REVIEWBLD2024-0977+Manufacturer_Specifications_and_Installation_Instructions+7.27.2024_4.23.27_PM+4405609RECEIVED
LCH0008MBACZ40000 -
Jul 29 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
LARKIN
REVIEWED
BY
CITY OF EDMONDS
El For Record El For PLproval
BLD2024-0977 SUBMITTAL
Project Name:
Project Location:
Quote ID:
Item A,
1000
Submitted For:
Submitted On:
Submitted By:
Submitted From:
Identity A-
Tag:
By:
Product Family:
LCH
Compressor Brand.,
Copeland
Application:
Outdoor
Compressor Type:
Scroll
Temperature Range:
Medium Temp
Compressor Hp:
0.8
Voltage: (Volts/Ph/Hz)
208-23011160
Compressor Model.,
ZB07KAE-PFV
Refrigerant Type:
R404A
Number of Compressor(s):
1
Piping:
Standard
Coil Type:
Microchannel
NOTE: THIS EQUIPMENT IS PROHIBITED FROM USE IN CALIFORNIA WITH ANY REFRIGERANTS ON THE "LIST OF PROHIBITED SUBSTANCES" FOR THAT SPECIFIC END -USE, IN ACCORDANCE WITH CALIFORNIA
CODE OF REGULATIONS, TITLE 17, SECTION 95374. THIS DISCLOSURE STATEMENT HAS BEEN REVIEWED AND APPROVED BY HEATCRAFT REFRIGERATION PRODUCTS LLC AND HEATCRAFT REFRIGERATION
PRODUCTS LLC ATTESTS, UNDER PENALTY OF PERJURY, THAT THESE STATEMENTS ARE TRUE AND ACCURATE.
Technical Information
Ambient
Saturated Suction
Capacity
Altitude
AWEF Value
Temperature (T)
Temperature (T)
(BTU/H)
(ft)
95
25.0
8.980
0
7.6
Compressor(s)
Fan Motor(s)
Electric Ratings
RLA
LRA
Quantity
Hp
FLA
Defrost
High or
Number of
MCA
MOPD
Evap.Fan Defrost
Type
Low Amps?
Contactors
Amps Heater
Amps
5.6
48
1
1115
0.5
AIR DEFROST
NA
15
15
5 15
Connections (in.) Receiver 90% Full (Ibs)
Fan Blade(s) Approx. Net
Sound Data
Diameter Weight
Liquid Line Suction Standard Over Sized
(dB)
(in) (Ibs)
0.375 0.625 9.0
14 61 168
Dimensional Drawing(s)
1 1
AGENCY LISTINGS
e UL us
28 1/2
LIQUID
AIR FLOW --W
SUCTION 19 3/n 6 3/e
3
6 5/16
3 3/16
�q
13/4
23
2 3/16
UOM- inches
Page 1 of 2
LCH0008MBACZ40000 -
LARKIN
SUBMITTAL
Project Name:
Project Location:
Quote ID:
Item A,
1000
Submitted For:
Submitted On:
Submitted By:
Submitted From:
Identity #:
Tag:
CABINET AND CONSTRUCTION
• MICROCHANNEL COIL TECHNOLOGY STANDARD ON ALL UNITS
PAINTED STEEL CABINETS FOR SUPERIOR STRENGTH AND CORROSION
PROTECTION
HEAVY DUTY, STEEL, 1-1/2 TALL BASE
QUALITY
ALL UNITS ARE COMPLETELY LEAK TESTED IN A HELIUM ENVIRONMENT, BUMP
TESTED AND ALLOWED TO CYCLE OFF ON THE HIGH AND LOW PRESSURE
CONTROL. EACH UNIT HAS A COPY OF THE RUN DATA SHIPPED INSIDE THE
ELECTRICAL PANEL
• ELECTRICAL CIRCUITS ARE COMPLETELY CHECKED FOR CONTINUITY
PIPING IS LAID OUT TO MINIMIZE STRESS AND VIBRATION AND IS PRE -BENT TO
ELIMINATE LEAKS
ENCAPSULATED, AUTO -RESET, HIGH AND LOW PRESSURE CONTROLS TO
ELIMINATE LEAKS (ADJUSTABLE LOW PRESSURE CONTROL STANDARD)
Brand Label - LARKIN
• Motor - FIXED SPEED EC
Receiver Options - STANDARD
Liquid Line Options - FILTER DRIER AND SIGHT GLASS
• Discharge Line Options - HEAD PRESSURE VALVE 150#
Fused Disconnect - NO FUSED DISCONNECT
• Crankcase Heater - CRANKCASE HEATER
Pre Charged - NONE
• Hail Guard Factory Installed - NONE
Walls or Obstructions for
Horizontal Air Flow
AIR _ W*
FLOW MIN.
SERVICEABILITY
SUCTION SERVICE VALVES FOR HERMETIC AND SCROLL COMPRESSORS
LOCATED OUTSIDE THE CABINET FOR QUICK INSTALLATIONS.
RECEIVER WITH FUSIBLE PLUG, LIQUID SHUTOFF VALVE AND CHARGING PORT
IS STANDARD
LARGE ELECTRICAL PANEL FOR EASE OF ACCESS
PREFABRICATED WIRING HARNESSES FOR TIGHT CRIMP CONNECTIONS AND
CONSISTENT LABELING
UNIT STAYS ON IF THE HOOD IS REMOVED FOR SERVICING
SIGHT GLASS IS EASILY VIEWABLE
Brand Label from Table - N/A
• Coil Selection - MICROCHANNEL COIL
Defrost Timer Options - NO TIMER
Suction Line Options - SUCTION TUBE ONLY
Cabinet Selection - Painted
Pressure Options - ADJUSTABLE LOW - FIXED HIGH
• Phase Loss Monitor - NONE
Snow Legs - NONE
• ETD ID - N/A
Multiple Units with Horizontal Air Flow
AIR FLOW AIR FLOW
*W = W* _
unit width F+ MIN.
W* MIN. W* MIN.
4 �
Page 2 of 2