APPROVED RESUB2 BLD2022-1346+Plumbing_Plan+4.6.2023_10.29.49_AM+3467107PLUMBING GENERAL NOTES 1. THE FOLLOWING NOTES APPLY TO ALL PLUMBING DRAWINGS. ADDITIONAL PLUMBING NOTES MAY BE INDICATED ON EACH PLUMBING DRAWING. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 2. INSTALL ALL WASTE LINE CLEANOUTS IN ACCORDANCE WITH CHAPTER SEVEN OF THE UNIFORM PLUMBING CODE. 3. ALL SANITARY SEWER PIPING BELOW SLAB SHALL BE INSTALLED AT A MINIMUM OF 1/41, PER FT SLOPE UNLESS APPROVAL IS PROVIDED BY THE "ADMINISTRATIVE AUTHORITY" IN WRITING FOR A SHALLOWER SLOPE. IN NO CASES SHALL SEWER PIPING BE INSTALLED AT LESS THAN 1/8" PER FT SLOPE. IN NO CASES WILL PIPING SMALLER THAN 4" BE INSTALLED AT SLOPES SHALLOWER THAN 1/4" PER FOOT. PIPING INSTALLED AT 1/8"/FT SHALL BE RESIZED PER CHAPTER 7 OF THE UNIFORM PLUMBING CODE AND SUPPORTING CALCULATION SUBMITTED TO ENGINEER FOR REVIEW. 4. PROVIDE STOPS PRIOR TO ALL PLUMBING EQUIPMENT. THIS SHALL ALSO INCLUDE PROVIDING INTEGRAL STOPS ON ALL SHOWER AND TUB/SHOWER VALVES (WHETHER SPECIFIED OR NOT). PROVIDE WASTE TRAPS AT ALL DIRECT CONNECTED EQUIPMENT IN ACCORDANCE WITH CODE AND THE SPECIFICATIONS. 5. INSULATE P-TRAPS EXPOSED IN UNHEATED SPACES. 6. SEE ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS AND PLUMBING FIXTURE HEIGHTS, AS WELL AS ROUGH -IN DIMENSIONS AND OTHER DETAILS. ALSO SEE ARCHITECTURAL DRAWINGS FOR FINISH REQUIREMENTS OF ALL PLUMBING FIXTURES INCLUDING REQUIREMENTS FOR FLUSH LEVER LOCATION AT ADA COMPLIANT TOILETS AND VALVE LOCATIONS OF ADA SHOWERS. REPORT ALL DISCREPANCIES TO ENGINEER PRIOR TO ANY WORK. 7. PLUMBING DRAWINGS SHOW APPROXIMATE LOCATIONS OF PLUMBING FIXTURES. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS. COORDINATE FLOOR DRAINS FOR MECHANICAL SPACES WITH MECHANICAL EQUIPMENT BEING SERVED. 8. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. 9. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL CHARACTERISTICS OF PLUMBING EQUIPMENT (VOLTAGES, ETC). ELECTRICAL CHARACTERISTICS OF LISTED EQUIPMENT SHALL BE VERIFIED BY CONTRACTOR DURING SUBMITTAL PROCESS. ANY ELECTRICAL CHARACTERISTICS THAT DEVIATE FROM THOSE LISTED SHALL BE IDENTIFIED BY THE CONTRACTOR, SUBMITTED TO THE ENGINEER FOR APPROVAL AND COORDINATED WITH DIVISION 26 ELECTRICAL PRIOR TO INSTALLATION OF EQUIPMENT AS REQUIRED TO PROPERLY SERVE EQUIPMENT. 10. PROVIDE PLUMBING ANCHORAGE AND EXPANSION EVERY 100' PIPE LENGTH PER CODE. 11. ACCESS PANELS ARE REQUIRED AT ALL CONCEALED VALVES AND EQUIPMENT. COORDINATE LOCATION AND SIZE WITH ARCHITECT. 12. STUB OUT TO SITE SERVICES 5' OUTSIDE BUILDING FOUNDATION. PIPE SIZE, FIXTURE UNITS, AREA DRAINED, INVERT ELEVATION, SIZES, AND SQUARE FOOTAGES AS INDICATED. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WORK. 13. INSULATE PIPING PER WSEC C404.6 AND PER DIVISION 22 SPECIFICATIONS (WHICHEVER IS GREATER). 14. GENERALLY DUCTWORK PLANNED TO BE TIGHT TO STRUCTURE WITH PIPING BELOW DUCTWORK AND BETWEEN LIGHT FIXTURES. ADJUST AS NECESSARY. 15. PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS SHALL ALLOW MINIMUM ACCESS OF 6" IF RUNNING PARALLEL AND ABOVE CABLE TRAYS, ALLOW 18" TO THE SIDE OF CABLE TRAYS. 16. COORDINATE LOCATIONS OF PLUMBING EQUIPMENT TO PROVIDE CLEARANCES OVER LIGHTING FIXTURES FOR REMOVAL AND SERVICE ACCESS DUE TO EQUIPMENT MAINTENANCE. 17. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR PLANS AND SECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY. 18. DO NOT CORE DRILL OR DRILL THROUGH BEAMS, COLUMNS, AND SHEAR WALLS, UNLESS INDICATED ON STRUCTURAL DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER. 19. PIPES INDICATED WITHOUT DIMENSIONS SHALL BE SIZED PER PRECEDING UPSTREAM PIPE SECTIONS. WHERE PIPE SIZES ARE NOT SHOWN ON DRAWINGS, SIZE PIPING PER THE UNIFORM PLUMBING CODE. 20. DRAWINGS ARE SCHEMATIC IN SOME AREAS AND MAY NOT SHOW PIPING OFFSETS WHICH MAY BE REQUIRED. 21. ALL WATER PIPING IN UNHEATED SPACES SHALL BE HEAT TRACED AND INSULATED. 22. PRIOR TO SUBMITTING ALL PLUMBING FIXTURES THE CONTRACTOR SHALL VERIFY COMPATIBILITY OF THE SPECIFIED FIXTURE WITH THE SIZES OF FINISH CABINETRY AS IDENTIFIED IN GENERAL CONTRACTOR'S SHOP DRAWINGS. ANY DISCREPANCIES BETWEEN THE SIZE OF THE FIXTURES SPECIFIED AND THE FINISH CABINETRY SIZES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE SUBMITTAL. 23. PLUMBING VENTS SHALL TERMINATE MINIMUM 10' FROM FRESH AIR INTAKES PER CODE. 24. LABEL ALL PIPING SYSTEMS PER THE IMC AND UPC. 25. SUPPORT AND BRACE PIPING SYSTEMS IN ACCORDANCE WITH UPC SECTION 314 AND AS REQUIRED IN THE SPECIFICATIONS. 26. TEST HYDRONIC PIPING PER IMC 1208. 27. ALL MATERIALS IN CONTACT WITH PIPING SYSTEMS SHALL BE COMPATIBLE FOR USE WITH AND FOR CONTACT WITH THE PIPING MATERIAL CONTRACTORS AND TRADES SHALL VERIFY COMPATIBILITY OF THEIR PRODUCTS WITH THE PIPING SYSTEMS. THIS INCLUDES, BUT IS NOT LIMITED TO, FIRE STOPPING SEALANTS, FIRE STOPPING COLLARS, VIBRATION ISOLATION ELEMENTS, THERMAL INSULATION, EXPANSION JOINTS AND ANY MATERIAL IN CONTACT WITH PIPES. 28. ALL CAST IRON SOIL PIPE AND FITTINGS SHALL BE MARKED WITH THE COLLECTIVE TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE (CISPI) AND BE LISTED BY NSF INTERNATIONAL. 29. PIPE BURIAL METHODS FOR BELOW GRADE PIPING SHALL COMPLY WITH MFR INSTALLATION INSTRUCTIONS, ASTM D 2321 AND ASTM F1668. FAILURE TO FOLLOW THESE REQUIREMENTS CAN LEAD TO PIPE FAILURE. 30. ALL ITEMS IN CONTACT WITH POTABLE WATER SHALL COMPLY WITH THE NATIONAL "REDUCTION OF LEAD IN DRINKING WATER ACT" S.3874. REVISIONS DATE PAGES CHANGES REV1 REV2 REV3 REV4 REV5 PLUMBING LEGEND SYMBOL DESCRIPTION A101 SECTION/ELEVATION VIEW 1 DETAIL VIEW A101 W PLUMBING EQUIPMENT TAG P-1 TYP # PLUMBING FIXTURE TAG TMV-1 PLUMBING ACCESSORIE TAG OSHEET NOTE TAG Al WASTE RISER TAG Al REVISION TAG D ENVELOPE PENETRATION PLAN - SECTION - SCHEMATIC CHECK VALVE V� BALL VALVE g� GATE VALVE MOTOR CONTROL VALVE o� PRESSURE REGULATING VALVE PRESURE RELEIF VALVE Do- BACK FLOW PREVENTER MANUAL BALANCING VALVE THERMOSTATIC BALANCING VALVE -I- UNION GAS PRESSURE REGULATOR WATER METER - ° (P) PRESSURE GAUGE TEMPERATURE GAUGE a PUMP D G EXPANSION TANK LINE TYPES - - --cW COLD WATER PIPING HW HOT WATER PIPING --- ---HWC HOT WATER CIRCULATION PIPING W WASTE PIPING - - - - - V VENT PIPING COND CONDENSATE PIPING �As GAS PIPING FP FIRE PROTECTION PIPING 2018 WSEC TABLE C403.2.9 MINIMUM PIPE INSULATION THICKNESS(THICKNESS IN INCHES) FLUID OPERATING TEMPERATURE RANGE AND USAGE (°F) INSULATION CONDUCTIVITY NOMINAL PIPE OR TUBE SIZE (inches) CONDUCTIVITY Btu•in/(h•ft2•OF)Ab MEAN RATING TEMPERATURE, OF <1 1 TO < 1-1/2 1-1/2 TO < 4 4 TO < 8 > 8 - >350 0.32 - 0.34 250 4.5 5.0 5.0 5.0 5.0 251-350 0.29 - 0.32 200 3.0 4.0 4.5 4.5 4.5 201-250 0.27 - 0.30 150 2.5 2.5 2.5 3.0 3.0 141-200 0.25 - 0.29 125 1.5 1.5 2.0 2.0 2.0 105-140 0.21 - 0.28 100 1.0 1.0 1.5 1.5 1.5 40-60 0.21 - 0.27 75 0.5 0.5 1.0 1.0 1.0 <40 0.20 - 0.26 75 0.5 1.0 1.0 1.0 1.5 A. FOR PIPING SMALLER THAN 1-1/2 INCH (38 MM) AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES, REDUCTION OF THESE THICKNESSES BY 1 INCH (25 MM) SHALL BE PERMITTED (BEFORE THICKNESS ADJUSTMENT REQUIRED IN FOOTNOTE B) BUT NOT TO A THICKNESS LESS THAN 1 INCH (25 MM). B. FOR INSULATION OUTSIDE THE STATED CONDUCTIVITY RANGE, THE MINIMUM THICKNESS (T) SHALL BE DETERMINED AS FOLLOWS: T = R{(1 + T/R)K/K - 11 WHERE: T = MINIMUM INSULATION THICKNESS, R = ACTUAL OUTSIDE RADIUS OF PIPE, T = INSULATION THICKNESS LISTED IN THE TABLE FOR APPLICABLE FLUID TEMPERATURE AND PIPE SIZE, K = CONDUCTIVITY OF ALTERNATE MATERIAL AT MEAN RATING TEMPERATURE INDICATED FOR THE APPLICABLE FLUID TEMPERATURE (BTU X IN/H X FT X °F) AND K = THE UPEER VALUE OF THE CONDUCTIVITY RANGE LISTED IN THE TABLE FOR THE APPLICABLE FLUID TEMPERATURE. C. FOR DIRECT -BURIED HEATING AND HOT WATER