REVIEWED FIR2022-0138+Fire_Sprinkler_Equipment_Specification_Sheets+12.23.2022_12.37.30_PM+3284483
RECEIVED FIR2022-0138 Dec 28 2022 DEVCITY ELO MPENTSOERVCES Red Hawk Fire Protection, LLC DEPARTMENT 801 Valley Ave NW, Suite D Puyallup, WA 98371 (253) 840-9900 REDHAHF901 OP Ever VLOi.lp wt� MATERIAL SUBMITTAL FOR HOUSING HOPE EDMONDS LUTHERAN EDMONDS, WA RHFP JOB NO. 70106 TABLE OF CONTENTS Material Notes: WREDHAWK FIRE PROTECTION, LLC Any material with comment "Or Equal" indicates cut sheet represents an the exact or similar product to what we will install. These products generally are generic in nature and due to vender availability, price changes, or other unknowns, a similar product my be selected. All products used will meet all NFPA 13's, authority having jurisdiction, and projects specifications requirements. Description Make Model Comments CPVC Piping System Spears N/A Covers entire CPVC product line Black Steel Sprinkler Pipe - SCHD 7 (Flow) Bull Moose N/A Or Equal Black Steel Sprinkler Pipe - SCHD 10 & 40 Bull Moose N/A Or Equal Threaded Fittings - Ductile Iron Titus N/A Or Equal Grooved Rigid Coupling Victaulic Style 009N Grooved Flexible Coupling Victaulic Style 75 Grooved Reducing Coupling Victaulic Style 750 Grooved Flange Adaptor Victaulic Style 741 Grooved Fittings - 2" & Larger Victaulic N/A Firelock Description Make Model Comments CPVC - Double Offset Tolco/Eaton Fig. 29 1" and 1%" only CPVC - Stand -Off Hanger (No -Block) Anvil/ASC Fig. 188R Or Equal CPVC - Side Mount Hanger Anvil/ASC Fig. 187 Or Equal Loop/Ring Hanger - Standard Duty Caddy/nVent 115 Or Equal Rigid Strut Clamp Caddy/nVent RIGD Or Equal Riser Clamp Caddy/nVent 510 Or Equal Attachment - Universal Beam Clamp Caddy/nVent 300 Or Equal - • • & Restraints Description Make Model Comments Loop/Ring Hanger - Surge Restraint Afcon 310 Brace Structure Attachment - Generic (EQ Ear) Caddy/nVent CSBU Brace Pipe Attachment - Longitudinal and Lateral Brace Caddy/nVent CSB Universal Sway Brace Branch Line Restraint - Pipe Attachment Caddy/nVent CSBBRPO Branch Line Restraint - Structure Attachment - Wood & Concrete Caddy/nVent CSBBRS2EG Description Check Valve - Grooved Backflow - Grooved Double Check Detector FDC - Wall Mounted, 2-Way FDC - Wall Plate FDC - Breakaway Caps Test & Drain Valve, With Pressure Relief Description Air Pressure Gauge Water Flow Switch Alarm Bell - 24v, 10" Description Extended Coverage, Dry Sidewall Residential Pendent, Semi -Recessed Standard Spray, Pendent, Semi -Recessed Description Teflon Tape Pipe Dope Thread Oil CPVC Glue Fire Caulk for Fire Rated Penetrations Fire Rated Sleeves Sprinkler Spare Stock Box Make Model Victaulic Series 717 Backflow Direct/Ames Deringer 30 FPPI/ASC Fig 09-000 FPPI/ASC Varies FPPI/ASC Fig 09-503 Victaulic UTD Make Wika Instrument LP Potter Signal Potter Signal Make Reliable Reliable Reliable Model 111.10SP VSR PDC-10-24 Model DH56 (5.6K) F1res49 (4.9K) F1FR56 (5.6K) Make Model Argco PTFE Tape Industrial Argco Tuf-Glide FPPI/ASC Threadfit Clear Oil Spears FS-5 One Step Cement Hilti FS-One Hilti CP 680-P Argco 6510150 Comments Or Equal Finish to be Aluminum Or Equal Supplied with UM & UMC Risers Comments Or Equal Provided upon request Comments Ref. plans, color, temp, and response Ref. plans, color, temp, and response Ref. plans, color, temp, and response Comments Pipe & Fittings Submittal Information for Spears° Manufacturing Company pil I FlameGuard ° CPVC Fire Sprinkler System Date: Job Name: Engineer: Scope: This submittal covers the Spears® FlameGuard® CPVC Fire Sprinkler System suitable for residential and light hazard occupancies in accordance with The National Fire Protection Association (NFPA). The FlameGuard® System shall be sold as a complete system which consists of pipe, fittings and a specially formulated one-step primerless cement intended for use in wet, dry and pre -action systems in residential and light hazard Applications where the operating temperature/pressure does not exceed 175psi @ 150' F. (1.2 MPa @ 66' C) Product Specification: All CPVC fire sprinkler fittings and pipe shall be Spears® FlameGuard®. All solvent cement shall be Spears® FS-5 One -Step, and all thread sealant shall be Spears® Blue 75Tm as produced by Spears® Manufacturing Company. All Spears® FlameGuard® CPVC fire sprinkler fittings shall be manufactured in the U.S.A. from a Chlorinated Polyvinyl Chloride (CPVC) compound having a minimum cell classification of 23447 in accordance with ASTM D1784. Fittings shall be manufactured in strict compliance to ASTM F438 or F439, as applicable. All CPVC fire sprinkler piping shall be manufactured in the U.S.A. from a Chlorinated Polyvinyl Chloride (CPVC) compound having a minimum cell classification of 23447 in accordance with ASTM D1784. Piping shall be manufactured in strict compliance to ASTM F442. All CPVC solvent cement shall be a primerless, one-step type manufactured in strict compliance to ASTM F493 and approved for use with CPVC fire sprinkler systems. All CPVC fire sprinkler fittings, pipe and solvent cement shall be listed by Underwriters Laboratories (UL®), Underwriters Laboratories Canada (ULC®) and/or Factory Mutual Research Corporation (FM Global) and/or LPCB for use in residential and light hazard wet, dry and pre -action systems and bear their authorized certification marks. Thread sealant shall be approved by the fitting manufacturer for use with CPVC fire sprinkler products. All CPVC fittings, pipe, solvent cement and thread sealant shall be certified by NSF International as applicable. Pipe and solvent cement shall be certified to UL 2818 GREENGUARD GOLD. Product Marking: FlameGuard® system components shall be orange in color for identification and include required markings and approvals prescribed in ASTM F442 for pipe GSFG-0221 Location: Contractor: and ASTM F438 or F439 for fittings. Pipe and cement shall have GREENGUARD GOLD marking. Installation: Spears® FlameGuard® CPVC Fire Sprinkler System shall carry a working pressure of 175 psi @ 150F (1.2 MPa @ 660 C) and shall be installed in accordance with Spears® Manufacturing Company FlameGuard® CPVC Fire Sprinkler Products Installation Instructions (FG-3) and Addendums. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the Installation Instructions and applicable local codes. Installation practices such as pipe support spacing, bracing, allowance for thermal expansion/contraction, solvent cementing and handling and storage shall be in accordance with the manufacturer's instructions and this specification. Buried pipe shall be in accordance with NFPA 24 for supply mains. The piping system shall be joined using a chemically resistant one-step primerless solvent cement joining process conforming to ASTM F493. The system shall be protected from ultra violet (UV) light exposure from the sun or other source and protected from any chemicals that are not compatible with the CPVC materials including but not limited to fire stopping materials, plasticizers, incompatible thread sealants, etc. NOTE: FlameGuard® CPVC piping systems can be leak tested using oil -free compressed air up to 25psi but must also be hydrostatically tested as required per NPFA standard. Referenced Standards: ASTM D1784 — Rigid Vinyl Compounds ASTM F438 — CPVC Schedule 40 Fittings ASTM F439 — CPVC Schedule 80 Fittings ASTM F442 — CPVC SDR Pipe ASTM F493 — Solvent Cements for CPVC Pipe & Fittings NFPA 13, 13D, 13R — National Fire Protection Association Standards NFPA 24 — Installation — Private Fire Service Mains NSF International Standard 14/61 — Potable Water Approvals: NSF° — NSF International Standard 14/61 — Potable Water Underwriters Laboratories — Listing Agency FM Global —Listing Agency UL-GREENGUARD GOLD Certified UL 2818 LPCB — Loss Prevention Council Board %v ,,,, BULL TVTOOSE® TUBE APPROVALS AND SPECIFICATIONS • ASTM A135, Grade A • ASTM A795, Type E, Grade A • Pressure rated to 300 psi • Underwriters Laboratories — United States of America • Underwriters Laboratories —Canada EDDY FLOW SPRINKLER PIPE SUBMITTAL DATA SHEET FINISHES AND COATINGS Eddy Flow Sprinkler Pipe receives an OD mill coating of water -based paint which has corrosion protection expected with a painted carbon steel product, i.e. it would be expected to resist corrosion for an extended and indefinite period in a clean and dry environment and, as environmental conditions deteriorate, the corrosion protection would also diminish. • Factory Mutual Eddy Flow Sprinkler Pipe (black) receives an ID mill coating of Eddy • NFPA-13 Guard II MIC preventative coating. EG2 has been tested at • NFPA-13R independent laboratories to resist bacterial growth and maintain • NFPA-14 minimal bacterial count after multiple flushes (25) of the pipe. • CIVIL DEFENSE APPROVAL — United Arab Emirates • Made in the United States of America • UL, ULC & FM listed for roll -groove, plain -end and welded joints for wet, dry, preaction and deluge sprinkler systems. • LEED v4 Certified • Eddy Flow Sprinkler Pipe when Hot Dip Galvanized by ASTM A123 and supplied by Bull Moose Tube is UL listed and FM approved. PRODUCT IDENTIFICATION • Every length of Bull Moose fire sprinkler pipe features large, easy -to - read, continuous stenciling, clearly identifying the manufacturer, type of pipe, size, and length. F11. O.D. (in) 1.660 1.900 2.375 2.875 3.500 4.500 I.D. (in) 1.530 1.728 2.203 2.705 3.334 4.310 Empty Weight (Ib/ft) 1.222 1.844 2.330 2.809 3.361 4.968 Water Filled Weight (lb/ft) 2.019 2.860 3.982 5.299 7.144 11.290 C.R.R.* 1.98 3.44 2.78 1.66 1.00 1.00 Pieces per Lift 61 61 37 30 19 19 *Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY SUBMITTAL INFORMATION Project Contractor Engineer Specification Reference Date System Type Locations Comments C Eddy Flow - Black Eddy Flow - Hot Dip Galvanized 1E3ULLTvT00SETUBE.00M UD C UDFM •nnnoveo BULL TVTOOSE® TUBE APPROVALS AND SPECIFICATIONS • ASTM A135, Grade A • ASTM A795, Type E, Grade A • Pressure rated to 300 psi • Underwriters Laboratories - United States of America • Underwriters Laboratories -Canada • Factory Mutual • NFPA-13 • NFPA-13R • NFPA-14 • CIVIL DEFENSE APPROVAL - United Arab Emirates • Made in the United States of America • UL, ULC & FM listed for roll -groove, plain -end and welded joints for wet, dry, preaction and deluge sprinkler systems. • LEED v4 Certified SCHEDULE 10 R 40 SPRINKLER PIPE SUBMITTAL DATA SHEET FINISHES AND COATINGS Schedule 10 & 40 Sprinkler Pipe receives an OD mill coating of water -based paint which has corrosion protection expected with a painted carbon steel product, i.e. it would be expected to resist corrosion for an extended and indefinite period in a clean and dry environment and, as environmental conditions deteriorate, the corrosion protection would also diminish. • Schedule 10 & 40 Sprinkler Pipe (black) receives an ID mill coating of Eddy Guard II MIC preventative coating. E62 has been tested at independent laboratories to resist bacterial growth and maintain minimal bacterial count after multiple flushes (25) of the pipe. • Schedule 10 & 40 Sprinkler Pipe when Hot Dip Galvanized by ASTM A123 and supplied by Bull Moose Tube is UL listed and FM approved. PRODUCT IDENTIFICATION • Every length of Bull Moose fire sprinkler pipe features large, easy -to - read, continuous stenciling, clearly identifying the manufacturer, type of pipe, size, and length. 0.0. (in) 1.315 1.660 1.900 2.375 2.815 3.500 4.500 6.625 8.625 I.D. (in) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6.357 8.249 Emptgweight (lb/ft) 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940 water Filled weight (lb/ft) 1.800 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086 C.R.R.* 15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805 Pieces per Lift 91 61 61 37 30 19 19 10 7 0.0. (in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 I.D. (in) 1.049 1.380 1.610 2.067 2.469 3.068 4.026 EmptyWeight (lb/ft) 1.680 2.270 2.720 3.660 5.800 7.580 10.800 Water Filled Weight (lb/ft) 2.055 2.918 3.602 5.114 7.875 10.783 16.316 C.R.R.