REVIEWED BLD2021-0357+Structural_Analysis_or_Calculations+3.10.2021_9.21.52_AM+2084803RECEIVED
Mar11 2021
REVIEWED
BY
CITY OF EDMONDS
STRUCTURAL
CALCULATIONS
PROJECT: 99 RANCH MARKET
EDMONDS, WA
PROJECT No: SNL202026
CLIENT: SMITH CO.
DATE: March 9, 2021
SHEET INDEX
CALCULATIONS
These calculations are the sole property of WRIGHT ENGINEERS and may not be reproduced
in whole or part without written permission. Calculations are valid only for the above named
project and location and are not valid unless engineer's original wet signed seal is affixed.
RIGHT
e n g i n e e r s
103/09/2021
Las Vegas
1645 Village Center Cir
Suite 10
Las Vegas, NV 89134
(p) 702.933.7000
800.933.7611
Irvine
2 Venture
Suite 200
Irvine, CA 92618
(p) 949.477.4001
Phoenix
1759 E. Queen Creek Rd
Suite I
Chandler, AZ 85286
(p) 480.483.61 11
Salt Lake
9160 S. 300 W.
Suite 2
Sandy, UT 84070
(p) 801.352.2001
wrightengineers.com
Dro'ect Name: RIGHT
1 CFS calculations Page 1 of 1
Model: Joist (Keynote 1) Date: 03/09/2021
�ers
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 100.00
20.00 I b/ft
R 1 100.00
Shear and Web Crippling Checks
Bending and Shear 8.1 % Stressed
(Unstiffened): @R2
Bending and Shear NA
I;
R2
(Stiffened):
Web Stiffeners No
10.00
Required?:
Section : 60OS162-43 (33 ksi) Single C Stud
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb
1 = 2.32 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Deflection
Mmax Mmax/
Mpos
Bracing Ma(Brc)
Mpos/
Span Ft -Lb Maxo
Ft -Lb
(in) Ft -Lb
Ma(Brc) (in) Ratio
Span 250.0 0.180
250.0
None 496.6
0.503 0.066 L/1822
Distortional Buckling Check
Span K-phi Lm Brac
Ma-d
Mmax/
lb-in/in in
Ft -Lb
Ma-d
Span 0.00 120.0
1205.1
0.207
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 j [SHEET: 1
Project Name: CFS calculations KEYNOTE 3 BOTTOM
Model: Simply supported exterior beam bottom
Code: 2012 NASPEC [AISI S100-20121
50.00 I b/ft
R2
21.50
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Section : (2) 80OS200-54 (50 ksi) Boxed C Stud
Maxo = 7477.9 Ft -Lb Va = 4182.6 lb I = 13.15 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Mmax Mmax/ Mpos
Bracing Ma(Brc)
Span Ft -Lb Maxo Ft -Lb
(in) Ft -Lb
Span 2889.1 0.386 2889.1
24.0 7477.9
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
Reactions
Support Reactions (lb)
R2 537.50
R1 537.50
Shear and Web Crippling Checks
Bending and Shear 12.9% Stressed
(Unstiffened): @R1
Bending and Shear NA
(Stiffened):
Web Stiffeners No
Required?:
Mpos/ Deflection
Ma(Brc) (in) Ratio
0.386 0.620 L/416
www.strongtie.com
L: SNL202026 J [SHEET: 2
Project Name: CFS calculations KEYNOTE 4 BOTTOM
Model: Cantilever beam
Code: 2012 NASPEC [AISI S100-20121
P,
1
60.00lb/ft
10.00
�► X
Point Loads P1
60.00 lb/ft
R1 R2
23.50
Load(lb) 538
X-Dist.(ft) 0.00
Section : (2) 140OS200-68 (50 ksi) Boxed C Stud
Maxo = 17487.6 Ft- Va = 4729.2 lb I = 59.59 in14
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 348.62
R1 2198.88
Shear and Web Crippling Checks
Bending and Shear 53.6% Stressed
(Unstiffened): @R1
Bending and Shear NA
(Stiffened):
Web Stiffeners No
Required?:
Mmax
Mmax/
Mpos
Bracing
Ma(Brc)
Mpos/
Span Ft -Lb
Maxo
Ft -Lb
(in)
Ft -Lb
Ma(Brc)
Left Cantilever 8375.0
0.479
6209.8
24.0
17487.6
0.355
Span 8375.0
0.479
4030.9
24.0
17487.6
0.230
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
Deflection
(in) Ratio
0.576 L/417
0.082 L/3449
www.strongtie.com
No: SNL202026 J SHEET: 3
Dro'ect Name: KEYNOTE 5 BOTTOM R ICHT
1 CFS calculations Page 1 of 1
�ers
Model: Cantilever beam - 2 Date: 03/09/2021
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
P,
Reactions
11 Support Reactions (lb)
R2-1483.87
R1 4967.89
Shear and Web Crippling Checks
Bending and Shear 55.9% Stressed
(Unstiffened): @R1
a Bending and Shear NA
;1 I112 (Stiffened):
{ Web Stiffeners No
Required?:
k
Point Loads P1
Load(lb) 2199
X-Dist.(ft) 0.00
Section : (2) 160OS200-118 (50 ksi) Boxed C Stud
Maxo = 41572.7 Ft- Va = 22175.8 lb I = 148.17 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Deflection
Mmax
Mmax/
Mpos
Bracing
Ma(Brc)
Mpos/
Span
Ft -Lb
Maxo
Ft -Lb
(in)
Ft -Lb
Ma(Brc) (in) Ratio
Left Cantilever
22679.2
0.546
17715.8
24.0
41572.7
0.426 0.563 L/391
Span
22679.2
0.546
17397.7
24.0
41572.7
0.418 0.080 L/1847
SIMPSON STRONG -TIE COMPANY INC.
DROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 j [SHEET: 4
Dro'ect Name: RIGHT
1 CFS calculations KEYNOTE 6 BOTTOM Page 1 of 1
�ers
Model: Interior double beam Date: 03/09/2021
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 215.00
20.00 I b/ft
R 1 215.00
Shear and Web Crippling Checks
Bending and Shear 8.7% Stressed
(Unstiffened): @R2
Bending and Shear NA
R2
(Stiffened):
Web Stiffeners No
21.50
Required?:
Section : (2) 60OS200-43 (33 ksi) Back -To -Back C Stud
Maxo = 2873.9 Ft -Lb Va = 2831.3 lb
I = 5.37 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Deflection
Mmax Mmax/
Mpos
Bracing Ma(Brc)
Mpos/
Span Ft -Lb Maxo
Ft -Lb
(in) Ft -Lb
Ma(Brc) (in) Ratio
Span 1155.6 0.402
1155.6
11.8 2873.9
0.402 0.608 L/425
Distortional Buckling Check
Span K-phi Lm Brac
Ma-d
Mmax/
lb-in/in in
Ft -Lb
Ma-d
Span 0.00 258.0
2564.7
0.451
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 j [SHEET: 5
Project Name: CFS calculations KEYNOTE 2 TOP
Model: Top joist
Code: 2012 NASPEC [AISI S100-20121
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 22.47
R1 22.47
Shear and Web Crippling Checks
Bending and Shear 1.8% Stressed
(Unstiffened): @R1
Bending and Shear NA
I;
(Stiffened):
Web Stiffeners No
Required?:
Section : 60OS162-43 (33 ksi) Single C Stud
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb
1 = 2.32 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Deflection
Mmax Mmax/
Mpos
Bracing Ma(Brc)
Mpos/
Span Ft -Lb Maxo
Ft -Lb
(in) Ft -Lb
Ma(Brc) (in) Ratio
Span 120.8 0.087
120.8
Mid -Pt 496.2
0.243 0.147 L/1754
Distortional Buckling Check
Span K-phi Lm Brac
Ma-d
Mmax/
lb-in/in in
Ft -Lb
Ma-d
Span 0.00 258.0
1205.1
0.100
SIMPSON STRONG -TIE COMPANY INC.
DROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 J [SHEET: 6
Project Name: CFS calculations KEYNOTE 3 TOP
Model: SS exterior beam top
Code: 2012 NASPEC [AISI S100-20121
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 59.13
R1 59.13
Shear and Web Crippling Checks
Bending and Shear 4.8% Stressed
(Unstiffened): @R2
Bending and Shear NA
I;
(Stiffened):
Web Stiffeners No
Required?:
Section : 60OS162-43 (33 ksi) Single C Stud
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb
1 = 2.32 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Flexural and Deflection Check
Deflection
Mmax Mmax/
Mpos
Bracing Ma(Brc)
Mpos/
Span Ft -Lb Maxo
Ft -Lb
(in) Ft -Lb
Ma(Brc) (in) Ratio
Span 317.8 0.229
317.8
60.0 1113.5
0.285 0.387 L/667
Distortional Buckling Check
Span K-phi Lm Brac
Ma-d
Mmax/
lb-in/in in
Ft -Lb
Ma-d
Span 0.00 258.0
1205.1
0.264
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 J [SHEET: 7
Project Name: CFS calculations KEYNOTE 4 TOP
Model: Cantilever exterior top beam
Code: 2012 NASPEC [AISI S100-20121
P,
1
6.25 Ib/tt
10.00
�► X
Point Loads P1
b.25 Ib/ft
R1 R2
23.50
Load(lb) 60
X-Dist.(ft) 0.00
Section : 60OS200-43 (33 ksi) Single C Stud
Maxo = 1436.9 Ft -Lb Va = 1415.7 lb I = 2.68 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2 34.61
R1 234.77
Shear and Web Crippling Checks
Bending and Shear 64.3% Stressed
(Unstiffened): @R1
Bending and Shear NA
(Stiffened):
Web Stiffeners No
Required?:
Flexural and Deflection Check
Deflection
Mmax
Mmax/
Mpos
Bracing
Ma(Brc)
Mpos/
Span
Ft -Lb
Maxo
Ft -Lb
(in)
Ft -Lb
Ma(Brc) (in) Ratio
Left Cantilever
912.5
0.635
678.9
24.0
1436.9
0.472 1.430 L/168
Span
912.5
0.635
451.9
24.0
1436.9
0.315 0.216 L/1305
Distortional Buckling
Check
Span
K-phi
Lm Brac
Ma-d
Mmax/
lb-in/in
in
Ft -Lb
Ma-d
Left Cantilever
0.00
120.0
1282.4
0.712
Span
0.00
282.0
1282.4
0.712
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 J [SHEET: 8
Project Name: CFS calculations KEYNOTE 5 TOP
Model: Cantilever exterior top beam - 2
Code: 2012 NASPEC [AISI S100-20121
P,
i
5.50 Ib/ft
9.17
I i. X
Point Loads P1
> W i:. !t
R1 1112
I
1
Load(lb) 235
X-Dist.(ft) 0.00
Section : 80OS162-54 (50 ksi) Single C Stud
Maxo = 3065.9 Ft -Lb Va = 2091.3 lb I = 5.60 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Reactions
Support Reactions (lb)
R2-161.10
R1 513.91
Shear and Web Crippling Checks
Bending and Shear 79.0% Stressed
(Unstiffened): @R1
Bending and Shear NA
(Stiffened):
Web Stiffeners No
Required?:
Flexural and Deflection Check
Deflection
Mmax
Mmax/
Mpos
Bracing
Ma(Brc)
Mpos/
Span
Ft -Lb
Maxo
Ft -Lb
(in)
Ft -Lb
Ma(Brc) (in) Ratio
Left Cantilever
2386.2
0.778
1869.4
24.0
3065.9
0.610 1.577 L/140
Span
2386.2
0.778
1840.3
24.0
3065.9
0.600 0.224 L/656
Distortional Buckling
Check
Span
K-phi
Lm Brac
Ma-d
Mmax/
lb-in/in
in
Ft -Lb
Ma-d
Left Cantilever
0.00
110.0
2734.3
0.873
Span
0.00
147.0
2734.3
0.873
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 J [SHEET: 9
Project Name: CFS calculations
Model: Wall stud
Code: 2012 NASPEC [AISI S100-20121
Simpson Strong -Tie® Connectors
Support Rx(lb) Ry(lb)
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Section : 60OS162-43 (33 ksi) Single C Stud
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb I = 2.32 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Bridginq Connectors - Design Method = AISI S100
Simpson Strong -Tie
Span/Cantilever Bridging Connector Stress Ratio
Span LSUBH3.25 (Min) 0.18
Shear and Web Crippling Checks
Bending and Shear (Unstiffened): 3.6% Stressed @R2
Bending and Shear (Stiffened): NA
Web Stiffeners Required?: No
Connector Anchor
Simpson Strong -Tie® Connector Interaction Interaction
R2 45 0 SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 7.38 %
R1 45 305 FCB43.5 Min(4#12-14) & (2) #12-24 SST X or XL to A36 31.85 %
Steel
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check
Mmax
Mmax/
Mpos
Span
Ft -Lb
Maxo
Ft -Lb
Span
101.2
0.073
101.2
Distortional Buckling
Check
Span
K-phi
Lm Brac
Ma-d
lb-in/in
in
Ft -Lb
Span
0.00
108.0
1205.1
Combined Bending
and Axial Load Details
Axial Ld
Bracing(in)
Span
(lb)
KyLy
KtLt
Span
305.0(c)
48.0
48.0
SIMPSON STRONG -TIE COMPANY INC.
'ROJECT: 99 RANCH MARKET
4.04 %
52.84 %
Bracing Ma(Brc) Mpos/ Deflection
(in) Ft -Lb Ma(Brc) (in) Ratio
48.0 1223.2 0.083 0.022 L/4998
Mmax/
Ma-d
0.084
Max K-phi Lm Bracing Allow Intr.
