APPROVED FIR2022-0136+Fire_Sprinkler_Plan+5.22.2023_7.14.02_AM+3558747RISER ROOM COMPONENTS LEGEND SPARE SPRINKLER STOCK SYMBOL LEGEND SCOPE OF WORK RIEDHAWK FIRE PROTECTION, LLC # QTY SIZE DESCRIPTION MANUFACTURER MODEL / PART NO REQUIRED SIGNAGE 1 1 4 GROOVED FLEXIBLE COUPLING GENERIC N/A N/A 2 1 21/2 DOUBLE CHECK DETECTOR ASSEMBLY DERINGER D30 N/A 3 1 4 x 2 GROOVED CONCENTRIC REDUCER GENERIC N/A N/A 4 1 1 2 CPVC GROOVED ADAPTER GENERIC N/A N/A 5 1 2 x 1 t/4 WATERFLOW SWITCH POTTER VSR-M N/A 6 1 2 TEST & DRAIN W/ t/2' PRESSURE RELIEF GLOBE UTD MAIN DRAIN (1) 7 1 t/2 PRESSURE GAUGE GENERIC N/A N/A 8 1 4 GROOVED CHECK VALVE RELIABLE N/A N/A 9 1 12 CT SPARE SPRINKLER STOCK BOX (SEE SPARE STOCK LEGEND) ARGCO 6510150 N/A NOTES: 1. SIGNAGE TO BE PROVIDED ON ALL CONTROL VALVES, DRAIN VALVES, TEST CONNECTIONS, FIRE DEPARTMENT CONNECTIONS AND SUPERVISORY AIRLINES AND INSTALLED AT LOCATIONS GIVEN PER NFPA 13 (2013) SECTION A6.10. 2. HYDRAULIC CALCULATION PLACARDS TO BE PROVIDED AND INSTALLED ON THE SYSTEM RISER PER NFPA 13 SECTION 25.5. a 22 22.5 23 SPRINKLER PIPING IN ATTIC SPACE TO BE TENTED WITH INSULATION TO HEATED 24 25 SPACE BELOW (BY OTHERS) F71 CPVC PIPE (TYP) 12" TJIs @ 16" O.C. SEMI -RECESSED PENDENT SPRINKLER (TYP) I 12" TJIs @ 16" O.C. 12" TJIs @ 16" O.C. A BUILDING CROSS SECTION (LOOKING NORTH) 0 2' 4' 8' 16' SCALE: 1 /8"=1 '-0" ENLARGED RISER ROOM PLAN B0 6" 1 ' 2' 4' SCALE: 1 /2"=Y-0" FIRE RISER SECTION C0 6" 1 ' 2' 4' SCALE: 1 /2"=1 '-0" HNGEN -3GONE FP POINT OF 6ONNECTION QTY SIZE DESCRIPTION 10 t/2 RELIABLE, F1 Res49, R3516, 4.9K, 155°F, WHITE 2 t/2 RELIABLE, F1 Res49, R3516, 4.9K, 175°F, WHITE 1 N/A RELIABLE SPRINKLER MODEL W4 WRENCH Approved DFM aMrls Burt South County Fire Date: 06/01 /2023 06-01-2023 PLAN REVIEW APPROVED WITH CONDITIONS: 1. SEE SOUTH COUNTY FIRE SPRINKLER STANDARDS REGARDING SIGNAGE REQUIREMENTS. (SOUTHCOUNTYFIRE.ORG) 2. AN ALL WEATHER MAP OF THE SPRINKLER SYSTEM REQUIRED IN THE RISER ROOM. 3. KNOX BOX REQUIRED AT RISER ROOM DOOR. (SOUTH COUNTY SPRINKLER STANDARD) 4. ALL CONTROL VALVES REQUIRED TAMPER SWITCHES INCLUDING DOUBLE CHECK VALVE CONTROL VALVES. 5. MEANS SHALL BE PROVIDED DOWNSTREAM OF BACKFLOW PREVENTION VALVES FOR FORWARD FLOW TESTS AT A MINIMUM FLOW RATE OF THE SYSTEM DEMAND. (NFPA 2013 6.8.8) 6. LOCKING KNOX FDC PLUG IS REQUIRED. (SOUTH COUNTY FIRE SPRINKLER STANDARD) 7. FDC STEM SHALL BE PAINTED RED WITH 4" WHITE ADDRESS OF THE BUILDING THE FDC SERVES. 