APPROVED RESUB2 BLD2022-1346+Plumbing_Plan+4.6.2023_10.29.49_AM+3467107PLUMBING GENERAL NOTES
1. THE FOLLOWING NOTES APPLY TO ALL PLUMBING DRAWINGS. ADDITIONAL PLUMBING NOTES
MAY BE INDICATED ON EACH PLUMBING DRAWING. SEE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
2. INSTALL ALL WASTE LINE CLEANOUTS IN ACCORDANCE WITH CHAPTER SEVEN OF THE
UNIFORM PLUMBING CODE.
3. ALL SANITARY SEWER PIPING BELOW SLAB SHALL BE INSTALLED AT A MINIMUM OF 1/41, PER
FT SLOPE UNLESS APPROVAL IS PROVIDED BY THE "ADMINISTRATIVE AUTHORITY" IN WRITING
FOR A SHALLOWER SLOPE. IN NO CASES SHALL SEWER PIPING BE INSTALLED AT LESS THAN
1/8" PER FT SLOPE. IN NO CASES WILL PIPING SMALLER THAN 4" BE INSTALLED AT SLOPES
SHALLOWER THAN 1/4" PER FOOT. PIPING INSTALLED AT 1/8"/FT SHALL BE RESIZED PER
CHAPTER 7 OF THE UNIFORM PLUMBING CODE AND SUPPORTING CALCULATION SUBMITTED
TO ENGINEER FOR REVIEW.
4. PROVIDE STOPS PRIOR TO ALL PLUMBING EQUIPMENT. THIS SHALL ALSO INCLUDE
PROVIDING INTEGRAL STOPS ON ALL SHOWER AND TUB/SHOWER VALVES (WHETHER
SPECIFIED OR NOT). PROVIDE WASTE TRAPS AT ALL DIRECT CONNECTED EQUIPMENT IN
ACCORDANCE WITH CODE AND THE SPECIFICATIONS.
5. INSULATE P-TRAPS EXPOSED IN UNHEATED SPACES.
6. SEE ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS AND PLUMBING FIXTURE HEIGHTS,
AS WELL AS ROUGH -IN DIMENSIONS AND OTHER DETAILS. ALSO SEE ARCHITECTURAL
DRAWINGS FOR FINISH REQUIREMENTS OF ALL PLUMBING FIXTURES INCLUDING
REQUIREMENTS FOR FLUSH LEVER LOCATION AT ADA COMPLIANT TOILETS AND VALVE
LOCATIONS OF ADA SHOWERS. REPORT ALL DISCREPANCIES TO ENGINEER PRIOR TO ANY
WORK.
7. PLUMBING DRAWINGS SHOW APPROXIMATE LOCATIONS OF PLUMBING FIXTURES. REFER TO
ARCHITECTURAL PLANS FOR EXACT LOCATIONS. COORDINATE FLOOR DRAINS FOR
MECHANICAL SPACES WITH MECHANICAL EQUIPMENT BEING SERVED.
8. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION
INCLUDING CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC.
9. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL CHARACTERISTICS OF
PLUMBING EQUIPMENT (VOLTAGES, ETC). ELECTRICAL CHARACTERISTICS OF LISTED
EQUIPMENT SHALL BE VERIFIED BY CONTRACTOR DURING SUBMITTAL PROCESS. ANY
ELECTRICAL CHARACTERISTICS THAT DEVIATE FROM THOSE LISTED SHALL BE IDENTIFIED BY
THE CONTRACTOR, SUBMITTED TO THE ENGINEER FOR APPROVAL AND COORDINATED WITH
DIVISION 26 ELECTRICAL PRIOR TO INSTALLATION OF EQUIPMENT AS REQUIRED TO
PROPERLY SERVE EQUIPMENT.
10. PROVIDE PLUMBING ANCHORAGE AND EXPANSION EVERY 100' PIPE LENGTH PER CODE.
11. ACCESS PANELS ARE REQUIRED AT ALL CONCEALED VALVES AND EQUIPMENT. COORDINATE
LOCATION AND SIZE WITH ARCHITECT.
12. STUB OUT TO SITE SERVICES 5' OUTSIDE BUILDING FOUNDATION. PIPE SIZE, FIXTURE UNITS,
AREA DRAINED, INVERT ELEVATION, SIZES, AND SQUARE FOOTAGES AS INDICATED. NOTIFY
ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WORK.
13. INSULATE PIPING PER WSEC C404.6 AND PER DIVISION 22 SPECIFICATIONS (WHICHEVER IS
GREATER).
14. GENERALLY DUCTWORK PLANNED TO BE TIGHT TO STRUCTURE WITH PIPING BELOW
DUCTWORK AND BETWEEN LIGHT FIXTURES. ADJUST AS NECESSARY.
15. PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS SHALL ALLOW MINIMUM ACCESS
OF 6" IF RUNNING PARALLEL AND ABOVE CABLE TRAYS, ALLOW 18" TO THE SIDE OF CABLE
TRAYS.
16. COORDINATE LOCATIONS OF PLUMBING EQUIPMENT TO PROVIDE CLEARANCES OVER
LIGHTING FIXTURES FOR REMOVAL AND SERVICE ACCESS DUE TO EQUIPMENT
MAINTENANCE.
17. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR
PLANS AND SECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY.
18. DO NOT CORE DRILL OR DRILL THROUGH BEAMS, COLUMNS, AND SHEAR WALLS, UNLESS
INDICATED ON STRUCTURAL DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
19. PIPES INDICATED WITHOUT DIMENSIONS SHALL BE SIZED PER PRECEDING UPSTREAM PIPE
SECTIONS. WHERE PIPE SIZES ARE NOT SHOWN ON DRAWINGS, SIZE PIPING PER THE
UNIFORM PLUMBING CODE.
20. DRAWINGS ARE SCHEMATIC IN SOME AREAS AND MAY NOT SHOW PIPING OFFSETS WHICH
MAY BE REQUIRED.
21. ALL WATER PIPING IN UNHEATED SPACES SHALL BE HEAT TRACED AND INSULATED.
22. PRIOR TO SUBMITTING ALL PLUMBING FIXTURES THE CONTRACTOR SHALL VERIFY
COMPATIBILITY OF THE SPECIFIED FIXTURE WITH THE SIZES OF FINISH CABINETRY AS
IDENTIFIED IN GENERAL CONTRACTOR'S SHOP DRAWINGS. ANY DISCREPANCIES BETWEEN
THE SIZE OF THE FIXTURES SPECIFIED AND THE FINISH CABINETRY SIZES SHALL BE
BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING BEFORE SUBMITTAL.
23. PLUMBING VENTS SHALL TERMINATE MINIMUM 10' FROM FRESH AIR INTAKES PER CODE.
24. LABEL ALL PIPING SYSTEMS PER THE IMC AND UPC.
25. SUPPORT AND BRACE PIPING SYSTEMS IN ACCORDANCE WITH UPC SECTION 314 AND AS
REQUIRED IN THE SPECIFICATIONS.
26. TEST HYDRONIC PIPING PER IMC 1208.
27. ALL MATERIALS IN CONTACT WITH PIPING SYSTEMS SHALL BE COMPATIBLE FOR USE WITH
AND FOR CONTACT WITH THE PIPING MATERIAL CONTRACTORS AND TRADES SHALL VERIFY
COMPATIBILITY OF THEIR PRODUCTS WITH THE PIPING SYSTEMS. THIS INCLUDES, BUT IS NOT
LIMITED TO, FIRE STOPPING SEALANTS, FIRE STOPPING COLLARS, VIBRATION ISOLATION
ELEMENTS, THERMAL INSULATION, EXPANSION JOINTS AND ANY MATERIAL IN CONTACT WITH
PIPES.
28. ALL CAST IRON SOIL PIPE AND FITTINGS SHALL BE MARKED WITH THE COLLECTIVE
TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE (CISPI) AND BE LISTED BY NSF
INTERNATIONAL.
29. PIPE BURIAL METHODS FOR BELOW GRADE PIPING SHALL COMPLY WITH MFR INSTALLATION
INSTRUCTIONS, ASTM D 2321 AND ASTM F1668. FAILURE TO FOLLOW THESE REQUIREMENTS
CAN LEAD TO PIPE FAILURE.
30. ALL ITEMS IN CONTACT WITH POTABLE WATER SHALL COMPLY WITH THE NATIONAL
"REDUCTION OF LEAD IN DRINKING WATER ACT" S.3874.
REVISIONS
DATE PAGES CHANGES
REV1
REV2
REV3
REV4
REV5
PLUMBING LEGEND
SYMBOL DESCRIPTION
A101 SECTION/ELEVATION VIEW
1 DETAIL VIEW
A101
W PLUMBING EQUIPMENT TAG
P-1
TYP # PLUMBING FIXTURE TAG
TMV-1 PLUMBING ACCESSORIE TAG
OSHEET NOTE TAG
Al WASTE RISER TAG
Al REVISION TAG
D ENVELOPE PENETRATION
PLAN
- SECTION
- SCHEMATIC
CHECK VALVE
V�
BALL VALVE
g�
GATE VALVE
MOTOR CONTROL VALVE
o�
PRESSURE REGULATING VALVE
PRESURE RELEIF VALVE
Do-
BACK FLOW PREVENTER
MANUAL BALANCING VALVE
THERMOSTATIC BALANCING VALVE
-I-
UNION
GAS PRESSURE REGULATOR
WATER METER
- °
(P)
PRESSURE GAUGE
TEMPERATURE GAUGE
a
PUMP
D
G
EXPANSION TANK
LINE TYPES
- -
--cW
COLD WATER PIPING
HW
HOT WATER PIPING
--- ---HWC
HOT WATER CIRCULATION PIPING
W
WASTE PIPING
- - - -
- V
VENT PIPING
COND
CONDENSATE PIPING
�As
GAS PIPING
FP
FIRE PROTECTION PIPING
2018 WSEC TABLE C403.2.9
MINIMUM PIPE INSULATION THICKNESS(THICKNESS IN INCHES)
FLUID OPERATING
TEMPERATURE
RANGE AND
USAGE (°F)
INSULATION CONDUCTIVITY
NOMINAL PIPE OR TUBE SIZE (inches)
CONDUCTIVITY
Btu•in/(h•ft2•OF)Ab
MEAN RATING
TEMPERATURE, OF
<1
1 TO
< 1-1/2
1-1/2
TO < 4
4 TO < 8
> 8
-
>350
0.32 - 0.34
250
4.5
5.0
5.0
5.0
5.0
251-350
0.29 - 0.32
200
3.0
4.0
4.5
4.5
4.5
201-250
0.27 - 0.30
150
2.5
2.5
2.5
3.0
3.0
141-200
0.25 - 0.29
125
1.5
1.5
2.0
2.0
2.0
105-140
0.21 - 0.28
100
1.0
1.0
1.5
1.5
1.5
40-60
0.21 - 0.27
75
0.5
0.5
1.0
1.0
1.0
<40
0.20 - 0.26
75
0.5
1.0
1.0
1.0
1.5
A. FOR PIPING SMALLER THAN 1-1/2 INCH (38 MM) AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES, REDUCTION OF
THESE THICKNESSES BY 1 INCH (25 MM) SHALL BE PERMITTED (BEFORE THICKNESS ADJUSTMENT REQUIRED IN FOOTNOTE B) BUT
NOT TO A THICKNESS LESS THAN 1 INCH (25 MM).
B. FOR INSULATION OUTSIDE THE STATED CONDUCTIVITY RANGE, THE MINIMUM THICKNESS (T) SHALL BE DETERMINED AS
FOLLOWS: T = R{(1 + T/R)K/K - 11 WHERE: T = MINIMUM INSULATION THICKNESS, R = ACTUAL OUTSIDE RADIUS OF PIPE, T =
INSULATION THICKNESS LISTED IN THE TABLE FOR APPLICABLE FLUID TEMPERATURE AND PIPE SIZE, K = CONDUCTIVITY OF
ALTERNATE MATERIAL AT MEAN RATING TEMPERATURE INDICATED FOR THE APPLICABLE FLUID TEMPERATURE (BTU X IN/H X FT X
°F) AND K = THE UPEER VALUE OF THE CONDUCTIVITY RANGE LISTED IN THE TABLE FOR THE APPLICABLE FLUID TEMPERATURE.