KL/r (lb-in/in) (in) load(lb) P/Pa Value
83 0.0 108.0 3522.2(c) 0.09 0.17
www.strongtie.com
No: SNL202026 SHEET: 11
Project Name: CFS calculations
Model: Hanging studs
Code: 2012 NASPEC [AISI S100-20121
)"
Simpson Strong -Tie® Connectors
Support Rx(lb) Ry(lb)
RIF!G1 of 1T
ge H
e r s
Date: 03/09/2021
Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Section : 60OS162-43 (33 ksi) Single C Stud
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb I = 2.32 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Bridginq Connectors - Design Method = AISI S100
Simpson Strong -Tie
Span/Cantilever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear (Unstiffened): 1.2% Stressed @R1
Bending and Shear (Stiffened): NA
Web Stiffeners Required?: No
Connector Anchor
Simpson Strong -Tie® Connector Interaction Interaction
R2 15 0 SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 2.46 %
R1 15 220 FCB43.5 Min(4#12-14) & (2) #12-24 SST X or XL to A36 21.18 %
Steel
* Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check
Mmax
Mmax/
Mpos
Span
Ft -Lb
Maxo
Ft -Lb
Span
11.3
0.008
11.3
Distortional Buckling
Check
Span
K-phi
Lm Brac
Ma-d
lb-in/in
in
Ft -Lb
Span
0.00
36.0
1205.1
Combined Bending
and Axial Load Details
Axial Ld
Bracing(in)
Span
(lb)
KyLy
KtLt
Span
220.0(c)
None
None
SIMPSON STRONG -TIE COMPANY INC.
'ROJECT: 99 RANCH MARKET
1.35 %
36.55 %
Bracing Ma(Brc) Mpos/ Deflection
(in) Ft -Lb Ma(Brc) (in) Ratio
None 1271.1 0.009 0.000 L/134945
Mmax/
Ma-d
0.009
Max K-phi Lm Bracing Allow Intr.
KL/r (lb-in/in) (in) load(lb) P/Pa Value
62 0.0 36.0 3991.9(c) 0.06 0.06
www.strongtie.com
No: SNL202026 SHEET: 12
Dro'ect Name: RIGHT
1 CFS calculations Page 1 of 1
�ers
Model: Trimmer -double Date:03/09/2021
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Section : (2) 60OS162-43 (33 ksi) @ 24" o.c. Back -To -Back C Stud (punc
Maxo = 2779.9 Ft -Lb Va = 2831.3 lb I = 4.63 in^4
Loads have not been modified for strength checks
Loads have not been modified for deflection calculations
Bridgincl Connectors - Design Method =AISI S100
Axial Flexual, Stress
Span KyLy, KtLt Distortional Connector Ratio
Span 48.0", None 48.0", 108.0" N/A -
Web Cripplina
Support Load (lb)
R2
45.0
R1
45.0
Gravity
Load
Type
Load (lb)
Bearing Pa M
(in) (lb) (ft-Ibs) Max Int. Stiffener?
--Shear Connection w/ clip-- NO
--Shear Connection w/ clip-- NO
Uniform 0.00plf
Ply 45661b @ 9ft
*A
Code Check Required Allowed Interaction Notes
Span Max. Axial, Ibs
Max. Shear, Ibs
Max. Moment (MaFy, Ma-dist), ft-Ibs
Moment Stability, ft-Ibs
Shear/Moment
Axial/Moment
Deflection Span, in
4566.0(c)
7626.7(c)
60%
KO=O.00Ib-in/in
45.0
2480.6
2%
Shear (Punched)
101.2
2410.3
4%
Ma-dist (control),KO=0.00 lb-in/in
101.2
2542.3
4%
0.04
1.00
4%
Shear 0.0, Moment 101.2
0.64
1.00
64%
Axial 4566.0(c), Moment 101.2
0.011
--meets L/9996--
Connector Anchor
Support Rx(lb) Ry(lb) Simpson Strong -Tie Connector Interaction Interaction
R2 45.0 0.0 SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 7.38 % 4.04 %
Rl 45.0 4566.0 600T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to 5.49 % 20.44 %
steel (3/16" to 1/2" thickness)
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
No: SNL202026 j SHEET: 13
Dro'ect Name: RIGHT
1 CFS calculations Page 1 of 1
�ers
Model: Trimmer Date:03/09/2021
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong -Tie® CFS DesignerTA° 3.4.4.0
Section : 60OS162-43 (33 ksi) @ 16" o.c. Single C Stud (punched)
Maxo = 1390.0 Ft -Lb Va = 1415.7 lb I = 2.32 in^4
Loads have not been modified for strength checks
Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors - Design Method =AISI S100
Axial Flexual, Stress
Span KyLy, KtLt Distortional Connector Ratio
Span 48.0", 48.0" 48.0", 120.0" LSUBH3.25 (Min) 0.51
Web Cripplina
Support Load (lb)
R2
133.3
R1
133.3
Gravity
Load
Type
Load (lb)
Bearing Pa M
(in) (lb) (ft-Ibs) Max Int. Stiffener?
