FIR2021-0016+plans+5.24.2021_5.53 (2)BUCKEYE KITCHEN MISTER BRF-15 WET CHEMICAL FIRE SUPPRESSION SYSTEM Nozzles/ Part No. Nl, N2 N-1LP N3, N4 N-lHP N5, N6 N-2HP N7 N-1LP N8 N-lHP N9, N10 N-2LP Nozzles heights: 40" (from tip Of nozzle to top of appliance) ` Hood dimensions 11' x 3' Duct dimensions 12" x 12"` Agent cylinder BRF-10 ��` Duct 12"x 2" Duct 12"x 2" Agent line: ''/2" & 3/8" black pipe `� Hood 11'x 3' Hood 6'x 3' 8-Detector/fusible links: 450°F ` Total flow points: 14 ` Total agent flow points: 15 _ _ _ _ S'_ _ _ _ _ _ _ N 1 / - - - �- / - N Note: Fire alarm and electrical on TqZt separate permits. r-----------r------7-- ---------- i N5 + N6 + N8 + N9 + N10 N7 ALA It o4 005 0 000 Mechanical I 3 6 Gas valve Class "K' Manual Fire Extinguisher Pull Station Appliances: AKA Dimensions. Heights 79,,-5 & of Of)-M574ZZ,47'70Z5 LTC 1.- Fryer 16" x 19 Yz " 36" 2.-Fryer 16"x 19'/z" 36" Fire Suppression Systems(Service & Installation) 3.- Griddle 24" x 24 " 36 Kitchen Hood Installations 4.-Broiler 24"x24" 36" • Fire Extinguishers Complete Food Truck Builds 5.- 6 Burner Range 36" x 24" 36" 6.- 6 Burner Range 36"x24" 36" 14611 Ambaum Blvd SW Burien, WA 98166 206-617-4951 Chapter 2 — Components Page 2 - 1 Revision 4 Chapter 2 System Components Cylinder sizes The Buckeye Fire Equipment Kitchen Mister Fire Suppression System has available four (4) cylinder sizes, the Model BFR-5 (5 flow points), Model BFR-10 (10 flow points), Model 13FR-15 (15 flow points), and Model BFR-20 (20 flow points). Cylinder sizes are based on the flow point capacity of the cylinder, for example, the BFR-5 is capable of supporting a maximum of five (5) flow points. All cylinders are manufactured, marked, and tested in accordance with DOT 4BW240. Each cylinder is shipped pre -filled with extinguishing agent, and charged with dry nitrogen to a pressure of 195 psig (1344 KPa) @ 70° F (21° C). Cylinder and valve assembly dimensions are shown in Figure 2-1. (Vote: Cylinders shall always be stored in an upright position. Figure 2-1. Cylinder and Valve Assembly Dimensions. Model Number A inches (cm) B inches (cm) C inches (cm) D inches (cm) Max. Flow Points Weight lbs. (kg) Mounting Bracket BFR-5 24.8 (63) 16.2 (41) 10 (25) 13.4 (34) 5 421bs. (19) MS-1 BFR-10 34.4 (87) 25.8 (66) 10 (25) 23 (68) 10 74 lbs. (33) MB-2 BFR-15 44.$ (114) 36.2 (92) 10 (25) 33.4 (85) 15 107Ibs_ (48) PA&2 BFR-20 42.4 (108) 33.8 (86) 12 (31) 31 (79) 20 130 Ibs. (60) MB-2 BPN: BFR-TM ULEX 5885 ULC-EX 6885 January 1, 2011 0 Systems Releasing Module - SRM The Model SRM Systems Releasing Module is a fully mechanical control head that can be connected dimctly or remotely to the system valve and is required for system actuation. The Systems Releasing Module will support the following system inputs and outputs: • One Fusible Link Detection Line • One Gas Valve Line • One Remote Pull Station Line Two windows in the front cover of the Model SRM allow for visual verification of the actuation cartridge presence and the status of