APPROVED FIR2024-0072+Fire_Alarm_Plan+8.27.2024_8.15.19_AM+4464174BATTERY & VOLTAGE -DROP
CALCULATIONS
NPS-1
NOTIFICATION APPLIANCE
POWER SUPPLY
NPS BATTERY CALCULATIONS:
NIPS-1
TOTAL STANDBY CURRENT:
0.1390A
TOTAL ALARM CURRENT:
0.3530A
24 HRS REQUIRED STANDBY (AMP HOURS):
3.336AH
5 MIN REQUIRED ALARM CURRENT (AMP HOURS):
0.03AH
TOTAL REQUIRED CAPACITY IN AMP HOURS:
3.37AH
TOTAL REQUIRED CAPACITY x1.2:
4.04AH
BATTERY INFORMATION:
MANUFACTURER:
NOTIFIER
MODEL NUMBER:
PS-1280
SPECIFICATIONS:
12V, 8AH
VOLTAGE DROP INFORMATION:
NAC 1
NAC CIRCUIT:
1
HORN/STROBES:
2
STROBES:
7
ESTIMATED CIRCUIT LENGTH:
240'
CURRENT DRAW:
0.196A
VOLTAGE AT LAST DEVICE:
20.16VDC
VOLTAGE DROP INFORMATION: NAC 2
NAC CIRCUIT: 2
HORN/STROBES: -
STROBES: -
ESTIMATED CIRCUIT LENGTH: -
CURRENT DRAW: -
VOLTAGE AT LAST DEVICE: -
VOLTAGE DROP INFORMATION: NAC 3
NAC CIRCUIT: 3
HORN/STROBES: -
STROBES: -
ESTIMATED CIRCUIT LENGTH: -
CURRENT DRAW: -
VOLTAGE AT LAST DEVICE: -
VOLTAGE DROP INFORMATION: NAC 4
NAC CIRCUIT: 4
HORN/STROBES: -
STROBES: -
ESTIMATED CIRCUIT LENGTH: -
CURRENT DRAW: -
VOLTAGE AT LAST DEVICE: -
BILL OF MATERIAL
ITEM
QTY
SYMBOL
PART DESCRIPTION
PART NUMBER
MANUFACTURER
Ol
1
FCP
FIRE ALARM CONTROL PANEL -EXISTING
7100
FCI-GAMEWELL
O2
1
NPS
NOTIFICATION APPLIANCE POWER SUPPLY
HPF-PS6
HONEYWELL
O3
1
(tP
SMOKE DETECTOR - EXISTING
ASD-PL3-IV
FCI-GAMEWELL
O4
7
0
ADA STROBE - CEILING MOUNT
SCWLED
SYSTEM SENSOR
O5
2
ADA HORN/STROBE -CEILING MOUNT
PC2WLED
SYSTEM SENSOR
O2
12V, 8AH BATTERIES
PS1280
POWER SONIC
SMOKE DETECTOR J
6'-0"
FCP
FIRE
ALARM
CONTROL
PANEL
L THERMAL DETECTOR
FSA
4'-8„
MIN. 6" TO CLG.
oo
Elp1 6,8„ N 8,0„
4'0" FRONT ACCESS
4'6" SIDE ACCESS
EQUIPMENT MOUNTING ELEVATIONS
SCALE: NONE (TYPICAL)
LOCATED
Approved
DFM ak& Suet
South County Fire
Date: 09/06/2024
Sl11TF '1 Ad FA LAYnl1T
GENERAL NOTES.
CEOMFOE®
�,_4a
1. MINIMUM WIRE SIZE SHALL BE 16 AWG UNLESS NOTED LEVEL III
JDE STEVENSON
OTHERWISE. DESIGNER
2. WIRE SHOWN IN THIS DRAWING SET IS PERMITTED
IN RACEWAYS LEADING TO FIRE PROTECTION
EQUIPMENT. OTHER WIRE SHALL NOT BE PERMITTED.
3. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM
TO NFPA STANDARDS AND TO NEC LATEST EDITION.
4. PARALLEL BRANCHING OF WIRE TO ALL NOTIFICATION J
APPLIANCE CIRCUITS SHALL NOT BE PERMITTED. v
5. PARALLEL BRANCHING OF WIRING TO ANALOG INITIATING
U Y
DEVICE CIRCUITS IS PERMISSIBLE. w
0
6. WIRE DESIGNATIONS: Q co
TP = TWISTED PAIR (NON —SHIELDED) cn c�
TSP = TWISTED SHIELDED PAIR CO
TYPE: FPLP, FPLR, OR FPL AS REQUIRED. O
o Z �U
U
7. ALL EQUIPMENT SHOWN ON FLOOR PLANS SHALL BE
O
LOCATED WITHIN 1'-0" AS SHOWN ON SCALED DRAWINGS.
O
c o
0
8. SLC = SIGNAL LINE CIRCUIT
i O
Fn
NAC = NOTIFICATION APPLIANCE CIRCUIT.
o � o
9. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A
O
3'-0" RADIUS OF SUPPLY —AIR DUCTS. a)
� N
U) N O
10. THESE DRAWINGS SHALL NOT BE MODIFIED WITHOUT o
PERMISSION FROM: SCT, INC DESIGN DEPARTMENT.
U O
> Z
11. ALL CANDELA RATINGS ARE 15 UNLESS NOTED OTHERWISE. cz
o
12. REFER TO INSTALLATION SPECIFICATION SHEETS FOR
WIRING DIAGRAMS.
w
00
c�
0
0
�o
DRAWING SET CONTENTS
U ~
z
FA-1 TITLE SHEET ° c
U
SCOPE OF WORK
C
a
N
INSTALLATION OF NECESSARY NOTIFICATION DEVICES
ZFis 0 al a
TO SUITE 104 TI PROJECT. INSTALLATION OF NEW
z
POWER SUPPLY TO BE TRIGGERED VIA EXISTING NAC
vo
CKT IN ELECTRICAL ROOM. FIRE ALARM CONTROL PANEL
AND ASSOCIATED SMOKE TO REMAIN EXISTING. Q °
w
Q
91P941yzI11l1Ma
RECEIVED
w
Q
Aug 27 2024
U
CITY OF EDMONDS
w
DEVELOPMENT SERVICES
O
DEPARTMENT
0-1
d
cn
w
z
J
J
W
oVl_ w
oa w C/)
Z_ U�
Q �o
a �LLJ
_ LU
It
O Q
r` z
00 w
O
cn N W L�
NORTH
1-3"1/'1 LC. I / `t — I —V
FA,l