--Shear Connection w/ clip-- NO
--Shear Connection w/ clip-- NO
Uniform 0.00plf
Ply 12881b @ 9ft
*A
Code Check Required Allowed Interaction Notes
Span Max. Axial, Ibs
Max. Shear, Ibs
Max. Moment (MaFy, Ma-dist), ft-Ibs
Moment Stability, ft-Ibs
Shear/Moment
Axial/Moment
Deflection Span, in
1288.0(c)
3522.2(c)
37%
KO=O.00Ib-in/in
133.3
1240.3
11 %
Shear (Punched)
333.3
1205.1
28%
Ma-dist (control),KO=0.00 lb-in/in
333.3
1222.3
27%
0.24
1.00
24%
Shear 0.0, Moment 333.3
0.66
1.00
66%
Axial 1288.0(c), Moment 333.3
0.061
--meets L/1952--
Connector Anchor
Support Rx(lb) Ry(lb) Simpson Strong -Tie Connector Interaction Interaction
R2 133.3 0.0 SCB45.5(2) & (2) #12-24 SST X or XL to A36 Steel 21.86 % 11.96 %
R1 133.3 1288.0 600T125-33 (33) & (1) .157" SST PDPA/PDPAT-62KP to 32.52 % 60.55 %
steel (3/16" to 1/2" thickness)
* Reference catalog for connector and anchor requirement notes as well as screw placement requirements
SIMPSON STRONG -TIE COMPANY INC.
PROJECT: 99 RANCH MARKET
www.strongtie.com
L: SNL202026 j [SHEET. 14
Company : WRIGHT ENGINEERS KEYNOTE 2 BOTTOM RIGHT
11RISA Designer : H RISHI
�i
Job Number : 202026 202026 Checked By n e e r s
r_raETscHEKcoMF Model Name : INTERIOR CONTINUOUS BEAM
Node Coordinates
Label X [ft] Y [ft] Z [ft] Detach From Diaphragm
1 N1
0
0
0
2 N2
22
0
0
3 N3
9.167
0
0
Node Boundary Conditions
Node Label X [lb/in] Y [lb/in] Z [lb/in] X Rot [k-ft/rad]
1 N1
Reaction
Reaction
Reaction
Reaction
2 N2
Reaction
Reaction
Reaction
3 N3
Reaction
Cold Formed Steel Properties
Label E fpsil[psil
Nu Therm. Coeff. [le5'F-11
Density lb :11 Yield[psi Fu psi
1 A653 SS Gr33
2.95e+07
1.135e+07
0.3
0.65
490
33000
45000
121 A653 SS Gr50/1 2.95e+07
Member Primary Data
1.135e+07 0.3 0.65
490 50000 65000
Label I Node J Node
Section/Shape Type Design List
Material Desicin Rule
1 r M1 N1 I N2
60OS200-43 Beam CS
A653 SS Gr33 I Typical
MemberAdvanced Data
Label Physical Deflection Ratio Options
Seismic DR
1 M1
Yes Default
None
Cold Formed Steel Design Parameters
Label Shape
Length ft Lb z-z ft Lcomp to ft
Lcomp bot [ftj Function
1 M1 60OS200-43
22 11.83 Lbyy
0 Lateral
Member Distributed Loads
Member Label Direction Start Magnitude[lb/ft, F, psfl End Ma nitude[lb/ft, F, psfl Start Location ft, % End Location ft, % Inactive Ib, k-ft, in, red), Ib'sl/ft, Ib*s'ft
ill M1 I Y 1 -20
-20 0 %100
Active
Basic Load Cases
BLC Description
Category
Y Gravity Distributed
1 Dead load
DL
-1 1
Load Combinations
Description
11 Deflection 1
Solve PDelta
Yes Y
BLC Factor
DL 1
121 IBC 16-8
Yes
Y
DL
1
Envelope AISI S100-16: ASD Cold Formed Steel Code Checks
Member Shape Code Check Loc ft LCShear Check Loc ftDirLCPn/Om Ib Tn/Om Ib Mn /Om k-ft Mnzz/Om k-ft Vn /Om Ib Vnz/Om Ib Cb E n
Ill M160OS200-431 0.737 116.952]--O—,11-8—T9.16712
545.476 9722.156 0.093 1 0.389 11415.37 1972.816 .10 H1.2-1
RIS -3D Version 18 [ Interior beam (continuous).r3d ] Page 1
PROJECT: 99 RANCH MARKET I ., SNL202026 I SHEET: 15
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 1
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity (1) Date: 3/8/2021
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter:
Item number:
Effective embedment depth:
Material:
Evaluation Service Report:
Issued I Valid:
Proof:
Stand-off installation:
Anchor platen
Profile:
Base material:
Installation:
Seismic loads
KWIK HUS-EZ (KH-EZ) 1/2 (2 1/4) Ij IL
418070 KH-EZ 1/2"x2 1/2"
hef = 2.250 in.
