APPROVED FIR2024-0056+Fire_Alarm_Plan+7.8.2024_11.31.22_AM+4361843Y
Klepps
b + Fire Alarm a Automation
J
224th StSW
3
a LJ
n r
2 2 5 5 FLANET f ITNE55
9e Q/Ranchrket 9
QMega CIi
85°C Be - Ed5 onds
9
Factory Direct Tire Pros Izon a Factory Direct 225th PI sw
ch to Tire Pros
:on and Save
EDMOND5, WA 9802G . .. ............... . .......
a —
r* s
28th st sw 228th St SW
k VICINITY MAP
Fire Alarm Device Numbering
(5LC) ADDRESSABLE DEVICES
NOTIFICATION DEVICES
SPEAKERS * SPEAKER/ STROBES
CIRCUIT
CIRCUIT
DEVICE #
CIRCUIT
DEVICE ADDRESS
DEVICE #
CANDELA
WATT SETTING @ (70VRM)
CANDELA
J
NAC # • ### / \ ## CD
NAC # • ### ## CD #.## W
DEVICE INSTALLATION REQUIREMENTS
AUDIO 4 VISUAL DEVICES G" MIN
HVAC SUPPLY
DIFFjUHF
3'MII1 tY FINISHED CEILING
3' MIN
:OM CEILING
SMOKE/HEAT SMOKE/HEAT DETECTOR
DETECTOR PERMITTED HERE
5MOKE/HEAT DETECTOR
NOT PERMITTED HERE —
SMOKE/HEAT DETECTOR
PERMITTED HERE
FIRE ALARM SYSTEM CABLE SCHEDULE MANUAL
PALL
STATION
RE
CABLE CABLE NO. OF CONDUCTORS COLOR AWG CABLE USE ACP FIGHTER FIGHT R
TAG nuclnro PFIONE HANDSET
CABINET
INGENESIS 1 PAIR NON -SHIELDED RED/BLACK #14 BUILDING NOTIFICATION (NAC) ao"MIN 9 w 3' ' W
PULL
96" MAX o
O
A GENESIS 1 PAIR NON -SHIELDED RED/BLACK #18 SIGNAL LINE CIRCUIT (SLC)
72"AFF 72"AFF 72"AFF
GO AFF
PLINK GENESIS 2 PAIR NON -SHIELDED RED/BLACK _ BLUE/BROWN #14 BUILDING ANNUNCIATION (ANN) I I I I FI 48° AFF
PHONE
JACK
SYMBOL
CITY
MANUFACTURER
PART NO
DESCRIPTION
INTELLINET 2.0 FIRE SUBSCRIBER, 4X4 ZONE (4 REVERSING POLARITY,
DACT
1
AES
7707P-44-ULP-M
4 SUPERVISED) WITH 7794A AES-INTELLIPRO, AND INTEGRATED
ONBOARD LOCAL ANNUNCIATOR PLUS MCT, RED ENCLOSURE
FACU
1
POTTER
AFC-1000
FIRE ALARM CONTROL PANEL
FAA
1
POTTER
RA-6500
160 CHARACTER LCD ANNUNCIATOR
�F
1
POTTER
PAD100-PSDA
ADDRESSABLE PULL STATION DUAL ACTION
AIM 2
4
POTTER
PAD100-DIM
DUAL INPUT MODULE
AIM
1
POTTER
PAD100-SIM
SINGLE INPUT MODULE
A0^^
1
POTTER
PAD100-RM
RELAY MODULE
PAD300-DUCTR
R
6
POTTER
W/PAD300-DD
ANALOG ADDRESSABLE DUCT DETECTOR W/ RELAY
0
1
POTTER
PAD200-PD
PHOTOELECTRIC SMOKE DETECTOR WITH 6" STANDARD BASE
W/PAD100-6DB
o C
18
EATON WHEELOCK
ELHSRC
CEILING HORN STROBE, RED, FIRE
�' C
12
EATON WHEELOCK
ELSTRC
CEILING STROBE, RED, FIRE
Approved
DFM akyr & Burt
South County Fire
Date: 07/09/2024
07-09-2024
PLAN REVIEW
NOTES: APPROVED
WITH CONDITIONS
NOTED ON SHEET
FA2.0.