the puncture pin mechanism. See Figure 2-5. a o Bd�KLYE L K n I iSET•�"01 +0 FIRED, ACTUATION LEVER AN \ACTUATION CARTRIDGE PUNCTURE PIN VIEWING VIEWING WINDOW WINDOW Figure 2-5. Model SRM, Systems Releasing Module The Model SRM can actuate a maximum of. three (3) agent cylinders when using the Model BFR-AC-S Nitrogen Activation Cartridge (included with SRM and SRM-D) or five (5) agent cylinders when a Model BFR- AC-L Nitrogen Activation Cartridge is installed. Systems Releasing Module - SRM-D The Model SRM-D (Systems Releasing Module _Dual) is exactly the same as the Model SRM except that it supports a second independent fusible link detection line. Nitrogen Actuation Cartridges The iQtchen Mister System can use two types of actuation cartridges for system actuation. BPN: BFR-TM Chapter 2 — Components Page 2 - 3 Revision 4 Model 13FR-AC-S is a small nitrogen cartridge (included with System Releasing Module) that can actuate up to three (3) agent cylinders. Model BFR-AC-L is a larger nitrogen cartridge that can actuate up to five agent cylinder (refer to Chapter 4 of this manual for limitations). See Figure 2-6. I _ 5.12 (13 cm) 01.57 (4 cm) " �___— - Model BFR-AC-L 3.70 i (9.4 cm) ` i i JuLads sae s`(2.5 cm) zS3 Model BFR-AC-S Figure 2-6. Model BFR-AC-S and BFR-AC-L, Nitrogen Actuation Cartridges Mounting Brackets The Model MB-1 Mounting Bracket is used to mount the Model BFR-5 cylinder. See Figure 2-7. Figure 2-7. Model MB-1, Shown With 13FR-5 Cylinder The Model MB-2 Mounting Bracket is used to mount the Model BFR-10, Model BFR-1S, or Model BFR-20 cylinders. See Figure 2-8. ULEX 6$8 r ULC-EX 6885 January 1, 2011 W Chapter 2 — Components Page 2 - 4 Revision 4 Figure 2-8. Model M8-2, Shown With SFR-20 Cylinder Remote Mechanical Pull Station The Model RPS-M Remote Mechanical Pull Station provides remote mechanical actuation of the Systems Releasing Module. It is connected to the Systems Releasing Module with: • 1t16" (0.16 cm) stainless steel cable enclosed in 1/2" (1.3 cm) EMT conduit with a comer pulley at each change of direction. • Buckeye Shielded Cable which does not require a comer pulley at each change of direction or conduit. • A combination of both. A remote pull station is required at the point of egress from the hazard area being protected. See Figure 2-9. TTOF � O� N CAS FIRE { PULL HANDLE HARD i o C FIRE SU SYSMI Figure 2-9. Model RPS-M, Remote Mechanical Pull Station ULEX 6885 ULC-EX 6885 January 1, 2011 Mechanical Gas Shutoff Valves A gas shutoff valve is required for all systems protecting gas fueled appliances. A mechanical means of stopping gas flow is provided by the Models BFGV-75 / 10o / 125 / 150 / 200 / 250 / 300 Gas Shutoff Valves. it is connected to the Systems Releasing Module with: • 1/16" (0.16 cm) stainless steel cable enclosed in 1/2" (1.3 cm) EMT conduit with a comer pulley at each change of direction. • Buckeye Shielded Cable which does not require a comer pulley at each change of direction or conduit. A combination of both. The valves are rated for natural or LP gas (see Figure 2- 10) and are available in the following sizes: Model Number Valve Size In (cm) Maximum Operating Pressure BFGV-75 3/ (1.9) 5 psi (A bar) BFGV-100 1(2.5) 5 psi A bar BFGV-125 1 %. 