REVIEWED BLD2021-0683+Manufacturer_Specifications_and_Installation_Instructions+5.17.2021_2.35.38_PM+2200931Job Name: .
TR E® Unit Prepared
YHC074F3RMAIX
0 Quantity: 1
Trane Precedent Gas/Electric Packaged Rooftop
Application Unit Size �Cpply Fan IMENEVII
= External �
DX cooling, 6 Ton Dual Airflow Static Height
gas heat compressor Pressure
2400 cfm 0.500 in H2O 3.91 ft
Unit Features
Fresh Air Selection Without fresh air selection
SupplyFan/Drive/ MotorType Multi speed fan
Panels/Filters Standard condenser coil
Unit Electrical
ge/phase/hertz 208-230/60/3
MCA 38.20 A
MOP 50.00 A
imensions m. Weight
Width Length Minimum Maximum
4.44 ft 7.39 ft 1016.0 lb 639 kg
• • Unit Controls Microprocessor controls 3ph
Communications Option Without communications
System Monitoring Controls 1 Without system monitoring controls
System Monitoring Controls 2 No monitoring controls
Entering Dry Bulb 80.00 F
Entering Wet Bulb 67.00 F
Ambient Temp 95.00 F
Leaving Coil Dry Bulb 57.35 F
Leaving Coil Wet Bulb 57.09 F
Leaving Unit Dry Bulb 58.26 F
Leaving Unit Wet Bulb 57.44 F
Refrigeration System Options i
Leaving Dew Point 56.92 F
Heat Type Gas Heat
Heating Stages 1
Output Heating Capacity 97.20 MBh
Output Heating Capacity with Fan 98.52 MBh
Heating EAT 70.00 F
Heating LAT 107.80 F
Heating Temp Rise 37.80 F
Capacity
Gross Total 73.60 MBh
Gross Sensible 58.70 MBh
Net Total 72.28 MBh
Net Sensible 57.38 MBh
Fan Motor Heat 1.32 MBh
EER IEER/SEER
13.1 EER 16.00
2017-09-18 15:17:53Z Page 1 of 9
Job Name: .
TR E® Unit Prepared
YHC074F3RMAIX
0 Quantity: 1
Indoor Fan Data
Drive Type Variable Direct
Indoor Fan Performance
Airflow 2400 cfm
r Design ESP 0.500 in H2O
Indoor Motor Operating Power 0.51 bhp
Indoor Motor Power 0.38 kW
Indoor RPM 916 rpm
Indoor Fan FLA 2.40 A
Power 4.51 kW
Circuit 1 RLA 6.80 A
Circuit 2 RLA 3.50 A
Outdoor Fan Data
Type Propeller
Fan Quantity 1
Drive Type Direct
Outdoor Fan Performance
Outdoor Motor Power 0.52 kW
Condenser Fan FLA 2.40 A
Exhaust Fan Data
Type FC Centrifugal
Drive Type Direct
Exhaust Fan Performance
Exhaust Fan FLA 8.50 A
2017-09-18 15:17:53Z Page 2 of 9
Job Name: .
TRAIVE® Unit Prepared
YHC074F3RMAlX
Quantity: 1
EVAPORATOR
SECTION ACCESS PANEL
CONDENSATE DRAIN (ALT)
3/4"-14 NPT DIA. HOLE —
4
PANEL
CONDENSER FAN
ONDENSER COIL
Y7 y8• NR CONTROL WIRE 7/8" DIA HOLE
e ERVICE GAUGE PORTACCESS 1 3/8'DIA HOLE
47 7/8` 1 UNIT POWER WIRE
12' NPT GAS CONNECTION �
(BOM BH 8120M B H )
3/4' NPT GAS CONNECTION
050MBM, 200MOH 6 250MBH) CON"T'ROLAND COMPRESSOR ACCESS PANEL
PACKAGED GAS / ELECTRICAL
THROUGH THE ISOMETRIC VIEW
BASE CONDENSATE 11B'
27 5/8'
NOTES:
1.THRU -THE -BASE ELECTRICALIS NOT STANDARD ON ALL UNITS.
2. VER IFYALL DIM EN SION S WITH INSTALLER DOCUMENTS
BEFORE INSTALLATION.