C. FOR DIRECT -BURIED HEATING AND HOT WATER SYSTEM PIPING, REDUCTION OF THESE THICKNESSES BY 1-1/2 INCHES SHALL
BE PERMITTED (BEFORE THICKNESS ADJUSTMENT REQUIRED IN FOOTNOTE B BUT NOT TO THICKNESSES LESS THAN 1 INCH.)
PLUMBING ABBREVIATIONS
AFF
ABOVE FINISHED FLOOR
AHJ
AUTHORITY HAVING JURISDICTION
ARCH
ARCHITECT
BFF
BELOW FINISHED FLOOR
BV
BALANCING VALVE
CTE
CONNECT TO EXISTING
CV
CHECK VALVE
CW
COLD WATER
DCVA
DOUBLE CHECK VALVE ASSEMBLY
DF
DRINKING FOUNTAIN
DFU
DRAIN FIXTURE UNIT
DIA
DIAMETER
DN
DOWN
DWV
DRAIN WASTE VENT
ELEV
ELEVATION
ESV
EARTHQUAKE SHUT-OFF VALVE
F
FIRE
FCO
FLOOR CLEAN OUT
FD
FLOOR DRAIN
FDC
FIRE DEPARTMENT CONNECTION
FLR
FLOOR
FP
FIRE PROTECTION
FS
FLOOR SINK
FV
FLUSH VALVE
FW
FIRE WATER
GC
GENERAL CONTRACTOR
GCO
GRADE CLEAN OUT
GI
GREASE INTERCEPTOR
GPF
GALLONS PER FLUSH
GPM
GALLONS PER MINUTE
GW
GREASE WASTE
HD
HUB DRAIN
HW
HOT WATER
HWR
HOT WATER RETURN
IE
INVERT ELEVATION
IW
INDIRECT WASTE
JSK
JANITOR SINK
LAV
LAVATORY
LPG
LIQUEFIED PETROLEUM GAS
MPG
MEDIUM PRESSURE GAS
NP
NON -POTABLE
OHP
OUTDOOR HEAT PUMP
PG
PRESSURE GAUGE
POC
POINT OF CONNECTION
PSI
POUNDS PER SQUARE INCH
RCW
RECLAIMED/NON-POTABLE COLD WATER
RL
RAINLEADER
RPBP
REDUCED PRESSURE BACKFLOW PREVENTER
RR
RESTROOM
S
STORM
SH
SHOWER
SK
SINK
SSV
SERVICE SHUT-OFF VALVE
SW
SANITARY WASTE
TP
TRAP PRIMER
TYP
TYPICAL
UR
URINAL
V
VENT
VTR
VENT THRU ROOF
W
WASTE
WC
WATER CLOSET
WCO
WALL CLEAN OUT
WM
WASHING MACHINE
WSFU
WATER SUPPLY FIXTRUE UNITS
City Of Edmonds
Building Department
Work PLUMBING- ALL BUILDINGS
---------------------------------------------------
---------------------------------------------------
Address 8215 236TH STS W
------------------------------------------------
Owner HOUSING HOPE
Approved Date
4/24/2023
Building Official V W.
----------------------------
Permit Number BLD2022-1346 BLDG A
BLD2022-1343
BLDG
C
BLD2022-1344
BLDG
D
LAVATORY MIXING VALVES
PER THE 2018 UPC 407.3 WATER DELIVERED TO PUBLIC -USE LAVATORIES
SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF 120°F BY A DEVICE
THAT IS IN ACCORDANCE WITH ASSE 1070 OR CSA B125.3 THE WATER
HEATER CONTROL IS NOT CONSIDERED A CONTROL MEETING THIS
PROVISION.
PUBLIC -USE LAVATORIES SHALL BE DEFINED AS A HAND SINK ADJACENT
TO WATER CLOSETS OR URINALS IN NON -LOCKING BATHROOMS
INTENDED FOR AN OCCUPANCY OF MORE THAN ONE PERSON AT A TIME.
PLUMBING CONTRACTOR TO PROVIDE MIXING VALVES FOR PUBLIC
LAVATORIES PER FIXTURE SCHEDULE.
PIPING MATERIALS -
SANITARY DRAINAGE
CONDENSATE PIPING SHALL BE TYPE "L" COPPER WITH WROT COPPER
FITTINGS OR SCH 40 PVC.
SANITARY DRAINAGE PIPING SHALL BE SOUND INSULATED WRAPPED PVC
PIPING IN ALL RESIDENTIAL AREAS INCLUDING VERTICAL WASTE STACKS AND
ALL DWELLING UNITS WASTE PIPING.
PIPING MATERIALS - WATER
ALL DOMESTIC WATER PIPING 3-1/2" AND LARGER TO BE STAINLESS STEEL
PIPING WITH STAINLESS STEEL FITTINGS, OR CPVC SCHED 80 WITH CPCV
FITTINGS.
ALL DOMESTIC WATER PIPING 3" AND SMALLER TO BE PEX TUBING WITH PEX
FITTINGS. ALL IRRIGATION PIPING TO BE COPPER TUBING AND FITTINGS.
PIPING SHALL BE INSTALLED IN ACCORDANCE WITH SIZES CALLED OUT ON
PLANS. MAXIMUM WATER VELOCITIES WITHIN PIPING SHALL BE AS FOLLOWS
STAINLESS TUBE AND FITTING SYSTEMS - 10 FT/SEC ON COLD WATER PIPING,
5FT/SEC ON HOT WATER PIPING, 3 FT/SEC ON HOT WATER RECIRC PIPING.
PEX TUBE AND FITTING SYSTEMS - 10 FT/SEC ON COLD WATER PIPING, 8
FT/SEC ON HOT WATER PIPING, 2 FT/SEC ON HOT WATER RECIRC PIPING.
MAX ALLOWABLE PRESSURE DROP FROM FRICTION FOR ENTIRE PIPING AND
FITTING SYSTEM IS 30 PSI.
PROVIDE DIELECTRIC UNIONS WHERE GALVANICALLY DISSIMILAR METALS
JOIN.
PLUMBING SHEET LIST
Sheet Number Sheet Name
P0.01
PLUMBING GENERAL NOTES
P0.02
PLUMBING SCHEDULE
P2.01
PLUMBING - FOUNDATION PLAN - BUILDING A & B
P2.02
PLUMBING - FOUNDATION PLAN - BUILDING C & D
P2.11
PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING A & B
P2.12
PLUMBING - FLOOR PLAN - LEVEL 1 - BUILDING C & D
P2.21
PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING A & B
P2.22
PLUMBING - FLOOR PLAN - LEVEL 2 - BUILDING C & D
P2.31
PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING A & B
P2.32
PLUMBING - FLOOR PLAN - LEVEL 3 - BUILDING C & D
P2.41
PLUMBING - ROOF PLAN - BUILDING A & B
P2.42
PLUMBING - ROOF PLAN - BUILDING C & D
P3.01
PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG A
P3.02
PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG B
P3.03
PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG C
P3.04
PLUMBING - HOT WATER PLANT SCHEMATIC - BLDG D
P4.01
PLUMBING - WATER RISER DIAGRAM - BUILDING A
P4.02
PLUMBING - WATER RISER DIAGRAM - BUILDING B
P4.03
PLUMBING - WATER RISER DIAGRAM - BUILDING C
P4.04
PLUMBING - WATER RISER DIAGRAM - BUILDING D
P4.05
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING A
P4.06
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING B
P4.07
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C
P4.08
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING C
P4.09
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D
P4.10
PLUMBING - WASTE WATER RISER DIAGRAM - BUILDING D
P5.01
PLUMBING - ENLARGED UNIT PLANS
P5.02
PLUMBING - ENLARGED UNIT PLANS
P5.03
PLUMBING - ENLARGED UNIT PLANS
P5.04
PLUMBING - ENLARGED AREA PLANS
P8.01
PLUMBING DETAILS
PLUMBING DETAILS
P8.02
ALL WORK SUBJECT
TO FIELD
INSPECTION FOR
CODE COMPLIANCE
APPROVED
PLANS MUST BE
ON JOB SITE
APPROVED BY PRE-TREATMENT
RICK BAGAN ON 3/15/23
HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
www.designsnw.com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
am
Cn
O
�z
U)
Z
Q
zO
Lu
C'
J
LL1
W
3;Z
Lu
Cl)
LL
w
V
Q
U)
=
O�aL0
c.0
N
L
L0
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
2 01/04/2023 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING
GENERAL NOTES
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
Polo
PLUMBING - FIXTURES
TAG
DESCRIPTION
MANUFACTURER
MODEL
FLOW
(GPM/GPF)
PIPE CONNECTION (INCH)
NOTES
CW
HW
W
V
BT-1
BATHTUB/SHOWER COMBO
AQUATIC
2603CTH
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA T13420-H20
BT-2
ACCESSIBLE BATHTUB/SHOWER COMBO
AQUATIC
2603CTH
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA T13420-H2O WITH RPW324HDF AND GRAB BARS
DF-1
DRINKING FOUNTAIN
ELKAY
EMABFTL8WSLK
0.0
1/2"
0"
0"
0"
FD-1
FLOOR DRAIN
ZURN
Z415B
0.0
0"
0"
2"
1 1/2"
FLOOR DRAIN FOR MECH AREAS
FD-2
FLOOR DRAIN
ZURN
Z415B
0.0
0"
0"
3"
2"
FLOOR DRAIN FOR WATER STORAGE AREAS
FD-3
FLOOR DRAIN
ZURN
Z415S
0.0
0"
0"
2"
1 1/2"
FLOOR DRAIN FOR AMENITY/INTERIOR RESIDENT AREAS
FS-1
FLOOR SINK
ZURN
FD2375
0.0
0"
0"
3"
2"
FLOOR SINK FOR PRV DISCHARGE ETC.
