per Row 4 Total Readings 20 Location of Holes 1 Left Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 33219 Average Velocity 1664 FPM Design Airflow 4000 CFM Actual Airflow 4360 CFM Static Pressure at Traverse 0.215 in. we Location Log: I RTU-05/Total Supply 9/10/2024 Chris Brittenham Fans set to Medium. Row 1 Row 2 Row 3 Row 4 Row 5 Traverse Data Points O O O O U U U U 1920 1 1693 1032 F511 1913 1864 1259 1131 2062 2161 F1 5611 1401 ch 2051 1878 1822 1846 1600 197D 1881 1683 29 Farrington Air Quality Services Page 10 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-06 Unit Manufacturer Unit Model Number Unit Serial Number Unit Discharge RTU-06/SF Filter Bank Filter Type Filter Qty - S1 Filter Size - S1 Unit Data 50FTQM12B2A6A8U2CO 3124P79665 Downblast Construction 4 20x2Ox2 Test Data O/A Damper Position 0 % R/A Damper Position 100 % Test Data Desian Actual Supply Airflow 4000 CFM 4229 CFM Return Airflow 4000 CFM 3800 CFM Tested By: Chris Brittenham Date: 9/10/2024 Motor Data RTU-06/Supply Fan Motor Type Direct Drive Nameplate Motor FL Amps 3.00 Amps Nameplate Motor Hertz 60 Hz Nominal Efficiency (0.00) 0.90 % Motor Power Factor (0.00) 0.80 Motor Data RTU-06/Supply Fan Desian Nameplate Motor HP Not Listed HP Motor Voltage 460 Volts Motor Phase 3 Log: I RTU-06 9/10/2024 Chris Brittenham Fans set to Medium. Farrington Air Quality Services Page 11 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-06/Total Return Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 13.00 in. Duct Width 38.00 in. Air Flow Area 3.43 sq. ft. Number Of Rows 4 Readings Per Row 7 Total Readings 28 Location of Holes 1 Left Row 1 Row 2 Row 3 Row 4 Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 31029 Average Velocity 1108 FPM Design Airflow 4000 CFM Actual Airflow 3800 CFM Static Pressure at Traverse -0.213 in. we Location Traverse Data Points 0 0 0 0 0 0 3 U U U U U U U 1120 1387 133b 1253 1273 1283 1320 1309 1364 l"8 1dD5 1523 1165 1301 1529 1257 11% F1 U01 F10611 805 I 1124 s72 I U9 779 ® 291 I 820 38 Farrington Air Quality Services Page 12 of 16 FARRINGTON AIR QUALITY SERVICES Roof Top Unit PROJECT: Planrt Fitness Edmonds DATE: 9/11/2024 LOCATION: Edmonds, WA CONTACT: Chris Brittenham PROJECT #: 24-1120 AUTHOR: SYSTEM/UNIT: RTU-06/Total Supply Unit Data Instrument Used Pitot Tube Shape of Traverse Rectangular Duct Height 13.00 in. Duct Width 29.00 in. Air Flow Area 2.62 sq. ft. Number Of Rows 5 Readings Per Row 4 Total Readings 20 Location of Holes 1 Left Row 1 Row 2 Row 