I I I I
I I I I
I I I I
I I I I
I 33" 1 I 3218"
SUPPLY I I
lI RETURN
17 12' 9 7/8' 17 12'
PLAN VIEW UNIT
DIMENSION DRAWING
1 RETURN
2.1(m- SUPPL
L
4
aii
32 1 /4'
1 3/1"
19 1/4" 9 3/8" 16 3/4" 3 7/8'
CONDENSATE
5/8'
46 718
24 12•
9 5/8"
5 5B"
4 1/4'
5 5/8"
7 5/8'
PACKAGED GAS / ELECTRICAL 53 1/4
0
0
DIMENSION DRAWING
HORIZONTAL
AIR FLOW
2017-09-18 15:17:53Z Page 3 of 9
DIMENSION DRAWING
HORIZONTAL
AIR FLOW
2017-09-18 15:17:53Z Page 3 of 9
0 TRIIIYE
Job Name: .
Prepared By: .
Unit Tag: YHC074F3RMAlX
Quantity: 1
�0�
3/4'44DIAH0LE
CONDENSATE DRAIN
SUPPLY
RETURN
27 5/8'
4 3/4'
ISOMETRIC -PACKAGED COOLING
2017-09-18 15:17:53Z Page 4 of 9
Job Name: .
TRAN6® Unit Prepared
YHC074F3RMA1X
Quantity: 1
ELECTRICAL / GENERAL DATA
12X4)(e)
GENERAL
HEATING PERFORMANCE
Model
YHC074F
Oversized Motor
HEATING -GENERALDATA
Unit Operating Voltage.
187-253
61 CA.
Unit Primary Voltage
208
I.IFS.
Heating 6lodel
Medium
Unit Secondary Voltage
230
LI CB
Heating Input (BTU)
120,000
Unit H ertz.
60
H eating Output (BTU ).
97.200
Unit Phase.
3
No Burners.
3
No Stages
1
EER
Standard Motor
Field Installed Oversized 61 otor
Gas Inlet Pressure
1.1C A.
374
1.1C A
Natural Gas (MiNM 11
4.5/14.0
MFS.
500
MFS
LP 11d in Al ax)
11.0/14.0
IdC B
50 0
1.1C8
Gas Pipe Connection Size:
1/2'
INDOOR MOTOR
Standard 1.1 otor
Oversized Motor
Field Installed Oversized Motor
Number
1
Number
Number.
Horsepower
3 8
Horsepower
Horsepower:
Motor Speed ( RPLI ).
_
Motor Speed(RPM i.
Motor Speed (RPM I,
Phase
3
Phase
Phase
Full Load Amps:
8,5
Full Load Amps.
Full Load Amps
Locked RotorAmps
_
Locked Rotor Amps.
Locked Rotor Amps:
COMPRESSOR
Circut 1R
OUTDOOR MOTOR
Number
1
Number 1
Horsepower
5.0/2.3
Horsepower: 0.7
Phase
3
6lotorSpeed (RPM): 1100
Rated Load Amps
14.617.1
Phase. I
Locked Rotor Amps
83.0/55.0
Full Load Amps. 3.5
Locked RotorAmps 109
POWER EXHAUST ACCESSORY
FILTERS
REFRIGERANT i2'
iF ie lei Installed Power E
xh aust)
Type R-410
Phase.
Type, Throwaway
Horsepower
Furnished. Yes
Factory Charge
Motor Speed(R PM)
Number 4
Crcuit$1 `_81b
Full Load Amps
Recommended 20'x2"x2'
Circuit*2 41 to
Locked Rotor Amps
R610
1 61 aximum (HACR ) Circuit Breaker sizing is br installations in the United States only
2 Refrigerant charge is an approxm ate value For a more pre ase value, see unit nameplate and sery ice instructions.
3 Value does not ncludePower Exhaust Accessory
4 Value includes oversized motor
5 Value does not include Power E xhaust Accessory
6. E E R is rated at AH RI conditions and in accordance with DOE test procedures
2017-09-18 15:17:53Z Page 5 of 9
Job Name: .