DFM BURT
NOT
PERMITTED
HERE
PROJECT NOTES
- INSTALL AN ADDRESSABLE FIRE ALARM SYSTEM IN A
COMMERCIAL BUILDING IN EDMOND5
- BUILDING 15 FULLY 5PRINKLERED.
J
O
0
O
�
U
U
Z _
Lu
0
H
z
O
_J
¢o
�w
0�
O
LU
C��
(Dw
Fn
of
LU
i
OfO
Co
m:�i
Q
O_Oct)
U
O
N Q
Q
ofLU
U
Q o
a_LU
z
Z:)Z
w
U
H
Q
U
Q
Q
Z
O
O F- Q J
Z O 3 a U a OME ME
Z
o¢ �c) mc) O)0 0w
�Z QO �O >L7 F-Q
2Q JZ OZ C�Z ZZ
U) U) QCY �� LU
2Q
QZ �O �O �O cn=
�= cq=00
O LL z 0 O ~ O m Q
92 zMi W2 o
F-
c�
F-
SYSTEM INPUTS
FACP MANUAL PULL STATION
FACP SMOKE DETECTOR
WATERFLOW SWITCH
SUPERVISORY SWITCHES
DUCT SMOKE DETECTORS
INITIATING CIRCUIT CONDITIONS:
OPEN WIRE
GROUNDED WIRE
SHORTED WIRES
NOTIFICATION CIRCUIT CONDITIONS:
OPEN WIRE
GROUNDED WIRE
SHORTED WIRES
'ANEL POWER LOSS
'ANEL LOW BATTERY
;EMOTE STATION DACT FAILURE
GENERAL NOTES / SCOPE OF WORK
1. FACTORY RECOMMENDED MINIMUM WIRING 51ZE5, TYPE AND
CONSTRUCTION A5 NOTED ON THE DRAWINGS MUST BE
STRICTLY FOLLOWED. ANYONE WILLING TO MAKE CHANGES WILL
DO 50 AT THEIR OWN RISK!!
2. WHEN POWERING UP THE FACP OR REMOTE POWER SUPPLIES
BE SURE TO APPLY AC VOLTAGE BEFORE DC VOLTAGE. WHEN
POWERING DOWN REMOVE DC SUPPLY BEFORE AC
DISCONNECT.
3. THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR
PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON
CONTINUOUS AND SHORTEST P055IDLE ROUTING FROM THE
CONTROL PANEL AND BETWEEN CONNECTED FIELD DEVICES WITH
NO PHY51CAL OBSTRUCTIONS. THE WIRING OR CIRCUIT COUNTS
(IF SHOWN) ARE PROVIDED A5 A CONVENIENCE ONLY AND A5
MEANS TO HASTEN INSTALLATION OR TO DETERMINE WIRING
ROUTES.
4. WIRE SHOWN IN TH15 DRAWING SET 15 PERMITTED IN
RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER
WIRE SHALL NOT BE PERMITTED.
5. PER NFFA 72-201 G, DETECTORS SHALL NOT BE INSTALLED
UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES 15
COMPLETE AND FINALED.
G. ALL WIRING, CABLE, AND EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 70,NATIONAL ELECTRICAL CODE,
ARTICLE 7GO, 770, 760, AND NFFA 72, FIRE PROTECTIVE
SIGNALING SYSTEMS.
7. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A 3'0"
RADIUS OF SUPPLY -AIR DUCTS. NFFA 72-201 G.
6. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH
THE LATEST U.L., N.E.C., N.F.P.A., W.A.C., AND OTHER
STANDARDS A5 APPLICABLE TO THE CITY STANDARDS.
