APPROVED FIR2024-0090+Fire_Alarm_Plan+9.24.2024_6.58.58_AM+4518672REDHAWK
FIRE PROTECTION, LLC
WOODWAY HIGH SCHOOL PORTABLE P3
EDMONDS SD
FIRE ALARM SYSTEM
7600 212TH ST. SW, EDMONDS, WA 98020
SYMBOL LEGEND
SYMBOL QTY DESCRIPTION MOUNTING REQUIREMENTS SUPPLIER PART NUMBER
CONVENTIONAL FIRE ALARM PANEL
PART INCLUDES ENCLOSURE; MOUNT AT 72" TO TOP
FACP
-
SIMPLEX
4001 SERIES
EX
PHOTO SMOKE DETECTOR
4 SQUARE DEEP w/ 3" ROUND RING
s
1
SIMPLEX
4098-9714
MANUAL PULL STATION
4 SQUARE DEEP w/ 1 GANG RING; MOUNTED AT 48" TO TOP
�
2
SIMPLEX
2099-9754
120VAC VOLTAGE PROTECTOR for CONTROL PANELS
MOUNTS IN 1/2" OR 3/4" CABINET KNOCKOUT
®
1
w/ LOCKOUT & LABELS
SPACEAGE
E120V-GT
24VDC SURGE SUPPRESSOR; 2PR, 14-30VDC, 16-22AWG
4 SQUARE DEEP
ss
1
DITEK
DTK-2MHLP24FWB
REMOTE NAC POWER SUPPLY w/ ONBOARD FCM-1
PART INCLUDE BACKBOX; SURFACE MOUNT
APs
1
6.OA, 5- 3.OA NAC & 1- 0.5A AUX POWER
HONEYWELL
HPF-PS6 w/ FCM-1
1
WALL HORN w/ STROBE: WHITE
4 SQUARE DEEP; MOUNTED AT 80" TO BOTTOM
SYSTEM SENSOR
P2WL
L'J
SEE DEVICE DESIGNATION FOR STROBE cd SETTING
V
1
WALL HORN w/ STROBE: WHITE: WEATHERPROOF
SA-WBB BACK BOX: SURFACE MOUNT AT 80" TO BOTTOM
SYSTEM SENSOR
P2WK
[i]
SEE DEVICE DESIGNATION FOR STROBE cd SETTING
NOTES:
1- DEVICE SUBSCRIPT: NW=NEW RR=REMOVE & RELOCATE EX=EXISITNG TO REMAIN AC=ABOVE CEILING RB=RELAY BASE WP=WATERPROOF WG=WIRE GUARD ISO=ISO BASE
2- CABLEING SHOWN IS FOR CIRCUIT REFERENCE ONLY AND DOES NOT INTENDED TO INDICATE THE EXACT PATHWAY.
3- DEVICES SHOWN ON DRAWINGS IN GRAY SCALE ARE EXISTING DEVICES AND MAY NOT BE INCLUDED IN THIS SYMBOL LEGEND UNLESS NOTED.
4- HORN/STROBE DECIBLE SETTING TO BE DETERMINED ON SITE, UNLESS OTHERWISE NOTED ON THE DRAWINGS. CAN BE FIELD ADJUSTED AT REQUEST OF AHJ.
5- ALL DEVICES WITH A WP SUBSCRIPT WILL REQUIRE THE USE OF A OUTDOOR OR WP BACKBOX.