3.2 5 psi (_4 bar) BFGV-150 1 Yz 3.8 5 Esi A bar) BFGV-200 2(5.1) 5 psi (A bar) BFGV-250 2 % 6.4 5 psi A bar BFGV-300 3 7.6 5 psi A bar) Note: Gas valve size must be no smaller than the size of the gas line it is connected to. Figure 2-10_ Model BFGV-XXX, Mechanical Gas Valve 0 Fusible Link Bracket Flit The Model FLB-1 Fusible Link Bracket kit (see Figure 2- 11) includes the following: • Standard high profile 10" (25 cm) fusible link bracket. • Two (2) W (1.3 cm) EMT connectors. • Two (2) cable crimps. • Two (2) "S" hooks. Note: Fusible links must be ordered separately. !- FUSIBLE LINK BRACKET i -S- HOOK 112- (1.3 cm) EAd \\ CONNECTOR CABLE CRIMP Figure 2-11. Model FLB-1, 10" (25 cm) Fusible Link Bracket Assembly Fusible Link Holder The Model FLH Fusible Link Holder is designed to allow for the use of a continuous fusible link line, thus eliminating the need to cut and crimp each individual fusible link. They can be used either with or without fusible link brackets. They are available in packages of 25 (Model FLH-25)_ See Figure 2A2. 111r 10_15 cm) STAINLESS DETECTION CABLE �Ubju e u KimL. STYLE) Figure 2-12. Model FLH, Fusible Link Holder Fusible Links ISLE The Kitchen Mister System uses Globe ML Fusible Links for automatic system activation. See Figure 2-13. Fusible links are designed to separate at specific temperatures: releasing tension from the fusible link Chapter 2 — Components Page 2 - 5 Revision 4 detection tine and causing system actuation_ Correct fusible link selection is an essential element in the design of any restaurant fire suppression system. After performing a temperature study to determine the maximum ambient temperature at the fusible link location, the correct fusible link should be selected from the following chart: Fusible Link Model Number Max. Ambient Temperature FL-280 2250 F. (1or C.) FL-360 300° F. (149° C.) FL-450 3750 F. (1910 C., FL-500 4300 F. (2210 C.) Figure 2-13. Globe ML Fusible Link Buckeye Shielded Cable As an alternative to using conduit and comer pulleys to connect the fusible link system, gas valve, and/or remote pull station to the Systems Releasing Module, the Kitchen Mister System utilizes Buckeye Shielded Cable to perform this function_ Buckeye Shielded Cable is 1/16" (0.16 cm) stainless steel cable encased in a protective, flexible conduit. See Figure 2-14. Buckeye Shielded Cable requires no conduit or corner pulleys, as the name implies, provided it is installed in accordance with the guidelines set forth in this manual. Model SFR-SC-100 comes with 100 feet (30.5 m) of flexible conduit with 200 feet (61 m) of 1116" (0.16 cm) stainless steel cable inside it. auctEYE 1116-10. TAMLESS = S Figure 2-14. Model BFR-SC-100, Buckeye Shielded Cable BPN:. BFR-TM ULEX 6885 ULC-EX 