REV1 REVIEWED BLD2024-0361+Interior_Lighting_Summary+6.13.2024_4.24.01_PM+4321865BLD2024-0361 REVISION
COMcheck Software Version COMcheckWeb Jun 14 2024
Interior Lighting Compliance Certificatc PANT m-N
RT'T' ES
Project Information
Energy Code:
Project Title:
Project Type:
Construction Site:
22515 Highway 99
Edmonds, Washington 98026
2018 IECC
Planet Fitness Edmonds
New Construction
Owner/Agent:
Bill Flax
Ohana Growth Partners
212 West Padonia Rd.
Timonium, Maryland 21093
443-418-9019
bill.flax@ohanagp.com
Additional Efficiency Package(s)
Credits: 1.0 Required 1.0 Proposed
Reduced Lighting Power, 1.0 credit
Allowed Interior Lighting Power
A
Area Category
REVIEWED
BY
CITY OF EDMONDS
Designer/Contractor:
Jason C. Adams, P.E.
1805 N 2nd St
Rogers, Arkansas 72756
479-636-5004
jca@teamofchoice.com
B C D
Floor Area Allowed Allowed
(ft2) Watts / ft2 Watts
1-Exercise Center 22952 0.58 13427
Total Allowed Watts = 13427
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
1-Exercise Center
LED: AL10: Other:
Track Lighting: BCL5A: Wattage based on current limiting device capacity
LED: C2: Other:
LED: BECW: Other:
LED: F: Other:
LED: G: Other:
LED: H: Other:
LED: J: Other:
LED: K: Other:
LED: M02: Other:
LED: M04: Other:
LED: M05: Other:
LED: MM4: Other:
LED: 0: Other:
Exemption: Emergency lighting automatically off during normal business operation
LED: P4: Other:
LED: Q: Other:
Exemption: Emergency lighting automatically off during normal business operation
LED: SR: Other:
Exemption:Exit signs
Project Title: Planet Fitness Edmonds
Data filename:
1 55
100
5500
0 0
600
600
1 1
52
52
1 12
4
48
1 5
18
88
1 89
12
1068
1 6
12
72
1 19
21
399
1 4
45
180
1 4
10
40
1 2
10
20
1 2
10
20
1 2
5
10
1 6
3
Exempt
1 6
40
240
1 4
3
Exempt
1 7
5
Exempt
Report date: 05/30/24
Page 1 of 6
REVISION
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
LED: TR: Other:
Exemption:Exit siqns
Interior Lighting Compliance
Lamps/ # of FixttulrWJc1;924
Fixture Fixture Watt. CITY OFEDMONDS
DEVELOPMENT SERVICES
1 17 5 xemp
Total Proposed Watts = 8336
Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title
Signature
Date
Project Title: Planet Fitness Edmonds Report date: 05/30/24
Data filename: Page 2 of 6
REVISION
COMcheck Software Version COMcheckWeb Jun 14 2024
Inspection Checklist CITY OF EPARTMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Energy Code: 2018 IECC
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
& Req.ID
Plan Review
Complies?
Comments/Assumptions
C103.2
Plans, specifications, and/or
QComplies Requirement will be met.
[PR4]1
calculations provide all information
QDoes Not
with which compliance can be
❑Not Observable
determined for the interior lighting
QNot Applicable
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
C406 Plans, specifications, and/or QComplies Requirement will be met.
[PR9]1 calculations provide all information QDoes Not
with which compliance can be
determined for the additional energy QNot Observable
efficiency package options. QNot Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Planet Fitness Edmonds Report date: 05/30/24
Data filename: Page 3 of 6
REVISION
Section
# Rough -In Electrical Inspection Complies? Comments/Assumptions un 14 2024
& Req.IID CITY OF EDMONDS
C405.2.2. Spaces required to have light-
p q 9
;QCom lies Requirement will be met. utvt�u PARTMEN EtNT cts
p q DEPARTMENT
2
reduction controls have a manual
:QDoes Not
[EL22]1
control that allows the occupant to
❑Not Observable
reduce the connected lighting load in
a reasonably uniform illumination
QNot Applicable
pattern >= 50 percent.
C405.2.1, Occupancy sensors installed in
C405.2.1. classrooms/lecture/training rooms,
1 conference/meeting/multipurpose
[EL18]1 rooms, copy/print rooms,
lounges/breakrooms, enclosed offices,
open plan office areas, restrooms,
storage rooms, locker rooms,
warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor -to -ceiling height partitions.
Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
C405.2.1.
Occupancy sensors control function in L
2
warehouses: In warehouses, the L
[EL19]1
lighting in aisleways and open areas is
controlled with occupant sensors that E
automatically reduce lighting power
by 50% or more when the areas are
unoccupied. The occupant sensors
control lighting in each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
Complies :Requirement will be met.
Does Not
Not Observable
Not Applicable
Complies Exception
Does Not
Not Observable
Not Applicable
C405.2.1.