City Of Edmonds
Building Department
Work FIRE ALARM MODIFICATION
Address 22515 HIGHWAY 99
Owner PLANET FITNESS
Approved Date
Building Official
------------ --
Permit Number FIR2024-0056
13330 SE 30th St
Bellevue WA 98005
(425) 223-3164 Fax: (425) 223-3165
Lic. #: KLEPPI"938C6
� � A
m a�C�C�4 0
LEVEL IV
GN ENGINEER
EXPIRES: 11/01/2024
PROJECT NAME
CV
LLLJ
z
�—
Ln
o
z
Ln
0
Q
CV
C)
JOB # 240GO37
DATE: G12112024
Um m m m m m m m
U U U U U U U U
m � � � � U_ LU �
n
z
O
� W
LU
ry w
U
z
Q
O
SHEET L15T
FA 1.0 COVER SHEET
FA2.0 GROUND FLOOR
* MEZZANINE
FA3.0 RISER DIAGRAM
FA4.0 CALCULATIONS
Jul 08 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
SHEET DESCRIPTION
COVER
SHEET
SHEET NUMBER
SEQUENCE OF OPERATION MATRIX
fA1.0
E6
E5
E3
C
E.6
C
C
C
C
C
3.8 3.5
\ 2 /
0
EXT STORAGE
29
STORAGE
za
a
RES OM
BREAK
n02
BACKFLOW
120
zs
11
N1.03
AIM
01
15cd
15cd
C
C
a
CA OSET�
OMS 15cd
tzs
BACKR
J12:11
Nl-05
Nl-06
777K
75cd
c
75cd
C
STORAGESTORA
E
iza
12a
Ll-01311
R g
a
STRETCH & MOBILITY
„e _J
750d
FUNCTIONAL TRAINING
111 s I
c
R
S
MENS LOCKERS
t15
L1.015
R
s
N2.02
�
N 1.OS
w
C
110cd
�
C
N1.07
75
110cd
C Z
C
w
UTILITY
LJ
q2.0
15cd
C
W
O
EXER
ISE FLOOR
1n
BOX
c
N1.10 EOL
110cd
Nl-09
C
110cd
C
WOMENS
LOCKEl
721
N3.02
15cd
N3.01 C
15G MA S GE
, O6 1 55
N3.04
17
BEAUTY 15cd BC SPA
104
16
L
•017
N3 03 C
R
R
S
S
15cd
C
N3.05
15cd N3.06
CH Y D 75cd
108 C
N3.07
15cd HYDRO N3.12
75cd 75cd
C 111 110cd
TA C C
1o9N3• 3
15c LF° RECEPTION
N3.13 BOX
101
110cd
C
TAN ING
110 FIC[N3.10
0z 15cd
N3.09 IT C
15cd 103 a VESTIBULE
C ,00
Ll-018
AOM FAA P-LINK•1
CONDITION:
LOCATE FAA TO
aHOME RUN TO
FACP
VESTIBULE.
aTONEXT
■❑
N0 8' 16, 24'
1 FIRST FLOOR FIRE ALARM Scale: 3/32" = 1'-0"
n
a3 FROM PREVIOUS
CONDITION:
INSTALL
DOCUMENT
CABINET
3.8 3.5
►�R.�11111II1111�11�
�'''''I
•-•
a HOME RUN TO FACP
a TO NEXT
a3 FROM PREVIOUS
N0 816' 24'
2 MEZZANINE FIRE ALARM ► scale: 3/32" = 1'-0"
Scale: 3/32" = 1' a
SYMBOL
DESCRIPTION
INTELLINET 2.0 FIRE SUBSCRIBER, 4X4 ZONE (4 REVERSING POLARITY,
DACT
4 SUPERVISED) WITH 7794A AES-INTELLIPRO, AND INTEGRATED
ONBOARD LOCAL ANNUNCIATOR PLUS MCT, RED ENCLOSURE
FACU
FIRE ALARM CONTROL PANEL
FAA
160 CHARACTER LCD ANNUNCIATOR
ADDRESSABLE PULL STATION DUAL ACTION
AIM 2
DUAL INPUT MODULE
AIM
SINGLE INPUT MODULE
AOM
RELAY MODULE
�s R
ANALOG ADDRESSABLE DUCT DETECTOR W/ RELAY
0
PHOTOELECTRIC SMOKE DETECTOR WITH 6" STANDARD BASE
CEILING HORN STROBE, RED, FIRE
C
CEILING STROBE, RED, FIRE
Klegs
Y
( + Fire Alarm a Automation