WIRE LEGEND
SYMBOL DESCRIPTION THHN FPL FPLP WET COLOR CODING CIRCUIT TYPE NOTES
A
1 PAIR 18AWG FIRE RATED CABLE
YES
970
D60980
AQ293
CONVENTIONAL (IDC) CIRCUIT
C
1 PAIR 14AWG FIRE RATED CABLE
YES
972
60993B
AQ226
AUDIBLE (NAC) CIRCUIT
NOTES:
** DIFFERENT COLORS/STRIPE COMBINATIONS TO BE USED FOR DIFFERENT CIRCUIT TYPES. LABEL ALL CIRCUITS ACCORDINGLY
1- WIRE MANUFACTURER IS FOR REFERENCE PURPOSE ONLY. WHEN USING OTHER MANUFACTURE, ENSURE PROPER CROSS REFERENCE
2- FPLP CAN BE USED IN MOST ALL APPLICATIONS WITH THE EXCLUSION OF WET AND CIRCUIT INTEGRITY REQUIREMENTS
3- INSTALL WIRING PER NEC. USE CABLE TYPE CONSISTENT WITH NEC REQUIREMENTS, IE: PLENUM, RISER, UNDERGROUND, ETC.
4- THE "Y" FIBER OPTIC CABLE LISTED IS A BELDEN CABLE PART NUMBER AS WEST PENN NO LONGER SUPPORTS FIBER OPTIC CABLE
5- THIS CABLE MUST BE INSTALLED IN A CONTINUOUS PATH POINT-TO-POINT. ABSOLUTLEY NO SPLICES ARE ALLOWED.
6- THIS IS A SPECIFIC CABLE, NO ALTERNATES ARE ALLOWED
=LAGNOTES
NOTE # DESCRIPTION
25 PROVIDE HINGED PLASTIC COVER FOR FIRE ALARM MANUAL PULL STATION (TYP.)
NAC Circuit Load, Voltage Drop & Battery Load Calculations
APS-1 A
APS Name: APS-1A
Location: NEXT TO FACP IN STADIUM
P.S. Type: HPF-PS6
Part#: Description:
Standby: Alarm:
P4
Output #1
NAC Sync
N1A
Output #2 Output #3
NAC Sync NAC Sync
X-X X-X
Output #4
Not Used
X-X
Output #5
Not Used
X-X
Output #6 Output #7
Not Used Not Used
X-X X-X
Aux
Power
X-X
Total Qty
0.1390 0.1570
P2WL (135) Wall Horn w/ Strobe set at 135cd
0.0000 0.1960
1
1
P2WK (75) Wall Horn w/ Strobe set at 75cd, WP
0.0000 0.1760
1
1
# Devices per Circuit:
Total Standby Circuit Calculated Amps (3):
Total Alarm Circuit Calculated Amps (1):
Wire Gauge Used (awg):
Circuit Length (ft):
Estimated Voltage Drop (dc):
Estimated EOL Voltage (dc):
Calculated Voltage Drop %:
2
0.000
0.372
14AWG
100
0.19
23.81
1 0.8%
0
0
0
0
0
0
0
2
0.000
0.000
0.000
0.000
0.000
0.000
0.0000
0.1390
0.000
0.000
0.000
0.000
0.000
0.000
0.0000
0.1570
14AWG
14AWG
14AWG
14AWG
14AWG
14AWG
0
0.00
24.00
14AWG
0
0.00
24.00
Total
Amps
Required
0.372
0
0
0
0
0
0.00
0.00
0.00
0.00
0.00
24.00
24.00
24.00
24.00
24.00
1 0.0%
0.0%
0.0%
0.0%
0.0%
0.0% 0.0%
1) Current Draw Measurement based on: UL1971, 16-33V, DC, High db & Temporal Patten
2) Some Outdoor/WP Devices have the same Measured Current Draw as the Indoor Devices and may not listed separately above.