* 1.00 1.00 1.00 1.00 1.00 1.00 1.00 Pieces per Lift 70 51 44 30 30 19 19 *Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY **Not Eddy Guard II treated/Not produced by BMT SUBMITTAL INFORMATION C Project Contractor Engineer Specification Reference Date System Type Locations Comments OSchedule 10 - Black Schedule 10 - Hot Dip Galvanized O Schedule 40 - Black O Schedule 40 - Hot Dip Galvanized BULLNE00SETUBE.11COM ELBOW 90' SIZE (INCH) A(in) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1/2 1.12 0.25 50 200 UL, FM 1 1.50 0.57 20 60 UL, FM 11/4 1.75 0.97 20 40 UL, FM 11/2 1.94 1.43 15 30 UL, FM 2 2.21 1.93 8 16 UL, FM 21/2 2.70 2.89 12 12 UL, FM 90° REDUCING ELBOW SIZE (INCH) A (in) B (in) WEIGHT (LBS.) INNER BOX PCS/BOX MASTER Ctn. PCS/Ctn. Remarks 1 X 1/2 1.26 1.40 0.43 25 100 UL, FM 1 X 3/4 1.37 1.45 0.56 50 100 UL, FM 11/4 X 1/2 1.34 1.53 0.61 20 80 UL, FM 11/4 X 3/4 1.45 1.62 0.71 15 60 UL, FM 11/4 X 1 1.58 1.67 0.73 10 40 UL, FM 11/2 X 1/2 1.52 1.75 0.71 15 60 UL, FM 11/2 X 3/4 1.52 1.75 1.01 10 40 UL, FM 11/2 X 1 1.65 1.80 0.92 10 40 UL, FM 11/2 X 11/4 1.82 1.88 1.04 15 30 UL, FM 2 X 3/4 1.60 1.97 1.10 9 36 UL, FM 2 X 1 1.73 2.02 1.22 14 28 UL, FM 2 X 11/4 1.90 2.10 1.48 30 20 UL, FM 2 X 11/2 2.02 2.16 1.56 10 20 UL, FM ELBOW45° SIZE (INCH) q(inl WEIGHT (LBS.) INNERBO PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1 1.12 0.55 20 60 UL, FM 11/4 1.29 0.85 20 40 UL, FM 11/2 1.43 1.12 10 30 UL, FM 2 1.68 1.14 12 24 UL, FM TEE SIZE (INCH) A (in) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1 1.50 0.83 20 40 UL, FM 11/4 1.75 1.30 14 28 UL, FM 11/2 1.94 1.68 12 24 UL, FM 2 2.25 2.79 8 16 UL, FM C&S <FM APPROVED DUCTILE IRON THREADED FITTINGS �-7eTITUS M1a MI `" 1 c Dus FM APPROVED COUPLING SIZE (INCH) A(in) WEIGHT (LBS.) INNERBOX PCs/BOX MASTERCtn. PCS/Ctn. Remarks 1 1.67 0.47 25 100 UL, FM 11/4 1.93 0.66 16 64 UL, FM 11/2 2.15 0.94 18 36 UL, FM 2 2.53 1.49 12 24 UL, FM REDUCING COUPLING SIZE (INCH) A(in) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 3/4 x 1/2 1.44 0.26 60 180 UL, FM 1 x 1/2 1.69 0.37 30 120 Hexagon small end, UL, FM 1 x 3/4 1.69 0.42 25 ? 00 Hexagon small end, UL, FM 11/4 x 1/2 2.06 0.57 25 75 UL, FM 11/4x 3/4 2.06 0.60 25 75 UL, FM 11/4 x 1 2.06 0.62 15 60 UL, FM BUSHINGS SIZE (INCH) Alin) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 3/4 x 1/2 1.02 0.14 75 300 outside head, UL, FM 1 x 1/2 1.14 0.28 50 200 outside head, UL, FM 1 x 3/4 1.14 0.19 50 200 outside head, UL, FM 11/4 x3/4 1.30 0.37 30 120 outside head, UL, FM 11/4 x 1 1.30 0.30 30 120 outside head, UL, FM 11/2 x 1 1.34 0.52 25 75 outside head, UL, FM 11/2 x 11/4 1.34 0.37 25 75 outside head, UL, FM 2 x 1/2 1.50 0.90 20 60 inside head, UL, FM 2 x 3/4 1.50 0.67 20 60 inside head, UL, FM 2 x 1 1.50 0.88 20 60 inside head, UL, FM 2 x 11/4 1.50 0.79 20 60 outside head, UL, FM 2 x 11/2 1.50 0.66 20 60 outside head, UL, FM PLUG SIZE (INCH) A (in) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1/2 0.95 0.10 50 600 hollow, UL, FM 3/4 1.07 0.16 35 420 hollow, UL, FM 1 1.25 0.26 20 240 hollow, UL, FM 11/4 1.36 0.31 40 120 hollow, UL, FM 11/2 1.42 0.51 30 90 hollow, UL, FM 2 1.57 0.65 20 60 hollow, UL, FM CROSS SIZE (INCH) Alin) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1 1.50 0.98 15 30 UL, FM 11/4 1.75 1.55 10 20 UL, FM 11/2 1.94 1.84 8 16 UL, FM 2 2.25 3.26 5 10 UL, FM CAP SIZE (INCH) A (in) WEIGHT (LBS.) INNERBOX PCS/BOX MASTERCtn. PCS/Ctn. Remarks 1 1.16 0.32 25 100 UL, FM 11/4 1.28 0.49 20 80 UL, FM 11/2 1.33 0.67 18 54 UL, FM 2 1.45 0.88 12 36 UL, FM c&us FM APPROVED Victaulic° Firel-ockT" Installation -Ready"' Rigid Couplings Aitaulic Style 009N and Style 109 10.64 Patented Patented 1.0 PRODUCT DESCRIPTION Available Sizes • Style 009N: 11/4 — 12"1 — DN300 • Style 109: 11/4 — 4"1 — DN100 Pipe Material • Schedule 10, Schedule 40 or specialty carbon steel pipe listed in Section 5. For use with alternative materials and wall thicknesses please contact Victaulic • For exceptions reference section 6.0 Notifications Maximum Working Pressure • Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) to 365 psi/2517 kPa Function • Joins carbon steel pipe with grooved ends conforming to publication 25.01 • Provides a rigid pipe joint designed to restrict axial or angular movement 2.0 CERTIFICATION/LISTINGS 0@11111 FM OLKB a VdS E L(SM Los 1219: Issue 3.1 EN 10311 Cert/LPCB Ref. 104-1a/36 Regulation (EU) No. 305/2011 ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 10.64 07072 Rev R Updated 1012021 © 2021 Victaulic Company. All rights reserved. 1 ictaulid victaulic.com 3.0 SPECIFICATIONS — MATERIAL ❑ Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade ❑ 65-45-15, is available upon special request. ❑ Housing Coating: (specify choice) ❑ Orange coating Red coating (standard for EMEA-I and Asia Pacific) ❑ Optional for Style 009N: Hot Dipped Galvanized per ASTM A123 Optional for Style 109: Mechanically Galvanized per ASTM B695 (available only in North America and Latin America). Gasket: (specify choice) Grade "E" EPDM (Type A) Vic-Plue" Pre -lubricated Gasket EPDM (Violet Color Code). Applicable for wet and dry (oil -free air) fire protection systems only. Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems at-40°F/-40°C and above. Not compatible for use with hot water services or steam services. NOTES • Reference should always be made to publication 1-100, Victaulic Field Installation Handbook for gasket lubrication instructions. ❑ • Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to publication 05.01, Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice) Standard: Carbon steel oval neck track bolt(s) meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (M10-M16) Class 8.8 (M20 and greater). Carbon steel hex nuts meeting the ❑ mechanical property requirements of ASTM A563 Grade B (imperial) and ASTM A563M Class 9 (metric). Track bolts and hex nuts are zinc electroplated per ASTM B633 Fe/Zn 5, finish Type III (imperial) or Type II (metric). Optional for Style 009N: Stainless steel oval neck track bolts meeting the requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel Heavy Hex nuts meeting the requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling -resistant coating.' 1 Optional bolts/nuts are available in imperial size only. Coupling Linkage: High Strength Steel with comparable physical properties to that of the Track Bolt (ASTM A449). Linkage is zinc electroplated per ASTM B633 Fe/Zn 5, Type III Finish. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulid victaulic.com 4.0 DIMENSIONS Style OO9N Two -Bolt Installation -Ready Coupling Size Maximum Maximum Allow. Bolt/Nut Dimensions Weight Actual Pre -assembled Joint Assembled Outside Working End Pipe End Approx. X Y X Y Nominal Diameter Pressure2 Load2 Separation3 Qty. Size Z (Each) inches inches psi lb inches inches inches inches inches inches inches Ib ON mm kPa N mm mm mm mm mm mm mm kg -MTa 1.660 365 790 0.10 2 3/8 x 2 3.13 5.00 2.75 5.00 2.00 1.4 DN32 42.4 2517 3514 2.54 M10 x 51 79 127 70 127 51 0.6 1 1/2 1.900 365 1035 0.10 3/8 x 2 3.38 5.13 3.00 5.13 2.00 1.5 DN40 48.3 2517 4604 2.54 2 M10 x 51 86 130 76 130 51 0.7 2 2.375 365 1617 0.12 2 3/a x 21/2 4.00 5.63 3.50 5.63 2.00 1.9 DN50 60.3 2517 7193 3.05 M10x63 102 143 89 143 51 0.9 21/2 2.875 365 2370 0.12 3/a x 21/2 4.50 6.13 4.00 6.13 2.00 2.1 73.0 2517 10542 3.05 2 M10 x 63 114 156 102 156 51 1.0 3.000 365 2580 0.12 3/8 x 21/2 4.63 6.00 4.13 6.13 2.00 2.1 DN65 76.1 