13330 SE 30th St
Bellevue WA 98005
(425) 223-3164 Fax: (425) 223-3165
Lic. #: KLEPPI"938C6
� � A
LEVEL IV
GN ENGINEER
EXPIRES: 11/01/2024
PROJECT NAME
CV
LLLJ
z
�-
L
z
Ln
�
nJ
CL_
C)
JQB # 240GO37
DATE: G/2 1 /2024
U m m m 7--7-
m m
U
U U TM
UU_Jw w w w w
LU N
Q O
<N9
O
SHEET LIST
FA 1.0 COVER SHEET
FA2.0 GROUND FLOOR
� MEZZANINE
FA3.0 RISER DIAGRAM
FA4.0 CALCULATIONS
SHEET DESCRIPTION
GROUND FLOOR
AND MEZZANINE
FI RE ALARM
SHEET NUMBER
fA2.0
SYMBOL I DESCRIPTION
Klegs
Y
+ Fire Alarm a Automation
z
z
z
N3.13 EOL N3.12 113.11 N3.10 N3.09 N3.08
N3.07 N3.06
N3.05
N3.04 N3.03
N3.02 N3.01 z
z
110cd 1100d 75cd 15cd 15cd 150d
C C C C C C
15cd 750d
C C
15cd
C
15cd 15cd
C C
150d 150d
C C �Z
N W
i N N
N
N N
N N
z
Z
N2.06 EOL N2.05 N2.04 N2.03 N2.02 N2.01
30cd 75cd 15cd 750d 30cd 75cd
C C C C C C
N N N N N z
N1.10 EOL N1.09 N1.08 N1.07 N1.06 N1.05 N1.04 N1.03 N1.02 N1.01 z
110cd 110cd 110cd 1100d 75cd 75cd 15cd 15cd 15cd 15cd
C C C C C C C C C C
N N N
INTELLINET 2.0 FIRE SUBSCRIBER, 4X4 ZONE (4 REVERSING POLARITY,
DACT SUPERVISED) WITH 7794A AES-INTELLIPRO, AND INTEGRATED
ONBOARD LOCAL ANNUNCIATOR PLUS MCT, RED ENCLOSURE
FACU FIRE ALARM CONTROL PANEL
lwl 1160 CHARACTER LCD ANNUNCIATOR
ADDRESSABLE PULL STATION DUAL ACTION
AIM 2 DUAL INPUT MODULE
AIM SINGLE INPUT MODULE
AOM RELAY MODULE
( R ANALOG ADDRESSABLE DUCT DETECTOR W/ RELAY
13330 SE 30th St
Bellevue WA 98005
(425) 223-3164 Fax: (425) 223-3165
Lic. #: KLEPPI*938C6
U
EXPIRES: 11/01/2024
PROJECT NAME
O PHOTOELECTRIC SMOKE DETECTOR WITH 6" STANDARD BASE
CEILING HORN STROBE, RED, FIRE
C
C CEILING STROBE, RED, FIRE
V J
W
�
�
z
�-
Lo
zL
J
�
JOB # 2400037
DATE: G12112024
m w w w w w w w w
n
Z
O
w
U�
LU
r w
U
1/01 •01 EOL
15cd
z
Q
C
-1
O -Nm�t LnU 00
L1.003
L1.002 R
L1.001 FACP RTU 1
5HEET LI
F S S A
FA I .0 COVER SKEET
MEZZANINE FA2.0 GROUND FLOOR
P-LINK•1 * MEZZANINE
m
FA3.0 RISER DIAGRAM
D
FA4.0 CALCULATIONS
D
D
D
D
L1.004-005 L1.006-007 L1.008-009 L1.010-011 L1.013 L1.014 L1.015 L1.016 L1.017
2 2 2 2 L1.012 R R R R R L1.018
SPRINKLER MONITOR n SPRINKLER MONITOR SPRINKLER MONITOR SPRINKLER MONITOR BACKFLOW RTU 4 RTU 5 RTU 2 RTU 3 RTU 6 FAN SHUTDOWN
AIM A A CAI A S S S S S
GROUND FLOOR
SHEET DESCRIPTION
FIRE ALARM MISER
1 FIRE ALARM RISER
Scale: N.T.S
SHEET NUMBER
fA3.0
KWpps
Fire Afarm&Automation
BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT =10A
TOTAL USED CAPACITY (IN ALARM) = 1.90394A (19.04 %)
STANDBY CURRENT (AMPS)
SECONDARY ALARM CURRENT (AMPS)
QTY
PART NO.
