Loading...
REVIEWED BLD2024-0362+MANUF SPECS+4.9.2024_11.32.27_AM+4185301Carrier SUBMITTAL Project PF - Edmonds, WA Date Tuesday, January 30, 2024 Carrier Corporation Strategic Accounts 6304 Thompson Rd. Syracuse NY 13221 Unit Report For Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM Unit Parameters Unit Size: 12 (12 Tons) Volts -Phase -Hertz: 460-3-60 Configuration:100% OA Vertical Supply / Vertical Return Cabinet-------------------------------------------------------------------C Cabinet Evaporator Coil Depth: 6 Row Evaporator Heating Capacity: None Filter Option: 4" MERV 13 Filters Unit Dimensions Unit Length: 16' 3" Unit Width: 5' 4" Unit Height: 5' 10" Shipping Weight: 3710 lb Operating Weight: 3710 lb —Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions refer to certified drawings. ** Shipping Weight does not include added weight for special order units (ETO). Control Configuration Factory installed and programmed LS-1628u controller with DOAS control program. Unit will enable cooling or dehumidification or heating based on "Configurable Supply Air Setpoints". Will control to maintain supply air dry bulb setpoint and dew point setpoint. NOTES: Liquid subcooling NOT recommended for supply air temperature reset applications. Special control configuration needed for "supply air dry bulb temperature reset" control options, field installed sensors are required as well and will need to be ordered separately. See Controls manual for further details of temperature reset. Exhaust Exhaust Fan Type: Backward Inclined Exhaust Fan P.E./ R.F. Motor HP: 3 HP Exhaust Fan Motor Exhaust Fan Motor Type: ODP Exhaust Fan Motor Supply Fan Supply Fan Type: Backward Inclined Supply Fan Supply Fan Motor HP: 7.5 HP Supply Fan Motor Supply Fan Motor Type: ODP Supply Fan Motor Warranty Information First Year - Parts Only (Standard) Start-up, First Unit NOTE: Please see Commercial Start -Up and Optional Extended Warranty price page for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 62XM12F-JFCJHKDJBB Dedicated Outdoor Air Unit 1 Base Unit 20" Backward Inclined Supply Fan, Direct Drive 18" Backward Inclined Exhaust Fan, Direct Drive 115V GFI Convenience Outlet - Unit -Powered Type Supply/Exhaust Pressure Control 460V/3Ph/60Hz, Variable Capacity Compressor on Lead Circuit, Standard Efficiency Condenser Rev H Controls 7.5 HP ODP Supply Fan Motor with VFD 6 Row Evaporator, Modulating HGRH on Lead Circuit 4" MERV 13 Filter 3 HP ODP Exhaust Fan Motor with VFD 48" Molecular Sieve ERV, 6" Thickness, Integral Bypass Dedicated Outdoor Air Systems Builder 1.09v Page 2 of 11 Unit Report For Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM Accessories Accessory Part # Description Quantity CRRFCURBXC2BA1 14-inch Roof Curb - With ERV 1 Dedicated Outdoor Air Systems Builder 1.09v Page 3 of 11 Certified Drawing for Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM U2AU2uannew/-"IbverDcai5uwv/verDcEdKewmm IlflLxnaus[ CONDENSERFANS OPTX�GIS FURNACEELECTRICHEAT 194314 SUPPLIBLOWER ///"- CONDENSATECONNECTION p LIFTINGPOINT 3758 GASINLEr 4058 861/4 ,x OUTSIDEAJR INTAKEHOOD BACKVEW 81/4 Dedicated Outdoor Air Systems Builder 1.09v Page 4 of 11 Certified Drawing for Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM OUTSIDEAIR INTAKE 373/4 j L 10 AIR J D WUST uzAuzLmnau/- I 