2517 11476 3.05 2 M10 x 63 118 152 105 156 51 1.0 3 3.500 365 3512 0.12 2 3/8 x 21/2 5.13 6.75 4.63 6.75 2.00 2.3 DN80 88.9 2517 15622 3.05 M10 x 63 130 171 117 171 51 1.0 4 4.500 365 5805 0.17 3/a x 21/2 6.00 7.88 5.63 7.50 2.13 2.9 DN100 114.3 2517 25822 4.32 2 M10x63 152 200 143 191 54 1.3 4.250 365 5178 0.17 3/8 x 21/2 5.63 7.38 5.38 7.38 2.13 3.1 108.0 2517 23020 4.32 2 M 10 x 63 152 1.87 137 187 54 1.4 5 5.563 365 8872 0.17 2 1/2 x 3 7.25 9.25 6.75 9.13 2.25 5.0 141.3 2517 39456 4.32 M 12 x 76 184 235 171 232 57 2.3 5.250 365 7901 0.17 2 1/2 x 3 6.63 9.00 6.38 9.00 2.25 4.8 133.0 2517 35106 4.32 M 12 x 76 168 229 162 229 57 2.2 5.500 365 8672 0.17 2 1h x 3 6.88 9.25 6.75 9.13 2.25 4.9 DN125 139.7 2517 38529 4.32 M12x76 175 235 171 232 57 2.2 6 6.625 365 12582 0.17 1/2 x 31/4 8.38 10.38 7.88 10.13 2.25 6.0 DN150 168.3 2517 44469 4.32 2 M12x83 213 264 200 257 57 2.7 6.250 365 11198 0.17 1/2x 31/4 7.88 10.00 7.38 9.88 2.25 5.6 159.0 2517 49753 4.32 2 M 12 x 83 200 254 187 251 57 2.5 6.500 365 12112 0.17 1/2 x 31/4 8.00 10.25 7.75 10.13 2.25 6.0 165.1 2517 53813 4.32 2 M12 x 83 203 260 197 257 57 2.7 8 8.625 365 21326 0.17 '/a x 4 10.88 13.38 10.25 13.13 2.50 11.4 DN200 219.1 2517 94863 4.32 2 M16x101 276 340 260 333 64 5.2 8.500 365 20712 0.17 5/s x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 2517 55968 4.32 2 M16x101 270 337 260 257 67 5.2 10 10.750 300 27229 0.25 7/8 x 61/2 13.75 17.00 13.25 17.13 2.75 22.6 DN250 273.0 2068 121121 6.4 2 M22 x 165 349 432 337 435 70 10.3 12 12.750 300 38303 0.25 7/a x 61/2 16.00 19.00 15.50 19.13 2.75 27.6 2 DN300 323.9 2068 170380 6.4 M22 x 165 406 483 394 486 70 12.5 2 Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. See the Listings/Approvals section of this publication for ratings on other pipe. 3 The allowable pipe separation dimension shown is for system layout purposes only. Style 009N couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. NOTES • When assembling Style 009N or Style 109 couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For Style 009N or Style 109 couplings, use FireLock No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009N or Style 109 couplings. IMPORTANT: Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N or Style 109 coupling. There is no interchanging of gaskets or housings between coupling styles. • Use Of FlushSeal Gaskets For Dry Pipe Systems Style 009N or Style 109 couplings are supplied with Grade "E" Type A gaskets. These gaskets include an integral pipe stop, that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard Victaulic FlushSeal gaskets cannot be used with the Style 009N or Style 109 couplings. • The Allowable Pipe End Separation dimension shown is for system layout purposes only. Style 009N or Style 109 Installation -Ready rigid couplings are considered rigid connections and will not accommodate expansion/contraction or angular movement of the piping system. Contact Victaulic for torsional resistance information. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 3 ✓ctaulid victaulic.com 4.1 DIMENSIONS Style 109 One -Bolt Installation -Ready Coupling 74 YB YL co ' Style 0• 0• Joint Assembled Size Max. Max. Allow. Pipe Bolt/Nut Dimensions Weight Actual Pre -Assembled Assembled Outside Working End End Sep. Approx. YL YB X Z YL YB X Z Nominal Diameter Pressure Load Maximum Qty. Size (Each) inches inches psi Lbs. inches inches inches inches inches inches inches inches inches inches lb DN mm kPa N mm mm mm mm mm m m mm mm mm mm kg 1 1/4 1.660 365 790 0.10 3/8 x 21/4 1.97 2.49 3.17 1.95 1.93 2.59 2.84 1.95 1.5 1 DN32 42A 2517 1 3514 2.54 1 1 M10 x 57 50 63 81 50 49 66 72 50 0.7 1 1/2 1.900 365 1035 0.10 3/a x 2 Y4 2.13 2.60 3.41 1.95 2.1 2.68 3.07 1.95 1.6 1 DN40 48.3 2517 4603 2.54 M10 x 57 54 66 87 50 53 68 78 50 0.7 2 2.375 365 1617 0.12 3/a x 21/4 2.32 2.85 3.76 1.98 2.29 2.95 3.45 1.98 1.9 1 DN50 60.3 2517 7192 3.048 M10 x 57 59 72 1 96 1 50 58 1 75 88 1 50 0.9 21/2 2.875 365 2370 0.12 3/8 x 21/4 2.63 3.09 4.29 1.99 2.61 3.15 3.93 1.99 2.1 1 73.0 2517 10540 3.048 M10 x 57 67 78 109 51 66 80 100 51 1.0 3.000 365 2580 0.12 �/16 x 2 3/4 2.68 3.22 4.56 2.03 2.64 3.45 4.22 2.03 2.4 1 DN65 76.1 2517 11476 3.048 M71 x 69 68 82 116 52 67 88 107 52 1.1 3 3.500 365 3512 0.12 7/16 x 2 3/4 2.93 3.53 5.13 2.07 2.89 3.78 4.67 2.07 2.7 1 DN80 88.9 2517 15620 3.048 M11 x69 74 90 130 53 73 96 119 53 1.2 4 4.500 300 4771 0.17 �/16 X 2 3/4 3.47 4.01 6.03 2.08 3.43 4.22 5.56 2.08 3.5 1 DN100 114.3 2068 21223 4.318 M11 x69 88 102 153 53 87 107 141 53 1.6 4 Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. See the Listings/Approvals section of this publication for ratings on other pipe. 5 The allowable pipe separation dimension shown is for system layout purposes only. Style 109 couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. NOTES • When assembling Style 009N or Style 109 couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For Style 009N or Style 109 couplings, use FireLock No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009N or Style 109 couplings. IMPORTANT: Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N or Style 109 coupling. There is no interchanging of gaskets or housings between coupling styles. • Use Of FlushSeal Gaskets For Dry Pipe Systems Style 009N or Style 109 couplings are supplied with Grade "E" Type A gaskets. These gaskets include an integral pipe stop, that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard Victaulic FlushSeal gaskets cannot be used with the Style 009N or Style 109 couplings. • The Allowable Pipe End Separation dimension shown is for system layout purposes only. Style 009N or Style 109 Installation -Ready rigid couplings are considered rigid connections and will not accommodate expansion/contraction or angular movement of the piping system. Contact Victaulic for torsional resistance information. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 4 ✓ctaulid victaulic.com 5.0 PERFORMANCE Style 009N Two -Bolt Installation -Ready Coupling Listings/Approvals6 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approval agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Size cULus FM VdS LPCB Actual Outside Nominal Diameter Sch.10 Sch.40 Sch.10 Sch.40 psi psi psi psi psi psi inches inches kPa kPa kPa kPa kPa kPa DN mm bar bar bar bar bar bar 365 365 363 363 363 ir 363 11/4 1.660 DN32 42.4 2517 2517 2503 2503 2500 2500 25 25 25 25 25 25 365 365 363 363 363 363 11/2 1.900 DN40 48.3 2517 2517 2503 2503 2500 2500 25 25 25 25 25 25 365 365 363 363 363 363 2 2.375 DN50 60.3 2517 2517 2503 2503 2500 2500 25 25 25 25 25 25 365 365 363 363 — 363 21/2 2.875 2517 2517 2503 2503 — 2500 73.0 25 25 25 25 — 25 365' — 3638 — 363 363 DN65 2517' — 2503' — 2500 2500 7600 257 — 258 — 25 25 365 365 363 363 363 363 3 3.500 DN80 88.9 2517 2517 2503 2503 2500 2500 25 25 25 25 25 25 — 363 363 — — 4.250 — — 2503 2503 — - 108.0 - — 25 25 — — 365 365 363 363 363 363 4 4.500 DN100 114.3 2517 2517 2503 2503 2500 2500 25 25 25 25 25 25 _ _ e _ _ _ 5.2500 33. 