FIR2021-0016+plans+5.24.2021_5.53 (2)BUCKEYE KITCHEN MISTER BRF-15 WET CHEMICAL FIRE SUPPRESSION SYSTEM
Nozzles/
Part No.
Nl, N2
N-1LP
N3, N4
N-lHP
N5, N6
N-2HP
N7
N-1LP
N8
N-lHP
N9, N10
N-2LP
Nozzles heights: 40"
(from tip Of nozzle to top of
appliance) `
Hood dimensions 11' x 3'
Duct dimensions 12" x 12"`
Agent cylinder BRF-10 ��` Duct 12"x 2" Duct 12"x 2"
Agent line: ''/2" & 3/8" black pipe `� Hood 11'x 3' Hood 6'x 3'
8-Detector/fusible links: 450°F `
Total flow points: 14 `
Total agent flow points: 15 _ _ _ _ S'_ _ _ _ _ _ _ N 1 / - - - �- / - N
Note: Fire alarm and electrical on TqZt
separate permits. r-----------r------7-- ---------- i
N5 + N6 + N8 + N9 + N10
N7
ALA It
o4 005 0 000
Mechanical I 3 6
Gas valve
Class "K'
Manual Fire Extinguisher
Pull Station
Appliances:
AKA
Dimensions.
Heights
79,,-5 & of Of)-M574ZZ,47'70Z5 LTC
1.- Fryer
16" x 19 Yz "
36"
2.-Fryer
16"x 19'/z"
36"
Fire Suppression Systems(Service & Installation)
3.- Griddle
24" x 24 "
36
Kitchen Hood Installations
4.-Broiler
24"x24"
36"
• Fire Extinguishers Complete Food Truck Builds
5.- 6 Burner Range
36" x 24"
36"
6.- 6 Burner Range
36"x24"
36"
14611 Ambaum Blvd SW Burien, WA 98166 206-617-4951
Chapter 2 — Components
Page 2 - 1
Revision 4
Chapter 2
System Components
Cylinder sizes
The Buckeye Fire Equipment Kitchen Mister Fire Suppression System has available four (4) cylinder sizes, the Model
BFR-5 (5 flow points), Model BFR-10 (10 flow points), Model 13FR-15 (15 flow points), and Model BFR-20 (20 flow
points). Cylinder sizes are based on the flow point capacity of the cylinder, for example, the BFR-5 is capable of
supporting a maximum of five (5) flow points. All cylinders are manufactured, marked, and tested in accordance with DOT
4BW240. Each cylinder is shipped pre -filled with extinguishing agent, and charged with dry nitrogen to a pressure of 195
psig (1344 KPa) @ 70° F (21° C). Cylinder and valve assembly dimensions are shown in Figure 2-1.
(Vote: Cylinders shall always be stored in an upright position.
Figure 2-1.
Cylinder and Valve Assembly Dimensions.
Model
Number
A
inches
(cm)
B
inches
(cm)
C
inches
(cm)
D
inches
(cm)
Max.
Flow
Points
Weight
lbs.
(kg)
Mounting
Bracket
BFR-5
24.8 (63)
16.2 (41)
10 (25)
13.4 (34)
5
421bs. (19)
MS-1
BFR-10
34.4 (87)
25.8 (66)
10 (25)
23 (68)
10
74 lbs. (33)
MB-2
BFR-15
44.$ (114)
36.2 (92)
10 (25)
33.4 (85)
15
107Ibs_ (48)
PA&2
BFR-20
42.4 (108)
33.8 (86)
12 (31)
31 (79)
20
130 Ibs. (60)
MB-2
BPN: BFR-TM ULEX 5885 ULC-EX 6885
January 1, 2011
0
Systems Releasing Module - SRM
The Model SRM Systems Releasing Module is a fully
mechanical control head that can be connected dimctly
or remotely to the system valve and is required for
system actuation. The Systems Releasing Module will
support the following system inputs and outputs:
• One Fusible Link Detection Line
• One Gas Valve Line
• One Remote Pull Station Line
Two windows in the front cover of the Model SRM allow
for visual verification of the actuation cartridge presence
and the status of the puncture pin mechanism. See
Figure 2-5.
a o
Bd�KLYE L K n
I
iSET•�"01
+0 FIRED,
ACTUATION LEVER AN \ACTUATION CARTRIDGE
PUNCTURE PIN VIEWING VIEWING WINDOW
WINDOW
Figure 2-5.