8. FDC SHALL HAVE INFORMATION STATING "AUTO SPRINKLER". DFM BURT : 0� � �� 7\­�e-01���� 8 DI WATER LINE ■ -.................................................................. ■ENNEE.■ ■■■GENE ■GENEEN■ ■OGE.GG■ ............./.......................■............................... ........ ....... ........ NONE..■. ................................................. sL.GGi..........■-: ■ '\ ■ ■ ■ ■ o 6" PRIVATE HYDRANT ■ (BY OTHERS) O • ■ r� • : : Cn : ' M • N : : W ; Z. J ■ ■ W • Q • ■ ■ 0: ■ 00 ■ ■ : : ■ ■ ■ ■ ■ ' M ' N ■ ■ kOT U 1 rICPCJ) �u i v 1 1 i�iwj ; ♦� 21 ■ 8' DI WATER LI ■ \�.................■................................................................................................■.................................■................■■■■...■■■■■..■■■■....................................................................■........■....� ■ : ALL UNDERGROUND WORK TO BE DONE BY OTHERS SITE PLAN - FOR REFERENCE ONLY �Iu 0 4' 8' 16' 32' SCALE: 1/ 1 6"= 1'-0" X EXISTING SPRINKLER PIPING WITH LABEL X NEW WET STEEL SPRINKLER PIPE WITH LABEL X-X X NEW WET CPVC SPRINKLER PIPE WITH LABEL / PIPE HANGER u GROOVED RIGID COUPLING u GROOVED FLEXIBLE COUPLING 1 SEISMIC BRACE - LATERAL (PERPENDICULAR TO PIPE) 0 5 SEISMIC BRACE -LONGITUDINAL (PARALLEL TO PIPE) SEISMIC BRACE - LATERAL AND LONGITUDINAL — — — — — REMOTE AREA BOUNDARY XX HYDRAULIC NODE 7k 0" TS ELEVATION TAG ELECTRIC FIRE ALARM BELL �y FIRE DEPARTMENT CONNECTION - REMOTE FIRE HYDRANT - m- GATE VALVE VAULT ABBREVIATIONS ATR ALL -THREAD ROD BB BOTTOM OF BEAM CL CENTERLINE CTS CUT TO SUIT DN PIPE DOWN DR DROP FDC FIRE DEPARTMENT CONNECTION FF (OR AFF) ABOVE FINISH FLOOR FOC FACE OF CONCRETE FOW FACE OF WALL GALV GALVANIZED GOL GROOVE-O-LET IFOW INSIDE FACE OF WALL MT MECHANICAL TEE O.C. ON CENTER PIV POST INDICATOR VALVE POL THREADED PIPE-O-LET RC REDUCING COUPLING RN RISER NIPPLE SP SPRIG SS STAINLESS STEEL THR THREAD TS TOP OF STEEL OR TO STRUCTURE TYP TYPICAL UNO UNLESS NOTED OTHERWISE UP PIPE UP UNDERGROUND NOTES 01 -ALL UNDERGROUND WORK BY OTHERS. CONTRACTOR TO BE STATE LICENSED AND CERTIFIED TO INSTALL UNDERGROUND PIPING PER WAC 212-80. 02 -PIPE TYPE AND CLASS TO MEET LOCAL JURISDICTION APPROVAL. 03 -ALL UNDERGROUND PIPING SHALL HAVE 3 FEET MINIMUM BURY DEPTH TO TOP OF PIPE. 04 -ALL UNDERGROUND PIPING SHALL BE UL LISTED AND/OR FM APPROVED FOR FIRE PROTECTION. 