HB-1
HOSE BIBB
WOODFOD
68
0.0
3/4"
0"
0"
FREEZE PROTECTED HOSE BIBB FOR EXTERIOR BUILDING LOCATIONS
HD-1
HUB DRAIN
ZURN
Z1870
0.0
0"
0"
4"
3"
HUB DRAIN FOR FIRE VALVES DRAIN NEEDS
L-1
LAVATORY
AMERICAN STANDARD
AQUALYN
0.5
1/2"
1/2"
2"
1 1/2"
DROP IN SINK; FAUCET: DELTA 523LF-HGMHDF, WATERSENSE RATED
L-2
LAVATORY - AMENITY RESTROOMS
AMERICAN STANDARD
LUCERNE
0.5
1/2"
1/2"
2"
1 1/2"
ACCESSIBLE WALL HUNG SINK; FAUCET: DELTA 523LF-HGMHDF, WATERSENSE RATED
MS-1
MOP SINK
FIAT
MSB2424
0.0
3/4"
3/4"
3"
2"
CHICAGO MOP SINK STYLE FAUCET 897
SH-1
SHOWER
AQUATIC
13636FHARF
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA T13420-H2O; WATERSENSE RATED
SH-2
ACCESSIBLE SHOWER
AQUATIC
1603BFST
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA T13420-H2O WITH RPW324HDF; WATERSENSE RATED
SK-1
SINK
ELKAY
DLR 331910
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA 10OLF-HDF
SK-2
SINK - ACCESSIBLE UNIT
ELKAY
BPSR2317
1.5
1/2"
1/2"
2"
1 1/2"
FAUCET: DELTA 1959LF
SK-3
SINK -AMENITY AREAS
ELKAY
PSLVR1917
1.5
1/2"
1/2"
2"
1 1/2"
ACCESSIBLE DEAPTH, SINGLE BASIN, DROP -IN, FAUCET: DELTA 1959LF
SK-4
SINK - HAND WASHING
ELKAY
BPSR15
1.5
1/2"
1/2"
2"
1 1/2"
SINGLE BASIN HAND WASHING SINK, FAUCET DELTA 1959LF
SK-5
SINK - UTILITY
FIAT
SERV-A-SINK FL-1
2.5
1/2"
1/2"
2"
1 1/2"
FREESTANDING UTILITY SINK. WITH CHICAGO FAUCET 772
UR-1
URINAL
AMERICAN STANDARD
MAYBROOK
0.1
1/2"
0"1
2"
1 1/2"
PINT URINAL; WATERSENSE RATED
WB-1
WASHER BOX
SOUIX CHIEF
OXBOX
0.0
1/2"
1/2"
2"
0"
CLOTHES WASHER CONNECTION BOX WITH WATER HAMMER ARRESTOR INTEGRAL
WC-1
WATER CLOSET
NIAGARA STEALTH
N7717
0.8
1"
0"
3"
2"
STEALTH PRESSURE ASSIST; WATER SENSE RATED
WC-2
WATER CLOSET - ACCESSIBLE UNITS AND AMENITY
NIAGARA STEALTH
N7717
0.8
1"
0"
3"
2"
STEALTH PRESSURE ASSIST; WATER SENSE RATED
PLUMBING - ACCESSORIES
PIPE CONNECTION DIAMETER (INCH)
TAG MANUFACTURER MODEL DESCRIPTION SERVICE CW HW W V FLOW VOLUME NOTES
EXP-A
AMTROL
TBD
EXPANSION TANK
DOMESTIC WATER
0.000
0.000
0.0 gal
EXP-B
AMTROL
TBD
EXPANSION TANK
DOMESTIC WATER
0.000
0.000
0.0 gal
EXP-C
AMTROL
TBD
EXPANSION TANK
DOMESTIC WATER
0.000
0.000
0.0 gal
EXP-D
AMTROL
TBD
EXPANSION TANK
DOMESTIC WATER
0.000
0.000
0.0 gal
TMV-A
CALEFFI
LEGIONMIX 6000
TEMPERATURE MIXING VALVE
HOT WATER
0.000
0.000
0 GPM
0.0 gal
TMV-B
CALEFFI
LEGIONMIX 6000
TEMPERATURE MIXING VALVE
HOT WATER
0.000
0.000
0 GPM
0.0 gal
TMV-C
CALEFFI
LEGIONMIX 6000
TEMPERATURE MIXING VALVE
HOT WATER
0.000
0.000
0 GPM
0.0 gal
TMV-D
CALEFFI
LEGIONMIX 6000
TEMPERATURE MIXING VALVE
HOT WATER
0.000
0.000
0 GPM
0.0 gal
TP-1
SIOUX CHIEF
PRIME PERFECT
MECHANICAL TRAP PRIMER
WASTE
0.250
0.000
0 GPM
0.0 gal
LOCATED IN MECHANICAL ROOMS
TP-2
SIOUX CHIEF
TRAP EASE
GRAVITY TRAP PRIMER
WASTE
0.250
0.000
0 GPM
0.0 gal
LOCATED IN AMENITY RESTROOMS
PLUMBING - HEAT TRACE
TAG
MANUFACTURER
MODEL
VOLTS/PHASE
NOTES
HTC-1
NVENT RAYCHEM
AMC-F5 CONTROLLER WITH 5XLE1-CR
120V
5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG A
HTC-2
NVENT RAYCHEM
AMC-1`5 CONTROLLER WITH 5XLE1-CR
120V
5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG B
HTC-3
NVENT RAYCHEM
AMC-1`5 CONTROLLER WITH 5XLE1-CR
120V
5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG C
HTC-4
NVENT RAYCHEM
AMC-1`5 CONTROLLER WITH 5XLE1-CR
I 120V
5W/FT HEAT TRACE FOR WATER LINES BETWEEN OUTDOOR HEAT PUMP UNITS AND WATER HEATER PLANT ROOM IN BLDG D
TAG
MANUFACTURER
MODEL
VOLUME (G.
WH-A
A.O. SMITH
DRE-120-12
120.0 gal
WH-B
A.O. SMITH
DRE-120-12
120.0 gal
WH-C
A.O. SMITH
DRE-120-18
120.0 gal
WH-D
A.O. SMITH
DRE-120-12
120.0 qal
PLUMBING - ELECTRIC WATER HEATER
PHYSICAL DATA
DIMENSIONS
FULL WEIGHT
(LBS)
DIAMETER (IN)
HEIGHT (IN)
5' - 3"
1000 lb
5' - 3"
1000 lb
5' - 3"
1000 lb
5' - 3"
1000 lb
TAG
MANUFACTURER
MODEL
DESCRIPTION
ST-Al
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-A2
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-B1
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-B2
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-Cl
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-C2
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-D1
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ST-D2
A.O. SMITH
TBD
HOT WATER STORAGE TANK
ELECTRICAL
DATA
PIPE CONNECTIONS
POWER (kW)
FLA
VOLTS/PHASE
CW (IN)
HW (IN)
0.000
0.000
12.3 kW
34
208V/3PH
0.000
0.000
12.3 kW
34
208V/3PH
0.000
0.000
18.0 kW
50
208V/3PH
0.000
0.000
12.3 kW
34
208V/3PH
PLUMBING - STORAGE TANKS
DIMENSIONS (INCH)
I FILLED
VOLUME (GAL) WEIGHT (LBS)
PIPE CONNECTION (INCH)
RADIUS
HEIGHT
CW
HW
1'- 8"
6' - 8"
285.0 gal
2950 lb
1'- 8"
6' - 8"
285.0 gal
2950 lb
1'- 8"
6' - 8"
285.0 gal
2950 lb
1'- 8"
6' - 8"
285.0 gal
2950 lb
1' - 11"
7' - 8"
455.0 gal
7500 lb
1' - 11"
7' - 8"
455.0 gal
7500 lb
1'- 8"
6' - 8"
285.0 gal
2950 lb
1'- 8"
6' - 8"
285.0 qal
2950 lb
NOTES
NOTES
PLUMBING - HEAT PUMP WATER HEATER
HEAT CAP COP -SEASONAL MCA PIPE CONNECTIONS WEIGHT
TAG MANUFACTURER MODEL SERVICE REFRIGERANT (BTU/HR @ 47F) (80/47/17 DEG F) VOLT/PHASE (AMPS) (INCH) SOUND (DbA) (LBS) NOTES
HPWH-A1 SANCO2 GS4-45HPC DHW - BLDG A R744 (CO2) 15400 Btu/h 5.5 / 4.2 / 2.8 208V/1 PH 7.2 1/2" 37 110 Ib UEF 3.4
HPWH-A2
SANCO2
GS4-45HPC
DHW - BLDG A
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-A3
SANCO2
GS4-45HPC
DHW - BLDG A
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-B1
SANCO2
GS4-45HPC
BHW - BLDG B
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-B2
SANCO2
GS4-45HPC
BHW - BLDG B
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-B3
SANCO2
GS4-45HPC
BHW - BLDG B
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-C1
SANCO2
GS4-45HPC
DHW - BLDG C
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-C2
SANCO2
GS4-45HPC
DHW - BLDG C
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-C3
SANCO2
GS4-45HPC
DHW - BLDG C
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-C4
SANCO2
GS4-45HPC
DHW - BLDG C
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-D1
SANCO2
GS4-45HPC
DHW - BLDG D
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-D2
SANCO2
GS4-45HPC
DHW - BLDG D
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-D3
SANCO2
GS4-45HPC
DHW - BLDG D
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HPWH-D4
SANCO2
GS4-45HPC
DHW - BLDG D
R744 (CO2)
15400 Btu/h
5.5 / 4.2 / 2.8
208V/1 PH
7.2
1/2"
37
110 Ib
UEF 3.4
HOUSING
HOPE
we keep hope alive
DESIGNS
\� northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
19 1 7 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
am
Cn
O
�z
U)
z
=
Q
Z
0
0
LU
C'
J
LL1
Z
3;W
I-
Lu
U)
LL
w
V
Q
U)
O
J
a
c�
Cy')
N
mc
�
L0
N 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 1 PERMIT RESUBM.
IK9J►1IRLI 'fi
PLUMBING
SCHEDULE
SCALE:
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
PO,02
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
A
A\\ \\ \\ 4" FIRE WATER POC
SEE CIVIL FOR CONTINUATION
\\ \\ \V/ /.
PLUMBING FOUNDATION PLAN - BLDG A & B
1 /8" = 1 I-011
4" WASTE POC
SEE CIVIL FOR CONTINUATION
IE= APPROX 4' BFF
SEE CIVIL FOR CONTINUATION
IE= APPROX 2.8' BFF
3" DOMESTIC WATER POC
SEE CIVIL FOR CONTINUATION
SEE CIVIL FOR BACKFLOW PREVENTOR
22.5 23
24 IIIIIIIII IIIIIIIII
II III III III III III
HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
us:
e-
If
C.0
N
O
00
W
Cn
3:
O
�z
U)
Z
Q
zO
LU
w
C'
J
W
U)
Z
W
`;
w
Um
w
V
Q
U)
=
O
J
a
C.0
M
N
mc
L
N 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev W-T Date I Description
2 01/04/2023 IPERMITRESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
CONTENTS:
PLUMBING -
FOUNDATION PLAN
- BUILDING A & B
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P2mO
1 2 3 4 5 6 7 8
J
4" FIRE WATER POC
SEE CIVIL FOR CONTINUATION
U- d a-: - - '°° a ram.°, d a4 _ - ..- ° •-
d'4
4
Q
•-".
a ° °3" DOMESTIC WATER POC
'
°d°d° ° •'2(°2
•=
d•
' •
° •A" °d °a d)°°`2
"W
1
(FROM
RO
M °-
77
°B, T ,UaSEE CIVIL FOR CONTINUATION (2DFd
4 4°P
°(2DFU)3"W 2"W FROM BT /2"V U-
4
°ad(2
FIRE (5DF° , °
a Wd 2o
SEE CIVIL FOR BACKFLOW PREVENTOR 1-1/2"V UP ; 1/2VU° d
4 4
2"W UP 2"W UP' (20 DFU °as W d 3n4-
(4DFU) $a°2"W U2 DFU 4"
° (12 DF
° DFU DFU)° a° a
°° °TP FROM ABOVEa"VW V UP 1-1/2D 3nV UP FROM HW
3CW UP 4ne 4"p e'Qe ° W2"W UP d a d °3W 33W FROM FS °3W(3 DFU)—`, ° d 12 DFU) 2nW- (4 DFU),
�'
- (3 DFU) (2 DFU)
°.,° "W
°W (3 DU)I�.< d,2"V UP d 3W 3 ° 4 4 ° -a
2 W (12 DFU)
a 2"W FROM FD _ FdDU) d 3FU)
d (2 D2,W ° aa° ,° d ° (8 DFU)AP�
_
e °
3 . a 4 2W dUP TO GCO ° ° d°VUP° °DFU
.°1-1/2"V UP (2
3W FROM FD°d4°
2"W UP d d- a
2"W UP--(3 DFU)— 4
(3 DFU) -
4 ad
UP TO GCO
o —I
III III III I IIIIIIIIIII
III —III —III IIIIIIIIIII
IIII
4
�-4" WASTE POC
SEE CIVIL FOR CONTINUATION
IE= APPROX 3.9' BFF
IILp' - 2"W -_ -' -_ - °_ _- °d d°-' • ,.
d
° °
, d °-7
° 4 d2 W-'
n
a
°
°
UP TO GCO ;2nW
(2DU) A d.
° d d °_ (8 DFU) ° (2DFU);d._(2DFU)
d
d
4 DFU4: 41 d.3��W:. a3"W ° °°d 2nW - 3"W-d 3"W ` ` a =1: 1 ° (12 DFU) a
4DFU ( ) 3 DFU ° a . 3 DFU ° ° • ":2DFU ° . 3 DFU° ?° 3 DFU ,
•° °.° " `d°_ 4 W - P ° °-.d 11 - 11 °d ° d - - -,dd- d 11 °d 11 _d : ° - $ �(8 DFU).-
3W - 3W:° 3W 3W,: °3W;_'
°°
(3 DFU) 'a(24DFU): ° ° ° ° (13 DFU) ° (13 DFU) , ° ';�2 DFU) d° °(13 DFU), ° aF ` (13 DFU)
W= Q_ dp - ,d - - d " - d - d^- ° °•4 - d°<, W.- - - - d °- °- °� ,�A/ - a
n - _ - - 4n� - p - - - 4 - ; 4 - -d - ° ° - .. -• .4n�=, - , d° e, -'3Y"� �d - -
° " ad" . e ° 1-1/2"V d a ° a b: $' a q° n Q °
�3W m 2W °
°° ° ° d 1 DFU °..