Model SRM,
Systems Releasing Module
The Model SRM can actuate a maximum of. three (3)
agent cylinders when using the Model BFR-AC-S
Nitrogen Activation Cartridge (included with SRM and
SRM-D) or five (5) agent cylinders when a Model BFR-
AC-L Nitrogen Activation Cartridge is installed.
Systems Releasing Module - SRM-D
The Model SRM-D (Systems Releasing Module _Dual) is
exactly the same as the Model SRM except that it
supports a second independent fusible link detection line.
Nitrogen Actuation Cartridges
The iQtchen Mister System can use two types of
actuation cartridges for system actuation.
BPN: BFR-TM
Chapter 2 — Components
Page 2 - 3
Revision 4
Model 13FR-AC-S is a small nitrogen cartridge (included
with System Releasing Module) that can actuate up to
three (3) agent cylinders.
Model BFR-AC-L is a larger nitrogen cartridge that can
actuate up to five agent cylinder (refer to Chapter 4 of
this manual for limitations). See Figure 2-6.
I _ 5.12
(13 cm)
01.57
(4 cm)
" �___— -
Model BFR-AC-L
3.70
i (9.4 cm) `
i
i JuLads sae
s`(2.5 cm)
zS3
Model BFR-AC-S
Figure 2-6.
Model BFR-AC-S and BFR-AC-L,
Nitrogen Actuation Cartridges
Mounting Brackets
The Model MB-1 Mounting Bracket is used to mount the
Model BFR-5 cylinder. See Figure 2-7.
Figure 2-7.
Model MB-1,
Shown With 13FR-5 Cylinder
The Model MB-2 Mounting Bracket is used to mount the
Model BFR-10, Model BFR-1S, or Model BFR-20
cylinders. See Figure 2-8.
ULEX 6$8 r ULC-EX 6885
January 1, 2011
W
Chapter 2 — Components
Page 2 - 4
Revision 4
Figure 2-8.
Model M8-2,
Shown With SFR-20 Cylinder
Remote Mechanical Pull Station
The Model RPS-M Remote Mechanical Pull Station
provides remote mechanical actuation of the Systems
Releasing Module. It is connected to the Systems
Releasing Module with:
• 1t16" (0.16 cm) stainless steel cable enclosed in 1/2"
(1.3 cm) EMT conduit with a comer pulley at each
change of direction.
• Buckeye Shielded Cable which does not require a
comer pulley at each change of direction or conduit.
• A combination of both.
A remote pull station is required at the point of egress
from the hazard area being protected. See Figure 2-9.
TTOF � O�
N CAS
FIRE
{ PULL HANDLE HARD
i o
C
FIRE SU SYSMI
Figure 2-9.
Model RPS-M,
Remote Mechanical Pull Station
ULEX 6885 ULC-EX 6885
January 1, 2011
Mechanical Gas Shutoff Valves
A gas shutoff valve is required for all systems protecting
gas fueled appliances. A mechanical means of stopping
gas flow is provided by the Models BFGV-75 / 10o / 125
/ 150 / 200 / 250 / 300 Gas Shutoff Valves. it is
connected to the Systems Releasing Module with:
• 1/16" (0.16 cm) stainless steel cable enclosed in 1/2"
(1.3 cm) EMT conduit with a comer pulley at each
change of direction.
• Buckeye Shielded Cable which does not require a
comer pulley at each change of direction or conduit.
A combination of both.
The valves are rated for natural or LP gas (see Figure 2-
10) and are available in the following sizes:
Model
Number
Valve
Size
In (cm)
Maximum
Operating
Pressure
BFGV-75
3/ (1.9)
5 psi (A bar)
BFGV-100
1(2.5)
5 psi A bar
BFGV-125
1 %. 3.2
5 psi (_4 bar)
BFGV-150
1 Yz 3.8
5 Esi A bar)
BFGV-200
2(5.1)
5 psi (A bar)
BFGV-250
2 % 6.4
5 psi A bar
BFGV-300
3 7.6
5 psi A bar)
Note: Gas valve size must be no smaller than the size of
the gas line it is connected to.