133.0 2503' — — — — — 258 — — — 290' — 3638 — 232 363 DN125 500 20009 — 2503' — 1600 2500 139.7 39.7 20' — 258 — 16 25 290 365 363 363 232 363 5 5.563 2000 2517 2503 2503 1600 2500 141.3 20 25 25 25 16 25 s _ _ _ 59 159 _ _ 2503' — — — _ 258 —6.500 — — 29010 — 3638 — — 363 200010 — 2503' — — 2500 1651 2010 — 258 — — 25 6 Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems -40° F/C and above. Please see the Victaulic Installation Manual 1-009N for details concerning when supplemental lubrication is required. 7 cULus listed for DIN 2458 (EN 10220) 2.6 mm pipe wall. 8 FM approved for BS 1387 (EN 10255) Medium 3.6 mm pipe wall. 9 cULus listed for EN 10220 4.0 mm pipe wall. 10 cULus listed for EN 10255 4.5 mm pipe wall. 11 With optional stainless steel fasteners, cULus Listed to 175psi/1207 kPa/12 bar and FM Approved to the FM ratings shown in the above table. The stainless steel fasteners have a marking designation of "316" on the end face of the bolt. 12 FM approved for 0.188" pipe wall. 13 cULus listed for 0.188" pipe wall. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 5 ✓ctaulid victaulic.com 5.0 PERFORMANCE (CONTINUED) Style 009N Two -Bolt Installation -Ready Coupling Listings/Approvals6 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approval agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Size cULus FIA VdS LPCB Actual Outside Nominal Diameter Sch.10 Sch.40 Sch.10 Sch.40 psi psi psi psi psi psi inches inches kPa kPa kPa kPa kPa kPa DIN mm bar bar bar bar bar bar 300 365 300 363 232 363 6 6.625 2068 2517 2068 2503 1600 2500 DN150 168.3 20 25 20 25 16 25 290 — 363' — — — 8.515 2000 — 2503' — — — 216.3 20 — 25' — — — 300 365 30012 363 232 363 8 8 8.625 2068 2517 206812 2503 1600 2500 D 219.1 20 25 1 2012 25 1 16 1 25 30013 300 30012 300 — — 10 .7 10.750 206813 2068 206812 2068 — DN250 2 0 2013 20 2012 20 — 30013 300 25012 300 — — 12 12.750 .75 206813 2068 172012 2068 — — DN300 323 2013 20 1712 20 — — 6 Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems -400 F/C and above. Please see the Victaulic Installation Manual 1-009N for details concerning when supplemental lubrication is required. 7 cULus listed for DIN 2458 (EN 10220) 2.6 mm pipe wall. 8 FM approved for BS 1387 (EN 10255) Medium 3.6 mm pipe wall. 9 cULus listed for EN 10220 4.0 mm pipe wall. 10 cULus listed for EN 10255 4.5 mm pipe wall. 11 With optional stainless steel fasteners, cULus Listed to 175psi/1207 kPa/12 bar and FM Approved to the FM ratings shown in the above table. The stainless steel fasteners have a marking designation of "316" on the end face of the bolt. 12 FM approved for 0.188" pipe wall. 13 cULus listed for 0.188" pipe wall. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 6 ✓ctaulid victaulic.com 5.1 PERFORMANCE Style 109 One -Bolt Installation -Ready Coupling Listings/ApprovalS15 The information provided below is based on the latest listing and approval data at the time of publication. Listings/ Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Size cULus FM VdS LPCB Actual Outside Sch.10 Sch.40 Sch.10 Sch.40 Nominal Diameter psi psi psi psi psi psi inches inches kPa kPa kPa kPa kPa kPa DIN mm bar bar bar bar bar bar 365 365 365 365 232 363 11/4 1.660 2517 2517 2517 2517 1600 2503 DN32 42.4 25 25 25 25 16 25 365 365 365 365 232 363 11h 1.900 DN40 48.3 2517 2517 2517 2517 1600 2503 25 25 25 25 16 25 365 365 365 365 232 363 2 2.375 DN50 60.3 2517 2517 2517 2517 1600 2503 25 25 25 25 16 25 365 365 365 365 — — 21/2 2.875 2517 2517 2517 2517 — — 73.0 25 25 25 25 — — 365 365 365 365 232 363 3.000 2517 2517 2517 2517 1600 2503 DN65 76.1 25 25 25 25 16 25 365 365 365 365 232 363 3 3.500 DN80 88.9 2517 2517 2517 2517 1600 2503 25 25 25 25 16 25 300 365 300 300 — 290 4 4.500 DN100 114.3 2068 2517 2068 2068 — 2000 20 25 20 20 — 20 15 Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems -40° F/C and above. Please see the Victaulic Installation Manual 1-109 for details concerning when supplemental lubrication is required. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 7 ✓ctaulid victaulic.com 5.2 PERFORMANCE Specialty Pipe Style 009N Two -Bolt Installation -Ready Coupling Listings/Approvals Size Pressure Rating cULus FM psi psi inches kPa kPa Pipe Type DN bar bar 1 1/4-4 300 EF DN32 — DN100 2068 N/A 20 300 300 EL 1 1/4-2 2068 2068 DN32 — DN50 20 20 300 ET40 1 1/4-2 2068 N/A DN32 — DN50 20 300 EZF 3-4 2068 N/A DN80 — DN100 20 300 300 EZT 1 1/4 — 2 2068 2068 DN32 — DN50 20 20 300 FF 11/2-4 2068 N/A DN40 — DN100 20 300 300 1 2 DN32 — DN50 2068 2068 IL 20 20 300 300 1 1/4-4 2068 2068 DN32— DN 100 20 20 MF 175 175 6 DN150 1205 1205 12 12 300 300 rMT 1 1/4 — 2 2068 2068 DN32 — DN50 20 20 300 MILT 1/4-2 N/A 2068 DN32 — DN50 DN32 20 300 TF 21/2-4 N/A 2068 73.0 mm — DN100 20 175 300 WG5, WG5E, WF5, WG7, WG7E, WL7 1 1/4-4 1205 2068 DN32 — DN100 12 20 300 300 WLS 1 1/4-2 2068 2068 DN32 — DN50 20 201& NOTES • EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF = EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF = Fire -Flo steel pipe manufactured by Youngstown Tube Co. • GL = GL steel pipe manufactured by Wheatland Tube Co. • MF = Mega -Flow steel pipe manufactured by Wheatland Tube Co. • MT = Mega -Thread steel pipe manufactured by Wheatland Tube Co. • MILT = MILT steel pipe manufactured by Wheatland Tube Co • TF = Tex -Flow steel pipe manufactured by Tex -Tube Co. • WG5, WG5E, WF5 = WGalweld 5, WGalweld 5E, WFlow 5 steel pipe manufactured by Wuppermann Stahl GmbH. • WG7, WG7E, WL7 = WGalweld 7, Wgalweld 7E, WLight 7 steel pipe manufactured by Wuppermann Stahl GmbH • WLS = WLS steel pipe manufactured by Wheatland Tube Co. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com ✓ctaulid victaulic.com 5.3 PERFORMANCE Specialty Pipe Style 109 One -Bolt Installation -Ready Coupling Listings/Approvals Size Pressure Rating cULus FM inches psi psi kPa kPa Pipe Type DN bar bar 300 11/a 21/z N/A 2068 DN32 — 73.0 mm 20 300 EF 1 1/z — 21/z 20668 N/A DN40 — 73.0 mm 20 300 300 3-4 DN80 — DN100 2068 2068 --Ami 20 20 300 1 1/4 — 2 DN32 — DN50 N/A 2068 20 Easy -Flow 3-4 N/A 300 2068 DN80 — DN100 20 300 EL 11/4-2 N/A 2268 DN32 — DN50 300 300 ET40 11/4 — 2 2068 2068 DN32 — DN50 20 20 300 11/a 2 N/A 2068 DN32 — DN50 20 EZT 300 1 1/z — 2 2068 N/A DN40 — DN50 20 300 300 FF 11/2-4 20268 2068 DN40 — DN100 20 300 GL 11/4 — 2 N/A 2068 DN32— DN50 300 300 MF 11/4 — 4 20268 2068 DN32 — DN100 6M 20 300 300 11/4 — 2 MT DN32 — DN50 2068 2068 20 20 300 300 MLT 1 1/4 — 2 2068 2068 DN32 — DN50 20 20 NOTES • EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • Easy -Flow = Easy -Flow steel pipe manufactured by Borusan Mannesmann Boru. • EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF = Fire -Flo steel pipe manufactured by Youngstown Tube Co. • GL = GL steel pipe manufactured by Wheatland Tube Co. • MF = Mega -Flow steel pipe manufactured by Wheatland Tube Co. • MT = Mega -Thread steel pipe manufactured by Wheatland Tube Co. • MLT = MLT steel pipe manufactured by Wheatland Tube Co. • TF = Tex -Flow steel pipe manufactured by Tex -Tube Co. • WG7, WG7E = WGalweld 7 and WGalweld 7E steel pipe manufactured by Wuppermann Stahl GmbH. • WLS = WLS steel pipe manufactured by Wheatland Tube Co. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 9 ✓ctaulid victaulic.com 5.3 PERFORMANCE (CONTINUED) Specialty Pipe Style 109 One -Bolt Installation -Ready Coupling Listings/Approvals Size Pressure Rating cULus FM inches psi psi kPa kPa Pipe Type DN bar bar 300 2 1/2 - 4 TF 73.00 mm - DN100 2068 20 300 1 1/4 - 2 N/A 2068 DN32 - DN50 20 WG7, WG7E 300 3-4 N/A 2068 DN80-DN100 20 300 WLS 1 '/4 - 2 N/A 7 2068 DN32 - DN50 � 1 20 NOTES • EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • Easy -Flow = Easy -Flow steel pipe manufactured by Borusan Mannesmann Boru. • EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF = Fire -Flo steel pipe manufactured by Youngstown Tube Co. • GL = GL steel pipe manufactured by Wheatland Tube Co. • MF = Mega -Flow steel pipe manufactured by Wheatland Tube Co. • MT = Mega -Thread steel pipe manufactured by Wheatland Tube Co. • MLT = MLT steel pipe manufactured by Wheatland Tube Co. • TF = Tex -Flow steel pipe manufactured by Tex -Tube Co. • WG7, WG7E = WGalweld 7 and WGalweld 7E steel pipe manufactured by Wuppermann Stahl GmbH. • WLS = WLS steel pipe manufactured by Wheatland Tube Co. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 10 ✓ctaulid victaulic.com 6.0 NOTIFICATIONS A WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. NOTICE • Victaulic does not recommend the use of any furnace butt -welded pipe with sizes 2'VDN50 and smaller Victaulic gasketed joint products. This includes, but is not limited to, ASTM A53 Type F pipe. 7.0 REFERENCE MATERIALS 05.01: Seal Selection Guide 25.01: Original Groove System (OGS) Groove Specifications 1-009N: Installation Instructions Fire Lock EZTm Rigid Coupling Style 009N 1-100: Victaulic Field Installation Handbook 1-109: Installation Instructions FireLockTM One -Bolt Rigid Coupling Style 109 I-ENDCAP: Victaulic End Caps Installation Instructions I -IMPACT: Impact Tool Usage Guidelines AN-001: Application Notification - Potential Incompatibility of Type F Pipe, Sizes NIPS 2" 1 DN50 and Smaller User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 11 ✓ctaulic® Victaulic° Flexible Coupling X'4taulic, Style 75 06.05 R3m6L tvaa7 � 1 — 87DN25 — DN200 Exaggerated for clarity 1.0 PRODUCT DESCRIPTION Available Sizes • 1 — 8"/DN25 — DN200 Pipe Material • Carbon steel • Stainless steel • For exceptions see section 6.0 Notifications Maximum Working Pressure • Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) up to 500 psi/3447 kPa/34 bar • Working pressure dependent on material, wall thickness and size of pipe Application • Joins standard roll grooved and cut grooved pipe, as well as grooved fittings, valves and accessories • Provides a flexible pipe joint which allows for expansion, contraction and deflection • Up to 50% lighter in weight than standard Victaulic Style 77 or Style 177N flexible couplings 2.0 CERTIFICATION/LISTINGS c @uS <FM> V LPCB LISTED NOTES • Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide. • See publication 02.06: Victaulic Potable Water Approvals ANSI/NSF for potable water approvals if applicable. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Submitted By Date Spec Section Paragraph Approved Date victaulic.com 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. 1 iictaulrc victaulic.com 3.0 SPECIFICATIONS — MATERIAL ❑ Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, Grade ❑ 65-45-15, is available upon special request. ❑ Housing Coating: (specify choice) Standard: Orange enamel ❑ Optional: Hot dipped galvanized Optional: Contact Victaulic with your requirements for other coatings. Gasket: (specify choice') Grade "E" EPDM EPDM (Green stripe color code). Temperature range —30°F to +230°F/-34°C to +110°C. May be specified for hot water service within the specified temperature range plus a variety of dilute acids, oil -free air and many ❑ chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot +180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR USE WITH PETROLEUM SERVICES OR STEAM SERVICES. Grade "T" Nitrile Nitrile (Orange stripe color code). Temperature range —20OF to +180°F/-290C to +82°C. May be specified for ❑ petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; not compatible for hot dry air over +140°F/+60°C and water over +150°F/+66°C. NOT COMPATIBLE FOR USE WITH HOT WATER. Others For alternate gasket selection, reference publication 05.01: Victaulic Seal Selection Guide - Elastomeric Seal Construction. Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should ❑ always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice2) Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (M10-M16) Class 8.8 (M20 and greater). Carbon steel hex nuts meeting the mechanical property requirements of ASTM A563 Grade B (imperial - Heavy Hex nuts) and ASTM A563M Class 9 (metric - ❑ hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FES, finish Type III (imperial) or Type II (metric). Optional (imperial): Stainless steel oval neck track bolts meeting the mechanical property requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy nuts meeting the mechanical property requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling reducing coating. 2 Optional bolts/nuts are available in imperial sizes only. 