SYSTEM PIPING, REDUCTION OF THESE THICKNESSES BY 1-1/2 INCHES SHALL BE PERMITTED (BEFORE THICKNESS ADJUSTMENT REQUIRED IN FOOTNOTE B BUT NOT TO THICKNESSES LESS THAN 1 INCH.) PLUMBING ABBREVIATIONS AFF ABOVE FINISHED FLOOR AHJ AUTHORITY HAVING JURISDICTION ARCH ARCHITECT BFF BELOW FINISHED FLOOR BV BALANCING VALVE CTE CONNECT TO EXISTING CV CHECK VALVE CW COLD WATER DCVA DOUBLE CHECK VALVE ASSEMBLY DF DRINKING FOUNTAIN DFU DRAIN FIXTURE UNIT DIA DIAMETER DN DOWN DWV DRAIN WASTE VENT ELEV ELEVATION ESV EARTHQUAKE SHUT-OFF VALVE F FIRE FCO FLOOR CLEAN OUT FD FLOOR DRAIN FDC FIRE DEPARTMENT CONNECTION FLR FLOOR FP FIRE PROTECTION FS FLOOR SINK FV FLUSH VALVE FW FIRE WATER GC GENERAL CONTRACTOR GCO GRADE CLEAN OUT GI GREASE INTERCEPTOR GPF GALLONS PER FLUSH GPM GALLONS PER MINUTE GW GREASE WASTE HD HUB DRAIN HW HOT WATER HWR HOT WATER RETURN IE INVERT ELEVATION IW INDIRECT WASTE JSK JANITOR SINK LAV LAVATORY LPG LIQUEFIED PETROLEUM GAS MPG MEDIUM PRESSURE GAS NP NON -POTABLE OHP OUTDOOR HEAT PUMP PG PRESSURE GAUGE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RCW RECLAIMED/NON-POTABLE COLD WATER RL RAINLEADER RPBP REDUCED PRESSURE BACKFLOW PREVENTER RR RESTROOM S STORM SH SHOWER SK SINK SSV SERVICE SHUT-OFF VALVE SW SANITARY WASTE TP TRAP PRIMER TYP TYPICAL UR URINAL V VENT VTR VENT THRU ROOF W WASTE WC WATER CLOSET WCO WALL CLEAN OUT WM WASHING MACHINE WSFU WATER SUPPLY FIXTRUE UNITS City Of Edmonds Building Department Work PLUMBING- ALL BUILDINGS --------------------------------------------------- --------------------------------------------------- Address 8215 236TH STS W ------------------------------------------------ Owner HOUSING HOPE Approved Date 4/24/2023 Building Official V W. ---------------------------- Permit Number BLD2022-1346 BLDG A BLD2022-1343 BLDG C BLD2022-1344 BLDG D LAVATORY MIXING VALVES PER THE 2018 UPC 407.3 WATER DELIVERED TO PUBLIC -USE LAVATORIES SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF 120°F BY A DEVICE THAT IS IN ACCORDANCE WITH ASSE 1070 OR CSA B125.3 THE WATER HEATER CONTROL IS NOT CONSIDERED A CONTROL MEETING THIS PROVISION. PUBLIC -USE LAVATORIES SHALL BE DEFINED AS A HAND SINK ADJACENT TO WATER CLOSETS OR URINALS IN NON -LOCKING BATHROOMS INTENDED FOR AN OCCUPANCY OF MORE THAN ONE PERSON AT A TIME. PLUMBING CONTRACTOR TO PROVIDE MIXING VALVES FOR PUBLIC LAVATORIES PER FIXTURE SCHEDULE. PIPING MATERIALS - SANITARY DRAINAGE CONDENSATE PIPING SHALL BE TYPE "L" COPPER WITH WROT COPPER FITTINGS OR SCH 40 PVC. SANITARY DRAINAGE PIPING SHALL BE SOUND INSULATED WRAPPED PVC PIPING IN ALL RESIDENTIAL AREAS INCLUDING VERTICAL WASTE STACKS AND ALL DWELLING UNITS WASTE PIPING. PIPING MATERIALS - WATER ALL DOMESTIC WATER PIPING 3-1/2" AND LARGER TO BE STAINLESS STEEL PIPING WITH STAINLESS STEEL FITTINGS, OR CPVC SCHED 80 WITH CPCV FITTINGS. ALL DOMESTIC WATER PIPING 3" AND SMALLER TO BE PEX TUBING WITH PEX FITTINGS. ALL IRRIGATION PIPING TO BE COPPER TUBING AND FITTINGS. PIPING SHALL BE INSTALLED IN ACCORDANCE WITH SIZES CALLED OUT ON PLANS. MAXIMUM WATER VELOCITIES WITHIN PIPING SHALL BE AS FOLLOWS STAINLESS TUBE AND FITTING SYSTEMS - 10 FT/SEC ON COLD WATER PIPING, 5FT/SEC ON HOT WATER PIPING, 3 FT/SEC ON HOT WATER RECIRC PIPING. PEX TUBE AND FITTING SYSTEMS - 10 FT/SEC ON COLD WATER PIPING, 8 FT/SEC ON HOT WATER PIPING, 2 FT/SEC ON HOT WATER RECIRC PIPING. MAX ALLOWABLE PRESSURE DROP FROM FRICTION FOR ENTIRE PIPING AND FITTING SYSTEM IS 30 PSI. PROVIDE DIELECTRIC UNIONS WHERE GALVANICALLY DISSIMILAR METALS JOIN. PLUMBING SHEET LIST Sheet Number Sheet Name P0.01 PLUMBING GENERAL NOTES P0.02 PLUMBING SCHEDULE P2.01 PLUMBING - FOUNDATION PLAN - BUILDING A & B P2.02 PLUMBING - FOUNDATION PLAN - BUILDING C & D P2.11 PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING A & B P2.12 PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING C & D P2.21 PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING A & B P2.22 PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING C & D P2.31 PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING A & B P2.32 PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING C & D P2.41 PLUMBING - ROOF PLAN - BUILDING A & B P2.42 PLUMBING - ROOF PLAN - BUILDING C & D P3.01 PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG A P3.02 PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG B P3.03 PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG C P3.04 PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG D P4.01 PLUMBING - WATER RISER DIAGRAM - BUILDING A P4.02 PLUMBING - WATER RISER DIAGRAM - BUILDING B P4.03 PLUMBING - WATER RISER DIAGRAM - BUILDING C P4.04 PLUMBING - WATER RISER DIAGRAM - BUILDING D P4.05 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING A P4.06 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING B P4.07 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C P4.08 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C P4.09 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D P4.10 PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D P5.01 PLUMBING - ENLARGED UNIT PLANS P5.02 PLUMBING - ENLARGED UNIT PLANS P5.03 PLUMBING - ENLARGED UNIT PLANS P5.04 PLUMBING - ENLARGED AREA PLANS P8.01 PLUMBING DETAILS PLUMBING DETAILS P8.02 ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE APPROVED PLANS MUST BE ON JOB SITE APPROVED BY PRE-TREATMENT RICK BAGAN ON 3/15/23 HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 www.designsnw.com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W am Cn O �z U) Z Q zO Lu C' J LL1 W 3;Z Lu Cl) LL w V Q U) = O�aL0 c.0 N L L0 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING GENERAL NOTES SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: Polo PLUMBING - FIXTURES TAG DESCRIPTION MANUFACTURER MODEL FLOW (GPM/GPF) PIPE CONNECTION (INCH) NOTES CW HW W V BT-1 BATHTUB/SHOWER COMBO AQUATIC 2603CTH 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA T13420-H20 BT-2 ACCESSIBLE BATHTUB/SHOWER COMBO AQUATIC 2603CTH 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA T13420-H2O WITH RPW324HDF AND GRAB BARS DF-1 DRINKING FOUNTAIN ELKAY EMABFTL8WSLK 0.0 1/2" 0" 0" 0" FD-1 FLOOR DRAIN ZURN Z415B 0.0 0" 0" 2" 1 1/2" FLOOR DRAIN FOR MECH AREAS FD-2 FLOOR DRAIN ZURN Z415B 0.0 0" 0" 3" 2" FLOOR DRAIN FOR WATER STORAGE AREAS FD-3 FLOOR DRAIN ZURN Z415S 0.0 0" 0" 2" 1 1/2" FLOOR DRAIN FOR AMENITY/INTERIOR RESIDENT AREAS FS-1 FLOOR SINK ZURN FD2375 0.0 0" 0" 3" 2" FLOOR SINK FOR PRV DISCHARGE ETC. HB-1 HOSE BIBB WOODFOD 68 0.0 3/4" 0" 0" FREEZE PROTECTED HOSE BIBB FOR EXTERIOR BUILDING LOCATIONS HD-1 HUB DRAIN ZURN Z1870 0.0 0" 0" 4" 3" HUB DRAIN FOR FIRE VALVES DRAIN NEEDS L-1 LAVATORY AMERICAN STANDARD AQUALYN 0.5 1/2" 1/2" 2" 1 1/2" DROP IN SINK; FAUCET: DELTA 523LF-HGMHDF, WATERSENSE RATED L-2 LAVATORY - AMENITY RESTROOMS AMERICAN STANDARD LUCERNE 0.5 1/2" 1/2" 2" 1 1/2" ACCESSIBLE WALL HUNG SINK; FAUCET: DELTA 523LF-HGMHDF, WATERSENSE RATED MS-1 MOP SINK FIAT MSB2424 0.0 3/4" 3/4" 3" 2" CHICAGO MOP SINK STYLE FAUCET 897 SH-1 SHOWER AQUATIC 13636FHARF 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA T13420-H2O; WATERSENSE RATED SH-2 ACCESSIBLE SHOWER AQUATIC 1603BFST 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA T13420-H2O WITH RPW324HDF; WATERSENSE RATED SK-1 SINK ELKAY DLR 331910 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA 10OLF-HDF SK-2 SINK - ACCESSIBLE UNIT ELKAY BPSR2317 1.5 1/2" 1/2" 2" 1 1/2" FAUCET: DELTA 1959LF SK-3 SINK -AMENITY AREAS ELKAY PSLVR1917 1.5 1/2" 1/2" 2" 1 1/2" ACCESSIBLE DEAPTH, SINGLE BASIN, DROP -IN, FAUCET: DELTA 1959LF SK-4 SINK - HAND WASHING ELKAY BPSR15 1.5 1/2" 1/2" 2" 1 1/2" SINGLE BASIN HAND WASHING SINK, FAUCET DELTA 1959LF SK-5 SINK - UTILITY FIAT SERV-A-SINK FL-1 2.5 1/2" 1/2" 2" 1 