0(3 DFU) a 2 W d' ° ¢d: 4 ( ). 3 W
° (3 DFU)° ?-
d, 2 W UP; ' (2 DFU) : a m d 4 d ° W °
°°.
d 1 DFU 2nW<1 ^ ° 8 >d °d d 4e
I
( ) , °d ` 11 l �_ ° $ a 2DFU °4"W 'FROM HD—
° - - - -
d (1 DFU)° _ ° 1 1/2 V 1 1/2 V° d° 4°a °1 1/2 V- a 1 1/2 V ( �' 4 {
° -- -
2"V11 FROM BT ° 2nW 2nW ' d d, 2nW °ed 2nW < „ °
1-1/2"V ° °"d °d n. a 4� V d -
° (2 DFU):a d a' d ° °,°(2 DFU), ° (2 DFU \ 9 (2 DFU),, d' ° . ° ° (2 DFU)m .
°d _ ° d°- ¢'d°-- .° -do- - ° °9 °- d° - .9 ° °° -a °TPLINESUP��- 44
-
a 41 4•j°' °.d °
a"
° ° „ • $- d' d" . ° 3_"W FROMFID
d - - p
Ad 3"W FROM FD a 4 3W FRO,2"V UP
d
I
N�
1
PLUMBING FOUNDATION PLAN - BLDG C & D
1/8"=11-011
N�
"111� / NN��
�3" DOMESTIC WATER POC
/SEE CIVIL FOR CONTINUATION
SEE CIVIL FOR BACKFLOW PREVENTOR
ri-9) 20
,-4" WASTE POC
SEE CIVIL FOR CONTINUATION
IE= APPROX 4.25' BFF
9
FIRE WATER POC
:E CIVIL FOR CONTINUATION
U
/avU
0
N
W
W
U) C .2 00
06
Q
z- C.1
co
HOUSING
i HOPE
we keep hope alive
DESIGNS
L IN northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
w ww. designs nw. com
ECOTOPE
19 1 7 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
R
M;
W
am
u)
z
Q
0
W
C'
J
LLI
Z
_
LLI
-
(�
LU
NW
L.L
�
V
Q
I-
OJaM
C.0
N
W00
N
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Description
Rev #
Date
2
01/04/2023
PERMIT RESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
B.
D
CONTENTS:
PLUMBING -
FOUNDATION PLAN
- BUILDING C & D
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2,02
D�
T 6 7 8 9
T T T ( 10 11 12
PLUMBING FLOOR PLAN - LEVEL 1 - BLDG A & B
118" = 1 I-011
rm
6 m6- F1
HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
N
O
00
am
Cn
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
LLI
U)
w
C/)
ILU)
w
V
Q
=
O
J
a
C.0
M
N
LL1
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date I Description
3 03/27/2023 CONFORMED
SET
KEYPLAN RESUB
CCITY OF EDMONDS
SERVICES
DEPARTMENT
D B
1w.,,t..a imm
PLUMBING -
FLOOR PLAN -
LEVEL 1 -
BUILDING A & B
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P20
2 (31 4 5 6 (7 �8
-----<O>
PLUMBING FLOOR PLAN - LEVEL 1 - BLDG C & D
1 /8" = 1 I-011
HOUSING
i HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
co
N
(D
00
m
am
Cn
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
L L1
U)
w
w
V
Q
U)
=
O
J
a
C.0
M
N
LL1
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
2 01/04/2023 IPERMITRESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
PLUMBING -
FLOOR PLAN -
LEVEL 1 -
BUILDING C & D
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P2m12
PLUMBING FLOOR PLAN - LEVEL 2 - BLDG A & B
118" = 1 I-011
HOUSING
AW\,
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
Cfl
N
O
00
am
Cn
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
LLI
U)
w
w
V
Q
U)
=
O
J
a
C.0
M
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
KEYPLAN
RESU B
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
CONTENTS:
PLUMBING -
FLOOR PLAN -
LEVEL 2 -
BUILDING A & B
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2,21
(A.3
D
�1 (2 3 4 5 6 7)
I I I I I
1 1
15 16 (17) (18i 19 20j 21
PLUMBING FLOOR PLAN - LEVEL 2 - BLDG C & D
1 /8 = 11-011
w
w
W
m
Q
c�
z
0
J
m
HOUSING
HOPE
we keep hope alive
ih�DESIGNS
northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
- 'Lk `==--*"R
05
W
am
Cl)
O
�z
U)
Z
Q
zO
Lu
C'
J
LLI
-
W
3;Z
LU
Nw
L.L
V
Q
U)
=
O
J
a
C.0
M
N
mc
�
N 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
2 01/04/2023 IPERMITRESUBM.
KEYPLAN
RESUB
C-,
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
PLUMBING -
FLOOR PLAN -
LEVEL 2 -
BUILDING C & D
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2m22
N
M
N
W
W
W
O 0
00
6l � �J 9 10 11) 12
PLUMBING FLOOR PLAN - LEVEL 3 - BLDG A & B
1/8"=11-011
C22
HOUSING
HOPE
we keep hope alive
DESIGNS
I northwest
ARCHITECTS
I P.O. Box 1 27 0
10031 SR 532, Suite B
I Stanwood, WA 98292
www. designs nw. com
I
I
ECOTOPE
I
1 1 9 17 1 ST AvE, #300
SEATTLE WA 9S 1 o 1
I PH: (206) 322-3753
FAX: (206) 325-7270
N
O
00
W
I
m
¢¢
O
�z
z
Q
zO
w
C'
J
L
Z
UI
U)
w
ico
V
Q
OJaM
UJI
Lo
00
N
00
� CONSTRUCTION
� DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
KEYPLAN
RESU B
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
CONTENTS:
PLUMBING -
FLOOR PLAN -
LEVEL 3 -
BUILDING A & B
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2,31
T
T
3
I
� T5) � 6 ,1 7 4
TI
3-BED 2-BED 2-BED 2-BED
D306 D305 D304 D3 33
922 SF 678 SF 689 SF 689 SF
1�2
2"V UP TO VTR
00 2"V UP TO VTR (46 DFU)
00(88 DFU)
UNIT WATER UNITWATER o 0 0 00 RISERS DN RISERS DNoil O o 0 0
UNIT WATER /
RISERS DN J III
THERMOSTATIC BALANCING VALVE
TYPICAL AT ALL HW TO HWC CONNECTIONS
I
1_.
�17) 18j
PLUMBING FLOOR PLAN - LEVEL 3 - BLDG C & D
1 /8" = 1 I-011
UNITWATER
RISERS DN,_j
I _i I
0
2-BED 2-BED
D302 D3 11
689 SF 733 SF
III 2"V UP TO VTR
(33 DFU)
III
UNIT WATER o 0
d � I
RISERS DIN,0 0
0 0
, D 0
---
UNIT WATER
RISERS DN
(?0
A J,11
"HWC DN
21
1-1
AW\ HOUSING
8 HOPE
we keep hope alive
DESIGNS
1 L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
w ww. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
05
W
U)
M O z � z
W z
w a � � w
co
C' J
Q �
z0
Z W U)
J
LU
m w
0L
U)
V Q
c�
O J a M
N
LLI N
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Description
Rev #
I Date
2
01/04/2023
PERMIT RESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
g
D
CONTENTS:
PLUMBING -
FLOOR PLAN -
LEVEL 3 -
BUILDING C & D
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2,32
\
N
w
w
0
06
U
z
J
D
m
D
\
6 7) 8 ,,•; 9 ,.,i 10 11 12
I I I
ii / 3"VTR
rA
II
m
0
El
/ 3VTR
0 }"0,/ (34 DFU)
A � 21 22 22.5 23 24 25
PLUMBING ROOF PLAN - BLDG A & B
1 /8" = 11-011
HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
19 1 7 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
0
W
am
Cn
O
�mmWz
Z
Q
zO
LU
C'
J
LLJ
Z
-
LLI
U)
LU
Cl)
LL
Nw
L.L
V
Q
U)
=
O
J
a
C.0
M
N
mc
�
N 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date
Description
2
01/04/2023
IPERMITRESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
CONTENTS:
PLUMBING - ROOF
PLAN - BUILDING A
&B
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2m41
T
3 4 5
i
3" VTR
(80 DFU)
PLUMBING ROOF PLAN - BLDG C & D
1 /8" = 1 I-011
3" VTR
�®8 DFU)
6 7
I I
3" VTR
+jd(33 DFU)
8 AIW\ HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www.designsnw.com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
C
w O
co
zZ
w
U
co�
Q
z
�
O
w
z
C'
J
m Z
W
U)
w
w
V
Q
U)
O
J
a
M
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date
Description
2
01/04/2023
IPERMITRESUBM.
KEYPLAN
RESUB
CCITY
—Aa�brzet�,
OF EDMONDS
SERVICES
DEPARTMENT
D
B
CONTENTS:
PLUMBING - ROOF
PLAN - BUILDING C
&D
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
N P2m42
HPWH A3 1„
(1)
HPWH A2 1„
(1)
HPWH Al 1„
MECHANICAL ROOM
(17)
311 / T
-- 4 � _ (13)
I '
I I I I
I I I
I
I I
I
I I
I
I
/4 (20)
75
2
I
I I I
311 (22)
2 --� -- (13) (13)
1n I
------------� T T4
311 311
--------------------- 4 (19)
PLUMBING - HPWH SCHEMATIC - BLDG A
1 /8" = 11-011
LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
PUMP
PIPE-T
MIXING VALVE
T&P RELIEF VALVE
PMP #
EQUIPMENT TAG
MANUAL AND AUTOMATIC AIR BLEED
QTEMPERATURE
SENSOR
PIPE UNION
FM
FLOW METER
PIPE FLOW DIRECTION
Cb�
BALL VALVE
31,
PIPE SIZE
BALANCING VALVE
---
CW PIPING
SPRING CHECK VALVE
HW PIPING
INLINE Y-STRAINER
HWC PIPING
I
I '
SHEET NOTES
(1) SEE HPWH EQUIPMENT DETAIL 4/P8.02
(2) DIRECT -75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(4) PROVIDE 12" HEAT TRAP
(5) EQUIPMENT DRAIN
(6) ROUTE T&P RELIEF TO DRAIN
(7) BAG FILTER (PENTAK, WF-1)
(8) INLINE PIPE STRAINER
(9) AUTOMATIC AIR BLEED
(10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM
(11) NOT USED
(12) NOT USED
(13) WIRE TO CONTROLLER (TYPICAL)
(14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS.
REFER TO HW1.00 FOR MORE INFORMATION.
(15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF
THERMAL BRIDGES
(16) NOT USED
(17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL)
(18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL)
(19) R-10 THERMAL ISOLATION
(20) PROVIDE SEISMIC BRACING
(21) CONNECT TO BUILDING COLD WATER SUPPLY LINE.
(22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW.
CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE
EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY
LINE DISTANCE TO THE PRIMARY STORAGE [ST-1].
(23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP
BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING
STARTUP.
(24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND
CONDENSATE DISCHARGE.