05 -ALL UNDERGROUND PIPING SHALL BE RESTRAINED IN ACCORDANCE WITH THE SPECIFICATIONS AND NFPA 24 (2014). 06 -ALL UNDERGROUND PIPING SHALL BE HYDROSTATICALLY TESTED AT NOT LESS THAN 200 PSI OR 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 PSI (WHICHEVER IS GREATER) FOR TWO HOURS IN ACCORDANCE WITH NFPA 24. 07 -ALL UNDERGROUND PIPING SHALL BE FLUSHED IN ACCORDANCE WITH NFPA 24. FLOW THE REQUIRED RATE UNTIL WATER IS CLEAR AS INDICATED BY NO COLLECTION OF FOREIGN MATERIAL IN BURLAP BAGS AT OUTLETS. 4" - 490 GPM 10" - 2,400 GPM 6" - 880 GPM 12" - 3,520 GPM EST SATE zzath St sw T ,04 1LE- VILLAGE 2aath St SIN HILLWOOD 228th St SW 228th sT SIN I SITE WhirlyBall q 1 � D l� Safeway 23atn s< sw 1 � - Burlington Q 1 1 I I -r . 4 � � ,.a Costco Wholesale Q I Z / Ballinger Commons Apartment Homes - VICINITY MAP RED HAWK FIRE PROTECTION, LLC. (RHFP) WILL PROVIDE (1) WET PIPE AUTOMATIC SPRINKLER SYSTEM TO PROTECT THE ENTIRE PROPOSED NEW BUILDING. RHFP WILL START WORK AT 4" THREADED CONNECTION 6" AFF IN RISER ROOM ON LEVEL 1. ALL AREAS PROTECTED BY A WET SYSTEM MUST BE MAINTAINED BY OTHERS AT A MINIMUM 40°F TO PREVENT FREEZING. EXCLUSIONS PAINTING OR LABELING OF PIPE AND/OR EQUIPMENT ELECTRICAL WIRING OF ANY KIND INCLUDING BUT NOT LIMITED TO WATERFLOW SWITCH, ELECTRIC BELL, AND TAMPER SWITCHES. CENTRAL STATION MONITORING EQUIPMENT, WIRING AND SERVICES ALL UNDERGROUND WORK INCLUDING BUT NOT LIMITED TO: BACKFILL, SELECT FILL, BREAKING PATCHING, SAW CUTTING, LAWN REPAIR, LANDSCAPING, TREE REMOVAL, STERILIZATION, DEVELOPMENT FEES AND CITY CONNECTION. HEAT TRACING IF REQUIRED GENERAL NOTES 01 - SPRINKLER SYSTEM DESIGN PER NFPA #13R (2016), AND CITY OF EDMONDS (AHJ). 02 - ALL MATERIALS SHALL BE NEW AND UL AND/OR FM APPROVED. 03 - FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH NFPA #13 AND AUTHORITY HAVING JURISDICTION. 04 - IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT THROUGH OUT THE WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE, DELUGE, AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. 5- FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM OR ANY APPURTENANCES THEREOF. 06 - ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING, OR PATCHING TO BE BY OTHERS. 07 - 1" - 2" CPVC PIPE TO BE SCHED 80 CPVC WITH GLUE -ON CPVC FITTINGS. 