3 Row 4 Row 5 Tested By: Chris Brittenham Date: 9/10/2024 Air Data Sum of Readings 32286 Average Velocity 1614 FPM Design Airflow 4000 CFM Actual Airflow 4229 CFM Static Pressure at Traverse 0.234 in. we Location Traverse Data Points 1883 1952 1923 1952 1870 ® 1909 1661 2242 2021 1J74 1911 1427 1340 ® 1685 1769 1429 429 Flu 29 Farrington Air Quality Services Page 13 of 16 IV z �I c� N �I W W I..L O T U O i 2 Q) i U D I O 6"0 6"0 8"0 50 50 6"t� RA 150 16"/8" RA � o � ._. ,,��►� ` m i Z Y � � • � /�I, ® ., i� I �� �., �. �� 0 `. ■ i � 0 © — ...�� i 9 i 9 � m i 9 o � I 11 � � ����� -� : 9 y `1� � �� �� � TYP 100 105 CFM OSA 10"/10" RA D 10"0 175 TYP 6-PEGS 16"o EA I 12"0 600 TYP 2-PEGS t�_ 12"r� RA MENS SHOWERS � 116 WOMENS SHOWERS 113 �, � , �4� T-STAY BANK (RTU 1-5) EA o :EPTION 101 I � I � I ® � I � W / \.� W � n 1 HVAC PLAN SCALE: 1/8"=1'-0" Page 14 of 16 DOAS-1 + � I —� .�_ FUNCTIONAL TRAINING 119 <a, <_ �r, � ,�. ,.. � �� ��-�-� , ;�y BACKFLOW 120 � 18"/6" 13 TYP 4-PEGS 12.�,e����=:: Iii i� i � � �I (��^-1✓ RTU-4 7 S EXERCISE FLOOR 117 �o - yam: �� __ - J,� _, P r=== .�Ji ,� >= ___-J� __ �' � _. �,� - � --- - J,� --- STORAGE 203 CL 14"/12" RA © , � • � � r � 9 . — — — — �� I%� � � •I 12"/12" SA TYP 5-PEGS HVAC PLAN -MEZZANINE SCALE: 1/8" = 1'-0" 8"ta SA 'ACKAGED ROOFTOP AC UNIT DUCTWORK DOWN TO CONNECT TO BUSKIN ROOFTOP SYSTEMS MODEL 570 DIFFUSER. MOUNT DIFFUS �S HIGH AS POSSIBLE AT CONSISTENT HEIGHT. FOLLOW ALL /IANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE FULL SI RETURN OPENING AND COVER WITH HARDWARE CLOTH. REFER TC )ETAIL 1/M001. /IOUNT TIGHT TO STRUCTURE. DEFER TO 2/M101 FOR CONTINUATION. 'ROVIDE THERMOSTAT BANK ON WALL OF ROOM TO ALLOW ;ONTROL OF ALL MECHANICAL UNITS FROM SINGLE CENTRAL .00ATION. COORDINATE FINAL THERMOSTAT BANK LOCATION WITI 3UILDING OWNER PRIOR TO INSTALLATION. )EDICATED OUTSIDE AIR SYSTEM, FULL SIZE DUCTWORK DOWN, 'ROVIDE VOLUME DAMPER AFTER BRANCH DUCT THEN CONNECT BUSKIN ROOFTOP SYSTEMS MODEL 570 DIFFUSER. MOUNT DIFFUS �S HIGH AS POSSIBLE AT CONSISTENT HEIGHT. FOLLOW ALL /IANUFACTURERS INSTALLATION INSTRUCTIONS. 'ROVIDE FULL SIZE OPENING ON END OF DUCT AFTER VOLUME )AMPER AND BRANCH DUCT COVERED WITH HARDWARE CLOTH. /IOUNT TEMPERATURE SENSOR 72" AFF UNLESS NOTED OTHERWI: /IOUNT TRANSFER AIR GRILLE 17'-10" A.F.F. TO BOTTOM OF GRILLE. /IOUNT EXHAUST AIR GRILLE 7'-6" ABOVE MEZZANINE FLOOR TO 30TTOM OF GRILLE. )OWN TO LOWER OFFICE LEVEL PLENUM. )UCT ROUTED FROM MEZZANINE PLENUM SPACE. /IOUNT TRANSFER GRILLE 1'-0" A.F.F. TO BOTTOM OF GRILLE. A/ll I�IT TCA�ICCCC (`_CII I C i� nn DCI /l\A/ fl C!"