Figure 2-10_
Model BFGV-XXX,
Mechanical Gas Valve
0
Fusible Link Bracket Flit
The Model FLB-1 Fusible Link Bracket kit (see Figure 2-
11) includes the following:
• Standard high profile 10" (25 cm) fusible link
bracket.
• Two (2) W (1.3 cm) EMT connectors.
• Two (2) cable crimps.
• Two (2) "S" hooks.
Note: Fusible links must be ordered separately.
!- FUSIBLE LINK BRACKET
i
-S- HOOK
112- (1.3 cm) EAd
\\ CONNECTOR
CABLE CRIMP
Figure 2-11.
Model FLB-1,
10" (25 cm) Fusible Link Bracket Assembly
Fusible Link Holder
The Model FLH Fusible Link Holder is designed to allow
for the use of a continuous fusible link line, thus
eliminating the need to cut and crimp each individual
fusible link. They can be used either with or without
fusible link brackets. They are available in packages of
25 (Model FLH-25)_ See Figure 2A2.
111r 10_15 cm) STAINLESS
DETECTION CABLE
�Ubju e u KimL.
STYLE)
Figure 2-12.
Model FLH,
Fusible Link Holder
Fusible Links
ISLE
The Kitchen Mister System uses Globe ML Fusible Links
for automatic system activation. See Figure 2-13.
Fusible links are designed to separate at specific
temperatures: releasing tension from the fusible link
Chapter 2 — Components
Page 2 - 5
Revision 4
detection tine and causing system actuation_ Correct
fusible link selection is an essential element in the design
of any restaurant fire suppression system. After
performing a temperature study to determine the
maximum ambient temperature at the fusible link
location, the correct fusible link should be selected from
the following chart:
Fusible Link
Model Number
Max. Ambient
Temperature
FL-280
2250 F. (1or C.)
FL-360
300° F. (149° C.)
FL-450
3750 F. (1910 C.,
FL-500
4300 F. (2210 C.)
Figure 2-13.
Globe ML Fusible Link
Buckeye Shielded Cable
As an alternative to using conduit and comer pulleys to
connect the fusible link system, gas valve, and/or remote
pull station to the Systems Releasing Module, the
Kitchen Mister System utilizes Buckeye Shielded Cable
to perform this function_ Buckeye Shielded Cable is 1/16"
(0.16 cm) stainless steel cable encased in a protective,
flexible conduit. See Figure 2-14.
Buckeye Shielded Cable requires no conduit or corner
pulleys, as the name implies, provided it is installed in
accordance with the guidelines set forth in this manual.
Model SFR-SC-100 comes with 100 feet (30.5 m) of
flexible conduit with 200 feet (61 m) of 1116" (0.16 cm)
stainless steel cable inside it.
auctEYE
1116-10.
TAMLESS =
S
Figure 2-14.
Model BFR-SC-100,
Buckeye Shielded Cable
BPN:. BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2011
Chapter 2 — Components
Page 2 - 5
Revision 4
Shielded Cable Interface
The Model BFR-SCI Buckeye Shielded Cable Interface
is required for connecting Buckeye Shielded Cable to any
standard 1/2" (1.3 cm) EMT conduit connector or corner
pulley. See Figure 2.15,
Figure 2-15.
Model BFR-SCI,
Shielded Cable Interface
Note: A 3/32" (0.2 cm) hex wrench is required to tighten
the set screw.
Compression Type Corner Pulley
When Buckeye Shielded Cable IS NOT used to connect
the fusible link system, gas valve, andlor remote pull
station to the control head, a comer pulley is required
whenever a change in stainless steel cable direction is
necessary. The Model CPCT-1 comer pulley is equipped
with a compression type fitting that connects to standard
1/2" (1.3 cm) EMT conduit. See Figure 2-16.