1/2" FREESTANDING UTILITY SINK. WITH CHICAGO FAUCET 772 UR-1 URINAL AMERICAN STANDARD MAYBROOK 0.1 1/2" 0"1 2" 1 1/2" PINT URINAL; WATERSENSE RATED WB-1 WASHER BOX SOUIX CHIEF OXBOX 0.0 1/2" 1/2" 2" 0" CLOTHES WASHER CONNECTION BOX WITH WATER HAMMER ARRESTOR INTEGRAL WC-1 WATER CLOSET NIAGARA STEALTH N7717 0.8 1" 0" 3" 2" STEALTH PRESSURE ASSIST; WATER SENSE RATED WC-2 WATER CLOSET - ACCESSIBLE UNITS AND AMENITY NIAGARA STEALTH N7717 0.8 1" 0" 3" 2" STEALTH PRESSURE ASSIST; WATER SENSE RATED PLUMBING - ACCESSORIES PIPE CONNECTION DIAMETER (INCH) TAG MANUFACTURER MODEL DESCRIPTION SERVICE CW HW W V FLOW VOLUME NOTES EXP-A AMTROL TBD EXPANSION TANK DOMESTIC WATER 0.000 0.000 0.0 gal EXP-B AMTROL TBD EXPANSION TANK DOMESTIC WATER 0.000 0.000 0.0 gal EXP-C AMTROL TBD EXPANSION TANK DOMESTIC WATER 0.000 0.000 0.0 gal EXP-D AMTROL TBD EXPANSION TANK DOMESTIC WATER 0.000 0.000 0.0 gal TMV-A CALEFFI LEGIONMIX 6000 TEMPERATURE MIXING VALVE HOT WATER 0.000 0.000 0 GPM 0.0 gal TMV-B CALEFFI LEGIONMIX 6000 TEMPERATURE MIXING VALVE HOT WATER 0.000 0.000 0 GPM 0.0 gal TMV-C CALEFFI LEGIONMIX 6000 TEMPERATURE MIXING VALVE HOT WATER 0.000 0.000 0 GPM 0.0 gal TMV-D CALEFFI LEGIONMIX 6000 TEMPERATURE MIXING VALVE HOT WATER 0.000 0.000 0 GPM 0.0 gal TP-1 SIOUX CHIEF PRIME PERFECT MECHANICAL TRAP PRIMER WASTE 0.250 0.000 0 GPM 0.0 gal LOCATED IN MECHANICAL ROOMS TP-2 SIOUX CHIEF TRAP EASE GRAVITY TRAP PRIMER WASTE 0.250 0.000 0 GPM 0.0 gal LOCATED IN AMENITY RESTROOMS PLUMBING - HEAT TRACE TAG MANUFACTURER MODEL VOLTS/PHASE NOTES HTC-1 NVENT RAYCHEM AMC-F5 CONTROLLER WITH 5XLE1-CR 120V 5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG A HTC-2 NVENT RAYCHEM AMC-1`5 CONTROLLER WITH 5XLE1-CR 120V 5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG B HTC-3 NVENT RAYCHEM AMC-1`5 CONTROLLER WITH 5XLE1-CR 120V 5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG C HTC-4 NVENT RAYCHEM AMC-1`5 CONTROLLER WITH 5XLE1-CR I 120V 5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG D TAG MANUFACTURER MODEL VOLUME (G. WH-A A.O. SMITH DRE-120-12 120.0 gal WH-B A.O. SMITH DRE-120-12 120.0 gal WH-C A.O. SMITH DRE-120-18 120.0 gal WH-D A.O. SMITH DRE-120-12 120.0 qal PLUMBING - ELECTRIC WATER HEATER PHYSICAL DATA DIMENSIONS FULL WEIGHT (LBS) DIAMETER (IN) HEIGHT (IN) 5' - 3" 1000 lb 5' - 3" 1000 lb 5' - 3" 1000 lb 5' - 3" 1000 lb TAG MANUFACTURER MODEL DESCRIPTION ST-Al A.O. SMITH TBD HOT WATER STORAGE TANK ST-A2 A.O. SMITH TBD HOT WATER STORAGE TANK ST-B1 A.O. SMITH TBD HOT WATER STORAGE TANK ST-B2 A.O. SMITH TBD HOT WATER STORAGE TANK ST-Cl A.O. SMITH TBD HOT WATER STORAGE TANK ST-C2 A.O. SMITH TBD HOT WATER STORAGE TANK ST-D1 A.O. SMITH TBD HOT WATER STORAGE TANK ST-D2 A.O. SMITH TBD HOT WATER STORAGE TANK ELECTRICAL DATA PIPE CONNECTIONS POWER (kW) FLA VOLTS/PHASE CW (IN) HW (IN) 0.000 0.000 12.3 kW 34 208V/3PH 0.000 0.000 12.3 kW 34 208V/3PH 0.000 0.000 18.0 kW 50 208V/3PH 0.000 0.000 12.3 kW 34 208V/3PH PLUMBING - STORAGE TANKS DIMENSIONS (INCH) I FILLED VOLUME (GAL) WEIGHT (LBS) PIPE CONNECTION (INCH) RADIUS HEIGHT CW HW 1'- 8" 6' - 8" 285.0 gal 2950 lb 1'- 8" 6' - 8" 285.0 gal 2950 lb 1'- 8" 6' - 8" 285.0 gal 2950 lb 1'- 8" 6' - 8" 285.0 gal 2950 lb 1' - 11" 7' - 8" 455.0 gal 7500 lb 1' - 11" 7' - 8" 455.0 gal 7500 lb 1'- 8" 6' - 8" 285.0 gal 2950 lb 1'- 8" 6' - 8" 285.0 qal 2950 lb NOTES NOTES PLUMBING - HEAT PUMP WATER HEATER HEAT CAP COP -SEASONAL MCA PIPE CONNECTIONS WEIGHT TAG MANUFACTURER MODEL SERVICE REFRIGERANT (BTU/HR @ 47F) (80/47/17 DEG F) VOLT/PHASE (AMPS) (INCH) SOUND (DbA) (LBS) NOTES HPWH-A1 SANCO2 GS4-45HPC DHW - BLDG A R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-A2 SANCO2 GS4-45HPC DHW - BLDG A R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-A3 SANCO2 GS4-45HPC DHW - BLDG A R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-B1 SANCO2 GS4-45HPC BHW - BLDG B R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-B2 SANCO2 GS4-45HPC BHW - BLDG B R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-B3 SANCO2 GS4-45HPC BHW - BLDG B R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-C1 SANCO2 GS4-45HPC DHW - BLDG C R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-C2 SANCO2 GS4-45HPC DHW - BLDG C R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-C3 SANCO2 GS4-45HPC DHW - BLDG C R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-C4 SANCO2 GS4-45HPC DHW - BLDG C R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-D1 SANCO2 GS4-45HPC DHW - BLDG D R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-D2 SANCO2 GS4-45HPC DHW - BLDG D R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-D3 SANCO2 GS4-45HPC DHW - BLDG D R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HPWH-D4 SANCO2 GS4-45HPC DHW - BLDG D R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4 HOUSING HOPE we keep hope alive DESIGNS \� northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W am Cn O �z U) z = Q Z 0 0 LU C' J LL1 Z 3;W I- Lu U) LL w V Q U) O J a c� Cy') N mc � L0 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 1 PERMIT RESUBM. IK9J►1IRLI 'fi PLUMBING SCHEDULE SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: PO,02 RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT A A\\ \\ \\ 4" FIRE WATER POC SEE CIVIL FOR CONTINUATION \\ \\ \V/ /. PLUMBING FOUNDATION PLAN - BLDG A & B 1 /8" = 1 I-011 4" WASTE POC SEE CIVIL FOR CONTINUATION IE= APPROX 4' BFF SEE CIVIL FOR CONTINUATION IE= APPROX 2.8' BFF 3" DOMESTIC WATER POC SEE CIVIL FOR CONTINUATION SEE CIVIL FOR BACKFLOW PREVENTOR 22.5 23 24 IIIIIIIII IIIIIIIII II III III III III III HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 us: e- If C.0 N O 00 W Cn 3: O �z U) Z Q zO LU w C' J W U) Z W `; w Um w V Q U) = O J a C.0 M N mc L N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev W-T Date I Description 2 01/04/2023 IPERMITRESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B CONTENTS: PLUMBING - FOUNDATION PLAN - BUILDING A & B SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P2mO 1 2 3 4 5 6 7 8 J 4" FIRE WATER POC SEE CIVIL FOR CONTINUATION U- d a-: - - '°° a ram.°, d a4 _ - ..- ° •- d'4 4 Q •-". a ° °3" DOMESTIC WATER POC ' °d°d° ° •'2(°2 •= d• ' • ° •A" °d °a d)°°`2 "W 1 (FROM RO M °- 77 °B, T ,UaSEE CIVIL FOR CONTINUATION (2DFd 4 4°P °(2DFU)3"W 2"W FROM BT /2"V U- 4 °ad(2 FIRE (5DF° , ° a Wd 2o SEE CIVIL FOR BACKFLOW PREVENTOR 1-1/2"V UP ; 1/2VU° d 4 4 2"W UP 2"W UP' (20 DFU °as W d 3n4- (4DFU) $a°2"W U2 DFU 4" ° (12 DF ° DFU DFU)° a° a °° °TP FROM ABOVEa"VW V UP 1-1/2D 3nV UP FROM HW 3CW UP 4ne 4"p e'Qe ° W2"W UP d a d °3W 33W FROM FS °3W(3 DFU)—`, ° d 12 DFU) 2nW- (4 DFU), �' - (3 DFU) (2 DFU) °.,° "W °W (3 DU)I�.< d,2"V UP d 3W 3 ° 4 4 ° -a 2 W (12 DFU) a 2"W FROM FD _ FdDU) d 3FU) d (2 D2,W ° aa° ,° d ° (8 DFU)AP� _ e ° 3 . a 4 2W dUP TO GCO ° ° d°VUP° °DFU .°1-1/2"V UP (2 3W FROM FD°d4° 2"W UP d d- a 2"W UP--(3 DFU)— 4 (3 DFU) - 4 ad UP TO GCO o —I III III III I IIIIIIIIIII III —III —III IIIIIIIIIII IIII 4 �-4" WASTE POC SEE CIVIL FOR CONTINUATION IE= APPROX 3.9' BFF IILp' - 2"W -_ -' -_ - °_ _- °d d°-' • ,. d ° ° , d °-7 ° 4 d2 W-' n a ° ° UP TO GCO ;2nW (2DU) A d. ° d d °_ (8 DFU) ° (2DFU);d._(2DFU) d d 4 DFU4: 41 d.3��W:. a3"W ° °°d 2nW - 3"W-d 3"W ` ` a =1: 1 ° (12 DFU) a 4DFU ( ) 3 DFU ° a . 3 DFU ° ° • ":2DFU ° . 3 DFU° ?° 3 DFU , •° °.° " `d°_ 4 W - P ° °-.d 11 - 11 °d ° d - - -,dd- d 11 °d 11 _d : ° - $ �(8 DFU).- 3W - 3W:° 3W 3W,: °3W;_' °° (3 DFU) 'a(24DFU): ° ° ° ° (13 DFU) ° (13 DFU) , ° ';�2 DFU) d° °(13 DFU), ° aF ` (13 DFU) W= Q_ dp - ,d - - d " - d - d^- ° °•4 - d°<, W.- - - - d °- °- °� ,�A/ - a n - _ - - 4n� - p - - - 4 - ; 4 - -d - ° ° - .. -• .4n�=, - , d° e, -'3Y"� �d - - ° " ad" . e ° 1-1/2"V d a ° a b: $' a q° n Q ° �3W m 2W ° °° ° ° d 1 DFU °.. 0(3 DFU) a 2 W d' ° ¢d: 4 ( ). 