6885 January 1, 2011 Chapter 2 — Components Page 2 - 5 Revision 4 Shielded Cable Interface The Model BFR-SCI Buckeye Shielded Cable Interface is required for connecting Buckeye Shielded Cable to any standard 1/2" (1.3 cm) EMT conduit connector or corner pulley. See Figure 2.15, Figure 2-15. Model BFR-SCI, Shielded Cable Interface Note: A 3/32" (0.2 cm) hex wrench is required to tighten the set screw. Compression Type Corner Pulley When Buckeye Shielded Cable IS NOT used to connect the fusible link system, gas valve, andlor remote pull station to the control head, a comer pulley is required whenever a change in stainless steel cable direction is necessary. The Model CPCT-1 comer pulley is equipped with a compression type fitting that connects to standard 1/2" (1.3 cm) EMT conduit. See Figure 2-16. Figure 2-16. Model CPCT-1, Compression Type Corner Pulley Discharge Nozzles Misting type discharge nozzles have been specifically developed for appliance, duct, and plenum applications. Each nozzle has a predetermined flow point value and comes equipped with a blow -off cap to protect the end orifice from blockage. Each nozzle is identified by the model number stamped on the nozzle body and has a unique color band for easy visual identification. See Figure 2-17. ULEX 6885 ULC-EX 6885 January 1, 2011 Model Number Flow Points and olor N-1HP 1 lue ;Red N-1 LP 1 N-2HP 2 een N-21-P 2 Yellow N-2W 2 White Note: Details on speck nozzle applications can found in the Design Section of this manual. i 3/ 16 (0.2 cm) U rEX. �- RETt i 1.50' f3.8 cr:) Figure 2-17. Discharge Nozzle Swivel Nozzle Adaptor The Model N-SA Swivel Adaptor can be used with discharge nozzle to facilitate the nozzle aiming proce They are chrome plated and allow for a 30' rotation the nozzle in any direction. See Figure 2-18. 30' ROTATION 318" (1.0 cm) NP T FEMALE THREAD 318" (1.0 cm) NPT MALE THREAD Figure 2"1$_ Model N-SA, Swivel Adaptor Chapter 3 — System Design { r Page 3 -1 Revision 4 Chapter 3 System Design OVERVIEW OF SYSTEM DESIGN side length of 12-1/2" (32 cm) (square) and 16-314" (43 cm) (rectangular) respectively. It can also protect a round duct with a maximum circumference of 50" (127 The following chapter will cover the proper design of the cm) (16" (41 cm) maximum diameter]. See Figure 3-1 Buckeye Fire Equipment Kitchen Mister Fire g 3-2. Suppression System. It is divided into three sections: Ducts -150" (381 cm) Maximum Perimeter 1. Nozzle Coverages and Placements 2. Piping Limitations Nozzle: N-2W (2 Flow Paint) 3, Detector Placement Design of the Kitchen Mister System must be in compliance with the parameters set forth in this manual and be performed by a factory trained, Authorized Buckeye Fire Equipment Dealer. Buckeye Fire Equipment is not responsible for systems installed or maintained by personnel that are not factory trained and Authorized. NOZZLE COVERAGE, PLACEMENT, AND AIMING This section will give detailed guidelines for determining nozzle type, positioning, and aim point