Occupant sensor control function in
QComplies
3
open plan office areas: Occupant
QDoes Not
[EL20]1
sensor controls in open office spaces
❑Not Observable
>= 300 sq.ft. have controls 1)
Applicable
configured so that general lighting can
:QNot
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) automatically turn
off general lighting in all control zones
within 20 minutes after all occupants
have left the space, 3) are configured
so that general lighting power in each
control zone is reduced by >= 80% of
the full zone general lighting power
within 20 minutes of all occupants
leaving that control zone, and 4) are
configured such that any daylight
responsive control will activate space
general lighting or control zone
general lighting only when occupancy
for the same area is detected.
Requirement does not apply.
Exception: Requirement does not apply.
C405.2.2, Each area not served by occupancy LJComplies Requirement will be met.
C405.2.2. sensors (per C405.2.1) have time- QDoes Not
1, switch controls and functions detailed ❑Tlot Observable
C405.2.2. in sections C405.2.2.1 and C405.2.2.2.
2 QNot Applicable
[EL21]z
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Planet Fitness Edmonds Report date: 05/30/24
Data filename: Page 4 of 6
REVISION
Section
#
Rough -In Electrical Inspection
Complies?
Comments/Assumptions un 14 2024
& Req.ID
CITY OF EDMONDS
Daylight zones provided with
DEVELOPMENT SERVICESC405.2.3,
�QCom lies Exception: Requirement does not apply. DEPARTMENT
C405.2.3. individual controls that control the
JETDoes Not
1, lights independent of general area
Observable
C405.2.3. lighting. See code section C405.2.3
;❑Not
;QNot Applicable
2 Daylight -responsive controls for
[EL23]2 applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
C405.2.4
Separate lighting control devices for
QComplies Requirement will be met.
[EL26]1
specific uses installed per approved
QDoes Not
lighting plans.
❑Not Observable:
QNot Applicable
C405.2.4
Additional interior lighting power
QComplies Requirement will be met.
[EL27]1
allowed for special functions per the
QDoes Not
approved lighting plans and is
❑Not Observable
automatically controlled and
'QNot Applicable
separated from general lighting.
C405.3
Exit signs do not exceed 5 watts per
QComplies :Requirement will be met.
[EL6]1
face.
QDoes Not
❑Not Observable
QNot Applicable
C405.6
Low -voltage dry -type distribution
❑Complies :Requirement will be met.
[EL26]2
electric transformers meet the
QDoes Not
minimum efficiency requirements of
❑Not Observable:
Table C405.6.
QNot Applicable
C405.
Electric motors meet the minimum
QComplies ; Requirement will be met.
[EL27]
efficiency requirements of Tables
QDoes Not
C405.7(1) through C405.7(4).
Efficiency verified through certification;
QNot Observable
under an approved certification
QNot Applicable
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
C405.8.2,
Escalators and moving walks comply QComplies Exception: Requirement does not apply.
C405.8.2.
with ASME A17.1/CSA B44 and have QDoes Not
1
[EL28]2
automatic controls configured to
reduce speed to the minimum ❑Not Observable
permitted speed in accordance with QNot Applicable
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Total voltage drop across the QComplies Requirement will be met.
C405.
[EL29]
combination of feeders and branch QDoes Not
circuits <= 5%.
❑Not Observable
QNot Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Planet Fitness Edmonds Report date: 05/30/24
Data filename: Page 5 of 6
REVISION
Section
#
Final Inspection
Complies?
Comments/Assumptions un 14 2024
& Req.ID
CITY OF EDMONDS
C303.3,
DEVELOPMENT SERVICES
Furnished O&M instructions for ;QComplies Requirement will be met. DEPARTMENT
C408.2.5.
'systems and equipment to the QDoes Not
2
building owner or designated
❑Not Observable
[F117]3
representative.
QNot Applicable
I
C405.4.1
Interior installed lamp and fixture
QComplies ;See the interior Lighting fixture schedule for values.
[FI18]1
lighting power is consistent with what
QDoes Not
is shown on the approved lighting
❑Not Observable:
plans, demonstrating proposed watts
QNot Applicable
are less than or equal to allowed
watts.
_
QComplies Requirement will be met.
C408.1.1
Building operations and maintenance
[F157]1
documents will be provided to the
QDoes Not
owner. Documents will cover
❑Not Observable
manufacturers' information,
QNot Applicable
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
C408.2.5.
Furnished as -built drawings for
QComplies :Requirement will be met.
1
electric power systems within 90 days
QDoes Not
[FI16]3
of system acceptance.
bNot Observable
QNot Applicable
C408.3
Lighting systems have been tested to
QComplies :Requirement will be met.
[F133]1
ensure proper calibration, adjustment,
QDoes Not
programming, and operation.
QNot Observable:
QNot Applicable
Additional Comments/Assumptions:
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Planet Fitness Edmonds Report date: 05/30/24
Data filename: Page 6 of 6