Carbon Steel
ESR-3056
7/1/2020 1 10/1/2020
Design Method ASD Masonry
eb = 0.000 in. (no stand-off); t = 0.118 in.
Ix x ly x t = 6.000 in. x 4.000 in. x 0.118 in.; (Recommended plate thickness: not calculated)
no profile
Grout -filled CMU, L x W x H: 16.000 in. x 8.000 in. x 8.000 in.;
Joints: vertical: 0.375 in.; horizontal: 0.375 in.
Base material temperature: 68 °F
Face installation
no
R - The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
1
No: SNL202026 SHEET: 16
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 2
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity (1) Date: 3/8/2021
Fastening point:
Geometry [in.] & Loading [lb, it lb]
1.1 Design results
Case Description
1 Combination 1
2 Load case/Resulting anchor forces
Load case: Service loads
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Forces [lb] / Moments [in.lb]
N = 0; Vx = 0; Vy =-1,400;
Mx = 0; My = 0; Mz = 0;
Anchor Tension force Shear force Shear force x Shear force
1 0 1,400 0 -1,400
max. compressive strain: - [%°]
max. compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Seismic Max. Util. Anchor [%]
no 95
y
ROJECT: 99 RANCH MARKET
2
No: SNL202026 SHEET: 17
Hilti PROFIS Engineering 3.0.67
www.hilti.com
Company:
Address:
Phone I Fax:
Design: Maximum anchor capacity (1)
Fastening point:
3 Tension load (Most utilized anchor 1)
Load P. [lb]
_RIGHT
L n g i n e e r s
Page:
Specifier:
E-Mail:
Date:
Capacity Pt [lb] Utilization Pp = P./Pt [%] Status
3
3/8/2021
Overall strength N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
PROJECT: 99 RANCH MARKET G. L
SNL202026 SHEET: 18
Hilti PROFIS Engineering 3.0.67
www.hilti.com
Company:
Page:
Address:
Specifier:
Phone I Fax:
E-Mail:
Design: Maximum anchor capacity (1)
Date:
Fastenina noint
4 Shear load (Most utilized anchor 1)
_RIGHT
L n g i n e e r s
0
3/8/2021
Load V. [lb]
Capacity Vt [lb]
Utilization Pv = V./Vt [%] Status
Overall strength pare and perp, (Dir. x-)
-
95 OK
Shear utilization may result from parallel and perpendicular shear (see details)
4.1 Overall strength parallel
Vt,Base,ll = ESR Value
refer to ICC-ES ESR-3056
Vtdl — Vt,Base,ll ' fred,E,ll ' fred,s,ll ' fred,Temp
Vvi > Vs,ll
Variables
Cmin [in.] ccr [in.]
Smin [in.]
scr [in.]
Temperature [°F]
4.000 8.000
4.000
8.000
68
Results
Vto [lb] VtBasell [lb]
Vs,, [lb]
fred,E,ll
fred,s,ll
fred,Temp Utilization [3vll [%]
1,476 1,476
-1,400
1.000
1.000
1.000 95
4.2 Overall strength perpendicular
Vt,Base,l = ESR Value refer to ICC-ES ESR-3056
Vt,l — Vt,Base,l ' fred,E,l ' fred,s,i ' fred,Temp
Vt L > Vs,L
Variables
Cmin [in.] cef [in.] Smin [in.] Scr [in.] Temperature [°F]
4.000 8.000 4.000 8.000 68
Results
Vt [Ib] VtBasei [lb] Vs [Ib] fred,E,l fred,S,l fred,Temp Utilization Rvl [%]
0 1,476 0 0.000 0.000 1.000 0
4.3 Shear interaction
_ _ V.,pv'll Val Rv,l Vt,l g Utilization Rv [%] Status
0.949 0.000 1.667 95 OK
Rv = Rv,II + YV,-L
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
4
[N, SNL202026 SHEET: 19
kURIGHT
Hilti PROMS Engineering 3.0.67 L n g i n e e r s
www.hilti.com
Company: Page: F
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity (1) Date: 3/8/2021
Fastening point:
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re -distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically — checking required(!): Noncompliance can lead to significantly different distribution of
forces and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)!
While installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the
mortar joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state -of the art guidelines!
• Warnings/Notes - OST in Masonry HNA!
Fastening meets the design criteria!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
5
No: SNL202026 SHEET: 20
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 6
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity (1) Date: 3/8/2021
Fastening point:
6 Installation data
Profile: no profile
Hole diameter in the fixture: df = - in.
Plate thickness (input): 0.118 in.
Drilling method: Drilled in hammer mode
Anchor type and diameter: KWIK HUS-EZ (KH-EZ) 1/2 (2
1/4)
Item number: 418070 KH-EZ 1/2"x2 1/2"
Installation torque: 408 in.lb
Hole diameter in the base material: 0.500 in.
Hole depth in the base material: 2.625 in.
Minimum thickness of the base material: 7.625 in.
Hilti KH-EZ screw anchor with 2.25 in embedment, 1/2 (2 1/4), Steel galvanized, installation per ESR-3056
o nnn
y
o nnn
O
O
N
O
O
N
O
O
N
O
O
N
3.000
3.000
Coordinates Anchor [in.]
Anchor x y c_x c+x c_y c.y
1 0.000 -0.000 24.000 24.000 36.000 36.000
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
6
No: SNL202026 SHEET: 21
kURIGHT
Hilti PROMS Engineering 3.0.67 L n g i n e e r s
www.hilti.com
Company: Page: i
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity (1) Date: 3/8/2021
Fastening point:
7 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use -specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
7
No: SNL202026 SHEET: 22
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 1
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity Date: 3/8/2021
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter:
Item number:
Effective embedment depth:
Material:
Evaluation Service Report:
Issued I Valid:
Proof:
Stand-off installation:
Anchor platen
Profile:
Base material:
Installation:
Seismic loads
KWIK HUS-EZ (KH-EZ) 1/4 (2 1/2) 1 IL
418045 KH-EZ 1/4"x2 5/8"
hef = 2.500 in.
Carbon Steel
ESR-3056
7/1/2020 1 10/1/2020
Design Method ASD Masonry
eb = 0.000 in. (no stand-off); t = 0.118 in.
Ix x ly x t = 48.000 in. x 4.000 in. x 0.118 in.; (Recommended plate thickness: not calculated)
no profile
Grout -filled CMU, L x W x H: 16.000 in. x 8.000 in. x 8.000 in.;
Joints: vertical: 0.375 in.; horizontal: 0.375 in.
Base material temperature: 68 °F
Face installation
no
R - The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
1
No: SNL202026 SHEET: 23
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 2
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity Date: 3/8/2021
Fastening point:
Geometry [in.] & Loading [lb, it lb]
Y
1.1 Design results
Case Description
1 Combination 1
2 Load case/Resulting anchor forces
Load case: Service loads
Forces [lb] / Moments [in.lb]
N=0;Vx=0;Vy=-650;
Mx = 0; My = 0; Mz = 0;
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force
1 0 650 0 -650
max. compressive strain: [%°]
max. compressive stress: [psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Seismic Max. Util. Anchor [%]
no 100
ROJECT: 99 RANCH MARKET
2
No: SNL202026 SHEET: 24
Hilti PROFIS Engineering 3.0.67
www.hilti.com
Company:
Address:
Phone I Fax:
Design: Maximum anchor capacity
Fastening point:
3 Tension load (Most utilized anchor 1)
Load P. [lb]
_RIGHT
L n g i n e e r s
Page:
Specifier:
E-Mail:
Date:
Capacity Pt [lb] Utilization Pp = P./Pt [%] Status
3
3/8/2021
Overall strength N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
PROJECT: 99 RANCH MARKET G. L
SNL202026 SHEET: 25
Hilti PROFIS Engineering 3.0.67
www.hilti.com
Company:
Address:
Phone I Fax:
Design: Maximum anchor capacity
Fastenina point:
4 Shear load (Most utilized anchor 1)
Load V. [lb] Capacity Vt [lb] Utilization Pv = V./Vt [%]
Overall strength para and perp, (Dir. x-) - 100
Shear utilization may result from parallel and perpendicular shear (see details)
Page:
Specifier:
E-Mail:
Date:
_RIGHT
L n g i n e e r s
4.1 Overall strength parallel
Status
OK
0
3/8/2021
Vt,Base,ll = ESR Value
refer to ICC-ES ESR-3056
Vtdl — Vt,Base,ll ' fred,E,ll
' fred,s,ll ' fred,Temp
Vvi ? Vs,ll
Variables
Cmin [in.]