for appliance, plenum, and duct protection_ Duct Protection It is not necessary to shut down or damper the exhaust fan for the system to function properly. It is recommended that the exhaust fan be left on during system discharge to help distribute the extinguishing agent throughout the ductwork. Ducts - 50" (127 cm) Maximum Perimeter Nozzle: N-11-P (1 Flow Point) Coverage: Unlimited length with: 50" (127 cm) Maximum Perimeter with a longest side of 16-3/4" (43 cm) for rectangular ducts and 12-1/2" (32 cm) for square ducts or 50" (127 cm) Maximum Circumference (maximum diameter of 16" (41 cm)) for round ducts. Placement: Centered in duct opening, from 1-6" (2-5- 15 cm) into the duct opening. Aim point: Center of duct. The Model N-1 LP nozzle is a one flow point nozzle that can protect a square or rectangular duct with a maximum 50" (127 cm) perimeter and a maximum one BPN; BFR-TM Coverage: Unlimited length with: 150" (381 cm) Maximum Perimeter with a longest side of 50" (127 cm) for rectangular ducts and 37-1/2" (95 cm) for square ducts or 150" (381 cm) Maximum Circumference [maximum diameter of 47-1/2" (121 cm)] for round ducts. Placement: Centered induct opening, from"" (0-15 cm) into the duct opening. Aim point: Center of duct_ AIM: CENTER OF 4OZZLE PLACEMENT: 1'- 6" (2.5-15 cm) 0 to 50" (o-127 cm), N-1 LP) 0" - 6" (0-15 cm) 0 to 1W (0-381 cm), N-2Wl INTO THE DUCT FOR DUCTS (VERTICAL OR HORIZONTAL) WITHOUT A TRANSITION AIM: CENTER OF i Due ENTRANCE TO HORIZONTAL DUCT . � NOZZLE PLACEMENT: (2.5-15 cm) (Per. 0 to 50" (0-127 cm), N-1 LP) 0'- 6" (0-15 cm) [Per. 0 to 150' (0-381 cm), N-2Wl L _ _ INTO THE DUCT TRANSITION FOR DUCTS WITH A VERTICAL TO HORIZONTAL TRANSITION Figure 3-1. Proper Duct Nozzle Placement :.ILEX 6885 ULC-EX 6885 January 1, 2011 Plenum Protection Nozzle: N-1 HP (1 Flow Point) Coverage: Length- 12 feet (3-7 m) max. Width: 4 feet (1.2 m) max. Placement: See Figure 3.7. Aim point: See Figure 3.7. The Model N-1HP nozzle is a one (1) flow point nozzle that can protect a plenum (either single bank or V-bank) of 12 feet (3.7 m) in length and 4 feet (1.2 m) in width per nozzle. Larger plenums must be divided into 12 foot (3.7 m) sections, with each section protected with a separate nozzle. See Figure 3-7. Plenum: V-bank Nozzle Placement The nozzle must be located at the center of the V-bank width and down 1/3 of the vertical height, within 6 inches (15 cm) of the end of the plenum or plenum module and aimed down the length of the plenum. See Figure 3-7. Plenum: Single Filter Bank Nozzle Placement The nozzle must be located at a point that is 2" (5.1 cm) from the back edge of the filter and 113 of the vertical height of the filter, within 6 inches (15 cm) off the end of the plenum or plenum module and aimed down the length of the plenum. See Figure 3-7. w i H / X v BANK 12 FT. i (3.7m) i MAX_ 12 FT. (3.7m) MAX. to6 1 SINGLE BANK `� s ;0.0 Figure 3-7. Model N-1 HP Plenum Nozzle Placement and Aiming Note: These examples are typical and do not