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL
PANEL COMPONENTS
1
AFC-1000 Main Board
Fire Alarm Control Panel
0.13
0.13
0.22
0.22
Main Board
CIRCUIT
SYMBOL
QTY
PART NO
DESCRIPTION
CURRENT DRAW (A)
TOTAL (A)
CURRENT DRAW (A)
TOTAL (A)
CEILING HORN STROBE,
I/01
0�
C
1
ELHSRC
RED, FIRE 15cd
0
0
0.037
0.037
AIM 2
4
PAD100-DIM
Dual Input Module
0.00024
0.00096
0.00024
0.00096
❑F
1
PAD100-PSDA
Addressable Pull Station
0.0002
0.0002
0.0002
0.0002
Dual Action
1
PAD100-RM
Relay Module
0.00024
0.00024
0.00024
0.00024
L1
AIM
1
PAD100-SIM
Single Input Module
0.00024
0.00024
0.00024
0.00024
PAD200-PD
Photoelectric Smoke
OS
1
w/PAD100 6DB
Detector with 6" Standard
0.0003
0.0003
0.0003
0.0003
Base
PAD300-DUCTR
Analog Addressable Duct
s R
6
w/PAD300-DD
Detector W/ Relay
CEILING HORN STROBE,
0.0005
0.003
0.0005
0.003
o�3
C
ELHSRC
RED, FIRE 15cd
0
0
0.037
0.111
CEILING HORN STROBE,
C
2
ELHSRC
RED, FIRE 75cd
0
0
0.077
0.154
N1
CEILING HORN STROBE,
C
4
ELHSRC
RED, FIRE 110cd
0
0
0.109
0.436
1
ELSTRC
CEILING STROBE, RED,
0
0
0.022
0.022
C
FIRE15cd
CEILING HORN STROBE,
C
2
ELHSRC
RED, FIRE 30cd
0
0
0.046
0.092
CEILING HORN STROBE,
o
1
ELHSRC
RED, FIRE 75cd
0
0
0.077
0.077
N2
C
1
ELSTRC
CEILING STROBE, RED,
0
0
0.022
0.022
C
FIRE 15cd
2
ELSTRC
CEILING STROBE, RED,
0
0
0.06
0.12
C
FIRE 75cd
CEILING HORN STROBE,
C
2
ELHSRC
RED, FIRE 15cd
0
0
0.037
0.074
CEILING HORN STROBE,
o�
C
1
ELHSRC
RED, FIRE 75cd
0
0
0.077
0.077
N3
CEILING HORN STROBE,
C
2
ELHSRC
RED, FIRE 110cd
0
0
0.109
0.218
b�
7
ELSTRC
CEILING STROBE, RED,
0
0
0.022
0.154
C
FIRE 15cd
1
ELSTRC
CEILING STROBE, RED,
0
0
0.06
0.06
C
FIRE 75cd
P-LINK
NI
1
RA-6500
160 Character LCD
0.02
0.02
0.025
0.025
Annunciator
TOTAL STANDBY (A)
0.15494
TOTAL ALARM (A)
1.90394
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A)
0.15494
24
3.72
SECONDARY ALARM LOAD (A)
1.90394
0.08
0.16
STANDBY AND ALARM SUBTOTAL (AMP HOURS)
3.88
DERATING FACTOR
1.2
SECONDARY LOAD REQUIREMENTS (AMP HOURS)
4.65
PROVIDE (2)12V 8AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
I/01 POINT-TO-POINT REPORT
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.01
Min. Operational Voltage:
16
End Of Line Voltage:
20.39
Max. Circuit Current (A):
1
Voltage Drop Percent:
0.03 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.037
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
26
Spare Current (A):
0.963
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (.0):
0.158107
Spare Current (A) Percent:
96.30 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous
(a)
Voltage Drop From
Previous
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
1/01 •01 EOL ELHSRC CEILING HORN STROBE, 0.037 0.037 26 0.158107 0.01 20.39 0.01 0.03 %
RED, FIRE 15cd
Calculation Methods:
Resistance From Previous (.0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
1.18
N1 POINT-TO-POINT REPORT
Min. Operational Voltage:
16
End Of Line Voltage:
19.22
Max. Circuit Current (A):
3
Voltage Drop Percent:
5.81 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.723
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
429
Spare Current (A):
2.277