3 W ° (3 DFU)° ?- d, 2 W UP; ' (2 DFU) : a m d 4 d ° W ° °°. d 1 DFU 2nW<1 ^ ° 8 >d °d d 4e I ( ) , °d ` 11 l �_ ° $ a 2DFU °4"W 'FROM HD— ° - - - - d (1 DFU)° _ ° 1 1/2 V 1 1/2 V° d° 4°a °1 1/2 V- a 1 1/2 V ( �' 4 { ° -- - 2"V11 FROM BT ° 2nW 2nW ' d d, 2nW °ed 2nW < „ ° 1-1/2"V ° °"d °d n. a 4� V d - ° (2 DFU):a d a' d ° °,°(2 DFU), ° (2 DFU \ 9 (2 DFU),, d' ° . ° ° (2 DFU)m . °d _ ° d°- ¢'d°-- .° -do- - ° °9 °- d° - .9 ° °° -a °TPLINESUP��- 44 - a 41 4•j°' °.d ° a" ° ° „ • $- d' d" . ° 3_"W FROMFID d - - p Ad 3"W FROM FD a 4 3W FRO,2"V UP d I N� 1 PLUMBING FOUNDATION PLAN - BLDG C & D 1/8"=11-011 N� "111� / NN�� �3" DOMESTIC WATER POC /SEE CIVIL FOR CONTINUATION SEE CIVIL FOR BACKFLOW PREVENTOR ri-9) 20 ,-4" WASTE POC SEE CIVIL FOR CONTINUATION IE= APPROX 4.25' BFF 9 FIRE WATER POC :E CIVIL FOR CONTINUATION U /avU 0 N W W U) C .2 00 06 Q z- C.1 co HOUSING i HOPE we keep hope alive DESIGNS L IN northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 R M; W am u) z Q 0 W C' J LLI Z _ LLI - (� LU NW L.L � V Q I- OJaM C.0 N W00 N CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Description Rev # Date 2 01/04/2023 PERMIT RESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT B. D CONTENTS: PLUMBING - FOUNDATION PLAN - BUILDING C & D SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2,02 D� T 6 7 8 9 T T T ( 10 11 12 PLUMBING FLOOR PLAN - LEVEL 1 - BLDG A & B 118" = 1 I-011 rm 6 m6- F1 HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W N O 00 am Cn O �z U) Z Q zO w C' J Liu Z LLI U) w C/) ILU) w V Q = O J a C.0 M N LL1 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date I Description 3 03/27/2023 CONFORMED SET KEYPLAN RESUB CCITY OF EDMONDS SERVICES DEPARTMENT D B 1w.,,t..a imm PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING A & B SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P20 2 (31 4 5 6 (7 �8 -----<O> PLUMBING FLOOR PLAN - LEVEL 1 - BLDG C & D 1 /8" = 1 I-011 HOUSING i HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W co N (D 00 m am Cn O �z U) Z Q zO w C' J Liu Z L L1 U) w w V Q U) = O J a C.0 M N LL1 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 IPERMITRESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING C & D SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P2m12 PLUMBING FLOOR PLAN - LEVEL 2 - BLDG A & B 118" = 1 I-011 HOUSING AW\, HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W Cfl N O 00 am Cn O �z U) Z Q zO w C' J Liu Z LLI U) w w V Q U) = O J a C.0 M N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description KEYPLAN RESU B CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B CONTENTS: PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING A & B SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2,21 (A.3 D �1 (2 3 4 5 6 7) I I I I I 1 1 15 16 (17) (18i 19 20j 21 PLUMBING FLOOR PLAN - LEVEL 2 - BLDG C & D 1 /8 = 11-011 w w W m Q c� z 0 J m HOUSING HOPE we keep hope alive ih�DESIGNS northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 - 'Lk `==--*"R 05 W am Cl) O �z U) Z Q zO Lu C' J LLI - W 3;Z LU Nw L.L V Q U) = O J a C.0 M N mc � N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 IPERMITRESUBM. KEYPLAN RESUB C-, —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING C & D SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2m22 N M N W W W O 0 00 6l � �J 9 10 11) 12 PLUMBING FLOOR PLAN - LEVEL 3 - BLDG A & B 1/8"=11-011 C22 HOUSING HOPE we keep hope alive DESIGNS I northwest ARCHITECTS I P.O. Box 1 27 0 10031 SR 532, Suite B I Stanwood, WA 98292 www. designs nw. com I I ECOTOPE I 1 1 9 17 1 ST AvE, #300 SEATTLE WA 9S 1 o 1 I PH: (206) 322-3753 FAX: (206) 325-7270 N O 00 W I m ¢¢ O �z z Q zO w C' J L Z UI U) w ico V Q OJaM UJI Lo 00 N 00 � CONSTRUCTION � DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description KEYPLAN RESU B CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B CONTENTS: PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING A & B SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2,31 T T 3 I � T5) � 6 ,1 7 4 TI 3-BED 2-BED 2-BED 2-BED D306 D305 D304 D3 33 922 SF 678 SF 689 SF 689 SF 1�2 2"V UP TO VTR 00 2"V UP TO VTR (46 DFU) 00(88 DFU) UNIT WATER UNITWATER o 0 0 00 RISERS DN RISERS DNoil O o 0 0 UNIT WATER / RISERS DN J III THERMOSTATIC BALANCING VALVE TYPICAL AT ALL HW TO HWC CONNECTIONS I 1_. �17) 18j PLUMBING FLOOR PLAN - LEVEL 3 - BLDG C & D 1 /8" = 1 I-011 UNITWATER RISERS DN,_j I _i I 0 2-BED 2-BED D302 D3 11 689 SF 733 SF III 2"V UP TO VTR (33 DFU) III UNIT WATER o 0 d � I RISERS DIN,0 0 0 0 , D 0 --- UNIT WATER RISERS DN (?0 A J,11 "HWC DN 21 1-1 AW\ HOUSING 8 HOPE we keep hope alive DESIGNS 1 L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W U) M O z � z W z w a � � w co C' J Q � z0 Z W U) J LU m w 0L U) V Q c� O J a M N LLI N CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Description Rev # I Date 2 01/04/2023 PERMIT RESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT g D CONTENTS: PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING C & D SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2,32 \ N w w 0 06 U z J D m D \ 6 7) 8 ,,•; 9 ,.,i 10 11 12 I I I ii / 3"VTR rA II m 0 El / 3VTR 0 }"0,/ (34 DFU) A � 21 22 22.5 23 24 25 PLUMBING ROOF PLAN - BLDG A & B 1 /8" = 11-011 HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 0 W am Cn O �mmWz Z Q zO LU C' J LLJ Z - LLI U) LU Cl) LL Nw L.L V Q U) = O J a C.0 M N mc � N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 IPERMITRESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B CONTENTS: PLUMBING - ROOF PLAN - BUILDING A &B SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2m41 T 3 4 5 i 3" VTR (80 DFU) PLUMBING ROOF PLAN - BLDG C & D 1 /8" = 1 I-011 3" VTR �®8 DFU) 6 7 I I 3" VTR +jd(33 DFU) 8 AIW\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www.designsnw.com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W C w O co zZ w U co� Q z � O w z C' J m Z W U) w w V Q U) O J a M N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 IPERMITRESUBM. KEYPLAN RESUB CCITY —Aa�brzet�, OF EDMONDS SERVICES DEPARTMENT D B CONTENTS: PLUMBING - ROOF PLAN - BUILDING C &D SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: N P2m42 HPWH A3 1„ (1) HPWH A2 1„ (1) HPWH Al 1„ MECHANICAL ROOM (17) 311 / T -- 4 � _ (13) I ' I I I I I I I I I I I I I I I /4 (20) 75 2 I I I I 311 (22) 2 --� -- (13) (13) 1n I ------------� T T4 311 311 --------------------- 4 (19) PLUMBING - HPWH SCHEMATIC - BLDG A 1 /8" = 11-011 LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION PUMP PIPE-T MIXING VALVE T&P RELIEF VALVE PMP # EQUIPMENT TAG MANUAL AND AUTOMATIC AIR BLEED QTEMPERATURE SENSOR PIPE UNION FM FLOW METER PIPE FLOW DIRECTION Cb� BALL VALVE 31, PIPE SIZE BALANCING VALVE --- CW PIPING SPRING CHECK VALVE HW PIPING INLINE Y-STRAINER HWC PIPING I I ' SHEET NOTES (1) SEE HPWH EQUIPMENT DETAIL 4/P8.02 (2) DIRECT -75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (4) PROVIDE 12" HEAT TRAP (5) EQUIPMENT DRAIN (6) ROUTE T&P RELIEF TO DRAIN (7) BAG FILTER (PENTAK, WF-1) (8) INLINE PIPE STRAINER (9) AUTOMATIC AIR BLEED (10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM (11) NOT USED (12) NOT USED (13) WIRE TO CONTROLLER (TYPICAL) (14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS. REFER TO HW1.00 FOR MORE INFORMATION. (15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF THERMAL BRIDGES (16) NOT USED (17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL) (18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL) (19) R-10 THERMAL ISOLATION (20) PROVIDE SEISMIC BRACING (21) CONNECT TO BUILDING COLD WATER SUPPLY LINE. (22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW. CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY LINE DISTANCE