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com ✓ct:auliic victaulic.com 4.0 DIMENSIONS Style 75 Flexible Coupling EMM. IF r I ►:� I� Pipe End Deflection from Size Separation3 Centerline3 Bolt/Nut Dimensions Weight Actual Outside Approx. Nominal Diameter Allowable Per Cplg. Pipe Qty. Size x Y Z (Each) inches inches inches inches/ft. imperial inches inches inches lb DIN mm mm Degrees mm/m metric mm mm mm kg 1 1.315 0-0.06 1 2-43' 0.57 2 ;% x 2 2.38 4.27 1.77 1.3 DN25 33.7 0-1.6 48 M10 x 51 61 108 45 0.6 1 1/4 1.660 0-0.06 2°-10 0.45 2 ;%x 2 2.68 4.61 1.77 1.4 DN32 42.4 0-1.6 38 M10 x 51 68 117 45 0.6 1 1/2 1.900 0-0.06 - 1056 0.40 2 4ix 2 2.91 4.82 1.77 1.5 DN40 48.3 0-1.6 33 M10 x 51 74 122 45 0.6 2 2.375 0-0.06 - 1031 0.32 2 %x2 3.43 5.22 1.88 1.7 DN50 60.3 0-1.6 26 M10 x 51 87 133 48 0.8 2 1/2 2.875 0-0.06 1 -15 0 0.26 2 ;%x 2 3.88 5.68 1.88 1.9 73.0 0-1.6 22 M 10 x 51 98 144 48 0.9 3.000 0-0.06 - 1012 0.26 2 % x 2 4.00 5.90 1.88 1.9 DN65 76.1 0-1.6 22 M10 x 51 102 150 48 0.9 3 3.500 0-0.06 1 o-2 0.22 1/2 x 2 3/4 4.50 7.00 1.88 2.9 DN80 88.9 0-1.6 18 M12 x 70 114 178 48 1.3 31/2 4.000 0-0.06 00 -54' 0.19 2 1/2 x 2 3/4 5.00 7.50 1.88 2.9 DN90 101.6 0-1.6 16 M12 x 70 127 191 48 1.3 4 4.500 0-0.13 10 36' 0.34 2 1/2 x 2 3/4 5.80 8.03 2.13 4.1 DN100 114.3 0-3.2 28 M12x70 147 204 54 1.9 4.250 0-0.13 1 °-41' 0.35 2 1/2 x 2 3/4 5.55 7.79 2.13 3.7 108.0 0-3.2 29 M 12 x 70 141 198 54 1.7 5.000 0-0.13 10 -26 0.25 2 ;%x 31/4 6.13 9.43 2.13 5.5 127.0 0-3.2 21 M16x83 156 240 54 2.5 5.250 0-0.13 0.28 # x 31/4 6.55 9.37 2.13 6.0 133.0 0-3.2 - 1021 24 2 M16x83 166 238 54 2.7 5.500 0-0.13 1u -18 0.28 2 %x31/4 6.80 9.59 2.13 6.3 DN125 139.7 0-3.2 24 M16x83 1 173 244 54 2.9 5 5.563 0-0.13 - 1018 0.27 2 % x 31/4 6.88 10.07 2.13 5.8 141.3 0-3.2 23 M 16 x 83 175 256 54 2.6 6.000 0-0.13 - 1012 0.21 2 % x 31/4 7.38 10.48 1.88 6.2 152.4 0-3.2 18 M 16 x 83 187 266 48 2.8 6.250 0-0.13 1-y 0.24 2 %x31/4 7.63 10.49 2.13 6.8 159.0 0-3.2 20 M16x83 194 266 54 3.1 6.500 0-0.13 1 0-7 0.23 21 %x31/4 7.84 10.66 2.08 6.6 165.1 0-3.2 58 M16x83 199 271 1 53 3.0 6 6.625 0-0.13 0 1 5 0.23 2 %x31/4 8.00 11.07 2.13 7.0 DN150 168.3 0-3.2 18 M16x83 203 281 54 3.2 0-0.13 - 0051 0.18 2 3/4 x 41/4 10.19 13.75 2.32 13.2 200A4 216.3 0-3.2 46 M20 x 108 259 350 59 6.0 8 8.625 0-0.13 00 -50' 0.18 2 3/4 x 41/4 10.34 13.97 2.13 12.4 DN200 219.1 0-3.2 14 M20 x 108 263 355 59 5.6 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50% for 3/4-31IWIDN20-DN90; 25% for 4"/DN100 and larger. 4 Japanese Industrial Standard (JIS) size NOTE • Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com ✓ctauhc victaulic.com 5.0 PERFORMANCE Style 75 Flexible Coupling Size Maximum Actual Outside Working Maximum Nominal Diameter Pressure' End Loads inches inches psi lb DIN mm kPa N 1 1.315 500 680 DN25 33.7 3447 3025 1.660 500 1080 1 Y4 DN32 42.4 3447 4805 1 '/2 1.900 500 1420 DN40 48.3 3447 6320 2 2.375 500 2215 DN50 60.3 3447 9860 21/2 2.875 500 3245 73.0 3447 14440 3.000 500 3535 DN65 76.1 3447 15730 3 3.500 500 4800 DN80 88.9 3447 21360 3'/2 4.000 500 6300 DN90 101.6 3447 28035 4 4.500 500 7950 DN 100 114.3 3447 35380 4.250 450 6380 108.0 3103 28395 5.000 450 8820 127.0 3103 39250 5.250 450 9735 133.0 3103 43325 5.500 450 10665 DN125 139.7 3103 47460 5 5.563 450 10935 141.3 3103 48660 6.000 450 12735 152.4 3103 56670 6.250 450 13800 159.0 3103 61405 6 6.625 450 15525 DN 150 168.3 3103 69085 6.500 450 14930 165.1 3103 66412 450 25625 200A4 216.3 1 3103 113986 8 8.625 450 26280 DN200 219.1 3103 116945 4 Japanese Industrial Standard (JIS) size ' Working Pressure and End Load are total, from all internal and external loads, based on ANSI B36.10 sized carbon steel pipe, grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. NOTE • WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 11h times the figures shown. 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 59 ✓ctauhc victaulic.com 6.0 NOTIFICATIONS A WARNING • Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. NO • Victaulic RX grooving rolls must be ordered separately RX on the front of the roll sets. 'ICE They are identified by a silver color and the designation NOTICE • Victaulic does not recommend the use of any furnace butt -welded pipe with sizes NPS 2'7DN50 and smaller Victaulic gasketed joint products. This includes, but is not limited to, ASTM A53 Type F pipe. 7.0 REFERENCE MATERIALS 02.06: Victaulic Potable Water Approvals ANSI/NSF 05.01: Victaulic Seal Selection Guide - Elastomeric Seal Construction 06.15: Victaulic Pressure Ratings and End Loads for Victaulic Couplings on Steel Pipe 10.01: Victaulic Products for Fire Protection Pipings Systems - Regulatory Approval Reference Guide 17.01: Victaulic Pipe Preparation for Use on Stainless Steel Pipe With Victaulic Products 17.09: Victaulic Ductile Iron Grooved Couplings Performance Data for Stainless Steel Pipe 25.01: Victaulic Standard Groove Specifications 26.01: Victaulic Design Data 29.01: Victaulic Terms and Conditions of Sale 1-100: Victaulic Field Installation Handbook I-ENDCAP: Victaulic End Cap Installation Safety Instructions User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end -use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms "Patented" or "Patent Pending" refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. Note This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 5 ✓ctaulic Victaulic° Reducing Coupling XActaulic, Style 750 06.08 1.0 PRODUCT DESCRIPTION Available Sizes • 2 x 1" through 10 x 87DN50 x DN25 through DN250 x DN200 Pipe Material • Carbon steel • For exceptions reference section 6.0 Notifications NOTE • For other pipe materials, contact Victaulic. Maximum Working Pressure • 500 psi/3447 kPa • Working pressure dependent on material, wall thickness and size of pipe Application • Joins Original Groove System (OGS) roll grooved and cut grooved pipe, as well as OGS grooved fittings, valves and accessories • Permits direct reduction on piping run • Optional steel washer prevents telescoping of the smaller pipe inside the larger pipe during vertical system assembly Pipe Preparation • Cut or roll grooved in accordance with publication 25.01: Victaulic Standard Groove Specifications. 