Loading...
APPROVED FIR2024-0072+Fire_Alarm_Plan+8.27.2024_8.15.19_AM+4464174BATTERY & VOLTAGE -DROP CALCULATIONS NPS-1 NOTIFICATION APPLIANCE POWER SUPPLY NPS BATTERY CALCULATIONS: NIPS-1 TOTAL STANDBY CURRENT: 0.1390A TOTAL ALARM CURRENT: 0.3530A 24 HRS REQUIRED STANDBY (AMP HOURS): 3.336AH 5 MIN REQUIRED ALARM CURRENT (AMP HOURS): 0.03AH TOTAL REQUIRED CAPACITY IN AMP HOURS: 3.37AH TOTAL REQUIRED CAPACITY x1.2: 4.04AH BATTERY INFORMATION: MANUFACTURER: NOTIFIER MODEL NUMBER: PS-1280 SPECIFICATIONS: 12V, 8AH VOLTAGE DROP INFORMATION: NAC 1 NAC CIRCUIT: 1 HORN/STROBES: 2 STROBES: 7 ESTIMATED CIRCUIT LENGTH: 240' CURRENT DRAW: 0.196A VOLTAGE AT LAST DEVICE: 20.16VDC VOLTAGE DROP INFORMATION: NAC 2 NAC CIRCUIT: 2 HORN/STROBES: - STROBES: - ESTIMATED CIRCUIT LENGTH: - CURRENT DRAW: - VOLTAGE AT LAST DEVICE: - VOLTAGE DROP INFORMATION: NAC 3 NAC CIRCUIT: 3 HORN/STROBES: - STROBES: - ESTIMATED CIRCUIT LENGTH: - CURRENT DRAW: - VOLTAGE AT LAST DEVICE: - VOLTAGE DROP INFORMATION: NAC 4 NAC CIRCUIT: 4 HORN/STROBES: - STROBES: - ESTIMATED CIRCUIT LENGTH: - CURRENT DRAW: - VOLTAGE AT LAST DEVICE: - BILL OF MATERIAL ITEM QTY SYMBOL PART DESCRIPTION PART NUMBER MANUFACTURER Ol 1 FCP FIRE ALARM CONTROL PANEL -EXISTING 7100 FCI-GAMEWELL O2 1 NPS NOTIFICATION APPLIANCE POWER SUPPLY HPF-PS6 HONEYWELL O3 1 (tP SMOKE DETECTOR - EXISTING ASD-PL3-IV FCI-GAMEWELL O4 7 0 ADA STROBE - CEILING MOUNT SCWLED SYSTEM SENSOR O5 2 ADA HORN/STROBE -CEILING MOUNT PC2WLED SYSTEM SENSOR O2 12V, 8AH BATTERIES PS1280 POWER SONIC SMOKE DETECTOR J 6'-0" FCP FIRE ALARM CONTROL PANEL L THERMAL DETECTOR FSA 4'-8„ MIN. 6" TO CLG. oo Elp1 6,8„ N 8,0„ 4'0" FRONT ACCESS 4'6" SIDE ACCESS EQUIPMENT MOUNTING ELEVATIONS SCALE: NONE (TYPICAL) LOCATED Approved DFM ak& Suet South County Fire Date: 09/06/2024 Sl11TF '1 Ad FA LAYnl1T GENERAL NOTES. CEOMFOE® �,_4a 1. MINIMUM WIRE SIZE SHALL BE 16 AWG UNLESS NOTED LEVEL III JDE STEVENSON OTHERWISE. DESIGNER 2. WIRE SHOWN IN THIS DRAWING SET IS PERMITTED IN RACEWAYS LEADING TO FIRE PROTECTION EQUIPMENT. OTHER WIRE SHALL NOT BE PERMITTED. 3. FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM TO NFPA STANDARDS AND TO NEC LATEST EDITION. 4. PARALLEL BRANCHING OF WIRE TO ALL NOTIFICATION J APPLIANCE CIRCUITS SHALL NOT BE PERMITTED. v 5. PARALLEL BRANCHING OF WIRING TO ANALOG INITIATING U Y DEVICE CIRCUITS IS PERMISSIBLE. w 0 6. WIRE DESIGNATIONS: Q co TP = TWISTED PAIR (NON —SHIELDED) cn c� TSP = TWISTED SHIELDED PAIR CO TYPE: FPLP, FPLR, OR FPL AS REQUIRED. O o Z �U U 7. ALL EQUIPMENT SHOWN ON FLOOR PLANS SHALL BE O LOCATED WITHIN 1'-0" AS SHOWN ON SCALED DRAWINGS. O c o 0 8. SLC = SIGNAL LINE CIRCUIT i O Fn NAC = NOTIFICATION APPLIANCE CIRCUIT. o � o 9. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN A O 3'-0" RADIUS OF SUPPLY —AIR DUCTS. a) � N U) N O 10. THESE DRAWINGS SHALL NOT BE MODIFIED WITHOUT o PERMISSION FROM: SCT, INC DESIGN DEPARTMENT. U O > Z 11. ALL CANDELA RATINGS ARE 15 UNLESS NOTED OTHERWISE. cz o 12. REFER TO INSTALLATION SPECIFICATION SHEETS FOR WIRING DIAGRAMS. w 00 c� 0 0 �o DRAWING SET CONTENTS U ~ z FA-1 TITLE SHEET ° c U SCOPE OF WORK C a N INSTALLATION OF NECESSARY NOTIFICATION DEVICES ZFis 0 al a TO SUITE 104 TI PROJECT. INSTALLATION OF NEW z POWER SUPPLY TO BE TRIGGERED VIA EXISTING NAC vo CKT IN ELECTRICAL ROOM. FIRE ALARM CONTROL PANEL AND ASSOCIATED SMOKE TO REMAIN EXISTING. Q ° w Q 91P941yzI11l1Ma RECEIVED w Q Aug 27 2024 U CITY OF EDMONDS w DEVELOPMENT SERVICES O DEPARTMENT 0-1 d cn w z J J W oVl_ w oa w C/) Z_ U� Q �o a �LLJ _ LU It O Q r` z 00 w O cn N W L� NORTH 1-3"1/'1 LC. I / `t — I —V FA,l