TO THE PRIMARY STORAGE [ST-1]. (23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING STARTUP. (24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND CONDENSATE DISCHARGE. TEMPERATURE GAUGE TYP. ALL T \ 211 ---------- CW (7) (21) (18) T \ (23) 311 (5) I 4 I P-1 3„ -*�— ---- 4 HWC 2" TMV-A (10) I (2) 2° T6 2" T2 - z (5) I I I 2" I I I I I I I I I I I I 2" I I I I I I %--u (24) FS-1 a TEMPERATURE SENSOR TYP. ALL (13) T3 Tl \J 2�� (5) Dc5 — � HW (14) (15) HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS P.O. Box 1^-70 10031 SR 532. Sure B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE 1 91 7 1 ST AVE, #300 SEATTLE WA 9B 1 O 1 PH: (ZO6) 3ZZ-3753 FAX: (206) 325-7270 W CID CV O 00 am Cn O �z Cn Z Q z0 0 w C� J Liu Z W cn w Cn LL w c, aC) C) 0 CID cy-) C14 W a L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG A SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P3,01 OUTDOORS 111 HPWH B2 111 HPWH B1 I111 111 I 11I I 11I 2 I I 411- (22) - -- -- (15) 311 1 11 ----- --- ------ ►-------% L(22)_ 311 ------------------ 4 — - — - — - C- PLUMBING�-lPW�IS�C HEMATIC �-1 LDG B 1 118" = 1'-0" MECHANICAL ROOM 311 4 (19) (17) (5) (19) (10) T2 T6 Q (18) 5) 211 LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION ® PUMP PIPE-T MIXING VALVE P- T&P RELIEF VALVE PMP # EQUIPMENT TAG MANUAL AND AUTOMATIC AIR BLEED QTEMPERATURE SENSOR PIPE UNION FM FLOW METER PIPE FLOW DIRECTION CZXI BALL VALVE � PIPE SIZE BALANCING VALVE --- CW PIPING SPRING CHECK VALVE HW PIPING INLINE Y-STRAINER HWC PIPING I I 211 I I TEMPERATURE GAUGE TYP. ALL SHEET NOTES (1) SEE HPWH EQUIPMENT DETAIL 4/P8.02 (2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (4) PROVIDE 12" HEAT TRAP (5) EQUIPMENT DRAIN (6) ROUTE T&P RELIEF TO DRAIN (7) BAG FILTER (PENTAK, WF-1) (8) INLINE PIPE STRAINER (9) AUTOMATIC AIR BLEED (10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM (11) NOT USED (12) NOT USED (13) WIRE TO CONTROLLER (TYPICAL) (14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS. REFER TO HW1.00 FOR MORE INFORMATION. (15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF THERMAL BRIDGES (16) NOT USED (17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL) (18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL) (19) R-10 THERMAL ISOLATION (20) PROVIDE SEISMIC BRACING (21) CONNECT TO BUILDING COLD WATER SUPPLY LINE. (22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW. CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY LINE DISTANCE TO THE PRIMARY STORAGE [ST-1]. (23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING STARTUP. (24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND CONDENSATE DISCHARGE. T \ 211 ---------- -------���� CW (7) (21) (23) T \ I 311 (5) I 4 P-1 311 - �- ---- ®�® HWC 2"I TMV-B (2) 211 I I tHT I L ---� I I I 311 4 (3) %==—I (24) FS-1 (20) 211 (19) (10) C7 211 z TEMPERATURE SENSOR TYP. ALL (13) T3 T \ 211 � Df*�®� I HW (14) (15) (5) AW\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629.3441 P.O. Box 1,70 10031 SR 532. Suile B Stanwood. WA 98292 wwww. des i gn sn-- ECOTOPE 1 91 7 1 ST AVE, #300 SEATTLE WA 9B 1 O 1 PH: (ZO6) 3ZZ-3753 FAX: (206) 325-7270 W am Cl) O �z Cf) Z Q z0 0 W C� J Liu Z W 1� Cf) W W c, aC) C) OJaM N mc W a L0 C00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG B SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 3,0 OUTDOORS HPWH C4 1„ HPWH C3 1„ HPWH C2 1„ HPWH -:C: 1: 1„ MECHANICAL ROOM (17) 31, / T -- 4 ® — (13) I I I I I I I I I I I I I ' ST-C1 I ' (20) I (20) - - 2 I I I I 311 311 i 2 — — (22) -- -- --� --LU (13) (13) -- 4 -- -- —� -- -- -- (15) 311 311 TT4 -----�------------------� (22) 311 311 --------- — — —--------- — -----4 --------- 4 (19) PLUMBING - HPWH SCHEMATIC - BLDG C 1 /8" = 1 1-0 11 T1 LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION PUMP PIPE-T MIXING VALVE T&P RELIEF VALVE PMP # EQUIPMENT TAG MANUAL AND AUTOMATIC AIR BLEED QTEMPERATURE SENSOR PIPE UNION FM FLOW METER PIPE FLOW DIRECTION DbQ BALL VALVE PIPE SIZE BALANCING VALVE --- CW PIPING SPRING CHECK VALVE HW PIPING 7d INLINE Y-STRAINER HWC PIPING SHEET NOTES (1) SEE HPWH EQUIPMENT DETAIL 4/P8.02 (2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (4) PROVIDE 12" HEAT TRAP (5) EQUIPMENT DRAIN (6) ROUTE T&P RELIEF TO DRAIN (7) BAG FILTER (PENTAK, WF-1) (8) INLINE PIPE STRAINER (9) AUTOMATIC AIR BLEED (10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM (11) NOT USED (12) NOT USED (13) WIRE TO CONTROLLER (TYPICAL) (14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS. REFER TO HW1.00 FOR MORE INFORMATION. (15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF THERMAL BRIDGES (16) NOT USED (17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL) (18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL) (19) R-10 THERMAL ISOLATION (20) PROVIDE SEISMIC BRACING (21) CONNECT TO BUILDING COLD WATER SUPPLY LINE. (22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW. CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY LINE DISTANCE TO THE PRIMARY STORAGE [ST-1]. (23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING STARTUP. (24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND CONDENSATE DISCHARGE. TEMPERATURE GAUGE TYP. ALL T \ 211 -��---- -------- --4)a�� CW CTRL-1 (7) (21) 0 I ' (18) (23) T P-1 311 �- - -- -- - ---- � I HWC 311 (5) TEMPERATURE SENSOR i 4 TYP. ALL (13) (10) 211 TMV-C i (2) 2" T3 T \ 2�� -- --� -- I D5�� HW I 2�� H T (14) (15) XT ' � I T2 (10) 2�� I I (6) 6 ) 2" 2" o WH-C I O i (20) I I I I li Lam _ 311 T6 I i (3) 211 (5) (5) (19) o� (24) FS-1 HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Sure B Sl--Iod. WA 98292 www.dexign�. nw.com ECOTOPE 1 91 7 1 ST AVE, #300 SEATTLE WA 9B 1 O 1 PH: (ZO6) 3ZZ-3753 FAX: (206) 325-7270 W CID CV O 00 am Cn O �z Cn Z Q Z0 o w C� J LLI Z L LI (� w Cn LL w c, a C) H OJaM c� CV W a L0 C V ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date I Description 2 +01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG C SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 3,0 A OUTDOORS HPWH D4 1„ HPWH D3 1�� HPWH D2 1„ HPWH -:D: 1: 1 17-1 a 2! ! a a 2! ! a a 2! ! 11 a 2 L 2 311 311 ( 22 ) i - I - - -- -- -- 4 -- -- 4 . n 7 I I I 311 311 -----11------------ --�►----� (22) 311 --- ----- - - ------------ - - ---------- PLUMBING - HPWH SCHEMATIC - BLDG D 1 1-011 MECHANICAL ROOM 311 F I I I I I I I I I I (20) I I I (13) (13) OT(T4 311 4 (19) T1 (17) /T (13) I I I i i I L I � I I (6) (20) (10) (4) (13) T6 n �I T2 211 LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION ® PUMP PIPE-T MIXING VALVE T&P RELIEF VALVE PMP # EQUIPMENT TAG MANUAL AND AUTOMATIC AIR BLEED QTEMPERATURE SENSOR PIPE UNION FM FLOW METER PIPE FLOW DIRECTION BALL VALVE 41 PIPE SIZE BALANCING VALVE --- CW PIPING SPRING CHECK VALVE HW PIPING INLINE Y-STRAINER HWC PIPING (18) a 5) 211 SHEET NOTES (1) SEE HPWH EQUIPMENT DETAIL 4/P8.02 (2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD CONDITION WITH CONTINUOUS HWC PUMP OPERATION (4) PROVIDE 12" HEAT TRAP (5) EQUIPMENT DRAIN (6) ROUTE T&P RELIEF TO DRAIN (7) BAG FILTER (PENTAK, WF-1) (8) INLINE PIPE STRAINER (9) AUTOMATIC AIR BLEED (10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM (11) NOT USED (12) NOT USED (13) WIRE TO CONTROLLER (TYPICAL) (14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS. REFER TO HW1.00 FOR MORE INFORMATION. (15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF THERMAL BRIDGES (16) NOT USED (17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL) (18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL) (19) R-10 THERMAL ISOLATION (20) PROVIDE SEISMIC BRACING (21) CONNECT TO BUILDING COLD WATER SUPPLY LINE. (22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW. CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY LINE DISTANCE TO THE PRIMARY STORAGE [ST-1]. (23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING STARTUP. (24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND CONDENSATE DISCHARGE. TEMPERATURE GAUGE TYP. ALL T\ - ------- --- 211 CW (21) (23) T \ P-1 311 -I - -- -- - ---- s I HWC (5) TEMPERATURE SENSOR TYP. ALL 4 (13) 211 TMV-D (2) 211 T3 T \ 2If -- I ��a---� HW H T (14) (15) I I (10) 211 I I I I I ' I (6) 211 WH-D I I C (20) I I I I I L (3) 211 L-----] (5) (19) %--® (24) FS-1 HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629.3441 P.O. Box I'll,10031 'a532, suite B Stanwood. WA 98191 www.dexig —l— ECOTOPE V 1 91 7 1 ST AVE, #3130 5EATTLE WA 9B 1 O 1 PH: (ZO6) 3ZZ-3753 FAX: (206) 325-7270 UU CID CV O 00 am Cn O �z C) Q Z 0 W C� J LLJ Z L LI 1� (� w m w c, a Cf) H OJaM c� CV W a L0 CV 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG D SCALE: 1/8" = 1'-01, DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 3,0 AW\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 W Cfl N O 00 am Cn O �z U) Z Q zO w C' J Liu Z LLI U) w w V Q U) = O J a C.0 M N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT lwullimmakimm PLUMBING - WATER RISER DIAGRAM - BUILDING A SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,0 ROOF LEVEL 3 3/4" 3/4" PM I 0.6822 GPM BA B304 8.5 CWFU 6 HWFU 1 BA B303 8.5 CWFU 6 HWFU 0.4548 GPM 3/4" 0 3/4" / 1 3/4" 1 3/4" ' f 18 HWFU 12 HWFU 14 GPM 9 GPM 1 BA 12 HWFU 1-1/4" 1" B204 9 GPM 25.5 CWFU 17 CWFU 1„ I 18 GPM 13 GPM 8.5 CWFU 17 CWFU 1-1/4" 1" 6 HWFU 13 GPM LEVEL 2 1 r-- 58.5 HWFU 32 GPM 142 CWFU SHUTOFF VALVE 52 GPM 2 LEVEL 1 76.5 HWFU 37 GPM 2" 0.9096 GPM 3/4" HOT WATE PLAN 109 CWFU 45 GPM 2" 2" DOMESTIC WATER CONNECTION THIS BUILDING 142 WFU, 52 GPM SEE CIVIL PLANS FOR CONTINUATION AND FOR SITE BACKFLOW PREVENTION AND WATER METER 83.5 CWFU 39 GPM 1-1/2" 7Y 1 BA -� B104 8.5 CWFU 6 HWFU --y 1 BA B203 8.5 CWFU 18 HWFU 6 HWFU 14 GPM 1-1/4" 25.5 CWFU 40.5 HWFU 18 GPM 25 GPM 1-1 /4" 1_1 /2" 18 HWFU 14 GPM 1-1/4" 1 BA B103 8.5 CWFU 6 HWFU 58 CWFU 32 GPM 1-1/2" 12 HWFU 9 GPM 1" 17 CWFU \13 GPM 1" 25.5 CWFU 18 GPM 1-1/4" DOMESTIC WATER PRESSURE CALCULATIONS STREET PRESSURE METER LOSS BACKFLOW DEVICE LOSS LOSS FROM DISTANCE MAIN INTO BUILDING SYSTEM 64 PSI -1.6 PSI -8 PSI -1 PSI CALCULATIONS - RESIDENTIAL UNIT SIZING CALCULATIONS KITCHEN SINK DISHWASHER BATH/SHOWER SHOWER BLDG 1 BA 1 1 1 0 B 2 BA 1 1 1 1 ELEVATION LOSS -12.6 PSI LAVATORY 1 2 PRESURE REQUIRED AT FURTHEST FIXTURE -30 PSI WATER CLOSET 1 2 PRESSURE AVAILABLE FOR FRICTION LOSS 10.8 PSI PER 2018 UPC TABLE A 103.1 AND FOOTNOT... COLD WATER WSFU 8.5 10 DEVELOPED LENGTH OF SYSTEM 130' HOT WATER WSFU 6 7.5 EQUIVALENT LENGTH FROM FITTINGS 33' COLD WATER GPM 7 GPM 8.5 GPM TOTAL DEVELOPED LENGTH 163' HOT WATER GPM 5 GPM 6.5 GPM PER CHART A 105.1(1): FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 163 FT PER 100 FT) 6.67 PSI/ 100 FT COLD WATER CONNECTION SIZE 3/4" 1" HOT WATER CONNECTION SIZE 3/4" 3/4" 0.2274 GPM 1 BA B302 8.5 CWFU 6 HWFU 1 BA B202 8.5 CWFU 6 HWFU 22.5 HWFU 17 GPM 1-1/4" 32.5 CWFU 21 GPM 1-1/4" 1 BA B102 8.5 CWFU 6 HWFU 3/4" z - 2 BA B301 10 CWFU 7.5 HWFU 1" 2 BA 15 HWFU B201 12 GPM 10 CWFU 7.5 HWFU HB-1 2.5 CWFU 2 BA 1B1:0 1 10 CWFU 7.5 HWFU 20 CWFU 15 GPM 1-1/4" ROOF LEVEL 3 LEVEL 1 Ahn HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O 11mmmWz Z Q zO W C' J Liu Z W Lu w V Q O J a c� M N L N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description CONTENTS: PLUMBING - WATER RISER DIAGRAM - BUILDING B SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,02 RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ROOF 3 HWFU 6 HWFU 9 HWFU 12 HWFU 15 HWFU 18 HWFU 21 HWFU 3 GPM 6 GPM 8 GPM 9 GPM 12 GPM 14 GPM 15 GPM LEVEL 2 3/4" 3/4" ill ill 1" 1-1 /4" 1-1 /4" 3 CWFU 6 CWFU 9 CWFUTI 2CWFU 15 CWFU 18 CWFU 21 CWFU 3 GM \ 6 GM 1 8 GPM 9 GPM 12 GPM 14 GPM 15 GPM P4P 1 1-1/4" 1-1/4'' I I I I WB-1 WB-1 FWB-1 FWB-1 WB-1 FWB-1 FWB-1 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU LEVEL 1 3/4" 24 HWFU 21 CWFU 18 GPM 15 GPM 1-1/4" 1-1/4" 24 CWFU 3/4" 18 GPM 1-1/4" 1.5 GPM2 GPM 3/4" 134 CWFU 51 GPM 100.5 HWFU 2" 44 GPM SHUTOFF VALVE SK-3 1= 172.5 CWFI 1.125 CWFU 59 GPM 1.125 HWFU 2 76.5 HWFU HOT 37 GPM WATER 2" PLANT 0 rn G� 1" 15 HWFU 12 GPM I 1" 20 CWFU 15 GPM 1-1/4" 110 CWFU 45 GPM 2" DOMESTIC WATER PRESSURE CALCULATIONS STREET PRESSURE METER LOSS BACKFLOW DEVICE LOSS LOSS FROM DISTANCE MAIN INTO BUILDING SYSTEM 64 PSI -1.6 PSI -8 PSI -1 PSI CALCULATIONS - RESIDENTIAL UNIT SIZING CALCULATIONS KITCHEN SINK DISHWASHER BATH/SHOWER SHOWER BLDG 1 BA 1 1 1 0 C 2 BA 1 1 1 1 ELEVATION LOSS -12.6 PSI LAVATORY 1 2 PRESURE REQUIRED AT FURTHEST FIXTURE -30 PSI WATER CLOSET 1 2 PRESSURE AVAILABLE FOR FRICTION LOSS 10.8 PSI PER 2018 UPC TABLE A 103.1 AND FOOTNOT... COLD WATER WSFU 8.5 10 DEVELOPED LENGTH OF SYSTEM 180' HOT WATER WSFU 6 7.5 EQUIVALENT LENGTH FROM FITTINGS 45' COLD WATER GPM 7 GPM 8.5 GPM TOTAL DEVELOPED LENGTH 225' HOT WATER GPM 5 GPM 6.5 GPM PER CHART A 105.1(1): FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 225 FT PER 100 FT) 4.82 PSI/ 100 FT COLD WATER CONNECTION SIZE 1" 1" HOT WATER CONNECTION SIZE 3/4" 1" 0.6822 GPM 0.4548 GPM 2 BA C304 10 CWFU 7.5 HWFU I I 1" 2 BA C204 10 CWFU 7.5 HWFU 18 HWFU 14 GPM 1-1/4" 1 BA C303 8.5 CWFU yWFU 3/4" 0.2274 GPM 1 BA C302 8.5 CWFU 6 HWFU 1 BA C301 8.5 CWFU 6 HWFU I I I I 3/4" 13/4" � 3/4" 1 BA 1 BA 1 BA C203 C202 C201 12 HWFU 12 HWFU 12 HWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 9 GPM 6 HWFU 9 GPM I 6 HWFU 9 GPM 6 HWFU 1" 1" 1" 17 CWFU 18 HWFU 17 CWFU 17 CWFU \ 13 GPM 14 GPM 13 GPM 13 GPM \ 1 1-1/4" 1 1 J 54 HWFU 30 GPM 2" ' 79 CWFU 38 GPM 2 61.5 HWFU 33 GPM 2" 25.5 CWFU - 89 CWFU 18 GPM 41 GPM 1-1/4" 2" 2 BA C104 10 CWFU FHB-1 7.5 HWFU 1 CWFU C� 2" DOMESTIC WATER CONNECTION THIS BUILDING 172.5 WFU, 59 GPM SEE CIVIL PLANS FOR CONTINUATION AND FOR SITE BACKFLOW PREVENTION AND WATER METER 36 HWFU 23 GPM 1-1/2" 53.5 CWFU 30 GPM 1-1/2" I 25.5 CWFU I 18 GPM 1-1/4" 1 BA -� C103 8.5 CWFU 6 HWFU J 18 HWFU 14 GPM 1-1/4" 28 CWFU 19 GPM 1-1/4" 1 BA -� C102 8.5 CWFU 6 HWFU 1 8.5 CWFU 6 HWFU HB-1 2.5 CWFU ROOF LEVEL 2 LEVEL 1 HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O �z U) Z Q z O w C' J Liu U) Z WU) Lu Cl) LL w V Q = O J m c.0 Cy') N L N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description CONTENTS: PLUMBING - WATER RISER DIAGRAM - BUILDING C SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,03 RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ROOF LEVEL 3 LEVEL 2 LEVEL 1 15 HWFU 12 GPM 1" 20 CWFU 15 GPM 1-1/4" I HB-1 ALJ 2.5 CWFU DOMESTIC WATER PRESSURE CALCULATIONS STREET PRESSURE METER LOSS BACKFLOW DEVICE LOSS LOSS FROM DISTANCE MAIN INTO BUILDING ELEVATION LOSS PRESURE REQUIRED AT FURTHEST FIXTURE SYSTEM 64 PSI -1.6 PSI -8 PSI -1 PSI -12.6 PSI -30 PSI CALCULATIONS - RESIDENTIAL UNIT SIZING CALCULATIONS KITCHEN SINK DISHWASHER BATH/SHOWER SHOWER LAVATORY WATER CLOSET BLDG 1 BA 1 1 1 0 1 1 D 2 BA 1 1 1 1 2 2 PRESSURE AVAILABLE FOR FRICTION LOSS 10.8 PSI PER 2018 UPC TABLE A 103.1 AND FOOTNOT... COLD WATER WSFU 8.5 10 DEVELOPED LENGTH OF SYSTEM 200' HOT WATER WSFU 6 7.5 EQUIVALENT LENGTH FROM FITTINGS 50' COLD WATER GPM 7 GPM 8.5 GPM TOTAL DEVELOPED LENGTH 250' HOT WATER GPM 5 GPM 6.5 GPM PER CHART A 105.1(1): FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 250 FT PER 100 FT) 4.34 PSI/ 100 FT COLD WATER CONNECTION SIZE 1" 1" HOT WATER CONNECTION SIZE 3/4" 1" 3/4" r 0.2274 GPM 0.4548 GPM 0.6822 GPM 0.9096 GPM 1.137 GPM I 2 BA D306 10 CWFU 7.5 HWFU 1" 2 BA D206 10 CWFU 7.5 HWFU 3/4" 12 HWFU 9 GPM 17 CWFU 13 GPM 1" 22.5 HWFU 17 GPM 1-1/2" 32.5 CWFU 21 GPM 1-1/2" 12.5 CWFU 10 GPM 1" I 2 BA 10 CWFU 7.5 HWFU HB-1 1 CWFU 1 BA 1 BA 1 BA 1 BA I 1 BA D305 D304 D303 D302 