Figure 2-16.
Model CPCT-1,
Compression Type Corner Pulley
Discharge Nozzles
Misting type discharge nozzles have been specifically
developed for appliance, duct, and plenum applications.
Each nozzle has a predetermined flow point value and
comes equipped with a blow -off cap to protect the end
orifice from blockage. Each nozzle is identified by the
model number stamped on the nozzle body and has a
unique color band for easy visual identification. See
Figure 2-17.
ULEX 6885 ULC-EX 6885
January 1, 2011
Model
Number
Flow
Points
and
olor
N-1HP
1
lue
;Red
N-1 LP
1
N-2HP
2
een
N-21-P
2
Yellow
N-2W
2
White
Note: Details on speck nozzle applications can
found in the Design Section of this manual.
i
3/ 16
(0.2 cm) U
rEX.
�- RETt
i
1.50'
f3.8 cr:)
Figure 2-17.
Discharge Nozzle
Swivel Nozzle Adaptor
The Model N-SA Swivel Adaptor can be used with
discharge nozzle to facilitate the nozzle aiming proce
They are chrome plated and allow for a 30' rotation
the nozzle in any direction. See Figure 2-18.
30' ROTATION
318" (1.0 cm) NP T
FEMALE THREAD
318" (1.0 cm) NPT
MALE THREAD
Figure 2"1$_
Model N-SA,
Swivel Adaptor
Chapter 3 — System Design
{ r Page 3 -1
Revision 4
Chapter 3
System Design
OVERVIEW OF SYSTEM DESIGN side length of 12-1/2" (32 cm) (square) and 16-314" (43
cm) (rectangular) respectively. It can also protect a
round duct with a maximum circumference of 50" (127
The following chapter will cover the proper design of the cm) (16" (41 cm) maximum diameter]. See Figure 3-1
Buckeye Fire Equipment Kitchen Mister Fire g 3-2.
Suppression System. It is divided into three sections:
Ducts -150" (381 cm) Maximum Perimeter
1. Nozzle Coverages and Placements
2. Piping Limitations Nozzle: N-2W (2 Flow Paint)
3, Detector Placement
Design of the Kitchen Mister System must be in
compliance with the parameters set forth in this manual
and be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Buckeye Fire
Equipment is not responsible for systems installed or
maintained by personnel that are not factory trained and
Authorized.
NOZZLE COVERAGE, PLACEMENT,
AND AIMING
This section will give detailed guidelines for determining
nozzle type, positioning, and aim point for appliance,
plenum, and duct protection_
Duct Protection
It is not necessary to shut down or damper the exhaust
fan for the system to function properly. It is
recommended that the exhaust fan be left on during
system discharge to help distribute the extinguishing
agent throughout the ductwork.
Ducts - 50" (127 cm) Maximum Perimeter
Nozzle: N-11-P (1 Flow Point)
Coverage: Unlimited length with:
50" (127 cm) Maximum Perimeter with a
longest side of 16-3/4" (43 cm) for
rectangular ducts and 12-1/2" (32 cm) for
square ducts
or
50" (127 cm) Maximum Circumference
(maximum diameter of 16" (41 cm)) for
round ducts.
Placement: Centered in duct opening, from 1-6" (2-5-
15 cm) into the duct opening.
Aim point: Center of duct.
The Model N-1 LP nozzle is a one flow point nozzle that
can protect a square or rectangular duct with a
maximum 50" (127 cm) perimeter and a maximum one
BPN; BFR-TM
Coverage: Unlimited length with:
150" (381 cm) Maximum Perimeter with a
longest side of 50" (127 cm) for
rectangular ducts and 37-1/2" (95 cm) for
square ducts
or
150" (381 cm) Maximum Circumference
[maximum diameter of 47-1/2" (121 cm)]
for round ducts.
Placement: Centered induct opening, from"" (0-15
cm) into the duct opening.