08 - TYPICAL CPVC HANGER TO BE CPVC TYPE UNO. BUILDING CODE ANALYSIS OCCUPANCY CLASSIFICATION AND USE: R-2 BUILDING CONSTRUCTION TYPE: V-B APPLICABLE CODE(S): IBC (2018), IFC (2015) APPLICABLE STANDARDS: NFPA 13R (2016) NUMBER OF STORIES: 3 ACTUAL BUILDING HEIGHT: 38'-3" BUILDING AREA IN SQUARE FEET: 8,886 FT FIRE SPRINKLERS: YES FIRE ALARM: YES SMOKE CONTROL SYSTEM: NO SITE CLASS: D SEISMIC DESIGN CATEGORY: D OCCUPANCY CATEGORY: II SS: 1.32 S1: 0.50 SIDS: 0.88 SD1: 0.50 WATER FLOW INFORMATION WATERFLOW INFORMATION HAS BEEN PROVIDED BY LAKEHAVEN WATER DISTRICT. THE FOLLOWING INFORMATION OBTAINED FROM WATER FLOW MODEL RECEIVED 02/07/2022. STATIC PRESSURE: 65 PSI RESIDUAL PRESSURE: 20 PSI @ 1900 GPM MODELED HYDRANT LOCATION ON 236TH ST. DESIGN CRITERIA PER NFPA 13R (2016), CITY OF EDMONDS, AND PROJECT SPECIFICATION RESIDENTIAL WET SYSTEM RESIDENTIAL (NFPA 13R) 16' x 16' SPACING DESIGN DENSITY: 13 GPM @ 7 PSI / MOST DEMANDING 4 SPRINKLERS Ballinger Park g i 236th SI 1 Nile Shrine Golf C:_,!_•se I , m Regal CineIrre�"!� Mountlake © 1olyrood Cemetery D � 1 s Z 80 1 VALLEY AVE NW, SUITE D PUYALLUP, WA 98371 PHONE: (253) 840-9900 FAx (800) 591-4382 WA CL# REDHAHF90I0P NICET Stamp ........ W....ASHINGTON S.'T0NST---•••-•-+ � TATE � CERTIFICATE OF COMPETENCY ■ FIRE PROTECTION SPRINKLER SYSTEMS Travis Clifton Kinne co ■ 0835-1021-C Level Red Hawk Fire Protection, LLC N ■ i REDHAHF901QPI o ii ■ o■ Signature LE ■ i.............. .............. a Approvals Required CITY OF EDMONDS OWNER/ARCHITECT Revisions Contract With: KIRTLEY-GOLF ASSOCIATES LLC 2820 OAKES AVE B EVERETT, WA 98201 PM: JAMES SCHWARTZ Phone: (425) 231-8426 Email: JSchwartz@Kirtley-Cole.com Contract Name: HOUSING HOPE EDMONDS LUTHERAN 8215 236TH ST SW EDMONDS, WA 98026 Drawing Title GENERAL NOTES Key Plan RECEIVED May 22 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT F I R2022-0136 Date: April 27, 2023 Job Number: 70106 Designer: LAUREN MAIN Building Permit: Drawing No FP1 OF 2 NOT TO SCALE REDHAWK FIRE PROTECTION, LLC CC CD DESIGN NOTES 10 EXTERNAL WATER SOURCE AND RISER LOCATION. 20 PIPE AND SPRINKLERS LAID OUT TO AVOID STRUCTURAL BEAMS, HVAC DUCTWORK, LIGHTING AND ANY OTHER OBSTACLES. (TYP) OWALKWAY LOCATED ABOVE, FIRE PROTECTION REQUIRED BELOW. (TYP) FIRE SPRINKLER PLAN - FIRST FLOOR 0 2' 4' 8' 16' SCALE: 1 /8"=1 '-0" CEILING LEGEND CEILING BUILT UP DIRECTLY TO TJIs, FINISH HEIGHT TO BE 8'-0" O 3 O 131?