3) When the APS is configured for "Doors", Output #4 shutsdown on loss of AC Power. Therefore no "Standby" Current Draw is shown
BATTERY LOAD CALC for APS-1 A: NAC P.S. Max Rating: 6.000
Hours Standby: 24 Total Standby Current: 0.1390
Minutes Alarm: 5 Total Alarm Current: 0.5290
Backup Generator? No
Voice Evacuation? No Spare Circuit Capacity: 20%
Military? No Spare Battery Load Factor: 25%
MAXIMUM CHARGER CAPACITY IS: 33AH
Total Amps Required: 0.372 % Used:
Total Hours Required for Standby (AH):
Total Hours Required for Alarm (AH):
Minimum Battery Size Needed (AH):
Spare Battery Capacity Required:
Actual Battery Size Required (AH):
Total AH Rated Batteries Supplied: =
6%
3.34
0.04
3.38
0.85
4.23
7.0
I
T
I
I
SYMBOL & WIRE STYLE IDENTIFICATION
-Box 2C,D WIREXABLE INDENTIFIER
2C = 2 TYPE "C" CABLES
D =1 TYPE "D" CABLE
oPE Rac�EW CABLE INSTALLATION TYPES
V7
S- ��- � �"� -S DEMO OR REMOVE EQUIPMENT FROM SERVICE
S- 2HR- -2HR -S RACEWAY REQUIRED TO BE INSTALLED UTILIZING
1 of 3 NEC APPROVED 2HR METHODS OF PROTECTION
--S AC POWER (120, 240 or 480VAC)
--]-ENLARGED VIEW BOUNDRY
i XTOP LINE INDICATES THE DETAIL #
XX ' BOTTOM LINE INDICATES THE SHEET #
XX
END of LINE RESISTOR ELEVATION DETAIL
CEILING INFO
FLAG NOTE SHEET NOTE
EQUIPMENT NOTE
- - - _ _ ADA ROOM, AREA OR
ZONE BOUNDRIES
- - - - 2HR RATED WALL
1HR RATED WALL
A
EXISTING STADIUM
FULL HEIGHT WALL
PARTIAL HEIGHT WALL
A,C C -CD C�- A
EX
APS FACP 120VAC
DEDICATED
MOUNT NEW APS
NEXT TO EXISTING
FACP IN STADIUM
CUSTODIAN ROOM
PORTABLE FIRE ALARM LAYOUT
SCALE:1/8" = 1'-0"
INSTALLATION & GENERAL WIRING NOTES:
GENERAL NOTES:
1.
INSTALLATION SHALL BE ACCOMPLISHED IN STRICT COMPLIANCE WITH NFPA, LOCAL
AND STATE AHJ's, NEC AND CONTRACT DRAWINGS
2.
WIRE ROUTING IS DIAGRAMMATIC IN NATURE ONLY AND NOT INTENDED FOR ACTUAL
CONDUIT ROUTING.
2.1.
WIRING SHOWN GOING "THRU" A DEVICE DOES NOT NEED TO TERMINATE AT
THAT DEVICE IF DEVICE IS NOT ON THAT CIRCUIT.
2.1.1.
MEANING VOICE, STROBE/NAC CIRCUITS DO NOT NEED TO PASS THRU SLC
DEVICES & SLC CIRCUITS DO NOT NEED TO PASS THRU NOTIFICATION
DEVICES. POWER CIRCUITS ONLY NEED TO GO FROM POWERED DEVICE
TO POWERED DEVICE.
3.
ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ.
4.
VERIFY ALL LOCATIONS OF DEVICES WITH ELECTRICAL/ARCHITECTURAL PLANS.
SCALE AND PLACE ALL DEVICES PER ELECTRICAL/ARCHITECTURAL PLANS.
5.
ALL CIRCUITS WILL BE PROPERLY TAGGED AND TESTED FOR OPENS, SHORTS,
GROUNDS AND PROPER "END -OF -LINE" RESISTANCE. EACH CIRCUITS METER
READING MUST BE DOCUMENTED AND PRESENTED TO RED HAWK FIRE PROTECTION
FIELD TECHNICIAN UPON ARRIVAL ONSITE FOR STARTUP & CHECKOUT.
6.
AS-BUILTS:
6.1.
A SET OF INSTALLATION AS -BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND
CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE BY RED
HAWK FIRE PROTECTION TECHNICIAN.
6.2.
AS-BUILTS SHALL BE KEPT ORDERLY AND BE CLEARLY MARKED WITH
DIFFERENT COLOR PENS FOR EACH CIRCUIT AND/OR CIRCUIT TYPE. AS-BUILTS
MUST INDICATE CHANGES TO THE FINAL DEVICE INSTALLED LOCATIONS IF NOT
INSTALLED AT LOCATION SHOWN ON DESIGN DOCUMENTS.