Aim point: Center of duct_
AIM: CENTER OF
4OZZLE PLACEMENT:
1'- 6" (2.5-15 cm)
0 to 50" (o-127 cm), N-1 LP)
0" - 6" (0-15 cm)
0 to 1W (0-381 cm), N-2Wl
INTO THE DUCT
FOR DUCTS (VERTICAL OR HORIZONTAL)
WITHOUT A TRANSITION
AIM: CENTER OF i Due
ENTRANCE TO
HORIZONTAL DUCT . � NOZZLE PLACEMENT:
(2.5-15 cm)
(Per. 0 to 50" (0-127 cm), N-1 LP)
0'- 6" (0-15 cm)
[Per. 0 to 150' (0-381 cm), N-2Wl
L _ _ INTO THE DUCT TRANSITION
FOR DUCTS WITH A VERTICAL TO HORIZONTAL
TRANSITION
Figure 3-1.
Proper Duct Nozzle Placement
:.ILEX 6885 ULC-EX 6885
January 1, 2011
Plenum Protection
Nozzle: N-1 HP (1 Flow Point)
Coverage: Length- 12 feet (3-7 m) max.
Width: 4 feet (1.2 m) max.
Placement: See Figure 3.7.
Aim point: See Figure 3.7.
The Model N-1HP nozzle is a one (1) flow point nozzle
that can protect a plenum (either single bank or V-bank)
of 12 feet (3.7 m) in length and 4 feet (1.2 m) in width
per nozzle. Larger plenums must be divided into 12 foot
(3.7 m) sections, with each section protected with a
separate nozzle. See Figure 3-7.
Plenum: V-bank Nozzle Placement
The nozzle must be located at the center of the V-bank
width and down 1/3 of the vertical height, within 6 inches
(15 cm) of the end of the plenum or plenum module and
aimed down the length of the plenum. See Figure 3-7.
Plenum: Single Filter Bank Nozzle Placement
The nozzle must be located at a point that is 2" (5.1 cm)
from the back edge of the filter and 113 of the vertical
height of the filter, within 6 inches (15 cm) off the end of
the plenum or plenum module and aimed down the
length of the plenum. See Figure 3-7.
w
i H
/ X v BANK
12 FT.
i (3.7m) i
MAX_
12 FT.
(3.7m)
MAX.
to6 1 SINGLE BANK
`� s
;0.0 Figure 3-7.
Model N-1 HP
Plenum Nozzle Placement and Aiming
Note: These examples are typical and do not represent
every acceptable nozzle configuration, only a
representative sample of them.
Designer Note
For plenums that exceed 12 feet (3.7 m) in length
and therefore require multiple nozzles, it is
recommended that the total length be divided into
equally sized protection zones and protected
accordingly. So a 16 foot (4.9 m) long plenum
should be divided into two 8 foot (2.4 m) zones, with
a nozzle protecting each, as opposed to a 12 foal
(3.7 m) zone and a 4 foot (1.2 m) zone_
SPN: BFR-TM
Chapter 3 — System Design
Page 3 - 3
Revision 4
APPLIANCE PROTECTION
Each different appliance must be protected in a specific
manner with regard to nozzle selection, placement, and
aiming. No deviations from these parameters are
allowed and failure to comply completely with these
requirements will void the UL Listing of the system and
may render the system ineffective.
In order to property understand this section, several key
terms need to be defined in advance.
DESIGN TERMINOLOGY
Nozzle Height: The distance from the tip of the
discharge nozzle to the top surface of the appliance
(except for woks, in which case the bottom of the wok is
used).
Hazard Area: All nozzle coverages include the
maximum. size of the hazard area they can protect.
Hazard area is NOT the overall size of the appliance
being protected, but rather the actual size of the
portion of the appliance used for cooking.
Appliances Requiring Multiple Nozzles
Some appliances may need to be protected by multiple
nozzles because of their size. If the size of an
appliance is larger than the approved coverage for that
appliance, multiple nozzles must be used. This is
accomplished by dividing the hazard area into individual
zones that comply with the parameters of the listing for
that appliance_ In this case, each zone will be protected
as an individual appliance with respect to nozzle
placement and aiming.