`I! T/l T/lD /lC r_`CII I C V cn 11C� /( CHITECTURE 2948 SIDCO DR. 4N N I N G NASHV I LEE, TN 37204 ERIORS (P) 615.244.8170 APHICS (F) 615.244.8141 www.mjmarch.com � M• SC �QS��t WASy�� T�c3' ��� CTO ;� 2 �!1 � 55145 � � �GISI'F.� .�.� '.:�s�c�v�r.���, Jul 11, 2024 Jason M. Scates teamofchoice.com P.E. SUITE 5274 479-636-5004 1805 N 2ND ST JOB NO.: 3t tgg ROGERS, AR 72756 DESIGNED BY: MBO ���, � �_ �,. >.:,,,;; <- <, • • OHANA GROWTH PARTNERS 212 WEST PADONIA RD. TIMONIUM, MD 21093 PLANET FITNESS — EDMONDS 22515 HIGHWAY 99, EDMONDS, WA 98026 SNOHOMISH COUNTY PERMIT SET 0 3/0 6/2 4 MJ M # 23450 NO. DESCRIPTION DATE 2 OWNER REO. UPDATES 04/23/24 4 KIOSK UPDATES 06/05/24 This drawing and the design shown is the property of the architect. The reproduction, copying or use of this drawing without their written consent is prohibited and any infringement will be subject to legal action. HVAC F LOO R P LA N J a I..LI z Q J z O U W Z O Z O Q U O J W Q 0 z O v / W LLI LLI IV co Z I c� N �I W I Q 0 E w I C� O I T C'7 U O i 2 i i U 250 TANNING � �I L. � � r � l� l) 106 - IL �� I 11 I� I 2 2 I� I BEAUTY 107 1 BLACK CARD HVAC PLAN SCALE: 3/8" = 1'-0" Page 15 of 16 10"/10" RA 200 CFM OSA I OFFICE 102 RECEPTION 101 EXERCISE FLOOR 117 /�' H ITECTU RE 2948 SIDCO DR. V N I N G NASHVILLE, TN 37204 R I O RS (P) 615.244.8170 P H I CS (F) 615.244.8141 www.mjmarch.com � M• SC �QS�Ct WASy7� T�c3' ��� CTO ;� 2 $jj45 �� ��:� ��GISI'F.�� ; '.:�s�c�v�r.���, Jul 11, 2024 Jason M. Scates teamofchoice.com P.E. SUITE 5274 479-636-5004 1805 N 2ND ST JOB NO.: 3t tgg ROGERS, AR 72756 DESIGNED BY: MBO �� ,, . _, ,�, � - ��_ � � OHANA GROWTH PARTNERS 212 WEST PADONIA RD. TIMONIUM, MD 21093 PLANET FITNESS - EDMONDS 22515 HIGHWAY 99, EDMONDS, WA 98026 SNOHOMISH COUNTY PERMIT SET 0 3/0 6/2 4 MJ M # 23450 NO. DESCRIPTION DATE 2 OWNER REO. UPDATES 04/23/24 4 KIOSK UPDATES 06/05/24 This drawing and the design shown is the property of the architect. The reproduction, copying or use of this drawing without their written consent is prohibited and any infringement will be subject to legal action. ENLARGED HVAC PLAN J Q W z Q J z O U o� w z O z O Q U O J w 0 z O W LLI LLI DEDICATED OUTDOOR AIR SYSTEM (DOHS) WITH ENERGY RECOVERY SCHEDULE SUPPLY FAN EXHAUST FAN ENERGY RECOVERY PERFORMANCE COOLING COIL REHEATING COIL HEATING SECTION ELECTRICAL INFORMATION SUMMER WINTER OUTDOOR AIR EXHAUST AIR OUTDOOR AIR EXHAUST AIR EXTERNAL EXTERNAL ENTERING AIR