6.3.
AS -BUILT REDLINES NOT PROVIDING THIS INFORMATION WILL BE RETURNED TO
THE INSTALLATION CONTRACTOR FOR CORRECTION. RED HAWK FIRE
PROTECTION IS NOT RESPONSIBLE FOR THESE DELAYS.
7.
AGREEMENT AND CONFIRMATION OF ALL MILESTONE EVENTS WILL BE MADE WITH
RED HAWK FIRE PROTECTION PROJECT MANAGER.
8.
ALL RED HAWK FIRE PROTECTION FIELD SERVICES MUST BE SCHEDULED WITH RED
HAWK FIRE PROTECTION PROJECT MANAGER WITH A MINIMUM OF 14 WORKING DAYS
ADVANCE NOTICE.
9.
DO NOT INSTALL LINE VOLTAGE IN SAME CONDUIT AS POWER LIMITED CABLES.
FIRE ALARM SPECIFIC NOTES:
1.
SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 36" OF ANY AIR DIFFUSER.
2.
2019 NFPA 72-17.7.1.12.3 REQUIRES THAT SMOKE DETECTORS SHALL NOT BE
INSTALLED UNTIL AFTER FINAL CONSTRUCTION CLEAN-UP.
2.1.
ANY SMOKE DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO CLEAN-UP MUST
BE CLEANED OR REPLACED AND WILL BE INVOICED ON A T&M BASIS.
3.
WALL MOUNTED NOTIFICATION DEVICES BACKBOX BETWEEN A MINIMUM OF 80" AFF TO
A MAXIMUM OF 96" AFF.
3.1.
DEVICES THAT ARE UNABLE TO BE MOUNTED WITHIN THAT RANGE MUST BE
VERIFIED BY RED HAWK FIRE PROTECTION PRIOR TO INSTALLATION.
3.2.
SEE FLOOR PLANS FOR CANDELA RATING OF EACH DEVICE INSTALLED.
4.
ALL MANUAL PULL STATIONS ARE TO BE MOUNTED AT A HEIGHT NO GREATER THAN 48"
TO TOP AND NO LOWER THAN 36" TO BOTTOM (PER ADA REQUIREMENTS).
5.
FIELD VERIFY ALL SPRINKLER MONITORING DEVICES WITH FIRE PROTECTION
CONTRACTOR
6.
FIELD VERIFY ALL HVAC, FAN CONTROL, FIRE/SMOKE DAMPERS AND DUCT DETECTORS
LOCATIONS WITH MECHANICAL CONTRACTOR
7.
FACP SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF RED HAWK FIRE
PROTECTION TECHNICIANS.
8.
NO TAPPING OF SIGNALING OR INITIATING ZONE CIRCUITS ARE ALLOWED. T-TAPPING
OF STYLE 4 ADDRESSABLE CIRCUITS IS ALLOWED PROVIDING A SPLICE IS
PROFESSIONALLY INSTALLED, POLARITY IS OBSERVED AND SHIELDS ARE
CONTINUOUS AND FREE OF GROUNDS. SHIELDS MUST BE TERMINATED AT FACP ONLY.
8.1.
CABLE SHIELDS SHALL BE SPLICED TOGETHER AT EVERY JUNCTION BETWEEN THE
FACP AND THE LAST DEVICE ON EACH CABLE RUN. SHIELDS AND OTHER FIRE
ALARM CONDUCTORS (EXCEPT POWER GROUNDS) SHALL BE INSULATED AND
COMPLETELY FREE FROM CONDUIT OR EARTH GROUNDS. SHIELDS WILL BE TIES
TO GROUND ONLY AT THE FACP BY THE RED HAWK FIRE PROTECTION FIELD
TECHNICIAN.
9.
THE SYSTEM SHALL BE MONITORED BY A U.L. LISTED MONITORING STATION BEFORE
AHJ TEST.
10.