represent every acceptable nozzle configuration, only a representative sample of them. Designer Note For plenums that exceed 12 feet (3.7 m) in length and therefore require multiple nozzles, it is recommended that the total length be divided into equally sized protection zones and protected accordingly. So a 16 foot (4.9 m) long plenum should be divided into two 8 foot (2.4 m) zones, with a nozzle protecting each, as opposed to a 12 foal (3.7 m) zone and a 4 foot (1.2 m) zone_ SPN: BFR-TM Chapter 3 — System Design Page 3 - 3 Revision 4 APPLIANCE PROTECTION Each different appliance must be protected in a specific manner with regard to nozzle selection, placement, and aiming. No deviations from these parameters are allowed and failure to comply completely with these requirements will void the UL Listing of the system and may render the system ineffective. In order to property understand this section, several key terms need to be defined in advance. DESIGN TERMINOLOGY Nozzle Height: The distance from the tip of the discharge nozzle to the top surface of the appliance (except for woks, in which case the bottom of the wok is used). Hazard Area: All nozzle coverages include the maximum. size of the hazard area they can protect. Hazard area is NOT the overall size of the appliance being protected, but rather the actual size of the portion of the appliance used for cooking. Appliances Requiring Multiple Nozzles Some appliances may need to be protected by multiple nozzles because of their size. If the size of an appliance is larger than the approved coverage for that appliance, multiple nozzles must be used. This is accomplished by dividing the hazard area into individual zones that comply with the parameters of the listing for that appliance_ In this case, each zone will be protected as an individual appliance with respect to nozzle placement and aiming. RANGE PROTECTION Two (2) Burner Ranee — LOW Proximi Nozzle: N-11-13 (1 Flow Point) Coverage: 12" (30.5 cm) x 24" (61 cm) Maximum (measured burner edge to burner edge) Nozzle Ht: 16" (41 cm) — 30" (76 cm) Placement: 3" (7.6 cm) from either edge of appliance, on appliance's long centerline. Aim point: 6" (15 cm) from opposite edge of appliance, on appliance's long centerline. The Model N-1 LP nozzle is a one (1) flow point nozzle that can protect a range cooking area of 12" (30.5 cm) wide by 24" (61 cm) deep. The nozzle must be located tia (41 cm) to 3T (75 cm) above Me cooking surface and positioned on the appliance's tong centerline within ULEX 6885 ULC-EX 5885 January 1, 2011 Buckeve KITCHEN MISTER Coverage Summary Sheet This summary sheet is provided as a quick reference, a complete understanding of the technical manual (BFR-TM) is required. The most current Buckeye Kdrhen MlWter Restaurant Cooking Area Fire Suppression System Technical Manual (Part Number BFR-TM) supersedes MIS reference sheet It is essential that this reference sheet be compared with the currem technical manual before using - DUCT, SMALL (50" MAXIMUM PERIMETER) I DUCT LARGE (150" MAXIMUM PERIMETER) NOZZLE: NALP I NOZZLE- N-2W FLOW PTS.: 1 _ j FLOW PTA.: 2 1 COLOR BAND: RED � � COLOR BAND: WHITE // p D 4T-1fZ DUCT I NOZZLE TIP %t6 MA)k DUCT NOZZLE TIP �t y r-si T {r{ S - o- p• � � 1j 12W NOZZLE TIP {1 t�� trz W w ti NOZZLE TIP t �{ —! Now y w i TIP TIP y-- L f 'N~ L —� I '; LONGEST SIDE ST HOOOtPLEP1UM LONGEST SIDE:1&3!4' HOOD/PLENUM PLENUM, SINGLE 8 ,_ _ N�. -1r3H RANGE, TWO BURNER (LOW PROXIM" "V' BANK �` 112W '"- i 1 NOZZLE: N-1LP 4 FT MAX 1 FLOW PTS.: 1 AIM: 6" FROM NOZZLE N-1 HP + COLOR BANG: RED OPPOSITE EDGE, FLOW PTS-: 1 H MAX. HEIGHT 30" ON LONG COLOR BAND' BLUE T CENTER V BANK CAN BE USED WITH MIN_ HEIGHT 16" LINE 12 Fr. --1f3H BACK -SHELF. SHELF6" MAX_ MUST NOT INTEFERE t WITH NOZZI E DISCHARGE MAX. HAZARD 12 FT. MAX. H 1 2 MAX. HAZARD WIDTH: 24' LENGTH:12' ,p6 SINGLE BANK PLACEMENT: 3'FROM FRONT OR Is BACK EDGE, ON LONG CENTER LINE RANGE, FOUR BURNER I RANGE, FOUR BURNER, PLACEMENT: (HIGH PROXIMITY) PLACEMENT: (LOW PROXIMITY) CENTER OF RANGE MAX. HEIGHT 40" WITHIN 3"OF i MAX HEIGN.T 30' NOZ21-E: NALP CENTER NOZZLE N-2W FLOW PTS.: 1 MIN, HEIGHT 30' 1. FLOW PTS.: 2 —MIN. HEIGHT te" COLOR BAND: RED i COLOR BAND: wHrrE AIM-E CENTR AfM: t CENTER OF OF RANGE RANGE CAN BE USED WITH ( BACK -SHELF. SHELF I ! MUST NOT WTEFERE Wrr H NOZZLE BURNER 70 BURNER \ BURNER TO DISCHARGE BURNERTO BURNER TO LENGTH: 247 BURNER BURNER BURNER WIDTH: 24' LENGTH:24" WIDTH: 24' t RANGE, SIX BURNER 1v PLACEMENT: CENTER OF RANGE RANGE/GRIDDLE COMBINATION NOZZLE: N-2LP j—MAX. HEIGHT 43" NOZZLE NALP MAX. HEIGHT 40" PLACEMENT: FLOW PTS.: 2 fftttt MIN. HEIGHT 35' FLOW PTS_: 1 WITHIN 3" OF COLOR BAND: YELLOW COLOR BAND: RED MIN_ HEIGHT 30' CENTER AIM: AIM: CENTER OF NGE-GRIDDLE CENTER OF RANGE I 0 0 Q MAX.12' BURNER TO BURL R MAX Mom' Q BURNERTO 24• I_ENGTH:36" BURNER i MAX_ LENGTH: 30' i WIDTH: 24" j DEEP FAT FRYER, LG. SINGLE VAT TILTING SKILLET COVER+MUST NOT iNTEFERE I PLACEMENT: WITHIN WITH N0771 : DISCHARGE j` NOZZLE: N-2HP THE PERIMETER OF THE �' NOZZLE N-2HP i. FLOW PTS.: 2 HAZARD i FLOW PTS--2 COLOR BAND: GREEN `a . g _� COLOR BAND: GREEN j 7 R ' I . MAX. HEIGHT 46* !: FOR MIN_ & MAK MIN. HEIGHT 24 NOZZLE HEIGHTS. 1 REFER TO FRYER ' AIM: CENTER' / NOZZLE J OF HAZARD 1 I PARAMETERS AREA I / Nate: ° Total hazard MAX_ WIDTH: 24' area can not MAX. LENGTH: 2026' II exceed 864 W . BPN: PIS10374 REV. DATE Decemeber 1, 2009 Buckeye KITCHEN MISTER Coverage Summary Sheet This summary sheet is provided as a quick reference, a Complete understanding of the technical manual (BFR-TM) is required- The most current Buckeye Kitchen Mister Restaurant Cooking Area Fire Suppression System Technical Manual (Part dumber: BFR-TM) supersedes this reference sheet. It is essential that this reference sheet be compared With the current technical manual before using. NOZZLE: N-`LP FLOW PTS.: I COLOR BAND: RED i AIM: 6' FROM CENTER 1 OF HAZARD AREA, ` INLINE WITH NOZZLE MAX. LENGTH: GRIDDLE, X4_4 RGE (60" NOZZLE: N-2LP FLOW Fri