46 (OPTONALWHEEL) EVAPORATORCOIL &FILTERACCESS 81/2 f- CONTROLPANEL 4712 131/2 3412 58 67/8 40 67/8 II I � IIII SIFAJR RY III I 101/4 257/8 4 1756 83/4 2112 2) 2112 851/8 4 321/8 ELECTRICALENTRY LEFT MEW TOFPLAM/EW CCrDBV:WME Dedicated Outdoor Air Systems Builder 1.09v Certified Drawing for Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM TNLSOOCUMEMISTHEPROPERTYOF BUBMISSKKJ OF UMESE Carrier UP.N THE RPORATIONHN�GEL— DOESDR-ICT DOCUMENT UPONTHE EXPREBBOONORX]N BED OOEBNOT iE C F A�A-�wd^�� 62X THECgNTENTBWILLNOTBEGI RRIEO PART PERFORMANCE lM{aV,1`NM/YOYYI1r {7�✓� A United Technologies Company OR USED wmpur OMRIER OR AOCEPTarvOE CORPORATpNSWRRTENCONSEM WMRPliT 13 56314 2 TY P 16 17 37 30 Dedicated Outdoor Air Systems Builder 1.09v Page 6 of 11 Certified Drawing for Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM Corner Weights Corner Weights Corner Weight (LF): 640.0 lb Corner Weight (LB): 570.0 lb Corner Weight (RF): 1330.0 lb Corner Weight (RB): 1170.0 lb Dedicated Outdoor Air Systems Builder 1.09v Page 7 of 11 Performance Summary For Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM Part Number: 62XM12F-JFCJHKDJBB Unit Refrigerant: R410A Application MRC: -56.8 Ib/hr Application MIRE: -3.3 Unit Dimensions Unit Length: 16' 3" Unit Width: 5' 4" Unit Height: 5' 10" Shipping Weight: 3710 lb Operating Weight: 3710 lb Unit Heat Options:. Configuration: Voltage: ------------- Altitude-------------- --------------------------------------------------------------------------- None 100% OA Vertical Supply / Vertical Return 460-3-60 ---------------------------------------------------------------------------------- 400 ft Dehumidification Performance Cooling Airflow: 5640 CFM Ambient Air Temp: 95.0 F Ent. Coil Air Dry Bulb: 79.0 F Ent. Coil Air Wet Bulb: 63.2 F Evap Lvg. Air Dry Bulb: 54.8 F Evap Lvg. Air Wet Bulb: 53.9 F Lvg. Air Dry Bulb (Max. Reheat): 67.3 F Lvg. Air Wet Bulb (Max. Reheat): 58.8 F Gross Cooling Capacity: 156.00 MBH Gross Sensible Clg. Cap: 150.30 MBH Compressor Power: 16.98 kW Energy Conservation Wheel ECW Size: ECW 486 Outside Airflow: 5640 CFM Exhaust Airflow: 4800 CFM Dehumidification Outdoor Air DB: 85.0 F Outdoor Air WB: 65.0 F Pre -Treated Outdoor Air DB: 79.0 F Pre -Treated Outdoor Air WB: 63.2 F Return Air DB: 75.0 F Return Air WB: 62.0 F Exhaust Air DB: 81.8 F Exhaust Air WB: 64.1 F Total Capacity: 40.68 MBH Latent Effectiveness: 66 % Sensible Effectiveness: 71 % Total Effectiveness: 71 % Heating Outdoor Air DB: 25.4 F Outdoor Air WB: 21.0 F Pre -Treated Outdoor Air DB: 50.5 F Pre -Treated Outdoor Air WB: 38.6 F Return Air DB: 70.0 F Return Air WB: 50.0 F Exhaust Air DB: 38.2 F Exhaust Air WB: 30.8 F Exhaust Air PD: 0.91 in wg Total Capacity: 179.56 MBH Latent Effectiveness: 69 % Dedicated Outdoor Air Systems Builder 1.09v Page 8 of 11 Performance Summary For Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM Sensible Effectiveness--------------- Total Effectiveness----------------------- ----- 74 % 73 % Supply Fan Performance: Ext. Static Pressure: 1.00 Total Static Pressure: 3.65 Supply Fan Type: Backward Inclined Supply Fan Supply Fan Size: 20" Backward Inclined Supply Fan, Direct Drive Supply Fan Motor Type: ODP Supply Fan Motor Supply Fan Motor Size: 7.5 HP Supply Fan Motor Supply Fan RPM: 1881 Supply Fan BHP: 4.91 