AS-BUILTS ARE REQUIRED AT TIME OF AHJ ACCEPTANCE. RED HAWK FIRE
PROTECTION REQUIRED ELECTRICAL RED LINES WITHIN 2 WEEKS PRIOR TO AHJ
TESTS.
10.1.
EACH CIRCUIT (SLC, NAC OR POWER) MUST BE CLEARLY IDENTIFIED WITH A
DISTINCT COLOR
10.2.
EACH NAC CIRCUIT MUST BE CLEARLY MARKED AS TO WHICH DEVICES ARE ON
EACH CIRCUIT AND IN THE ORDER THE DEVICES ARE WIRED TO COMPLETE THE
CIRCUIT.
FIRE ALARM - SEQUENCE OF OPERATIONS
PANEL OUTPUTS
o
Cn
m
0
Of�
>,
I_-cv
o
cn
06
co
o
�
U_
c
W
N
Q
N
C
N
W
F
a
Alarm From
�
0
0
0.0.0
E
Area Smoke or Heat Detector
X
X
X
X
Manual Station
X
X
X
X
NOTES: X = ACTIVATE
PROJECT CONTACT INFORMATION:
CUSTOMER:
NAME: SCOTT'S ELECTRIC SERVICE, LLC
ADDRESS: 23811 STATE ROUTE 2
MONROE, WA 98272
CONTACT: BRIAN FURRIER
PHONE: 206-679-3613
FAX:
EMAIL: Brian@scottselectricservice.com
FIRE ALARM / LIFE SAFETY PROVIDER:
NAME: RED HAWK FIRE PROTECTION
ADDRESS: 917 134TH AVE SW SUITE B-3
EVERETT, WA 98204
PHONE: 425-818-3313
FAX:
SALESMAN: JEREMY MUNSON JeremyM@redhawkfp.com EXT:
PM: JAMES PAN JamesP@redhawkfp.com EXT:
DESIGNER: SEAN FODOR SeanF@redhawkfp.com EXT:
SCOPE OF WORK & DESIGN BASIS
FIRE ALARM SYSTEM INSTALL IN NEWLY ADDED PORTABLE BUILDING. NEW POWER
SUPPLY, NOTIFICATION, INITIATION & DETECTION DEVICES TO BE ADDED. AREAS OF
WORK SHOWN IN THESE DRAWINGS ARE ONLY AREAS WITHIN RED HAWK'S SCOPE.
SITE MAP:
hw� • VM r--,
E J0,-
row '
-W'P W .
4%9�. I
T
AREA OF WORK
PORTABLE P3
SCALE: "' = 1'-O"
16 8 6 4 2 0
917 134nu Avc SW, STE B-3
Evotm, WA 98204
P"omE: )42S) 818-3313
WA CLN REDHAHF901 C2P
WA EL# REDHAHF8030D
NICET Stamp
NICET
CERTIFICATION
THESE FIRE ALARM DRAWINGS
HAVE BEEN REVIEWED BY:
MIKE SERESUN
FIRE PROTECTION ENGINEERING
TECHNOLOGY
FIRE ALARM SYSTEMS - LEVEL III
NICET CERTIFICATION # 101668
CERTIFICATION EXPIRES-11101/2024
Approvals Required
Revisions
ISSUE DATE BY DESCRIPTION
0 09/23/2024 SDF PERMIT SUBMITTAL SET
Contract With
SCOTT'S ELECTRIC
SERVICE, LLC
23811 STATE ROUTE 2
MONROE, WA 98272
Contract Name
WOODWAY
HIGH SCHOOL
PORTABLE #3
EDMONDS SD
7600 212TH ST. SW,
EDMONDS, WA 98020
FIRE ALARM SYSTEM
Sheet Title
FIRE ALARM SYSTEM
PROJECT INFO, CALC
& FAS LAYOUT
Key Plan
Date: 09/23/2024
Job Number: 390031
Designer: SEAN D. FODOR
Building Permit:
Sheet Number
FA=1 mOO
SHEET 1 OF 1