TEMPERATURE GAUGE TYP. ALL
T \ 211
---------- CW
(7) (21)
(18) T \
(23)
311 (5)
I 4
I
P-1 3„
-*�— ---- 4 HWC
2" TMV-A
(10) I (2) 2°
T6
2"
T2 -
z
(5)
I
I
I
2"
I
I
I
I
I
I
I
I
I
I
I
I
2"
I
I
I
I
I
I
%--u (24)
FS-1
a
TEMPERATURE SENSOR
TYP. ALL
(13)
T3 Tl \J 2��
(5)
Dc5 — � HW
(14) (15)
HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
P.O. Box 1^-70
10031 SR 532. Sure B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
1 91 7 1 ST AVE, #300
SEATTLE WA 9B 1 O 1
PH: (ZO6) 3ZZ-3753
FAX: (206) 325-7270
W
CID
CV
O
00
am
Cn
O
�z
Cn
Z
Q
z0
0
w
C�
J
Liu
Z
W
cn
w
Cn
LL
w
c,
aC)
C)
0
CID
cy-)
C14
W
a
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING - HOT
WATER PLANT
SCHEMATIC - BLDG
A
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P3,01
OUTDOORS
111 HPWH B2 111 HPWH B1 I111
111 I 11I I 11I
2
I I
411- (22) - -- --
(15)
311 1 11
----- --- ------ ►-------%
L(22)_ 311
------------------ 4 — - — - — -
C- PLUMBING�-lPW�IS�C HEMATIC �-1 LDG B
1 118" = 1'-0"
MECHANICAL ROOM
311
4 (19)
(17)
(5) (19)
(10)
T2
T6
Q
(18)
5)
211
LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
®
PUMP
PIPE-T
MIXING VALVE
P-
T&P RELIEF VALVE
PMP #
EQUIPMENT TAG
MANUAL AND AUTOMATIC AIR BLEED
QTEMPERATURE
SENSOR
PIPE UNION
FM
FLOW METER
PIPE FLOW DIRECTION
CZXI
BALL VALVE
�
PIPE SIZE
BALANCING VALVE
---
CW PIPING
SPRING CHECK VALVE
HW PIPING
INLINE Y-STRAINER
HWC PIPING
I
I
211
I
I
TEMPERATURE GAUGE TYP. ALL
SHEET NOTES
(1) SEE HPWH EQUIPMENT DETAIL 4/P8.02
(2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(4) PROVIDE 12" HEAT TRAP
(5) EQUIPMENT DRAIN
(6) ROUTE T&P RELIEF TO DRAIN
(7) BAG FILTER (PENTAK, WF-1)
(8) INLINE PIPE STRAINER
(9) AUTOMATIC AIR BLEED
(10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM
(11) NOT USED
(12) NOT USED
(13) WIRE TO CONTROLLER (TYPICAL)
(14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS.
REFER TO HW1.00 FOR MORE INFORMATION.
(15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF
THERMAL BRIDGES
(16) NOT USED
(17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL)
(18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL)
(19) R-10 THERMAL ISOLATION
(20) PROVIDE SEISMIC BRACING
(21) CONNECT TO BUILDING COLD WATER SUPPLY LINE.
(22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW.
CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE
EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY
LINE DISTANCE TO THE PRIMARY STORAGE [ST-1].
(23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP
BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING
STARTUP.
(24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND
CONDENSATE DISCHARGE.
T \ 211
----------
-------���� CW
(7) (21)
(23) T \
I
311 (5)
I 4
P-1 311
- �- ---- ®�® HWC
2"I TMV-B
(2) 211
I I tHT
I L
---�
I
I
I
311
4
(3)
%==—I (24)
FS-1
(20)
211
(19)
(10) C7 211
z
TEMPERATURE SENSOR
TYP. ALL
(13)
T3 T \ 211
� Df*�®� I HW
(14) (15)
(5)
AW\ HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 629.3441
P.O. Box 1,70
10031 SR 532. Suile B
Stanwood. WA 98292
wwww. des i gn sn--
ECOTOPE
1 91 7 1 ST AVE, #300
SEATTLE WA 9B 1 O 1
PH: (ZO6) 3ZZ-3753
FAX: (206) 325-7270
W
am
Cl)
O
�z
Cf)
Z
Q
z0
0
W
C�
J
Liu
Z
W
1�
Cf)
W
W
c,
aC)
C)
OJaM
N
mc
W
a
L0
C00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING - HOT
WATER PLANT
SCHEMATIC - BLDG
B
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
3,0
OUTDOORS
HPWH C4 1„ HPWH C3 1„ HPWH C2 1„ HPWH -:C: 1: 1„
MECHANICAL ROOM
(17)
31, / T
-- 4 ® — (13)
I
I
I I I I
I I I
I
I I
I '
ST-C1
I '
(20) I (20)
- - 2
I
I I I
311 311
i 2 — — (22)
-- -- --� --LU (13) (13)
-- 4 -- -- —� -- -- -- (15)
311 311 TT4
-----�------------------�
(22) 311 311
--------- — — —--------- — -----4 --------- 4 (19)
PLUMBING - HPWH SCHEMATIC - BLDG C
1 /8" = 1 1-0 11
T1
LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
PUMP
PIPE-T
MIXING VALVE
T&P RELIEF VALVE
PMP #
EQUIPMENT TAG
MANUAL AND AUTOMATIC AIR BLEED
QTEMPERATURE
SENSOR
PIPE UNION
FM
FLOW METER
PIPE FLOW DIRECTION
DbQ
BALL VALVE
PIPE SIZE
BALANCING VALVE
---
CW PIPING
SPRING CHECK VALVE
HW PIPING
7d
INLINE Y-STRAINER
HWC PIPING
SHEET NOTES
(1) SEE HPWH EQUIPMENT DETAIL 4/P8.02
(2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(4) PROVIDE 12" HEAT TRAP
(5) EQUIPMENT DRAIN
(6) ROUTE T&P RELIEF TO DRAIN
(7) BAG FILTER (PENTAK, WF-1)
(8) INLINE PIPE STRAINER
(9) AUTOMATIC AIR BLEED
(10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM
(11) NOT USED
(12) NOT USED
(13) WIRE TO CONTROLLER (TYPICAL)
(14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS.
REFER TO HW1.00 FOR MORE INFORMATION.
(15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF
THERMAL BRIDGES
(16) NOT USED
(17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL)
(18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL)
(19) R-10 THERMAL ISOLATION
(20) PROVIDE SEISMIC BRACING
(21) CONNECT TO BUILDING COLD WATER SUPPLY LINE.
(22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW.
CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE
EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY
LINE DISTANCE TO THE PRIMARY STORAGE [ST-1].
(23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP
BEFORE BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING
STARTUP.
(24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND
CONDENSATE DISCHARGE.
TEMPERATURE GAUGE TYP. ALL
T \ 211
-��---- -------- --4)a�� CW
CTRL-1 (7) (21)
0
I '
(18)
(23) T P-1 311
�- - -- -- - ---- � I HWC
311 (5) TEMPERATURE SENSOR
i 4 TYP. ALL
(13)
(10) 211 TMV-C
i (2) 2" T3 T \ 2��
-- --� -- I D5�� HW
I
2�� H T (14) (15)
XT
' � I
T2 (10) 2��
I
I
(6)
6
)
2" 2" o WH-C
I O
i (20)
I I
I
I
li
Lam _ 311
T6 I i (3) 211
(5)
(5)
(19)
o� (24)
FS-1
HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Sure B
Sl--Iod. WA 98292
www.dexign�. nw.com
ECOTOPE
1 91 7 1 ST AVE, #300
SEATTLE WA 9B 1 O 1
PH: (ZO6) 3ZZ-3753
FAX: (206) 325-7270
W
CID
CV
O
00
am
Cn
O
�z
Cn
Z
Q
Z0
o
w
C�
J
LLI
Z
L LI
(�
w
Cn
LL
w
c,
a
C)
H
OJaM
c�
CV
W
a
L0
C V
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date I Description
2 +01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING - HOT
WATER PLANT
SCHEMATIC - BLDG
C
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
3,0
A
OUTDOORS
HPWH D4 1„ HPWH D3 1�� HPWH D2 1„ HPWH -:D: 1: 1
17-1 a 2! ! a a 2! ! a a 2! ! 11 a 2
L 2 311 311 ( 22 )
i - I - -
-- -- -- 4 -- -- 4 .
n
7
I
I I
311 311
-----11------------ --�►----�
(22) 311
--- ----- - - ------------ - - ----------
PLUMBING - HPWH SCHEMATIC - BLDG D
1 1-011
MECHANICAL ROOM
311
F
I
I
I
I
I
I
I
I
I
I
(20)
I
I
I
(13) (13)
OT(T4
311
4 (19)
T1
(17)
/T
(13)
I
I
I
i i I
L I
� I
I
(6)
(20)
(10)
(4)
(13) T6
n
�I
T2
211
LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
®
PUMP
PIPE-T
MIXING VALVE
T&P RELIEF VALVE
PMP #
EQUIPMENT TAG
MANUAL AND AUTOMATIC AIR BLEED
QTEMPERATURE
SENSOR
PIPE UNION
FM
FLOW METER
PIPE FLOW DIRECTION
BALL VALVE
41
PIPE SIZE
BALANCING VALVE
---
CW PIPING
SPRING CHECK VALVE
HW PIPING
INLINE Y-STRAINER
HWC PIPING
(18)
a
5)
211
SHEET NOTES
(1) SEE HPWH EQUIPMENT DETAIL 4/P8.02
(2) DIRECT =75% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(3) DIRECT =25% OF FLOW THROUGH PIPING PATH UNDER NO LOAD
CONDITION WITH CONTINUOUS HWC PUMP OPERATION
(4) PROVIDE 12" HEAT TRAP
(5) EQUIPMENT DRAIN
(6) ROUTE T&P RELIEF TO DRAIN
(7) BAG FILTER (PENTAK, WF-1)
(8) INLINE PIPE STRAINER
(9) AUTOMATIC AIR BLEED
(10) MANUAL AIR BLEED AT HIGH POINT IN DHW ROOM
(11) NOT USED
(12) NOT USED
(13) WIRE TO CONTROLLER (TYPICAL)
(14) ALL HW AND HWC PIPING SHALL BE INSULATED TO CODE LEVELS.
REFER TO HW1.00 FOR MORE INFORMATION.
(15) ALL PIPE CLAMPS ON HOT WATER PIPING SHALL BE FREE OF
THERMAL BRIDGES
(16) NOT USED
(17) CONTROL WIRE, CONNECT TO HPWH (TYPICAL)
(18) CONTROL WIRE, CONNECT TO SENSOR (TYPICAL)
(19) R-10 THERMAL ISOLATION
(20) PROVIDE SEISMIC BRACING
(21) CONNECT TO BUILDING COLD WATER SUPPLY LINE.
(22) PROVIDE EQUAL DISTANCE PIPING TO HPWHs TO BALANCE FLOW.
CW SUPPLY LINE TO HPWHs SHALL BE EXTENDED TO ACHIEVE
EQUAL DISTANCE PIPING. MINIMIZE OUTGOING HW SUPPLY LINE
DISTANCE TO THE PRIMARY STORAGE [ST-1].
(23) PROVIDE BALANCING VALVE DOWNSTREAM OF CIRC PUMP BEFORE
BRANCH TO EWH-1/ST-8. LEAVE WIDE OPEN DURING STARTUP.
(24) FLOOR SINK FOR T&P RELIEF VALVE DISCHARGE, AND CONDENSATE
DISCHARGE.