RANGE PROTECTION
Two (2) Burner Ranee — LOW Proximi
Nozzle:
N-11-13 (1 Flow Point)
Coverage:
12" (30.5 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht:
16" (41 cm) — 30" (76 cm)
Placement:
3" (7.6 cm) from either edge of appliance,
on appliance's long centerline.
Aim point:
6" (15 cm) from opposite edge of
appliance, on appliance's long centerline.
The Model N-1 LP nozzle is a one (1) flow point nozzle
that can protect a range cooking area of 12" (30.5 cm)
wide by 24" (61 cm) deep. The nozzle must be located
tia (41 cm) to 3T (75 cm) above Me cooking surface
and positioned on the appliance's tong centerline within
ULEX 6885 ULC-EX 5885
January 1, 2011
Buckeve KITCHEN MISTER Coverage Summary Sheet
This summary sheet is provided as a quick reference, a complete understanding of the technical manual (BFR-TM) is required. The most current
Buckeye Kdrhen MlWter Restaurant Cooking Area Fire Suppression System Technical Manual (Part Number BFR-TM) supersedes MIS reference sheet
It is essential that this reference sheet be compared with the currem technical manual before using -
DUCT, SMALL (50" MAXIMUM PERIMETER) I DUCT LARGE (150" MAXIMUM PERIMETER)
NOZZLE: NALP I NOZZLE- N-2W
FLOW PTS.: 1 _ j FLOW PTA.: 2 1
COLOR BAND: RED � � COLOR BAND: WHITE // p
D 4T-1fZ
DUCT I NOZZLE TIP %t6 MA)k DUCT NOZZLE TIP �t
y
r-si T {r{ S - o- p• � �
1j
12W
NOZZLE TIP {1 t�� trz W w ti NOZZLE TIP t �{ —! Now y w
i TIP TIP
y-- L
f
'N~ L —� I '; LONGEST SIDE ST
HOOOtPLEP1UM LONGEST SIDE:1&3!4' HOOD/PLENUM
PLENUM, SINGLE 8 ,_ _ N�. -1r3H RANGE, TWO BURNER (LOW PROXIM"
"V' BANK �` 112W '"- i 1 NOZZLE: N-1LP
4 FT MAX 1 FLOW PTS.: 1
AIM: 6" FROM
NOZZLE N-1 HP + COLOR BANG: RED OPPOSITE EDGE,
FLOW PTS-: 1 H MAX. HEIGHT 30" ON LONG
COLOR BAND' BLUE T CENTER
V BANK CAN BE USED WITH MIN_ HEIGHT 16" LINE
12 Fr. --1f3H BACK -SHELF. SHELF6"
MAX_ MUST NOT INTEFERE
t WITH NOZZI E DISCHARGE MAX. HAZARD
12 FT. MAX. H 1 2 MAX. HAZARD WIDTH: 24'
LENGTH:12'
,p6 SINGLE BANK PLACEMENT: 3'FROM FRONT OR
Is BACK EDGE, ON LONG CENTER LINE
RANGE, FOUR BURNER I RANGE, FOUR BURNER, PLACEMENT:
(HIGH PROXIMITY) PLACEMENT: (LOW PROXIMITY) CENTER OF RANGE
MAX. HEIGHT 40" WITHIN 3"OF i MAX HEIGN.T 30'
NOZ21-E: NALP CENTER NOZZLE N-2W
FLOW PTS.: 1 MIN, HEIGHT 30' 1. FLOW PTS.: 2 —MIN. HEIGHT te"
COLOR BAND: RED i COLOR BAND: wHrrE
AIM-E CENTR
AfM:
t CENTER OF OF RANGE
RANGE CAN BE USED WITH (
BACK -SHELF. SHELF I
! MUST NOT WTEFERE
Wrr H NOZZLE
BURNER 70 BURNER \ BURNER TO DISCHARGE BURNERTO BURNER TO
LENGTH: 247 BURNER BURNER BURNER
WIDTH: 24' LENGTH:24" WIDTH: 24'
t
RANGE, SIX BURNER 1v PLACEMENT: CENTER OF RANGE RANGE/GRIDDLE COMBINATION
NOZZLE: N-2LP j—MAX. HEIGHT 43" NOZZLE NALP MAX. HEIGHT 40" PLACEMENT:
FLOW PTS.: 2 fftttt MIN. HEIGHT 35' FLOW PTS_: 1 WITHIN 3" OF
COLOR BAND: YELLOW COLOR BAND: RED MIN_ HEIGHT 30' CENTER
AIM: AIM: CENTER OF
NGE-GRIDDLE
CENTER OF RANGE
I 0 0
Q MAX.12'
BURNER TO BURL R MAX Mom'
Q BURNERTO 24•
I_ENGTH:36" BURNER i MAX_ LENGTH: 30'
i WIDTH: 24" j
DEEP FAT FRYER, LG. SINGLE VAT TILTING SKILLET COVER+MUST NOT iNTEFERE I
PLACEMENT: WITHIN WITH N0771 : DISCHARGE
j` NOZZLE: N-2HP THE PERIMETER OF THE �' NOZZLE N-2HP i.