TEMPS LEAVING AIR ENTERING AIR TEMP LEAVING AIR ENTERING AIR LEAVING AIR ENTERING AIR LEAVING AIR ENTERING AIR LEAVING AIR ENTERING AIR TEMPS LEAVING AIR TEMPS ENTERING AIR TEMPS LEAVING AIR TEMPS MAXIMUM MINIMUM STATIC MAXIMUM MAXIMUM STATIC TEMPS (°F) TEMPS (°F) TEMPS (°F) TEMPS (°F) (°F) (°F) (°F) (°F) (°F) TEMPS (°F) TOTAL SENSIBLE (°F) TEMP (°F) TEMP (°F) TEMP (°F) AIRFLOW AIRFLOW PRESSURE AIRFLOW AIRFLOW PRESSURE CAPACITY CAPACITY MARK LOCATION AREA SERVED MANUFACTURER MODEL (CFM) (CFM) (IN. WC) (CFM) (CFM) (IN. WC) DB WB DB WB DB WB DB WB DB WB DB WB DB WB DB WB DB WB DB WB (MBH) (MBH) DB WB DB TYPE DB DB TEMP RISE (°F) CAPACITY V / PH / HZ MCA MOCP WEIGHT NOTES DOAS-1 ROOF EXERCISE FLOOR, FUNCTIONAL CARRIER 62XM12F-JFCJHKDJBB 5640 5640 1.0 4800 4800 0.2 85 65 79 63.2 75 62.0 81.8 64.1 25.4 21.0 50.5 38.6 70.0 50.0 38.2 30.8 79.0 63.2 54.8 53.9 156.0 150.3 54.8 53.9 67.3 ELECTRIC 50.5 85.1 34.6 179.56 MBH 460 / 3 / 60 41.2 50 3710 LBS A-J TRAINING, 30 MINUTE WORKOUT GENERAL NOTES (APPLICABLE TO ALL UNITS): 1. ALL EQUIPMENT SHALL BE IN COMPLIANCE WITH THE MINIMUM REQUIREMENTS OFANSI/AHRI 920 PERFORMANCE RATING OF DX -DEDICATED OUTDOOR AIR SYSTEM UNITS. 2. EXTERNAL STATIC PRESSURE LOSSES ARE DUCT STATIC PRESSURE LOSSES EXTERNAL TO THE UNIT. MANUFACTURER TO TAKE INTO ACCOUNT INTERNAL LOSS FOR TOTAL STATIC PRESSURE CALCULATION. 3. REFER TO STRUCTURAL DRAWINGS FOR MOUNTING DETAILS. 4. CONTACT CARRIER NATIONAL ACCOUNTS, nationalaccounts@carrier.com, FOR ADDITIONAL INFORMATION FOR DEDICATED OUTDOOR AIR SYSTEMS. NOTES: A. PROVIDE WITH MERV 13 FILTERS AND BIRD SCREEN ON OUTSIDE AIR INLET. B. PROVIDE WITH 120V CONVENIENCE RECEPTACLE. C. PROVIDE WITH DISCONNECT. D. PROVIDE WITH (1) INVERTER SCROLL COMPRESSOR WITH ADDITIONAL STANDARD COMPRESSORS FOR STAGING AS REQUIRED. E. ALL CONDENSER AND EVAPORATOR COILS TO BE COATED IN COMPLIANCE WITH ASTM B117-90 5,000 HOUR SALT SPRAY TESTING. F. PROVIDE WITH 80/20 NiCr ELECTRIC RESISTANCE HEATER. G. PROVIDE WITH VARIABLE FREQUENCY DRIVE ON SUPPLY AIR FAN. H. PROVIDE WITH VARIABLE FREQUEN 3 I. PROVIDE WITH 14" TALL ROOF CUR ,WITH GC PROVIDED R-13 INSULATION IN COMPLIANCE WITH WASHINGTON STATE ENERGY CODE. J. PROVIDE WITH FACTORY INSTALLE - AIR BALANCE SCHEDULE MARK OUTSIDE AIR EXHAUST AIR NET RTU-1 0 0 RTU-2 0 0 RTU-3 0 0 RTU-4 0 0 RTU-5 0 0 RTU-6 0 0 DOAS-1 (O.A) 5640 +5640 DOAS-1 (E.A) 4800 -4800 TOTAL +840 Page 16 of 16 ROOFTOP UNIT SCHEDULE NOMINAL INDOOR SUPPLY AIR OUTSIDE AIR ESP COOLING TOTAL HEATING VOLT PHASE OPERATING