TEMPERATURE GAUGE TYP. ALL
T\
- -------
---
211
CW
(21)
(23) T \ P-1 311
-I - -- -- - ---- s I HWC
(5) TEMPERATURE SENSOR
TYP. ALL
4 (13)
211 TMV-D
(2) 211 T3 T \ 2If
-- I ��a---� HW
H T (14) (15)
I I
(10) 211
I
I
I
I
I '
I
(6)
211
WH-D
I
I C
(20)
I I
I
I
I
L
(3) 211
L-----]
(5)
(19)
%--® (24)
FS-1
HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 629.3441
P.O. Box I'll,10031 'a532, suite B
Stanwood. WA 98191
www.dexig —l—
ECOTOPE
V
1 91 7 1 ST AVE, #3130
5EATTLE WA 9B 1 O 1
PH: (ZO6) 3ZZ-3753
FAX: (206) 325-7270
UU
CID
CV
O
00
am
Cn
O
�z
C)
Q
Z
0
W
C�
J
LLJ
Z
L LI
1�
(�
w
m
w
c,
a
Cf)
H
OJaM
c�
CV
W
a
L0
CV 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING - HOT
WATER PLANT
SCHEMATIC - BLDG
D
SCALE: 1/8" = 1'-01,
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
3,0
AW\ HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
Cfl
N
O
00
am
Cn
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
LLI
U)
w
w
V
Q
U)
=
O
J
a
C.0
M
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
lwullimmakimm
PLUMBING -
WATER RISER
DIAGRAM -
BUILDING A
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,0
ROOF
LEVEL 3
3/4"
3/4"
PM I 0.6822 GPM
BA
B304
8.5 CWFU
6 HWFU
1 BA
B303
8.5 CWFU
6 HWFU
0.4548 GPM
3/4"
0
3/4" / 1 3/4" 1 3/4"
' f
18 HWFU 12 HWFU
14 GPM
9 GPM
1 BA
12 HWFU
1-1/4"
1"
B204
9 GPM
25.5 CWFU
17 CWFU
1„
I
18 GPM
13 GPM
8.5 CWFU
17 CWFU
1-1/4"
1"
6 HWFU
13 GPM
LEVEL 2
1
r--
58.5 HWFU
32 GPM
142 CWFU
SHUTOFF VALVE 52 GPM
2
LEVEL 1
76.5 HWFU
37 GPM
2"
0.9096 GPM
3/4"
HOT
WATE
PLAN
109 CWFU
45 GPM
2"
2" DOMESTIC WATER CONNECTION THIS BUILDING
142 WFU, 52 GPM
SEE CIVIL PLANS FOR CONTINUATION
AND FOR SITE BACKFLOW PREVENTION AND WATER METER
83.5 CWFU
39 GPM
1-1/2"
7Y
1 BA
-� B104
8.5 CWFU
6 HWFU
--y 1 BA
B203
8.5 CWFU 18 HWFU
6 HWFU 14 GPM
1-1/4"
25.5 CWFU 40.5 HWFU
18 GPM 25 GPM
1-1 /4" 1_1 /2"
18 HWFU
14 GPM
1-1/4"
1 BA
B103
8.5 CWFU
6 HWFU
58 CWFU
32 GPM
1-1/2"
12 HWFU
9 GPM
1"
17 CWFU
\13 GPM
1"
25.5 CWFU
18 GPM
1-1/4"
DOMESTIC WATER
PRESSURE CALCULATIONS
STREET PRESSURE
METER LOSS
BACKFLOW DEVICE LOSS
LOSS FROM DISTANCE MAIN INTO BUILDING
SYSTEM
64 PSI
-1.6 PSI
-8 PSI
-1 PSI
CALCULATIONS -
RESIDENTIAL UNIT SIZING CALCULATIONS
KITCHEN SINK
DISHWASHER
BATH/SHOWER
SHOWER
BLDG
1 BA
1
1
1
0
B
2 BA
1
1
1
1
ELEVATION LOSS
-12.6 PSI
LAVATORY
1
2
PRESURE REQUIRED AT FURTHEST FIXTURE
-30 PSI
WATER CLOSET
1
2
PRESSURE AVAILABLE FOR FRICTION LOSS
10.8 PSI
PER 2018 UPC TABLE A 103.1 AND FOOTNOT...
COLD WATER WSFU
8.5
10
DEVELOPED LENGTH OF SYSTEM
130'
HOT WATER WSFU
6
7.5
EQUIVALENT LENGTH FROM FITTINGS
33'
COLD WATER GPM
7 GPM
8.5 GPM
TOTAL DEVELOPED LENGTH
163'
HOT WATER GPM
5 GPM
6.5 GPM
PER CHART A 105.1(1):
FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 163 FT PER 100 FT)
6.67 PSI/ 100 FT
COLD WATER CONNECTION SIZE
3/4"
1"
HOT WATER CONNECTION SIZE
3/4"
3/4"
0.2274 GPM
1 BA
B302
8.5 CWFU
6 HWFU
1 BA
B202
8.5 CWFU
6 HWFU
22.5 HWFU
17 GPM
1-1/4"
32.5 CWFU
21 GPM
1-1/4"
1 BA
B102
8.5 CWFU
6 HWFU
3/4"
z -
2 BA
B301
10 CWFU
7.5 HWFU
1"
2 BA
15 HWFU B201
12 GPM 10 CWFU
7.5 HWFU
HB-1
2.5 CWFU
2 BA
1B1:0 1
10 CWFU
7.5 HWFU
20 CWFU
15 GPM
1-1/4"
ROOF
LEVEL 3
LEVEL 1
Ahn HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
05
W
am
Cn
O
11mmmWz
Z
Q
zO
W
C'
J
Liu
Z
W
Lu
w
V
Q
O
J
a
c�
M
N
L
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
CONTENTS:
PLUMBING -
WATER RISER
DIAGRAM -
BUILDING B
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,02
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
ROOF
3 HWFU 6 HWFU 9 HWFU 12 HWFU 15 HWFU 18 HWFU 21 HWFU
3 GPM 6 GPM 8 GPM 9 GPM 12 GPM 14 GPM 15 GPM
LEVEL 2 3/4" 3/4" ill ill 1" 1-1 /4" 1-1 /4"
3 CWFU 6 CWFU 9 CWFUTI
2CWFU 15 CWFU 18 CWFU 21 CWFU
3 GM \ 6 GM 1 8 GPM 9 GPM 12 GPM 14 GPM 15 GPM
P4P
1 1-1/4" 1-1/4''
I I
I
I
WB-1 WB-1 FWB-1 FWB-1 WB-1 FWB-1 FWB-1
3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU 3 CWFU
3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU 3 HWFU
LEVEL 1
3/4"
24 HWFU 21 CWFU
18 GPM 15 GPM
1-1/4" 1-1/4"
24 CWFU 3/4"
18 GPM
1-1/4"
1.5 GPM2 GPM
3/4" 134 CWFU
51 GPM
100.5 HWFU 2"
44 GPM
SHUTOFF VALVE
SK-3
1= 172.5 CWFI
1.125 CWFU 59 GPM
1.125 HWFU 2
76.5 HWFU
HOT 37 GPM
WATER 2"
PLANT
0
rn
G�
1"
15 HWFU
12 GPM
I 1"
20 CWFU
15 GPM
1-1/4"
110 CWFU
45 GPM
2"
DOMESTIC WATER
PRESSURE CALCULATIONS
STREET PRESSURE
METER LOSS
BACKFLOW DEVICE LOSS
LOSS FROM DISTANCE MAIN INTO BUILDING
SYSTEM
64 PSI
-1.6 PSI
-8 PSI
-1 PSI
CALCULATIONS -
RESIDENTIAL UNIT SIZING CALCULATIONS
KITCHEN SINK
DISHWASHER
BATH/SHOWER
SHOWER
BLDG
1 BA
1
1
1
0
C
2 BA
1
1
1
1
ELEVATION LOSS
-12.6 PSI
LAVATORY
1
2
PRESURE REQUIRED AT FURTHEST FIXTURE
-30 PSI
WATER CLOSET
1
2
PRESSURE AVAILABLE FOR FRICTION LOSS
10.8 PSI
PER 2018 UPC TABLE A 103.1 AND FOOTNOT...
COLD WATER WSFU
8.5
10
DEVELOPED LENGTH OF SYSTEM
180'
HOT WATER WSFU
6
7.5
EQUIVALENT LENGTH FROM FITTINGS
45'
COLD WATER GPM
7 GPM
8.5 GPM
TOTAL DEVELOPED LENGTH
225'
HOT WATER GPM
5 GPM
6.5 GPM
PER CHART A 105.1(1):
FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 225 FT PER 100 FT)
4.82 PSI/ 100 FT
COLD WATER CONNECTION SIZE
1"
1"
HOT WATER CONNECTION SIZE
3/4"
1"
0.6822 GPM 0.4548 GPM
2 BA
C304
10 CWFU
7.5 HWFU
I
I
1"
2 BA
C204
10 CWFU
7.5 HWFU
18 HWFU
14 GPM
1-1/4"
1 BA
C303
8.5 CWFU
yWFU
3/4"
0.2274 GPM
1 BA
C302
8.5 CWFU
6 HWFU
1 BA
C301
8.5 CWFU
6 HWFU
I I
I
I
3/4" 13/4" � 3/4"
1 BA 1 BA 1 BA
C203 C202 C201
12 HWFU 12 HWFU 12 HWFU
8.5 CWFU 8.5 CWFU 8.5 CWFU
9 GPM 6 HWFU 9 GPM I 6 HWFU 9 GPM 6 HWFU
1" 1" 1"
17 CWFU 18 HWFU 17 CWFU 17 CWFU
\ 13 GPM 14 GPM 13 GPM 13 GPM
\ 1 1-1/4" 1 1
J
54 HWFU
30 GPM
2"
'
79 CWFU
38 GPM
2
61.5 HWFU
33 GPM
2"
25.5 CWFU -
89 CWFU
18 GPM
41 GPM
1-1/4"
2"
2 BA
C104
10 CWFU
FHB-1
7.5 HWFU
1 CWFU
C�
2" DOMESTIC WATER CONNECTION THIS BUILDING
172.5 WFU, 59 GPM
SEE CIVIL PLANS FOR CONTINUATION
AND FOR SITE BACKFLOW PREVENTION AND WATER METER
36 HWFU
23 GPM
1-1/2"
53.5 CWFU
30 GPM
1-1/2"
I
25.5 CWFU
I 18 GPM
1-1/4"
1 BA
-� C103
8.5 CWFU
6 HWFU
J
18 HWFU
14 GPM
1-1/4"
28 CWFU
19 GPM
1-1/4"
1 BA
-� C102
8.5 CWFU
6 HWFU
1
8.5 CWFU
6 HWFU
HB-1
2.5 CWFU
ROOF
LEVEL 2
LEVEL 1
HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
05
W
am
Cn
O
�z
U)
Z
Q
z
O
w
C'
J
Liu
U)
Z
WU)
Lu
Cl)
LL
w
V
Q
=
O
J
m
c.0
Cy')
N
L
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
CONTENTS:
PLUMBING -
WATER RISER
DIAGRAM -
BUILDING C
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,03
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
ROOF
LEVEL 3
LEVEL 2
LEVEL 1
15 HWFU
12 GPM
1"
20 CWFU
15 GPM
1-1/4"
I
HB-1 ALJ
2.5 CWFU
DOMESTIC WATER
PRESSURE CALCULATIONS
STREET PRESSURE
METER LOSS
BACKFLOW DEVICE LOSS
LOSS FROM DISTANCE MAIN INTO BUILDING
ELEVATION LOSS
PRESURE REQUIRED AT FURTHEST FIXTURE
SYSTEM
64 PSI
-1.6 PSI
-8 PSI
-1 PSI
-12.6 PSI
-30 PSI
CALCULATIONS -
RESIDENTIAL UNIT SIZING CALCULATIONS
KITCHEN SINK
DISHWASHER
BATH/SHOWER
SHOWER
LAVATORY
WATER CLOSET
BLDG
1 BA
1
1
1
0
1
1
D
2 BA
1
1
1
1
2
2
PRESSURE AVAILABLE FOR FRICTION LOSS
10.8 PSI
PER 2018 UPC TABLE A 103.1 AND FOOTNOT...