FLOW PTS.: 2 HAZARD i FLOW PTS--2
COLOR BAND: GREEN `a . g _� COLOR BAND: GREEN j
7 R '
I . MAX. HEIGHT 46*
!: FOR MIN_ & MAK
MIN. HEIGHT 24 NOZZLE HEIGHTS. 1
REFER TO FRYER '
AIM: CENTER' / NOZZLE
J OF HAZARD 1
I PARAMETERS
AREA I /
Nate:
° Total hazard MAX_ WIDTH: 24'
area can not MAX. LENGTH: 2026' II
exceed 864 W .
BPN: PIS10374 REV. DATE
Decemeber 1, 2009
Buckeye KITCHEN MISTER Coverage Summary Sheet
This summary sheet is provided as a quick reference, a Complete understanding of the technical manual (BFR-TM) is required- The most current
Buckeye Kitchen Mister Restaurant Cooking Area Fire Suppression System Technical Manual (Part dumber: BFR-TM) supersedes this reference sheet.
It is essential that this reference sheet be compared With the current technical manual before using.
NOZZLE: N-`LP
FLOW PTS.: I
COLOR BAND: RED
i
AIM: 6' FROM CENTER 1
OF HAZARD AREA, `
INLINE WITH NOZZLE
MAX. LENGTH:
GRIDDLE, X4_4 RGE (60"
NOZZLE: N-2LP
FLOW Fri S.; 2
COLOR BAND: YELLOW
AIM: 8" FROM CENTER
OF HAZARD AREA
INLINE WITH NOZZLE
MAX.
LAVA ROCK CHARBROILER
NOZZLE: N-2HP
I_
FLOW ITS.: 2
IJ COLOR BAND: GREEN
1
AIM: CENTER OF
44j{j HAZARD AREA
t
NIAX_ LrNC;:H: 2@
GRIDDLE, LARGE (48" MAX.)
NOZZLE: NALP
PLACEMENT: ON THE FLOW PTS.: t PLACEMENT: 5" OFF
PERIMETER OF THE HAZARD COLOR BAND: RED GRIDDLE EDGE. ON LONG
CENTER LINE
AIM: 3' FROM
—MAX. HEIGHT 48' t MAX. HEIGHT 43" ���ENHTERIN LINE
—MIN- HEIGHT 24" OZZLE
M1N- HEIGHT 30'
WIDTH:
30"
MAX. WIDTH: 30'
LENGTH: 48"
\
RADIANT CHARBROILER PLACEMENT- WITHIN THE
PLACEMENT: ON THE t
\
NOZZLE: N-1HP PERIMETER OF THE HAZARD
PERIMETER OF THE ;-IAZARP
I
FLOW PTS-: 1
COLOR BAND BLUE �
MAX. HEIGHT 4S"
— MIN. HEIGHT 330"
AIM: CENTER OF
IN HEIGHT 24' I
HAZARD AREA
t is
8'
�.
MAX. WIDTH_ 24'
MAX. JriD.H: 30„ ',
MAX. LENGTH: 36"
BROILER AND UPRIGHT BROILER
PLACEMENT: WITHIN THE ..