/ 13A 13204 I 320 23p/ 13A [3202 p/ 23�A 3201 8' 0 g, i g _� 8 01 , 7 �I ® HI ,- 2 2 •� • 2 • ' 0 FP1 • LL • • • 2 2 2 2 2 2 co 2 • 201 JQ �0 202 ti ).5 ti O�v 23 �0�� SPRINKLER LEGEND Symbol Manufacturer SIN Model K-Factor Type Size Response Finish Temperature Note Quantity Reliable R3516 F1res49 4.9 Pendent '/2 Quick White 155 OF SEMI -RECESSED 103 Reliable RA1664 DH56 5.6 Sidewall % Quick Brass 155 OF DRY HEAD 8 Reliable R3516 F1Res49 4.9 Pendent '/2 Quick White 175 °F SEMI -RECESSED 2 Total =113 CC C Hydraulic Information Remote Area B OCCUPANCY CLASSIFICATION Residential 13R DENSITY (gpm/ft2) 0.10 for 355.31 ft2 (Actual 355.31 ft2) TOTAL HOSE STREAMS 100.00 TOTAL HEADS FLOWING 4 K-FACTOR 4.9 TOTAL WATER REQUIRED 154.69 TOTAL PRESSURE REQUIRED 29.661 BASE of RISER (gpm) 154.69 BASE of RISER (psi) 29.661 SAFETY MARGIN (psi) +34.905 (54.1%) [3504 � 133 3302 � 3301 � eo �� - ao 8,el I� 254 252 207 • O� 253 205 i 251 2 , 2 -� • ... 2 �� ��' • O• A • • • • 2 206 2 2 �I 2 2 2 2 • • • 204 203 O • ti ti� �O Q ).5 FIRE SPRINKLER PLAN - SECOND FLOOR FIRE SPRINKLER PLAN - THIRD FLOOR 0 2' 4' 8' 16' 0 2' 4' 8' 16' SCALE: 1 /8"=l'-0" SCALE: 1 /8"=1'-0" 0905 UNHEATED AREA FIG. 187 EWS W/ HANGER - BACKING NUTS —INSULATION FIRE SPRINKLER PIPING CPVC PIPE (1" - 2" ONLY) FIG. 187 HANGER TJI JOISTS AFCON FIG 187 TO WOOD JOIST CPVC / STEEL HANGER N.T.S INSULATION J AIR GAP REQUIRED TENTING PIPE AROUND ALL WET (BY OTHERS) SPRINKLER PIPING HEATED AREA PIPE TENTING (BY OTHERS) N.T.S S2CREWS W/ ( ) �—BACKING NUTS S2CREWS FIG. 188��_ HANGER FIG.29—/ 00.' HANGER (1'C 2V ON Y)� CPVC (1" ONLY) FIG. 188 HANGER n�H . 188 NGER TJI JOISTS AFCON FIG 188 TO WOOD JOIST CPVC / STEEL HANGER N.T.S TJI JOISTS TOLCO FIG 29 TO WOOD JOIST CPVC / STEEL HANGER N.T.S 801 VALLEY AVE NW, SUITE D PUYALLUP, WA 98371 PHONE: (253) 840-9900 FAX (800) 591-4382 WA CL# REDHAHF901 OP NICET Stamp WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS Travis Clifton Kinne N 0835 1021 C Level 3 N Red Hawk Fire Protection, LLC ° on REDHAHF901QP og'� /�.--f •� l�Ir�s i signature oEca�.x� � � Approvals Required CITY OF EDMONDS OWNER/ARCHITECT Revisions Contract With: KIRTLEY-COLE ASSOCIATES LLC 2820 OAKES AVE B EVERETT, WA 98201 PM: JAMES SCHWARTZ Phone: (425) 231-8426 Email: JSchwartz@Kirtley-Cole.com Contract Name: HOUSING HOPE EDMONDS LUTHERAN 8215 236TH ST SW EDMONDS, WA 98026 Drawing Title FIRE SPRINKLER PLANS Key Plan RECEIVED May 22 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT F I R2022-0136 Date: April 27, 2023 Job Number: 70106 Designer: LAUREN MAIN Building Permit: Drawing No. FP2 OF 2