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (.0):
2.633966
Spare Current (A) Percent:
75.90 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous
Voltage Drop From
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
(a)
Previous
CEILING HORN STROBE,
N1.01
ELHSRC
RED, FIRE 15cd
0.037
0.723
82
0.502407
0.36
20.04
0.36
1.78 %
CEILING HORN STROBE,
Nl-02
ELHSRC
RED, FIRE 15cd
0.037
0.686
12
0.0713
0.05
19.99
0.41
2.02 %
Nl-03
ELSTRC
CEILING STROBE, RED,
0.022
0.649
24
0.148415
0.1
19.89
0.51
2.49 %
FIRE 15cd
CEILING HORN STROBE,
Nl-04
ELHSRC
RED, FIRE 15cd
0.037
0.627
11
0.069586
0.04
19.85
0.55
2.71 %
CEILING HORN STROBE,
Nl-05
ELHSRC
RED, FIRE 75cd
0.077
0.59
32
0.198151
0.12
19.73
0.67
3.28 %
CEILING HORN STROBE,
Nl-06
ELHSRC
RED, FIRE 75cd
0.077
0.513
49
0.298589
0.15
19.58
0.82
4.03 %
CEILING HORN STROBE,
Nl-07
ELHSRC
RED, FIRE 110cd
0.109
0.436
52
0.317028
0.14
19.44
0.96
4.71 %
CEILING HORN STROBE,
Nl-08
ELHSRC
RED, FIRE 110cd
0.109
0.327
56
0.34235
0.11
19.33
1.07
5.26 %
CEILING HORN STROBE,
N1-09
ELHSRC
RED, FIRE 110cd
0.109
0.218
56
0.34379
0.07
19.25
1.15
5.62 %
CEILING HORN STROBE,
N1.10 EOL
ELHSRC
RED, FIRE 110cd
0.109
0.109
56
0.34235
0.04
19.22
1.18
5.81 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (Q/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
0.36
N2 POINT-TO-POINT REPORT
Min. Operational Voltage:
16
End Of Line Voltage:
20.04
Max. Circuit Current (A):
3
Voltage Drop Percent:
1.79 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.311
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
265
Spare Current (A):
2.689
Distance measured using drawn segment lengths with 10.00
% additional length calculated
Total Circuit Resistance (0):
1.62547
Spare Current (A) Percent:
89.63 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous
Voltage Drop From
Voltage At Device
Total Voltage Drop
Voltage Drop Percent
(a)
Previous
CEILING HORN STROBE,
N2.01
ELHSRC
RED, FIRE 75cd
0.077
0.311
127
0.781731
0.24
20.16
0.24
1.19 %
CEILING HORN STROBE,
N2.02
ELHSRC
RED, FIRE 30cd
CEILING STROBE, RED,
0.046
0.234
31
0.190226
0.04
20.11
0.29
1.41 %
N2.03
ELSTRC
0.06
0.188
18
0.111805
0.02
20.09
0.31
1.51 %
FIRE 75cd
N2.04
ELSTRC
CEILING STROBE, RED,
0.022
0.128
36
0.219988
0.03
20.06
0.34
1.65 %
FIRE 15cd
N2.05
ELSTRC
CEILING STROBE, RED,
0.06
0.106
35
0.212442
0.02
20.04
0.36
1.76 %
FIRE 75cd
CEILING HORN STROBE,
N2.06 EOL
ELHSRC
RED, FIRE 30cd
0.046
0.046
18
0.109278
0.01
20.04
0.36
1.79 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (0/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
CIRCUIT SETTINGS
TOTALS
Starting Calculation Voltage:
20.4
Max. Voltage Drop:
1.36
N3 POINT-TO-POINT REPORT
Min. Operational Voltage:
16
End Of Line Voltage:
19.04
Max. Circuit Current (A):
3
Voltage Drop Percent:
6.67 %
Wire Resistance (0/kFt):
3.07
Total Circuit Current (A):
0.583
Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
494
Spare Current (A):
2.417
Distance
measured using drawn
segment lengths with 10.00
% additional length calculated
Total Circuit Resistance (0):
3.031284
Spare Current (A) Percent:
80.57 %
Part No.