COLD WATER WSFU
8.5
10
DEVELOPED LENGTH OF SYSTEM
200'
HOT WATER WSFU
6
7.5
EQUIVALENT LENGTH FROM FITTINGS
50'
COLD WATER GPM
7 GPM
8.5 GPM
TOTAL DEVELOPED LENGTH
250'
HOT WATER GPM
5 GPM
6.5 GPM
PER CHART A 105.1(1):
FRICTION LOSS IN HEAD (100 X 10.8 PSI/ 250 FT PER 100 FT)
4.34 PSI/ 100 FT
COLD WATER CONNECTION SIZE
1"
1"
HOT WATER CONNECTION SIZE
3/4"
1"
3/4"
r
0.2274 GPM 0.4548 GPM 0.6822 GPM 0.9096 GPM 1.137 GPM
I
2 BA
D306
10 CWFU
7.5 HWFU
1"
2 BA
D206
10 CWFU
7.5 HWFU
3/4"
12 HWFU
9 GPM
17 CWFU
13 GPM
1"
22.5 HWFU
17 GPM
1-1/2"
32.5 CWFU
21 GPM
1-1/2"
12.5 CWFU
10 GPM
1"
I
2 BA
10 CWFU
7.5 HWFU
HB-1
1 CWFU
1 BA 1 BA 1 BA 1 BA I 1 BA
D305 D304 D303 D302 1 D301
8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU
6 HWFU 6 HWFU 6 HWFU 6 HWFU 6 HWFU
� I I
1 3/4" 1 3/4" 1 3/4" 1 3/4" 1
I� G�
q-� 1 gq 12 HWFU I q-� 1 BA 12 HWFU I q--� 1 BA 12 HWFU I q-� 1 BA 12 HWFU 1 BA
9 GPM I 9 GPM I 9 GPM I 9 GPM
17 CWFU 17 CWFU 17 CWFU 17 CWFU
8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU 8.5 CWFU I
13 GPM U 6 HWF
13 GPM U 6 H
13 GPM WFU 13 GPM
6 HWFU 6 HWF
6 HWFU
25.5 CWFU 25.5 CWFU 1, 25.5 CWFU 25.5 CWFU I 3/4"
18 GPM 18 GPM 18 GPM 18 GPM 94.5 HWFU
1-1/4" 40.5 HWFU 1-1/4" 58.5 HWFU 1-1/4" 76.5 HWFU 1-1/4" 43 GPM 100.5 HWFU 112.5 HWFU
25 GPM 32 GPM 37 GPM 2" 44 GPM 46 GPM
1-1/2" 2" 2" 2" 2"
-
59 CWFU 84.5 CWFU 110 CWFU 135.5 CWFU 144 CWFU 161 CWFU
32 GPM 40 GPM 45 GPM 52 GPM 54 GPM 56 GPM \
1-1/2" 2" 2" 2" 2" 2"
18 HWFU 18 HWFU 18 HWFU 18 HWFU
14 GPM 14 GPM 14 GPM 14 GPM '
33.5 CWFU 1-1/4"
21 GPM
1-1/2"
1 BA
D105
8.5 CWFU
6 HWFU
1-1/4"
1 BA
D104
8.5 CWFU
6 HWFU
1-1/4"
1 BA
D103
8.5 CWFU
6 HWFU
1-1/4"
1 BA
D102
8.5 CWFU
6 HWFU
1 BA
8.5 CWFU
6 HWFU
H
WP
PLANT
208 CWFU
65 GPM
2" DOMESTIC WATER CONNECTION THIS BUILDING
208 WFU, 65 GPM
SEE CIVIL PLANS FOR CONTINUATION
AND FOR SITE BACKFLOW PREVENTION AND WATER METER
ROOF
LEVEL 3
LEVEL 1
HOUSING
HOPE
we keep hope alive
DESIGNS
1 L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
w ww. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
05
W
am
Cn
O
�mmz
U)
Z
Q
zO
w
C'
J
Liu
Z
W
U)
Lu
w
V
Q
U)
O
J
a
c�
M
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
CONTENTS:
PLUMBING -
WATER RISER
DIAGRAM -
BUILDING D
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,04
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
ROOF
1 Inl VI\L VIVI 1 V — ILV.J
IE = 4' BELOW FF
SEE CIVIL PLANS FOR CONTINUATION
3" VTR
(62.5 DFU)
J I L
3" VTR
(32 DFU)
J I L
50.5DFU r
311 I
2" 2"
f--1—
3" 0 2"3"
o 3" 3" 3"
LL
AWk HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Suile B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
V
1 91 7 1 ST AVE, #300
SEATTLE WA 9B 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
W
CV
O
00
am
Cn
O
�z
Cn
Z
Q
z0
0
W
C�
J
LLI
Z
_
L LI
-
(�
w
C�
LLC)
w
c,
a
0
cy-)
CV
L
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # j Date I Description
2 101/04/2023 1 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING A
SCALE: 1/8" = 11-01,
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,05
ROOF
1 Inl VI\L VIVI I V— 1 1/
IE = 2.81 BELOW FF
SEE CIVIL PLANS FOR CONTINUATION
3" VTR
(51 DFU)
J I L
2" I 2"
12DFU � /4DFU�11
3" VTR
(66DFU)
I
jL
2" 3" 2"
24DFU 42DFU 35DFU 19DFU 13DFU 9DFU
71 0
LL
0 LL LL
2" (D o LL
0
rn
o _ 1 1/211 4� 2"
LEVEL 3
LEVEL 2
LEVEL 1
Ahn HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Suile B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
V
1 91 7 1 ST AVE, #300
SEATTLE WA 9B 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
W
CV
O
00
am
Cn
O
�z
Cn
Z
Q
z0
m
w
C�
J
Lu
Z
_
L LI
-
(�
w
Ljj
c,
a
C)
O�aL0
CV
L
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # j Date I Description
2 101/04/2023 1 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING B
SCALE: 1/8" = 11-01,
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,06
ROOF
3" VTR
(83 DFU)
J I L
2"
55DFU 28DFU
LO I
0
AWk HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Suile B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
1 91 7 1 ST AVE, #300
8EATTLE WA 9B 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
W
(0
CV
O
00
am
Cn
O
Cn
z
Z
Q
z0
0
W
C�
J
LLJ
M
Z
_
LLI
-
3
w
m
w
c,
aCID
C)
0
cy-)
C14
L
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # j Date I Description
2 101/04/2023 1 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING C
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,07
C1
3" VTR
(54 DFU)
J I L
2't 2"30DFU 24DFU 10DFU
I- LL
0
0 0 0
LL
LL
0 2"
I
" rIAI UMr— UIN110 — IJ/
SEE SHEET P4.07 IE = 3.9' BELOW FF
SEE CIVIL PLANS FOR CONTINUATION
ROOF
LEVEL 3
LEVEL 2
LEVEL 1
HOUSING
HOPE
we keep hope alive
DESIGNS
L 'V northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 91 7 1 ST AVE, #300
SEATTLE WA 9a 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
W
am
Cl)
O
Cn
z
Z
Q
z0
0
w
C�
J
LLJ
M
�
Z
L LI
(�
w
Ljj
c,
a
C)
0
(L
cy-)
CV
Mc
L
L0
CV 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING C
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,08
ROOF
3" VTR
(84DFU)
J I L
2" 24DFU 28DFU 48DFU 36DFU
F LL = I >
LL LO LO
0 2" 2" 00 � 2
2 N O
onnrl
Ahn HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Suile B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
V
1 91 7 1 ST AVE, #3130
5EATTLE WA 9B 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
UU
(0
CV
O
00
am
Cn
O
�z
Cn
Z
Q
z0
0
W
C�
J
Liu
Z
_
LLI
-
Cf)
w
Ljj
c,
aCID
C)
O�aL0
CV
L
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # j Date I Description
2 101/04/2023 1 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING D
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,09
ROOF
3" VTR
(48 DFU)
J I L
36DFU
LL
LL
0 L
0 0
2" 2" °' � 2"
3" VTR
(33 DFU)
J I L
12DFU
0 2"
N
2"
" rIAI UMr— UINI 10 — 100
SEE SHEET P4.09 I = 4.25, BELOW FF
SEE CIVIL PLANS FOR CONTINUATION
ROOF
Ahn HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 639.3441
P.O. Box 1^_70
10031 SR 532. Suile B
Sl--Iod. WA 98292
wwww.designsnw.com
ECOTOPE
1 91 7 1 ST AVE, #3130
5EATTLE WA 9B 1 O 1
PH: (Z06) 3ZZ-3753
FAX: (206) 325-7270
UU
(0
CV
O
00
am
Cn
O
Cn
z
Z
Q
z0
0
W
C�
J
LLJ
M
Z
_
LLI
-
3
w
m
w
c,
aCID
C)
0
cy-)
C14
L
L0
CV
ao
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # j Date I Description
2 101/04/2023 1 PERMIT RESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
WASTE WATER
RISER DIAGRAM -
BUILDING D
SCALE: 1/8" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P4,1
O SHEET NOTES
1
HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE
PLANS AND RISER DIAGRAMS FOR SIZES.
2
PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE
WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS
AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS
CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL.
3
WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN
SIDE WALL AND BEHIND CABINETRY.
4
USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS
WHERE POSSIBLE
PI 11MRINC-, FNI ARC-,Fn HNIT PI ANq - Rini
Akr\ HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
Cfl
N
O
00
am
Cn
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
LLI
U)
w
w
V
Q
U)
O
J
a
M
N
LL1
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
PLUMBING -
ENLARGED UNIT
PLANS
SCALE: 1/4" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P5,0
PLUMBING ENLARGED UNIT PLANS - D206
1 /4" = 11-011
SIM:
D306
PLUMBING ENLARGED UNIT PLANS - D101
1 /4" = 11-011
PLUMBING ENLARGED UNIT PLANS - C104
1 /4" = 11-011
S I M :
D106
O SHEET NOTES
1
HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE
PLANS AND RISER DIAGRAMS FOR SIZES.
2
PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE
WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS
AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS
CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL.
3
WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN
SIDE WALL AND BEHIND CABINETRY.
4
USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS
WHERE POSSIBLE
O PLUMBING ENLARGED UNIT PLANS -C101
1 /4 = 11-011
SIM : C 102, C 103, D 102, D 103, D 104, D 105
AW\ HOUSING
HOPE
we keep hope alive
DESIGNS
1 L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
w ww. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
W
c0
N
O
00
a
O
�z
U)
Z
Q
zO
w
C'
J
Liu
Z
L L1
U)
w
w
V
Q
U)
O
J
a
M
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # I Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
PLUMBING -
ENLARGED UNIT
PLANS
SCALE: 1/4" = V-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
5,0
PLUMBING ENLARGED UNIT PLANS - A204
1 /4" = 11-011
SIM: A202, A2035 A3025 A3035 A3045
B2025 B3025 C2015 C2025 C2035 C3015
C3025 C3035 D2015 D2025 D2035 D2045
D2055 D3015 D3025 D3035 D3045 D305
PLUMBING ENLARGED UNIT PLANS - A201
2 1 /4" = 11-011
SIM: A205, A3015 A3055 B2015 B3015 C2045 C304
O SHEET NOTES
1
HOT AND COLD DOMESTIC WATER RISERS SUPPLYING UNITS. SEE
PLANS AND RISER DIAGRAMS FOR SIZES.
2
PROVIDE SHUT OFF VALVES FOR WATER SUPPLIES HIGH IN SIDE
WALL OR CORNER OF BACK WALL OF CLOSETS. FEED PEX MANIFOLDS
AFTER SHUT OFF VALVES. PLACE HOT WATER SHUT OFF VALVE AS
CHOSE TO CIRCULATED WATER IN RISER AS IS PRACTICAL.
3
WASTE, VENT, AND SUPPLY LINES FOR PENINSULA SINK TO RUN IN
SIDE WALL AND BEHIND CABINETRY.
4
USE WET VENTING FOR WASTE AND VENT LINES IN RESTROOMS
WHERE POSSIBLE
1-BED
B203
556 SF
PLUMBING ENLARGED UNIT PLANS - B203
1 /4" = 11-011
SIM: B204, B3035 B304
HOUSING
HOPE
we keep hope alive
DESIGNS
L v northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 0 1
PH: (206) 322-3753
FAX: (206) 325-7270
r-
W
cD
N
O
00
am
V ♦
O
u)
z
z
Q
zo
w
C'
J
Liu
Z
LLI
U)
w
w
V
Q
U)
Cy')
N
LLI
N
00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
ENLARGED UNIT
PLANS
SCALE: 1/4" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
5,0
FIRE RISER
C124
HW I CW HUB DRAIN FOR HD-1 '
I 1/2"o I I 1/2"o AFIRE VALVES
I I I HWC
— — ' 3/4" o
HWC TP-1 - _ _-- HW
3/4"0 1 + 2"o
3" DOMESTIC WATER
MAIN FROM BELOW — - -_I I CW
2„o
THERMOSTATIC _ ________________I�
BALANCING
VALVE FS-1 I 1 ST-C1 I 3"V
2" CW 2" HW I �2"V
W B-1 I EXP-C 3/4" HWC
I I CW MECH I HPWH I TMV-C
1 HWC HW 1 1/4"o EL C I
11 3/4"o 1 1/4"o -I
C120
W B-1 128 SF
11 I
! WH
J �V I I -C FD-2
6 -IW 1
LAUNDRY 1 IN 2"V DN ,
C122 i11 FD-3 I I ELEC. I
126 SF CW I -I C121
H W W B-1 3/4"o W B-1 27 SF
3/4"o 1 '�
W B-1-;J-—I---!