MARK AREA SERVED MANUFACTURER MODEL TONNAGE FAN HP (CFM) (CFM) (IN-WG) CAPACITY(MBH) EER/SEER CAPACITY (MBH) HERTZ MCA MOCP WEIGHT (LBS) NOTES RTU-1 OFFICE CARRIER 50FCQA04 3 0.57 1200 0 0.90 36.7 - / 14.3 2.25 460 / 3 / 60 13 A 15 A 683 1 THRU 8 RTU-2 SHOWERS CARRIER 50FCQA04 3 0.57 1200 0 0.70 36.7 - / 14.3 2.25 460 / 3 / 60 13 A 15 A 683 1 THRU 8 RTU-3 BLACK CARD CARRIER 50FCQM12 10 2.36 4000 0 0.90 125.7 15.0 / - 2.25 460 / 3 / 60 30 A 35 A 955 1 THRU 8 RTU-4 CIRCUITS CARRIER 50FCQM07 6 1.3 2400 0 0.50 74.0 15.0 / - 2.4 460 / 3 / 60 18 A 25 A 792 1 THRU 8 RTU-5 EXERCISE FLOOR CARRIER 50FCQM12 10 2.32 4000 0 0.50 125.7 15.0 / - 2.25 460 / 3 / 60 30 A 35 A 955 1 THRU 8 RTU-6 EXERCISE FLOOR CARRIER 50FCQM12 10 2.32 4000 0 0.50 125.7 15.0 / - 2.25 460 / 3 / 60 30 A 35 A 955 1 THRU 8 NOTES: 1. PROVIDE RETURN DUCT MOUNTED SMOKE DETECTORS 2. PROVIDE INTERNAL DISCONNECT 3. PROVIDE FACTORY INSTALLED SERVICE RECEPTACLE 4. PROVIDE DRY BULB ECONOMIZER WITH BAROMETRIC RELIEF 3 5. PROVIDE 14" ROOF CUR ,WITH GC PROVIDED R-13 INSULATION IN COMPLIANCE WITH WASHINGTON STATE ENERGY CODE 6. PROVIDE 2" MERV 8 FILTERS 7. PROVIDE MOTORIZED OUTSIDE AIR DAMPER 8. HIGH EFFICIENCY, DOWN DISCHARGE CONFIGURATION MECHANICAL VENTILATION OUTSIDE AIR SCHEDULE CALCULATED ZONE AIR DIST. ROOM AREA CFM/PERSON CFM/ft2 REQUIRED EFFECTIVENESS ZONE O.A. PEOPLE NO. SPACE (FT2) GROSS CLASSIFICATION PER TABLE PER TABLE CFM1 CFM2 O.A. PER TABLE RATE (Az) PER OF OCCUP. (Table 403.3) (Table 403.3) (Rp�Pz) (Ra�Az) (Vbz= (Table 403.3.1.2) (Voz= 1000 ft2 (Pz) (Rp) (Ra) RpPz+RaAz) (Ez) Vbz/Ez) EXERCISE HEALTH FLOOR 11747 CLUB/WEIGHT 10 117 20 0.06 2340 705 3045 0.8 3805 ROOM HEALTH CIRCUITS 3960 CLUB/WEIGHT 10 40 20 0.06 800 238 1038 0.8 1297 ROOM BLACK CARD 1760 OFFICE SPACES 5 9 5 0.06 45 106 151 0.8 188 MEZZANINE / g62 OFFICE SPACES 5 5 5 0.06 25 58 83 0.8 104 BREAK ROOM TOTAL 5394 AIR TERMINAL SCHEDULE MARK MANUFACTURER MODEL MOUNTING STYLE DESCRIPTION FACE SIZE NECK SIZE NOTES D TITUS OMNI-AA LAY -IN ALL ALUMNIMUM SQUARE PLAQUE FACE 24" x 24" REF PLANS B, H, I DIFFUSER E TITUS OMNI-AA SURFACE MOUNT ALL ALUMNIMUM SQUARE PLAQUE FACE 24" x 24" REF PLANS A, H, I DIFFUSER I TITUS PAR -AA LAY -IN PERFORATED RETURN DIFFUSER, 24" x 24" REF PLANS B, G ALUMINUM FACE WITH STEEL BACK PAN. J TITUS PAR -AA SURFACE MOUNT PERFORATED RETURN DIFFUSER, 24" x 24" REF PLANS A, G ALUMINUM FACE WITH STEEL BACK PAN. O TITUS PAR -AA LAY -IN PERFORATED RETURN DIFFUSER, 24" x 24" REF PLANS B, G ALUMINUM FACE WITH STEEL BACK PAN. R