S.; 2 COLOR BAND: YELLOW AIM: 8" FROM CENTER OF HAZARD AREA INLINE WITH NOZZLE MAX. LAVA ROCK CHARBROILER NOZZLE: N-2HP I_ FLOW ITS.: 2 IJ COLOR BAND: GREEN 1 AIM: CENTER OF 44j{j HAZARD AREA t NIAX_ LrNC;:H: 2@ GRIDDLE, LARGE (48" MAX.) NOZZLE: NALP PLACEMENT: ON THE FLOW PTS.: t PLACEMENT: 5" OFF PERIMETER OF THE HAZARD COLOR BAND: RED GRIDDLE EDGE. ON LONG CENTER LINE AIM: 3' FROM —MAX. HEIGHT 48' t MAX. HEIGHT 43" ���ENHTERIN LINE —MIN- HEIGHT 24" OZZLE M1N- HEIGHT 30' WIDTH: 30" MAX. WIDTH: 30' LENGTH: 48" \ RADIANT CHARBROILER PLACEMENT- WITHIN THE PLACEMENT: ON THE t \ NOZZLE: N-1HP PERIMETER OF THE HAZARD PERIMETER OF THE ;-IAZARP I FLOW PTS-: 1 COLOR BAND BLUE � MAX. HEIGHT 4S" — MIN. HEIGHT 330" AIM: CENTER OF IN HEIGHT 24' I HAZARD AREA t is 8' �. MAX. WIDTH_ 24' MAX. JriD.H: 30„ ', MAX. LENGTH: 36" BROILER AND UPRIGHT BROILER PLACEMENT: WITHIN THE .. N077r E NALP PERIMETER OF THE HAZARD FLOW PTS.: 1 AIM: CENTER COLOR BAND: RED L� OF COOKING — MAX. HEIGHT 4O' GRATE — MIN_ HEIGHT 24' PLACEMENT: TOP CORNER OF FRONT OPENING MAX- LENGTH: 36" MAX. WIDTH: 24' ( } MAX. W I ft. 2�� NOZZLE; N-1 FiP AM: AT CENTER OF FLOW PTS.: 1 WOK BOTTOM COLOR BAND BLUE MAX. WOK DIA_ 30'_ MIN. WOK DIA.: 12' HEIGHT 48' HEIGHT 30" PLACEMENT. WfrHiN THE PERIMETER OF THE HAZARD Piping Limitations: > aw x 12• Sch. a0 bfa4 Pps. > V,.-x. numb-r r eIb, s bet— any 2 wales: 3. > Pipe --d l 9.W, 9 SmaB2 — .!q > :1�C vC C� ri5C' tQ f22t i > st-1w sL1 Irat: amino euc sd. `tc:ry�tes f oek a wk i I I MAXIPAI IM PtPINC PFR C-LINDER SIZE 1 UYLINGER SIZE MAX FLOW POIN v S MAX PIPE VOLT WE OWED trti) MAX_ PIPE VOL BE-W--- f ANY �IYO NOZ ES :mti MAX 4 OF r790VY5 BFRo 5 ism low 2C t 8FR-t0 10 25M 2M 25 SFR-15 15 28W 2600 25 ! BFR-20 20 2800' 25M 25 ?aetp volume of 3IS' ?'P#15 �baM Ls 250D mL CONDUIT AND BUCKEYE SHIELDED CABLE!,'BM LIMITATIONS =L;NCT:ON MAX ONDUIT I-7Tt,SENDS iq CSSC !n.AX1M[SM NUMBER OF IN TIE (MN. 6@1D RRDfUS) BSC TO CONDUIT TRANSITIONS (MMSER OF BSCI) MAXIMUM NUMBER OF FUSIBLE UNJKS A.ND HOLDERS FUSIBLE LINK UNIT_ CONDUIT& BSC 25 6 9 6 1D GAS VALVE L INF: CONDUIT & BSC 25 5 (!n 6 NA RPS-M UNE; CONDUIT & BSC Z5 6(9") 6 NA FttSIBLE LINK LINE: CONDUIT ONNLY 150 NA NA 1 20 GAS VALVE LINE' CONDUrr ONLY 150 35 1 NA NA NA NA IS-M LINE: CONDUIT ONLY i50 35 NA NA NA NA FUSIBLE LINK LINE: 3SC ONLY NA NA 35 6 g o 10 GAS VALVE LINE; BBC ONLY NA RPS-M LINE: 89C ONLY NA NA 35 I 6 (9-) 1 6 NA > BBC CAN NOT be cmW a MPP� —In —In BPN: PIS10374 PIPE SrZE (SCti 40) PIPE VOLUr 3IS 37 a mUF7 t.2r 59Z irk FT Minimum PipkV Requirements (Wok. Range. & DFF only): �> &fsr. Oaf etbews before Doses: nctile• 5. > GtiI. pipe volume bek— dosed n ,W 36D mL T.W.yseem aroe vok,mz sw m > Fdenawm nwr4w of IleY oc s;Is m system. 3 mpunTF rYI iNRFR Ac-nNATION LIMITATIONS I NUMBER OF MAX. LENGTH NWS. L=NG`1'I ACTUATION GYLMIOER(5) OF !WOO OF TUBING CARTRIDGE PART NUMBER THAT CAN BE COPPER BETWEEN ACTUATED -USING CYLINDERS i BFR-ADS 1-3 15 FEET 3 FEET BFR-AC-L 1-5 25 FEET 3 FEET i REV -DATE December 1, 2009