N077r E NALP
PERIMETER OF THE HAZARD
FLOW PTS.: 1
AIM: CENTER
COLOR BAND: RED L�
OF COOKING
— MAX. HEIGHT 4O'
GRATE
— MIN_ HEIGHT 24'
PLACEMENT:
TOP
CORNER OF
FRONT
OPENING
MAX- LENGTH: 36"
MAX. WIDTH: 24' (
}
MAX. W I ft. 2��
NOZZLE; N-1 FiP AM: AT CENTER OF
FLOW PTS.: 1 WOK BOTTOM
COLOR BAND BLUE
MAX. WOK DIA_ 30'_
MIN. WOK DIA.: 12'
HEIGHT 48'
HEIGHT 30"
PLACEMENT.
WfrHiN THE
PERIMETER OF THE
HAZARD
Piping Limitations:
> aw x 12• Sch. a0 bfa4 Pps. > V,.-x. numb-r r eIb, s bet— any 2 wales: 3.
> Pipe --d l 9.W, 9 SmaB2 — .!q > :1�C vC C� ri5C' tQ f22t
i > st-1w sL1 Irat: amino euc sd. `tc:ry�tes
f oek a wk i
I I
MAXIPAI IM PtPINC PFR C-LINDER SIZE
1 UYLINGER
SIZE
MAX FLOW
POIN v S
MAX PIPE VOLT WE
OWED trti)
MAX_ PIPE VOL BE-W--- f
ANY �IYO NOZ ES :mti
MAX 4 OF
r790VY5
BFRo
5
ism
low
2C
t 8FR-t0
10
25M
2M
25
SFR-15
15
28W
2600
25
! BFR-20
20
2800'
25M
25
?aetp volume of 3IS' ?'P#15 �baM Ls 250D mL
CONDUIT AND BUCKEYE SHIELDED CABLE!,'BM LIMITATIONS
=L;NCT:ON
MAX
ONDUIT I-7Tt,SENDS
iq
CSSC
!n.AX1M[SM
NUMBER OF
IN TIE
(MN.
6@1D RRDfUS)
BSC TO
CONDUIT
TRANSITIONS
(MMSER OF
BSCI)
MAXIMUM
NUMBER OF
FUSIBLE
UNJKS A.ND
HOLDERS
FUSIBLE LINK UNIT_ CONDUIT& BSC
25
6 9
6
1D
GAS VALVE L INF: CONDUIT & BSC
25
5 (!n
6
NA
RPS-M UNE; CONDUIT & BSC
Z5
6(9")
6
NA
FttSIBLE LINK LINE: CONDUIT ONNLY
150
NA
NA
1 20
GAS VALVE LINE' CONDUrr ONLY
150
35
1 NA
NA
NA
NA
IS-M LINE: CONDUIT ONLY
i50
35
NA
NA
NA
NA
FUSIBLE LINK LINE: 3SC ONLY
NA
NA
35
6 g
o
10
GAS VALVE LINE; BBC ONLY
NA
RPS-M LINE: 89C ONLY
NA
NA
35
I 6 (9-)
1 6
NA
> BBC CAN NOT be cmW a MPP� —In —In
BPN: PIS10374
PIPE SrZE (SCti 40) PIPE VOLUr
3IS 37 a mUF7
t.2r 59Z irk FT
Minimum PipkV Requirements (Wok. Range. & DFF only):
�> &fsr. Oaf etbews before Doses: nctile• 5.
> GtiI. pipe volume bek— dosed n ,W 36D mL
T.W.yseem aroe vok,mz sw m
> Fdenawm nwr4w of IleY oc s;Is m system. 3
mpunTF rYI iNRFR Ac-nNATION LIMITATIONS I
NUMBER OF
MAX. LENGTH
NWS. L=NG`1'I
ACTUATION
GYLMIOER(5)
OF !WOO
OF TUBING
CARTRIDGE
PART NUMBER
THAT CAN BE
COPPER
BETWEEN
ACTUATED
-USING
CYLINDERS
i BFR-ADS
1-3
15 FEET
3 FEET
BFR-AC-L
1-5
25 FEET
3 FEET i
REV -DATE
December 1, 2009