TITUS 350FL SURFACE MOUNT ALUMINUM LOUVERED RETURN GRILLE, 3/4" --- REF PLANS C BLADE SPACING, 35 DEGREE DEFLECTION, LONG BLADES NOTES: A. PROVIDE WITH MANUFACTURER'S OPPOSED BLADE DAMPER AT NECK. B. PROVIDE WITH BALANCING DAMPER AT BRANCH TAKE OFF. LOCATE DAMPER IN ACCESSIBLE AREA. IF THERE IS NO ACCESSIBLE AREA, PROVIDE 8"x8" ACCESS PANEL. C. PROVIDE WITH FACE MOUNTED DAMPER. D. PROVIDE WITH SQUARE TO ROUND ADAPTER. E. PROVIDE WITH BLANK OFF FOR CEILING GRID. F. PROVIDE WITH MANUFACTURER'S PLENUM BOX. G. PAINT BACK PAN AND INSIDE OF DUCTWORK AT DIFFUSER BLACK UNTIL FIRST ELBOW. H. PROVIDE WITH MANUFACTUER'S MOLDED INSULATION BLANKET. I. REFER TO FLOOR PLAN FOR DIFFUSER BLANK OUTS. PROVIDE WITH FLOW ON ALL DIRECTIONS UNLESS NOTED OTHERWISE ON FLOOR PLANS. FAN SCHEDULE MOUNTING FAN EXHAUST FAN VOLT PHASE MARK AREA SERVED MANUFACTURER MODEL TYPE CFM ESP (in-wg) HERTZ MOTOR - HP CONTROL METHOD NOTES TF-1 ELECTRICAL ROOM GREENHECK CSP-A700-VG IN -LINE 760 0.25 120 / 1 / 60 1/3 T-STAY SET @ 90°F A,B,C,D,F GENERAL INFORMATION (ALL DEVICES): 1. FAN AND CURB ARE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.REF ARCH/STRUCTURE DRAWINGS FOR FRAMING AND FLASHING DETAILS. 2. FANS ARE FURNISHED WITH BACKDRAFT DAMPER, SPEED CONTROLLER, BIRDSCREEN, AND DISCONNECT. A. REFERENCE ELECTRICAL DRAWINGS FOR INFORMATION REGARDING FAN INTERLOCK. B. PROVIDE WITH 1"x1" WIRE MESH AND HARDWARE CLOTH. C. PROVIDE SPRING ISOLATORS WITH ALL -THREAD ROD FOR VIBRATION DAMPENING. D. PROVIDE THERMOSTAT FOR FAN CONTROL. E. FASTEN FAN TO ROOF CURB ON ALL SIDES WITH SCREWS. F. INSTALL PER MANUFACTURERS RECOMMENDATIONS. V cn I�` � � ARCHITECTURE PLANNING INTERIORS GRAPHICS 2948 SIDCO DR. NASHVILLE, TN 37204 (P) 615.244.8170 (F) 615.244.8141 www.mjmarch.com � M• SC �Q500t WASy7� T�c3' ��� CTO ;� 2 $j145 �� ��:� ��GISI'F.�� ; '.:�s�c�v�r.���, May 03, 2024 Jason M. Scates teamofchoice.com P.E. SUITE 5274 479-636-5004 1805 N 2ND ST JOB NO.: 3t tgg ROGERS, AR 72756 DESIGNED BY: MBO ., , "� _. � � ., ��_ � � OHANA GROWTH PARTNERS 212 WEST PADONIA RD. TIMONIUM, MD 21093 PLANET FITNESS - EDMONDS 22515 HIGHWAY 99, EDMONDS, WA 98026 SNOHOMISH COUNTY PERMIT SET 0 3/0 6/2 4 MJ M # 23450 NO. DESCRIPTION DATE 3 AHJ COMMENTS 05/03/24 This drawing and the design shown is the property of the architect. The reproduction, copying or use of this drawing without their written consent is prohibited and any infringement will be subject to legal action. HVAC SCHEDULES J Q w z Q J z O U o� w z O z O a U O J w 0 z O w w w