1 D301 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 6 HWFU 6 HWFU 6 HWFU 6 HWFU 6 HWFU � I I 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 I� G� q-� 1 gq 12 HWFU I q-� 1 BA 12 HWFU I q--� 1 BA 12 HWFU I q-� 1 BA 12 HWFU 1 BA 9 GPM I 9 GPM I 9 GPM I 9 GPM 17 CWFU 17 CWFU 17 CWFU 17 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU I 13 GPM U 6 HWF 13 GPM U 6 H 13 GPM WFU 13 GPM 6 HWFU 6 HWF 6 HWFU 25.5 CWFU 25.5 CWFU 1, 25.5 CWFU 25.5 CWFU I 3/4" 18 GPM 18 GPM 18 GPM 18 GPM 94.5 HWFU 1-1/4" 40.5 HWFU 1-1/4" 58.5 HWFU 1-1/4" 76.5 HWFU 1-1/4" 43 GPM 100.5 HWFU 112.5 HWFU 25 GPM 32 GPM 37 GPM 2" 44 GPM 46 GPM 1-1/2" 2" 2" 2" 2" - 59 CWFU 84.5 CWFU 110 CWFU 135.5 CWFU 144 CWFU 161 CWFU 32 GPM 40 GPM 45 GPM 52 GPM 54 GPM 56 GPM \ 1-1/2" 2" 2" 2" 2" 2" 18 HWFU 18 HWFU 18 HWFU 18 HWFU 14 GPM 14 GPM 14 GPM 14 GPM ' 33.5 CWFU 1-1/4" 21 GPM 1-1/2" 1 BA D105 8.5 CWFU 6 HWFU 1-1/4" 1 BA D104 8.5 CWFU 6 HWFU 1-1/4" 1 BA D103 8.5 CWFU 6 HWFU 1-1/4" 1 BA D102 8.5 CWFU 6 HWFU 1 BA 8.5 CWFU 6 HWFU H WP PLANT 208 CWFU 65 GPM 2" DOMESTIC WATER CONNECTION THIS BUILDING 208 WFU, 65 GPM SEE CIVIL PLANS FOR CONTINUATION AND FOR SITE BACKFLOW PREVENTION AND WATER METER ROOF LEVEL 3 LEVEL 1 HOUSING HOPE we keep hope alive DESIGNS 1 L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O �mmz U) Z Q zO w C' J Liu Z W U) Lu w V Q U) O J a c� M N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description CONTENTS: PLUMBING - WATER RISER DIAGRAM - BUILDING D SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,04 RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ROOF 1 Inl VI\L VIVI 1 V — ILV.J IE = 4' BELOW FF SEE CIVIL PLANS FOR CONTINUATION 3" VTR (62.5 DFU) J I L 3" VTR (32 DFU) J I L 50.5DFU r 311 I 2" 2" f--1— 3" 0 2"3" o 3" 3" 3" LL AWk HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Suile B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE V 1 91 7 1 ST AVE, #300 SEATTLE WA 9B 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 W CV O 00 am Cn O �z Cn Z Q z0 0 W C� J LLI Z _ L LI - (� w C� LLC) w c, a 0 cy-) CV L L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # j Date I Description 2 101/04/2023 1 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING A SCALE: 1/8" = 11-01, DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,05 ROOF 1 Inl VI\L VIVI I V— 1 1/ IE = 2.81 BELOW FF SEE CIVIL PLANS FOR CONTINUATION 3" VTR (51 DFU) J I L 2" I 2" 12DFU � /4DFU�11 3" VTR (66DFU) I jL 2" 3" 2" 24DFU 42DFU 35DFU 19DFU 13DFU 9DFU 71 0 LL 0 LL LL 2" (D o LL 0 rn o _ 1 1/211 4� 2" LEVEL 3 LEVEL 2 LEVEL 1 Ahn HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Suile B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE V 1 91 7 1 ST AVE, #300 SEATTLE WA 9B 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 W CV O 00 am Cn O �z Cn Z Q z0 m w C� J Lu Z _ L LI - (� w Ljj c, a C) O�aL0 CV L L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # j Date I Description 2 101/04/2023 1 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING B SCALE: 1/8" = 11-01, DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,06 ROOF 3" VTR (83 DFU) J I L 2" 55DFU 28DFU LO I 0 AWk HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Suile B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE 1 91 7 1 ST AVE, #300 8EATTLE WA 9B 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 W (0 CV O 00 am Cn O Cn z Z Q z0 0 W C� J LLJ M Z _ LLI - 3 w m w c, aCID C) 0 cy-) C14 L L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # j Date I Description 2 101/04/2023 1 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,07 C1 3" VTR (54 DFU) J I L 2't 2"30DFU 24DFU 10DFU I- LL 0 0 0 0 LL LL 0 2" I " rIAI UMr— UIN110 — IJ/ SEE SHEET P4.07 IE = 3.9' BELOW FF SEE CIVIL PLANS FOR CONTINUATION ROOF LEVEL 3 LEVEL 2 LEVEL 1 HOUSING HOPE we keep hope alive DESIGNS L 'V northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 91 7 1 ST AVE, #300 SEATTLE WA 9a 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 W am Cl) O Cn z Z Q z0 0 w C� J LLJ M � Z L LI (� w Ljj c, a C) 0 (L cy-) CV Mc L L0 CV 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,08 ROOF 3" VTR (84DFU) J I L 2" 24DFU 28DFU 48DFU 36DFU F LL = I > LL LO LO 0 2" 2" 00 � 2 2 N O onnrl Ahn HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Suile B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE V 1 91 7 1 ST AVE, #3130 5EATTLE WA 9B 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 UU (0 CV O 00 am Cn O �z Cn Z Q z0 0 W C� J Liu Z _ LLI - Cf) w Ljj c, aCID C) O�aL0 CV L L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # j Date I Description 2 101/04/2023 1 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,09 ROOF 3" VTR (48 DFU) J I L 36DFU LL LL 0 L 0 0 2" 2" °' � 2" 3" VTR (33 DFU) J I L 12DFU 0 2" N 2" " rIAI UMr— UINI 10 — 100 SEE SHEET P4.09 I = 4.25, BELOW FF SEE CIVIL PLANS FOR CONTINUATION ROOF Ahn HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 639.3441 P.O. Box 1^_70 10031 SR 532. Suile B Sl--Iod. WA 98292 wwww.designsnw.com ECOTOPE 1 91 7 1 ST AVE, #3130 5EATTLE WA 9B 1 O 1 PH: (Z06) 3ZZ-3753 FAX: (206) 325-7270 UU (0 CV O 00 am Cn O Cn z Z Q z0 0 W C� J LLJ M Z _ LLI - 3 w m w c, aCID C) 0 cy-) C14 L L0 CV ao CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # j Date I Description 2 101/04/2023 1 PERMIT RESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P4,1 O SHEET NOTES 1 HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE PLANS AND RISER DIAGRAMS FOR SIZES. 2 PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL. 3 WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN SIDE WALL AND BEHIND CABINETRY. 4 USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS WHERE POSSIBLE PI 11MRINC-, FNI ARC-,Fn HNIT PI ANq - Rini Akr\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 W Cfl N O 00 am Cn O �z U) Z Q zO w C' J Liu Z LLI U) w w V Q U) O J a M N LL1 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PLUMBING - ENLARGED UNIT PLANS SCALE: 1/4" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P5,0 PLUMBING ENLARGED UNIT PLANS - D206 1 /4" = 11-011 SIM: D306 PLUMBING ENLARGED UNIT PLANS - D101 1 /4" = 11-011 PLUMBING ENLARGED UNIT PLANS - C104 1 /4" = 11-011 S I M : D106 O SHEET NOTES 1 HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE PLANS AND RISER DIAGRAMS FOR SIZES. 2 PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL. 3 WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN SIDE WALL AND BEHIND CABINETRY. 4 USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS WHERE POSSIBLE O PLUMBING ENLARGED UNIT PLANS -C101 1 /4 = 11-011 SIM : C 102, C 103, D 102, D 103, D 104, D 105 AW\ HOUSING HOPE we keep hope alive DESIGNS 1 L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W c0 N O 00 a O �z U) Z Q zO w C' J Liu Z L L1 U) w w V Q U) O J a M N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PLUMBING - ENLARGED UNIT PLANS SCALE: 1/4" = V-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 5,0 PLUMBING ENLARGED UNIT PLANS - A204 1 /4" = 11-011 SIM: A202, A2035 A3025 A3035 A3045 B2025 B3025 C2015 C2025 C2035 C3015 C3025 C3035 D2015 D2025 D2035 D2045 D2055 D3015 D3025 D3035 D3045 D305 PLUMBING ENLARGED UNIT PLANS - A201 2 1 /4" = 11-011 SIM: A205, A3015 A3055 B2015 B3015 C2045 C304 O SHEET NOTES 1 HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE PLANS AND RISER DIAGRAMS FOR SIZES. 2 PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL. 3 WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN SIDE WALL AND BEHIND CABINETRY. 