r
1/2"CW&HW
2"W , 1-1 /2"V
(TYP 7)
CW HW
1"o 1"o
ENLARGED PLUMBING PLAN - BLDG C MECHIWATER ROOM AND LAUNDRY ROOM
1 /4" = 11-011
FS-1
el
HW
CW 2"o HWC
2"o `3/4"o
ST-D1 MECH 1 HPWH I
0 ELEC
D120 I c
98 SF& TMV-D c
J I c
FD-2
I
. 1
FIRE VALVE SPACE
B H D-1
FIRE RISER
D121
68 SF
1 8 FD-2
2"V
ENLARGED PLUMBING PLAN - BLDG D MECHANICAL/WATER ROOMS
1 /4" = 11-011
U A CW HW HWC FD-2
2 "o 2"o - 3/4"0 ---- —
FD-2 eMECH 1 HPWH I I B
(ELEC
I
Al P-A
TP-1 I122 ST-A1 ST-A2
I
I �
W H-A I
• • I ��
FS-1 2„V
! 2"V
I
STORAGE CW i I
A 223 1 3"o Ili I
95 SIF I
I
I
HW I
1
CW ^�
1 1 /4"o
2"W FROM SH
'--2"V UP
3"W
21
j 3"W DN
14"HWC UP
5�,,2"W FROM BT
1/2"CW&HW
2"W , 1-1 /2"V
ITM V-A I
FIRE RISER
A125
68 SF
B H D-1
ftTA
FIRE WATER FROM BELOW
IRE VALVE SPACE
OCATION TO BE COORDINATED
ENLARGED PLUMBING PLAN - BLDG A MECHANICAL/WATER ROOM
1 /4" = 11-011
4"W DN
1/2"CW TP-2 WCO-
1/2"HW
2"W L _
HW CW
1/2": 3/4"o
L-2 W C
CW
FD-3
1 1/4"o c I
-'IV UP
U P
53 SF
HW
1"0 —
7 __r T
HW
3"W UP 1 1"o
"W DNJ 1-1/2" V
HW CW
1 1 /2"o 1 1 /4"o
---STORAGE'--
_ A110
— —53 SF -
CW
1 1 /2"o
i
WC-2 ® 9R-1
C
-- �-- -T ILET--
__
— ��-53SF M _�
CW&HW UNIT
RISERS UP
1 /2"C W
2"W
1-1 /2"V
------- 1 /2"C W
------ - S K-4 1 /2"H W
2"W
1-1 /2"V
< > -
CW �—_I
1 1/2"0 l e ! _, DF-1
1-1/2" V
1 /2"C W
1 /2"H W
2"W
1-1 /2"V
ENLARGED PLUMBING PLAN - BLDG A AMENITY RESTROOMS
1 /4" = 11-011
FIRE VALVE SPACE
FIRE WATER
FROM BELOW HD-1 B
,USER
6120
66 SF
B FD-2
HW CW HWC
2"o 2"o 3/4"o
::�TMV-B11
II
ST-B1 I
e
FS-1 MECHIHPWHI • ,
ELEC W
B121
ST-62 105 S I
r
mm
II __1 II I II II
3" DOMESTIC WATER
MAIN FROM BELOW
ENLARGED PLUMBING PLAN - BLDG B MECHANICAL/WATER ROOM
1 /4" = 11-011
AkF\ HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
w ww. designs nw. com
ECOTOPE
1 9 17 1 ST AvE, #300
SEATTLE WA 9B 1 o 1
PH: (206) 322-3753
FAX: (206) 325-7270
M;
W
am
Cn
O
�mmz
Z
Q
zO
LU
C'
J
LLI
E
�
Z
W
U)
w
m
w
V
Q
U)
O
J
a
c�
M
N
mc
L
N 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING -
ENLARGED AREA
PLANS
SCALE: 1/4" = 1'-0"
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
5,0
ULATION
BACKII
MATEF
AS RE(
A�PIPE THRU INTERIOR WALL WITH PIPE INSULATION
IT
IPE
BACKI
MATEI
AS RE
SULATION
JG
IAL
)UIRED
r PIPE THRU FLOOR WITH PIPE INSULATION
PIPE
RISER CLAMP
WHERE
APPLICABLE
SEALANT" BACKING
gPIPE THRU INTERIOR WALL WITHOUT PIPE INSULATION MATERIAL
AS REQUIRED
D�PIPE THRU FLOOR WITHOUT PIPE INSULATION
PIPE THRU INTERIOR WALL AND THRU FLOOR
1211 = 11-011
VIBRATION ISOLATION SEE
SPEC FOR TYPE
PRESSURE GAUGE
II II
SHUT-OFF VALVE TY
U KuU11 5t I I tK tS&6
PLUS, NOMINAL LINE
SIZE
BLOW DOWN VALVE
NOTE: MOUNT PUMP MOTOR HORIZONTAL, OR BELOW PUMP FOR HOT
WATER
APPLICATIONS
INLINE PUMP PIPING TRIM DETAIL
1211 - 11-011
_L
ANOUT
VENT AS HIGH AC DncclDI E:
UNDER COU
SH
--LOOR
1
PITCH VENT UP
TOWARD WALL
"Y" FITTING -
ISLAND VENT DETAIL
9 1 211 = 1 1-011
WASTE PIPING, SIZE AS
SHOWN ON PLAN
If
VANDAL RESISTANT
COVER MARKED
"SEWER"
WASTE STACK RECIEVING DISCHARGE
FROM 3 OR MORE STORIES OF SUDS
PRODICING FIXTURES
8FT MIN
HORIZONTAL CHANGE IN DIRECTION
(BOTTOM OF STACK). NO DRAINAGE
CONNECTIONS WITHIN 8FT
HORIZONTALLY AND 8FT VERTICALLY
FROM STACK CHANGE IN DIRECTION
000,
0
O/AFC
T%
M
8FT MIN
DRAINAGE CONNECTION
SUDS RELIEF PIPING DETAIL
611 - 11-011
PIPE SLEEVE OF SIZE TO
PASS PIPE AND LEAVE
ROOM
FOR PIPE INSULATION
TERMINATE SLEEVE
FLUSH WITH WALL
SURFACE
ICI»
FILL ANNULAR GAPS EACH
SIDE OF SLEEVE WITH
NONCOMBUSTIBLE
SEALANT
PIPE WALL PENETRATION
1 211 = 1 1-011
SEE MINIMUM PIPE
INSULATION TABLE
FOR INSULATION
THICKNESS
FINISHED WALL
SURFACE
1O GROUT SLOPE
TC
DRAIN INLE1
DRAIN INLET STRAINEF
CORED HOLE
DRAIN BODY
STYLE WITH
DRAINLINE
CORE DRILL FLOOR DRAIN
1211 - 11-011
4
5
-RUCTURAL
DNCRETE
OOR
RAINER EXTENSION
SHRINK CONCRETE-
tF'UAY IiKUU 1 IIV
ANNULAR CORE SPACE & SURFACE
SLOPE.
20 SHEET METAL CLOSURE ANCHORED TO
CONCRETE FLOOR.
OSAFING MATERIAL 1-1/2 x DRAIN
DIAMETER (8) MINIMUM STUD
PIN SUPPORTS.
40 1-1/2"0"x12" ANGLE STEEL SUPPORT
EACH SIDE MINIMUM (4)
STUD PIN FASTENERS.
:HANGER
;UT TO LENGTH
LATION - LENGTH
1.5 TIMES INSULATION DIAMETER
INSULATION
CARRIER PIPE
PIPE HANGER - CLEVIS TYPE
1211 - 11-011
nnnrn "In" AKIM Pr/�I Inr1 \/
LRESIDENTIAL SINK AND DISHWASHER
1 211 = 1 1-011
AW\ HOUSING
HOPE
we keep hope alive
DESIGNS
northwest
ARCHITECTS
360. 629. 3441
P.O. Box 1 27 0
31 100SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
ECOTOPE
19 1 7 1 ST AvE, #300
SEATTLE WA 9B 1 O 1
PH: (206) 322-3753
FAX: (206) 325-7270
R
M
W
O
�Wz
z
Q
z
W
C'
J
Uj
Z
W
W
W
V
Q
0
c�
CV
mc
U
Lo
CV 00
CONSTRUCTION
DOCUMENTS
ISSUE DATE: JAN. 3, 2023
REVISION SCHEDULE
Rev # Date Description
2 01/04/2023 IPERMITRESUBM.
RESUB
4/8/2023
CITY OF EDMONDS
DEVELOPMENT
SERVICES
DEPARTMENT
CONTENTS:
PLUMBING
DETAILS
SCALE: As indicated
DRAWN: Author
CHECKED: Checker
PROJECT NO: 2021031.00
SHEET:
P810
T&P RELIEF VALVE TO DRAIN
TEMPERATURE GAUGE (TYP)O
O/T
OUTGOING
DOMESTIC HOT
WATER
SERVICE SHUTOFF VALVE (TYP) Al
INCOMING DOMESTIC
COLD WATER
CHECK VALVE
TO DRAIN FOR BACKFLUSHING
STATIC DEFLECTION SPRING ISOLATORS (TYP)
HPWH TYPICAL DETAIL
1211 = 1'-011
COLD WATER LINE
-$" HOUSING
HOPE
we keep hope alive
SHUT-OFF VALVE -
TRAP PRIMER VALE
VACUUM BREAKER PORT ` DESIGNS
h w e s t
DISTRIBUTION UNITS) ARCHITECTS
(WHERE REQUIRED)
360. 629. 3441
P.O. Box 1270
10031 SR 532, Suite B
Stanwood, WA 98292
www. designs nw. com
H
�pn
�$„ O FLOOR SINK, FLOOR
DRAIN OR HUB
DRAIN
1BEVEL
ECOTOPE
CUT Tp
AIRGAP
\ _8"x1
-8" 1 917 1 5T AvE, a300
SEATTLE WA 9B 1 O 1
CONNECT TRAP PRIMER PH: (206) 322-3753
INLET TO FIXTURE FAX: (206) 325-7270
OUTLET TAILPIECE SIDE
OF TRAP
NOTES:
1. PROVIDE ACCESS PANEL IN WALLS AT TRAP PRIMER UNIT LOCATIONS.
2. TRAP PRIMER VALVE SHALL BE MOUNTED ONE FOOT ABOVE THE
FINISHED FLOOR FOR EVERY 20 FEET OF PRIMER LINE.
3. INSTALL TRAP PRIMER PIPING AND UNIT PER
MANUFACTURER'S RECOMMENDATIONS. PIPING MUST SLOPE
TO POINT OF CONNECTION TO DRAIN WITHOUT TRAPS IN
PIPING
c0
N
TRAP PRIMER INSTALLATIONCD
00
1211 — 1'-011
UJI
am
COMMON VENT c
STACK TO ROOF O Wz
Z
zO
Q2" DRY VENT � w
LAV TRAP
ARM
2" WET VENT
LU
VERTICAL WET VENTING NOTES: Lu
U) UmWATER CLST WET VENT NOT TO EXCEED 6 FT IN DEVELOPED
pC
TRAP ARM LENGTH.
TUB TRAP WET VENT PIPE SIZE TO BE ONE PIPE SIZE LARGER
ARM THAN THE REQUIRED MINIMUM OF THE UPPER co
N
FIXTURE OR SHALL BE ONE PIPE SIZE LARGER LO
THANT HE SUM OF THE FIXTURES SERVED BY THE
WET VENT, WHICHEVER IS GREATER. NO WE VENT = W 00
IS ALLOWED LESS THAN 2".
COMMON WASTE DRY VENT CONNECTION SIZE SHALL BE THE SUM
STACK TO OF THE FIXTURE UNITS SERVED BUT NEVER LESS
BUILDING DRAIN THAN 2". CONSTRUCTION
DOCUMENTS
WET VENT PIPING DETAIL ISSUE DATE: JAN. 3, 2023
12" = 1'-0"
REVISION SCHEDULE
R-11 INSULATION JACKET Rev# 11 Date Description
2 01/04/2023 IPERMITRESUBM.
SERVICE SHUTOFF VALVE (TYP) UNION (TYP)
RESUB
MANUAL AIR BLEED VALVE1 CITY OF EDMONDS
\ DEVELOPMENT
11 SERVICES
1 DEPARTMENT
/ \ --- CAPPED FITTING
EARTHQUAKE STRAPPING PER UPC
WATER HEATER OR HOT WATER
STORAGE TANK
T&P RELIEF VALVE (TYP)
ROUTE TO APPROVED LOCATION
THERMO WELL
TEMPERATURE PROBE
INSULATED PIPING
CONNECTION (TYP)
R-10 RIGID INSULATION
PLUMBING
DETAILS
SCALE: 12" = 1'-0"
DRAWN: SLB
CHECKED: SLB
PROJECT NO: 2021031.00
SHEET:
HOT WATER STORAGE TANK DETAIL1
1211 = 1'-011