Description
Device Current (A)
Remaining Current (A)
Resistance From Previous
Voltage Drop From
Voltage At Device Total Voltage Drop
Voltage Drop Percent
Device Label
Dist. From Previous (Ft)
0.022
0.583
216
(12)
1.323811
Previous
0.77
3.78 %
N3.01
ELSTRC
CEILING STROBE, RED,
19.63
0.77
FIRE 15cd
0.561
16
0.099222
19.57
0.83
4.06 %
N3.02
ELSTRC
CEILING STROBE, RED,
0.022
0.06
FIRE 15cd
N3.03
ELSTRC
CEILING STROBE, RED,
0.022
0.539
32
0.194623
0.1
19.47
0.93
4.57 %
FIRE 15cd
CEILING HORN STROBE,
N3.04
ELHSRC
RED, FIRE 15cd
0.037
0.517
8
0.052102
0.03
19.44
0.96
4.70 %
CEILING STROBE, RED,
N3.05
ELSTRC
0.022
0.48
19
0.113801
0.05
19.39
1.01
4.97 %
FIRE 15cd
CEILING STROBE, RED,
N3.06
ELSTRC
0.06
0.458
18
0.111804
0.05
19.33
1.07
5.22 %
FIRE 75cd
N3.07
ELSTRC
CEILING STROBE, RED,
0.022
0.398
24
0.147524
0.06
19.28
1.12
5.51 %
FIRE 15cd
CEILING HORN STROBE,
N3.08
ELHSRC
RED, FIRE 15cd
0.037
0.376
15
0.090009
0.03
19.24
1.16
5.67 %
N3.09
ELSTRC
CEILING STROBE, RED,
0.022
0.339
18
0.111144
0.04
19.2
1.2
5.86 %
FIRE 15cd
CEILING STROBE, RED,
N3.10
ELSTRC
0.022
0.317
22
0.137025
0.04
19.16
1.24
6.07 %
FIRE 15cd
CEILING HORN STROBE,
N3.11
ELHSRC
RED, FIRE 75cd
0.077
0.295
35
0.217605
0.06
19.1
1.3
6.39 %
CEILING HORN STROBE,
N3.12
ELHSRC
RED, FIRE 110cd
0.109
0.218
15
0.090264
0.02
19.08
1.32
6.48 %
CEILING HORN STROBE,
N3.13 EOL
ELHSRC
RED, FIRE 110cd
0.109
0.109
56
0.34235
0.04
19.04
1.36
6.67 %
Calculation Methods:
Resistance From Previous (0) = Wire Resistance (O/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
P-LINK POINT-TO-POINT REPORT
CIRCUIT
SETTINGS
TOTALS
Starting Calculation Voltage:
24
Max. Voltage Drop:
0.12
Min. Operational Voltage:
18
End Of Line Voltage:
23.88
Max. Circuit Current (A):
1
Voltage Drop Percent:
0.49 %
Wire Resistance (0/kFt):
7.77
Total Circuit Current (A):
0.025
Circuit Wiring Properties: 'PLINK+' 18/4 FPLP/R (P-LINK/PWR) 18 AWG, 4 Cond. Solid Copper FPLP/R Analog Unshielded
Total Circuit Length (Ft):
303
Spare Current (A):
0.975
Distance measured using drawn segment lengths with 10.00 % additional length calculated
Total Circuit Resistance (.0):
Voltage Drop From
Previous
4.71555
Voltage At Device
Spare Current (A) Percent:
97.50 %
Device Label
Part No.
Description
Device Current (A)
Remaining Current (A)
Dist. From Previous (Ft)
Resistance From Previous
(a)
Total Voltage Drop
Voltage Drop Percent
P-LINK•1
RA-6500
160 Character LCD
Annunciator
0.025
0.025
303
4.71555
0.12
23.88
0.12
0.49 %
Calculation Methods:
Resistance From Previous (Q) = Wire Resistance (f)/Ft) x 2 x Dist. From Previous (Ft)
Voltage Drop From Previous = Resistance From Previous (0) x Remaining Current (A)
13330 SE 30th St
Bellevue WA 98005
(425) 223-3164 Fax: (425) 223-3165
Lic. #: KLEPPI*938C6
� � A
m o LEVEL IV
EXPIRES: 11/01/2024
PROJECT NAME
V J
�
W
CIO
z
LL_
_
f-
Ln
�
Q
N
D-
F)
,JOB # 2400037
DATE: G12112024
= m m m m m m m m
U
co w w w w w w w w
It
N
w
~Q NO
N
<1
O
SHEET LIST
FA 1.0 COVER SHEET
FA2.0 GROUND FLOOR
* MEZZANINE
FA3.0 RISER DIAGRAM
FA4.0 CALCULATIONS
SHEET DESCRIPTION
FIRE ALARM
CALCULATIONS
CALCULATIONs
Scale: N.T.S
SHEET NUMBER
fA4.0