Ccr [in.]
Smin [in.] scr [in.]
Temperature [°F]
4.000
4.000
4.000 4.000
68
Results
Vto [lb]
VtBasell [lb]
Vs,, [lb] fred,E,ll
fred,s,ll fred,Temp Utilization [3vll [%]
650
650
-650 1.000
1.000 1.000 100
4.2 Overall strength perpendicular
Vt,Base,l = ESR Value
Vt,l — Vt,Base,l ' fred,E,l ' fred,s,i ' fred,Temp
Vt L > VS,L
Variables
Cmin [in.] cef [in.]
4.000 4.000
Results
Vt_ [Ib]ytBasei [lb]
0 650
4.3 Shear interaction
_ - Vs,v a�.11 RV.l - v
t.11 t,l
1.000 0.000
Rv = Rv,II + YV,-L
min [in.] Scr [in.] Temperature [°F]
4.000 4.000 68
Vs_ [Ib] fred,E,l fred,S,l fred,Temp Utilization Rvl [%]
0 0.000 0.000 1.000 0
S Utilization Rv [%] Status
1.667 100 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
4
[N, SNL202026 SHEET: 26
kURIGHT
Hilti PROMS Engineering 3.0.67 L n g i n e e r s
www.hilti.com
Company: Page: F
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity Date: 3/8/2021
Fastening point:
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re -distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• The min. sizes of the bricks, the masonry compressive strength, the type / strength of the mortar and the grout (in case of fully grouted CMU
walls) has to fulfill the requirements given in the relevant ESR-approval or in the PTG.
• Only the local load transfer from the anchor(s) to the wall is considered, a further load transfer in the wall is not covered by PROFIS!
• Wall is assumed as being perfectly aligned vertically — checking required(!): Noncompliance can lead to significantly different distribution of
forces and higher tension loads than those calculated by PROFIS. Masonry wall must not have any damages (neither visible nor not visible)!
While installation, the positioning of the anchors needs to be maintained as in the design phase i.e. either relative to the brick or relative to the
mortar joints.
• The effect of the joints on the compressive stress distribution on the plate / bricks was not taken into consideration.
• If no significant resistance is felt over the entire depth of the hole when drilling (e.g. in unfilled butt joints), the anchor should not be set at this
position or the area should be assessed and reinforced. Hilti recommends the anchoring in masonry always with sieve sleeve. Anchors can only
be installed without sieve sleeves in solid bricks when it is guaranteed that it has not any hole or void.
• The accessories and installation remarks listed on this report are for the information of the user only. In any case, the instructions for use
provided with the product have to be followed to ensure a proper installation.
• The compliance with current standards (e.g. 2015, 2012, 2009 and 2006 IBC) is the responsibility of the user.
• Drilling method (hammer, rotary) to be in accordance with the approval!
• Masonry needs to be built in a regular way in accordance with state -of the art guidelines!
• Warnings/Notes - OST in Masonry HNA!
Fastening meets the design criteria!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
5
No: SNL202026 SHEET: 27
Hilti PROMS Engineering 3.0.67
www.hilti.com
_RIGHT
L n g i n e e r s
Company: Page: 6
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity Date: 3/8/2021
Fastening point:
6 Installation data
Profile: no profile
Hole diameter in the fixture: df = - in.
Plate thickness (input): 0.118 in.
Drilling method: Drilled in hammer mode
Anchor type and diameter: KWIK HUS-EZ (KH-EZ) 1/4 (2
1/2)
Item number: 418045 KH-EZ 1/4"x2 5/8"
Installation torque: 252 in.lb
Hole diameter in the base material: 0.250 in.
Hole depth in the base material: 2.875 in.
Minimum thickness of the base material: 7.625 in.
Hilti KH-EZ screw anchor with 2.5 in embedment, 1/4 (2 1/2), Steel galvanized, installation per ESR-3056
Coordinates Anchor [in.]
Anchor x y c_x c+x c_y c.y
1 0.000 -0.000 24.000 24.000 36.000 36.000
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
K
PROJECT: 99 RANCH MARKET
6
No: SNL202026 SHEET: 28
kURIGHT
Hilti PROMS Engineering 3.0.67 L n g i n e e r s
www.hilti.com
Company: Page: i
Address: Specifier:
Phone I Fax: E-Mail:
Design: Maximum anchor capacity Date: 3/8/2021
Fastening point:
7 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use -specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
PROJECT: 99 RANCH MARKET
7
No: SNL202026 SHEET: 29