4 USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS WHERE POSSIBLE 1-BED B203 556 SF PLUMBING ENLARGED UNIT PLANS - B203 1 /4" = 11-011 SIM: B204, B3035 B304 HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 0 1 PH: (206) 322-3753 FAX: (206) 325-7270 r- W cD N O 00 am V ♦ O u) z z Q zo w C' J Liu Z LLI U) w w V Q U) Cy') N LLI N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - ENLARGED UNIT PLANS SCALE: 1/4" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 5,0 FIRE RISER C124 HW I CW HUB DRAIN FOR HD-1 ' I 1/2"o I I 1/2"o AFIRE VALVES I I I HWC — — ' 3/4" o HWC TP-1 - _ _-- HW 3/4"0 1 + 2"o 3" DOMESTIC WATER MAIN FROM BELOW — - -_I I CW 2„o THERMOSTATIC _ ________________I� BALANCING VALVE FS-1 I 1 ST-C1 I 3"V 2" CW 2" HW I �2"V W B-1 I EXP-C 3/4" HWC I I CW MECH I HPWH I TMV-C 1 HWC HW 1 1/4"o EL C I 11 3/4"o 1 1/4"o -I C120 W B-1 128 SF 11 I ! WH J �V I I -C FD-2 6 -IW 1 LAUNDRY 1 IN 2"V DN , C122 i11 FD-3 I I ELEC. I 126 SF CW I -I C121 H W W B-1 3/4"o W B-1 27 SF 3/4"o 1 '� W B-1-;J-—I---! r 1/2"CW&HW 2"W , 1-1 /2"V (TYP 7) CW HW 1"o 1"o ENLARGED PLUMBING PLAN - BLDG C MECHIWATER ROOM AND LAUNDRY ROOM 1 /4" = 11-011 FS-1 el HW CW 2"o HWC 2"o `3/4"o ST-D1 MECH 1 HPWH I 0 ELEC D120 I c 98 SF& TMV-D c J I c FD-2 I . 1 FIRE VALVE SPACE B H D-1 FIRE RISER D121 68 SF 1 8 FD-2 2"V ENLARGED PLUMBING PLAN - BLDG D MECHANICAL/WATER ROOMS 1 /4" = 11-011 U A CW HW HWC FD-2 2 "o 2"o - 3/4"0 ---- — FD-2 eMECH 1 HPWH I I B (ELEC I Al P-A TP-1 I122 ST-A1 ST-A2 I I � W H-A I • • I �� FS-1 2„V ! 2"V I STORAGE CW i I A 223 1 3"o Ili I 95 SIF I I I HW I 1 CW ^� 1 1 /4"o 2"W FROM SH '--2"V UP 3"W 21 j 3"W DN 14"HWC UP 5�,,2"W FROM BT 1/2"CW&HW 2"W , 1-1 /2"V ITM V-A I FIRE RISER A125 68 SF B H D-1 ftTA FIRE WATER FROM BELOW IRE VALVE SPACE OCATION TO BE COORDINATED ENLARGED PLUMBING PLAN - BLDG A MECHANICAL/WATER ROOM 1 /4" = 11-011 4"W DN 1/2"CW TP-2 WCO- 1/2"HW 2"W L _ HW CW 1/2": 3/4"o L-2 W C CW FD-3 1 1/4"o c I -'IV UP U P 53 SF HW 1"0 — 7 __r T HW 3"W UP 1 1"o "W DNJ 1-1/2" V HW CW 1 1 /2"o 1 1 /4"o ---STORAGE'-- _ A110 — —53 SF - CW 1 1 /2"o i WC-2 ® 9R-1 C -- �-- -T ILET-- __ — ��-53SF M _� CW&HW UNIT RISERS UP 1 /2"C W 2"W 1-1 /2"V ------- 1 /2"C W ------ - S K-4 1 /2"H W 2"W 1-1 /2"V < > - CW �—_I 1 1/2"0 l e ! _, DF-1 1-1/2" V 1 /2"C W 1 /2"H W 2"W 1-1 /2"V ENLARGED PLUMBING PLAN - BLDG A AMENITY RESTROOMS 1 /4" = 11-011 FIRE VALVE SPACE FIRE WATER FROM BELOW HD-1 B ,USER 6120 66 SF B FD-2 HW CW HWC 2"o 2"o 3/4"o ::�TMV-B11 II ST-B1 I e FS-1 MECHIHPWHI • , ELEC W B121 ST-62 105 S I r mm II __1 II I II II 3" DOMESTIC WATER MAIN FROM BELOW ENLARGED PLUMBING PLAN - BLDG B MECHANICAL/WATER ROOM 1 /4" = 11-011 AkF\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. com ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 M; W am Cn O �mmz Z Q zO LU C' J LLI E � Z W U) w m w V Q U) O J a c� M N mc L N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING - ENLARGED AREA PLANS SCALE: 1/4" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: 5,0 ULATION BACKII MATEF AS RE( A�PIPE THRU INTERIOR WALL WITH PIPE INSULATION IT IPE BACKI MATEI AS RE SULATION JG IAL )UIRED r PIPE THRU FLOOR WITH PIPE INSULATION PIPE RISER CLAMP WHERE APPLICABLE SEALANT" BACKING gPIPE THRU INTERIOR WALL WITHOUT PIPE INSULATION MATERIAL AS REQUIRED D�PIPE THRU FLOOR WITHOUT PIPE INSULATION PIPE THRU INTERIOR WALL AND THRU FLOOR 1211 = 11-011 VIBRATION ISOLATION SEE SPEC FOR TYPE PRESSURE GAUGE II II SHUT-OFF VALVE TY U KuU11 5t I I tK tS&6 PLUS, NOMINAL LINE SIZE BLOW DOWN VALVE NOTE: MOUNT PUMP MOTOR HORIZONTAL, OR BELOW PUMP FOR HOT WATER APPLICATIONS INLINE PUMP PIPING TRIM DETAIL 1211 - 11-011 _L ANOUT VENT AS HIGH AC DncclDI E: UNDER COU SH --LOOR 1 PITCH VENT UP TOWARD WALL "Y" FITTING - ISLAND VENT DETAIL 9 1 211 = 1 1-011 WASTE PIPING, SIZE AS SHOWN ON PLAN If VANDAL RESISTANT COVER MARKED "SEWER" WASTE STACK RECIEVING DISCHARGE FROM 3 OR MORE STORIES OF SUDS PRODICING FIXTURES 8FT MIN HORIZONTAL CHANGE IN DIRECTION (BOTTOM OF STACK). NO DRAINAGE CONNECTIONS WITHIN 8FT HORIZONTALLY AND 8FT VERTICALLY FROM STACK CHANGE IN DIRECTION 000, 0 O/AFC T% M 8FT MIN DRAINAGE CONNECTION SUDS RELIEF PIPING DETAIL 611 - 11-011 PIPE SLEEVE OF SIZE TO PASS PIPE AND LEAVE ROOM FOR PIPE INSULATION TERMINATE SLEEVE FLUSH WITH WALL SURFACE ICI» FILL ANNULAR GAPS EACH SIDE OF SLEEVE WITH NONCOMBUSTIBLE SEALANT PIPE WALL PENETRATION 1 211 = 1 1-011 SEE MINIMUM PIPE INSULATION TABLE FOR INSULATION THICKNESS FINISHED WALL SURFACE 1O GROUT SLOPE TC DRAIN INLE1 DRAIN INLET STRAINEF CORED HOLE DRAIN BODY STYLE WITH DRAINLINE CORE DRILL FLOOR DRAIN 1211 - 11-011 4 5 -RUCTURAL DNCRETE OOR RAINER EXTENSION SHRINK CONCRETE- tF'UAY IiKUU 1 IIV ANNULAR CORE SPACE & SURFACE SLOPE. 20 SHEET METAL CLOSURE ANCHORED TO CONCRETE FLOOR. OSAFING MATERIAL 1-1/2 x DRAIN DIAMETER (8) MINIMUM STUD PIN SUPPORTS. 40 1-1/2"0"x12" ANGLE STEEL SUPPORT EACH SIDE MINIMUM (4) STUD PIN FASTENERS. :HANGER ;UT TO LENGTH LATION - LENGTH 1.5 TIMES INSULATION DIAMETER INSULATION CARRIER PIPE PIPE HANGER - CLEVIS TYPE 1211 - 11-011 nnnrn "In" AKIM Pr/�I Inr1 \/ LRESIDENTIAL SINK AND DISHWASHER 1 211 = 1 1-011 AW\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 31 100SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 O 1 PH: (206) 322-3753 FAX: (206) 325-7270 R M W O �Wz z Q z W C' J Uj Z W W W V Q 0 c� CV mc U Lo CV 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description 2 01/04/2023 IPERMITRESUBM. RESUB 4/8/2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: PLUMBING DETAILS SCALE: As indicated DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: P810 T&P RELIEF VALVE TO DRAIN TEMPERATURE GAUGE (TYP)O O/T OUTGOING DOMESTIC HOT WATER SERVICE SHUTOFF VALVE (TYP) Al INCOMING DOMESTIC COLD WATER CHECK VALVE TO DRAIN FOR BACKFLUSHING STATIC DEFLECTION SPRING ISOLATORS (TYP) HPWH TYPICAL DETAIL 1211 = 1'-011 COLD WATER LINE -$" HOUSING HOPE we keep hope alive SHUT-OFF VALVE - TRAP PRIMER VALE VACUUM BREAKER PORT ` DESIGNS h w e s t DISTRIBUTION UNITS) ARCHITECTS (WHERE REQUIRED) 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com H �pn �$„ O FLOOR SINK, FLOOR DRAIN OR HUB DRAIN 1BEVEL ECOTOPE CUT Tp AIRGAP \ _8"x1 -8" 1 917 1 5T AvE, a300 SEATTLE WA 9B 1 O 1 CONNECT TRAP PRIMER PH: (206) 322-3753 INLET TO FIXTURE FAX: (206) 325-7270 OUTLET TAILPIECE SIDE OF TRAP NOTES: 1. PROVIDE ACCESS PANEL IN WALLS AT TRAP PRIMER UNIT LOCATIONS. 2. TRAP PRIMER VALVE SHALL BE MOUNTED ONE FOOT ABOVE THE FINISHED FLOOR FOR EVERY 20 FEET OF PRIMER LINE. 3. INSTALL TRAP PRIMER PIPING AND UNIT PER MANUFACTURER'S RECOMMENDATIONS. PIPING MUST SLOPE TO POINT OF CONNECTION TO DRAIN WITHOUT TRAPS IN PIPING c0 N TRAP PRIMER INSTALLATIONCD 00 1211 — 1'-011 UJI am COMMON VENT c STACK TO ROOF O Wz Z zO Q2" DRY VENT � w LAV TRAP ARM 2" WET VENT LU VERTICAL WET VENTING NOTES: Lu U) UmWATER CLST WET VENT NOT TO EXCEED 6 FT IN DEVELOPED pC TRAP ARM LENGTH. TUB TRAP WET VENT PIPE SIZE TO BE ONE PIPE SIZE LARGER ARM THAN THE REQUIRED MINIMUM OF THE UPPER co N FIXTURE OR SHALL BE ONE PIPE SIZE LARGER LO THANT HE SUM OF THE FIXTURES SERVED BY THE WET VENT, WHICHEVER IS GREATER. NO WE VENT = W 00 IS ALLOWED LESS THAN 2". COMMON WASTE DRY VENT CONNECTION SIZE SHALL BE THE SUM STACK TO OF THE FIXTURE UNITS SERVED BUT NEVER LESS BUILDING DRAIN THAN 2". CONSTRUCTION DOCUMENTS WET VENT PIPING DETAIL ISSUE DATE: JAN. 3, 2023 12" = 1'-0" REVISION SCHEDULE R-11 INSULATION JACKET Rev# 11 Date Description 2 01/04/2023 IPERMITRESUBM. SERVICE SHUTOFF VALVE (TYP) UNION (TYP) RESUB MANUAL AIR BLEED VALVE1 CITY OF EDMONDS \ DEVELOPMENT 11 SERVICES 1 DEPARTMENT / \ --- CAPPED FITTING EARTHQUAKE STRAPPING PER UPC WATER HEATER OR HOT WATER STORAGE TANK T&P RELIEF VALVE (TYP) ROUTE TO APPROVED LOCATION THERMO WELL TEMPERATURE PROBE INSULATED PIPING CONNECTION (TYP) R-10 RIGID INSULATION PLUMBING DETAILS SCALE: 12" = 1'-0" DRAWN: SLB CHECKED: SLB PROJECT NO: 2021031.00 SHEET: HOT WATER STORAGE TANK DETAIL1 1211 = 1'-011