Exhaust Fan Performance: Exhaust Airflow-------------------------- Ext. Static: ------------------------------------- Total Static Pressure-------------- Power Exhaust Fan Type: --- Power Exhaust Fan Size: ----. Power Exhaust Motor Type Power Exhaust Motor Size:. FanRPM: -------------------------------------- FanBHP---------------------------------------- 4800 0.20 1.40 Backward Inclined Exhaust Fan 18" Backward Inclined Exhaust Fan, Direct Drive ODP Exhaust Fan Motor 3 HP Exhaust Fan Motor 1818 2.23 Electrical Data Unit Voltage: 460-3-60 Unit Amps - FLA: 38.03 Min. Circuit Ampacity - MCA: 41.2 Maximum Fuse Size - MFS: 50 Compressor RLA (ea.): 7.82 Compressor LRA (ea.): 54 Supply Fan FLA: 9.25 Power Exhaust FLA: 3.86 Condenser FLA (ea.): 1.6 Sound Power Data Condenser Fan Supply Fan Exhaust Fan 63 Hz 66.5 55.0 50.0 125 Hz 84.1 62.0 58.0 250 Hz 82.0 74.0 71.0 500 Hz 86.9 75.0 72.0 1000 Hz 85.3 78.0 72.0 2000 Hz 80.5 78.0 72.0 4000 Hz 75.0 78.0 72.0 8000 Hz 69.8 70.0 64.0 Note: Sound ratings are based on the fan's manufacturer data. in wg in wg BHP CFM in wg in wg BHP Dedicated Outdoor Air Systems Builder 1.09v Page 9 of 11 Performance Summary For Untitledl Project: PF - Edmonds, WA 01/30/2024 Prep red By: Carrier Corporation 03:29PM SUPPLY FAN CURVE 5.5- . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.0 5.0 - ----- - .............. ............... ............... ........... ............... I ............... --4.5 4.5 ---------------------------------------------------- --- ---•------------ ............... ........... -------------- ------- .............. --4.0 4.0 ------------- - ------------------------------ --------------- ---------------- --------- r --------------- --------------- I ------- -------- 3.5 3.5 ------------ - -------------- ------------------------------------------------------- ------ L ................................................ 3.0 3.0- ............ .............. I ............... I ............... ................ r ................ I ... .......... ----------------------- 0 -25 0 2.5 - ---------- - ---------------------------------------------------------------------------------------------- ................................ --2.0 2.0- - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - r - - - - - - - - - - - - - r ------------------ -------- ---------------------------- T 0 15 1-- 1.5 - ---------- - -------------- ---------------- I --------------- ............... I ---------------- ---------- -- - ............... ------------ 1.0 ............................ ............... ............................................... L --------------- ............... J ---------------------- 1.0 0.5 - --------------- ---------- --------------- --------------- --------------- ...............•---------- -- - .... ....... --------------- --0.5 0.0 0.0 3500 4000 4500 5000 5500 6000 6500 7000 7500 Volume(CFM) Selection RPM - BHP - User Selection Dedicated Outdoor Air Systems Builder 1.09v Page 10 of 11 Performance Summary For Untitled1 Project: PF - Edmonds, WA 01/30/2024 Prepared By: Carrier Corporation 03:29PM 4 3 Q3 c o2 Cn 0 0-2 U w N U)1 m 0 1 NI FXNATTCT FAN CTTRVF 2500 3000 3500 4000 4500 5000 Volume (CFM) Selection RPM — - BHP — User Selection f, m M 50 w M 0 N J W 3 Dedicated Outdoor Air Systems Builder 1.09v Page 11 of 11