BLD2024-0977+WAIVER REQ+7.27.2024_4.23.38_PM+4405610RECEIVED LCH0025LBACZA0200 - SUBMITTAL
Jul 29 2024
L CITY OF E DEVELOPMENT
DEVSERVICES
DEPARTMENT
BLD2024-0977
Project Name:
Project Location:
Quote ID:
Item A,
1000
Submitted For.,
Submitted On:
Submitted By.,
Submitted From:
Identity #:
Tag:
❑ For Record ❑ For Approval By: Date:
Product Family:
LCH
Compressor Brand:
Copeland
Application:
Outdoor
Compressor Type:
Scroll
Temperature Range:
Low Temp
Compressor Hp:
2.5
Voltage: (Volts/Ph/Hz)
208-23011160
Compressor Model.,
ZF08K4E-PFV-231
Refrigerant Type:
R404A
Number of Compressor(s):
1
Piping:
Standard
Coil Type:
Microchannel
NOTE: THIS EQUIPMENT IS PROHIBITED FROM USE IN CALIFORNIA WITH ANY REFRIGERANTS ON THE "LIST OF PROHIBITED SUBSTANCES" FOR THAT SPECIFIC END -USE, IN ACCORDANCE WITH CALIFORNIA
CODE OF REGULATIONS, TITLE 17, SECTION 95374. THIS DISCLOSURE STATEMENT HAS BEEN REVIEWED AND APPROVED BY HEATCRAFT REFRIGERATION PRODUCTS LLC AND HEATCRAFT REFRIGERATION
PRODUCTS LLC ATTESTS, UNDER PENALTY OF PERJURY, THAT THESE STATEMENTS ARE TRUE AND ACCURATE.
Technical Information
PerformanceData
Ambient Saturated Suction Capacity
Altitude AWEF Value
Temperature (°F)
Temperature (°F) (BTU/H)
(ft)
95
-10.0 11.970
0 3.15
HIMM•. .
Compressor(s)
Fan Motor(s)
Electric Ratings
RLA
LRA
Quantity
Hp
FLA
Defrost
High or
Number of
MCA
MOPD
Evap.Fan
Defrost
Type
Low Amps?
Contactors
Amps
Heater
Amps
14.7
73
2
1115
1
ELECTRIC DEFROST
NA
37.5
40
10
30
Connections (in.)
Receiver 90% Full (Ibs)
Fan Blade(s)
Approx. Net
Diameter
Sound Data
Weight
Liquid Line
Suction
Standard
Over Sized
(in)
(dB)
(Ibs)
230
0.5
0.875 14.0
20.0
14
64
Dimensional Drawing(s)
AGENCY LISTINGS
o UL us
�285/16
LIQUID
SUCTION
AIR FLOW
3 3/16
19 3/4
y
6 5/16
I IS/16
- 38 3/8 IL
2 3/4
23 I/2 CL
39 1 /8
3
UOM- inches
2 I/16
4 I I/16
Page 1 of 2
LCH0025LBACZ40200 - SUBMITTAL
LARKIN
Project Name:
Project Location:
Quote ID:
Item Al
1000
Submitted For.,
Submitted On:
Submitted By.,
Submitted From:
Identity A:
Tag:
CABINET AND CONSTRUCTION
• MICROCHANNEL COIL TECHNOLOGY STANDARD ON ALL UNITS
PAINTED STEEL CABINETS FOR SUPERIOR STRENGTH AND CORROSION
PROTECTION
HEAVY DUTY, STEEL, 1-1/2 TALL BASE
QUALITY
ALL UNITS ARE COMPLETELY LEAK TESTED IN A HELIUM ENVIRONMENT, BUMP
TESTED AND ALLOWED TO CYCLE OFF ON THE HIGH AND LOW PRESSURE
CONTROL. EACH UNIT HAS A COPY OF THE RUN DATA SHIPPED INSIDE THE
ELECTRICAL PANEL
• ELECTRICAL CIRCUITS ARE COMPLETELY CHECKED FOR CONTINUITY
PIPING IS LAID OUT TO MINIMIZE STRESS AND VIBRATION AND IS PRE -BENT TO
ELIMINATE LEAKS
ENCAPSULATED, AUTO -RESET, HIGH AND LOW PRESSURE CONTROLS TO
ELIMINATE LEAKS (ADJUSTABLE LOW PRESSURE CONTROL STANDARD)
Brand Label - LARKIN
• Motor - FIXED SPEED EC
Receiver Options - STANDARD
Liquid Line Options - FILTER DRIER AND SIGHT GLASS
• Discharge Line Options - HEAD PRESSURE VALVE 100#
Fused Disconnect - NO FUSED DISCONNECT
• Crankcase Heater - CRANKCASE HEATER
Pre Charged - NONE
• Hail Guard Factory Installed - NONE
Walls or Obstructions for
Horizontal Air Flow
AIR W*
FLOW MIN.
SERVICEABILITY
SUCTION SERVICE VALVES FOR HERMETIC AND SCROLL COMPRESSORS
LOCATED OUTSIDE THE CABINET FOR QUICK INSTALLATIONS.
RECEIVER WITH FUSIBLE PLUG, LIQUID SHUTOFF VALVE AND CHARGING PORT
IS STANDARD
LARGE ELECTRICAL PANEL FOR EASE OF ACCESS
PREFABRICATED WIRING HARNESSES FOR TIGHT CRIMP CONNECTIONS AND
CONSISTENT LABELING
UNIT STAYS ON IF THE HOOD IS REMOVED FOR SERVICING
SIGHT GLASS IS EASILY VIEWABLE
Brand Label from Table - N/A
• Coil Selection - MICROCHANNEL COIL
Defrost Timer Options - ELECTRIC DEFROST TIMER
Suction Line Options - SUCTION TUBE ONLY
Cabinet Selection - Painted
Pressure Options - ADJUSTABLE LOW - FIXED HIGH
• Phase Loss Monitor - NONE
Snow Legs - NONE
• ETD ID - N/A
Multiple Units with Horizontal Air Flow
AIR FLOW AIR FLOW
1
*W = F_ W* _
unit width MIN.
W* MIN. W* MIN.
4 �
Page 2 of 2