2.0 CERTIFICATION/LISTINGS c vL - <FM> SS LPCB ER[ uano NOTE • Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Submitted By Date Spec Section Paragraph Approved Date victaulic.com 06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved. 1 iictaulrc victaulic.com 3.0 SPECIFICATIONS — MATERIAL ❑ Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, ❑ Grade 65-45-15, is available upon special request. ❑ Housing Coating: (specify choice) Standard: Orange enamel. ❑ Optional: Hot dipped galvanized conforming to ASTM A153. Optional: Contact Victaulic with your requirements. Gasket: (specify choice') Grade "E" EPDM EPDM (Green stripe color code). Temperature range —30OF to +230°F/-340C to +110°C. May be specified for hot water service within the specified temperature range plus a variety of dilute acids, oil -free air and many chemical ❑ services. UL Classified in accordance with ANSI/NSF 61 for cold +730F/+230C and hot +180°F/+820C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR USE WITH PETROLEUM SERVICES OR STEAM SERVICES. Grade "T" Nitrile Nitrile (Orange stripe color code). Temperature range —20OF to +180°F/-290C to +82°C. May be specified for oil related services, including air with oil vapor, this gasket may be specified for temperatures rated up to +180°F/+82°C. For water related services, this gasket may be specified for temperatures rated up to +150°F/+66°C. For oil free, dry air services, this gasket may be specified for temperatures rated up to ❑ +140°F/+600C. NOT COMPATIBLE FOR USE WITH HOT WATER SERVICES OR STEAM SERVICES. Others For alternate gasket selection, reference publication 05.01: Victaulic Seal Selection Guide. 1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should Elalways be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts (specify choice2): Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (M10-M16) Class 8.8 (M20 and greater). Carbon steel hex nuts meeting the mechanical property requirements of ASTM A563 Grade B (imperial — heavy hex nuts) and ASTM A563M Class ❑ 9 (metric — hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FES, finish Type III (imperial) or Type II (metric). Optional: Stainless steel oval neck track bolts meeting the mechanical property requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy nuts meeting the mechanical property requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling reducing coating. Assembly Washer (optional): Galvanized carbon steel. 2 Optional bolts/nuts are available in imperial size only 06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 4 ✓ctaulrc victaulic.com 4.0 DIMENSIONS Style 750 Reducing Coupling Pipe End Size Separation3 Deflect. From CL3 Bolt/Nut Dimensions Weight Actual Outside Approximate Nominal Diameter Allowable Per Cplg. Pipe Qty. Size X Y Z (Each) inches inches inches in/ft inches inches inches inches lb DN mm mm Degrees mm/m mm mm mm mm kg 2 x 1 DN50 DN25 2.375 1.315 x 60.3 33.7 0 - 0.07 0 - 1.8 0° - 57' 0.20 17 2 3/a x 2 3.38 85 5.28 134 1.88 48 2.7 1.2 0 - 0.07 0 - 1.8 0° 57 0.20 17 2 1/8 x 2 3.38 85 5.28 134 1.88 48 2.0 1.0 1 1/z DN40 1.900 48.3 2 1/z 2 x DN50 2.875 2.375 73.0 x 60.3 0 - 0.07 0 - 1.8 0° 47' 0.16 14 2 3/a x 2 4.00 102 5.93 151 1.88 48 3.1 1.4 2 DN65 x DN50 3.000 2.375 76.1 x 60.3 0 - 0.07 0 - 1.8 0° 47 0.16 14 2 1/z x 2'/a 4.38 111 6.63 168 1.88 48 4.6 2.1 3 2 DN80 x DN50 3.500 2.375 88.9 x 60.3 0 - 0.07 0 - 1.8 0° 39' 0.13 11 2 /z x 2 3/a 4.75 121 7.13 181 1.88 48 4.9 2.2 0 - 0.07 0 - 1.8 0° 39' 0.13 11 2 /z x 2 3/a 4.75 121 7.13 181 1.88 48 4.3 2.0 21/z 2.875 73.0 0 - 0.07 0-1.8 0° 39' 0.13 11 2 /z x 2'/a 4.75 121 7.13 181 1.88 48 4.2 1.9 DN65 3.00 76.1 4 2 414.500 DN100 x DN50 2.375 114.3 x 60.3 0-0.13 0-3.2 1° 19 0.28 25 2 5/a x 3'/a 6.25 159 8.90 226 2.25 57 8.1 3.7 0-0.13 0 - 3.2 1 ° 19' 0.28 25 2 5/a x 31/a 6.25 159 8.90 226 2.25 57 8.6 3.9 21/2 2.875 73.0 0-0.13 0 - 3.2 1 ° - 19' 0.28 25 2 5/a x 31/a 6.25 159 8.90 226 2.25 57 6.9 3.1 DN65 3.000 76.1 0-0.13 0 - 3.2 1 ° - 19' 0.28 25 2 5/a x 31/a 6.00 152 8.90 226 2.25 57 6.7 3.0 3 DN80 3.500 88.9 5 4 x DN 100 5.563 4.500 141.3 x 114.3 0-0.13 0 - 3.2 1 ° 3 0.22 19 2 3/4 x 4 /a 7.18 182 10.70 272 2.13 54 11.2 5.1 4 165.1 x DN 100 6.500 4.500 165.1 x 114.3 0-0.13 0 - 3.2 0° 55' 0.19 16 2 3/4 x 41/a 8.63 219 11.90 302 2.25 57 15.2 6.9 6 x 4 DN150 DN100 6.625 4.500 x 168.3 114.3 0-0.13 0-3.2 0° - 52' 0.18 15 2 3/4 x 41/a 8.63 219 11.90 302 2.25 57 16.7 7.6 0-0.13 0-3.2 0° 52' 0.18 15 2 3/a x 41/a 8.31 211 11.90 302 2.25 57 12.9 5.9 5 5.563 141.3 8 DN200 x 165.1 8.625 6.500 219.1 x 165.1 0-0.13 0 - 3.2 0° 38 0.13 11 2 7/8 x 5 10.75 273 14.88 378 2.50 64 23.2 10.5 0-0.13 0 - 3.2 0° 38 0.13 11 2 /a x 5 10.81 275 14.88 378 2.50 64 22.4 10.2 6 DN 150 6.625 168.3 10 8 DN250 x DN200 10.750 8.625 273.0 x 219.1 0-0.13 0 - 3.2 0° - 25' 0.90 8 2 1 x 51/2 13.12 333 17.26 438 2.62 67 31.4 14.2 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes, these figures should be reduced by: 50 % for 3/a - 3 1/z"/DN20 - DN90; and 25% for 4"/DN100 and larger. NOTE • Metric thread size bolts are available (color -coded gold) for all coupling sizes upon request. Contact Victaulic for details. 06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 3 ✓ctauhc victaulic.com 5.0 PERFORMANCE Style 750 Reducing Coupling Size Maximum Working Maximum End Actual Outside Nominal Diameter Pressure4 Load4 inches inches psi lb DIN mm kPa N 2 1 2.375 1.315 350 500 DN50 x DN25 60.3 x 33.7 2413 2225 350 1000 11/2 1.900 DN40 48.3 2413 4450 21/2 2 2.875 2.375 500 2215 x DN50 73.0 x 60.3 3447 9850 2 3.000 2.375 350 1550 DN65 x DN50 76.1 x 60.3 2413 6900 3 2 3.500 2.375 350 1550 DN80 x DN50 88.9 x 60.3 2413 6900 500 3250 21/2 2.875 73.0 3447 14460 350 2475 3.00 DN65 76.1 2413 11010 4 2 4.500 2.375 350 1550 DN100 x DN50 114.3 x 60.3 2413 6900 350 2275 21/2 2.875 73.0 2413 10125 350 2475 3.000 DN65 76.1 2413 11014 500 4810 3 3.500 DN80 88.9 3447 21400 5 4 5.563 4.500 350 5565 x DN100 141.3 x 114.3 2413 24765 4 6.500 4.500 350 5565 165.1 x 114.3 165.1 x 114.3 2413 24765 6 4 6.625 4.500 350 5565 DN150 x DN100 168.3 x 114.3 2413 24765 350 8500 5 5.563 141.3 2413 37825 8 8.625 6.500 350 11610 DN200 x 165.1 219.1 x 165.1 2413 51645 350 12060 6 6.625 DN150 168.3 12413 53645 10 8 10.750 8.625 350 20450 DN250 x DN200 273.0 x 219.1 2413 90970 Working Presssure and End Load are total from all internal and external loads based on standard weight (ANSI) steel pipe standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe and material. Maximum working pressure rating based on larger pipe size. Maximum end load rating based on smaller pipe size. NOTES • WARNING: FOR ONE-TIME FIELD USE ONLY the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. • For joint pressure ratings on additional carbon steel wall thicknesses see publication 06.15. 06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com ✓ctauhc