TR E® Unit Prepared
YHC074F3RMAIX
0 Quantity: 1
PACKAGED GAS / ELECTRICAL
CORNER WEIGHT
\O
A
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCE SSORY
E IGH—S
ECONOMIZER
1.1OTORIZED OUTSIDE AIR DAMPER
I.IANUAl- OUTSIDE AIR DAMPER
BAROMETRIC RELIEF
OVERSIZED MOTOR
BELT DRIVE MOTOR
POWER EXHAUST
THROUGHTTHE BASE ELECTRICAL/GAS.FIOPS
UNIT MOUNTED CIRCUIT BREAKER (FIOPS)
UNIT MOUNTED DISCONNECT (FIOPS)
POWERED CONVENIENCE OUTLET (FIOPS)
HINGED DOORS iFIOPS1
HAIL GUARD
SMOKE DETECTOR, SUPPLY/ RETURN
NOVAR CONTROL
STAINLESS STEEL HEAT EXCHANGER
REHEAT
ROOFCURB
BASIC UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITIY
SHIPPING NET AO 33a 01b CO 2s801b EI LEN GH7 (F)WID7H
1114.0 b 1016.0 Ib BO 23LO Ib O 202 O Ib s t 23'
OTE:
All weights are a ppro w m a to
Weights for options that are not list refer to Installation guide
The actual walght are listed on the unit nameplate
Ion guide for weights before scheduling transportation and Installation
olcal unit operating veight for the configuration sekrted Estimated
nenslon with installer documents before Installation
Ition only
�ssones should be added to unit velght Men ordering factory or field
PACKAGED GAS/ELECTRICAL
RIGGING AND CENTER OF GRAVITY
2017-09-18 15:17:53Z Page 6 of 9
Job Name: .
TR E® Unit Prepared
YHC074F3RMAlX
0 Quantity: 1
CLEARANCE 36"
DOWNFLOW CLEARANCE 36"
HORIZONTAL CLEARANCE 18"
ROOF OPENING
UNIT OUTLINE —
PACKAGED GAS/ELECTRIC
CLEARANCE
46-
88 558'
PACKAGED GAS/ELECTRIC
DOWN FLOW TYPICALROOF OPENING
CLEARANCE FROM TOP OF UNIT 72'
CLEARANCE48"
CLEARANCE 36"
46- 53 1/4'
2017-09-18 15:17:53Z Page 7 of 9
Aft
Job Name: .
TJMME® Unit Prepared
YHC074F3RMA1X
W Quantity: 1
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall
be cleaned, phosphatized, and finished with a weather -resistant baked enamel finish. Unit's surface
shall be tested 672 hours in a salt spray test in compliance with ASTM 13117. Cabinet construction
shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be
removed and reinstalled by removing two fasteners while providing a water and air tight seal. All
exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil -
faced, fire -retardant permanent, odorless glass fiber material. The base of the unit shall be insulated
with 1/8 inch, foil -faced, closed -cell insulation. All insulation edges shall be either captured or sealed.
The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1
1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with
forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double -hemmed and
gasket -sealed. The ribbed top adds extra strength and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall
also be available.
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F,
T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward -curved fan wheel along
with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a
variable speed adjustment potentiometer located in the control box.
3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with
adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed,
direct drive motors. All 6 to 8'/2 ton units (standard efficiency) shall have belt drive motors with an
adjustable idler -arm assembly for quick -adjustment to fan belts and motor sheaves. All motors shall be
thermally protected. All 10 tons, 6 ton (074), 7'/2 to 81/2 (high efficiency) units have variable speed
direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Outdoor Fans
The outdoor fan shall be direct -drive, statically and dynamically balanced, draw -through in the vertical
discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal
overload protection.
Multi -Speed Indoor Fan System
Multi -speed indoor fan system is designed for use in applications for meeting the minimum
requirement of CA Title 24. This system incorporates a multi -speed fan control to change the speed of
the fan to 67% of full airflow based off of compressor stages.
Evaporator and Condenser Coils
Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be
standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel
condenser coils are standard for all 3 to 10 ton standard efficiency models and 4, 5, 6, 7.5, 8.5 ton high
efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton
dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube -to -fin
bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can
reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to
better compressor reliability. Compact all -aluminum microchannel coils also help to reduce the unit
weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all
aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition,
flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils
2017-09-18 15:17:53Z Page 8 of 9
Aft
Job Name: .
TJMME® Unit Prepared
YHC074F3RMA1X
V Quantity: 1
shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser
coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The
condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of
cleaning. A plastic, dual -sloped, removable and reversible condensate drain pan with through -the -base
condensate drain is standard.
High Pressure Control
All units include High Pressure Cutout as standard.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by
phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that
provides an ON or FAULT indicator. There are no field adjustments. The module will automatically
reset from a fault condition.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and
refrigerant line filter driers are factory -installed as standard. An area shall be provided for replacement
suction line driers.
Gas Heating Section
The heating section shall have a progressive tubular heat exchanger design using stainless steel
burners
and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the
combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system.
On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until
manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or
propane (field -installed kit) and also comply with the California requirement for low NOx emissions
(Gas/Electric Only).
Human Interface
The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15
Class B with an Ingress Protection Rating of IP24.The display text shall be readable by a person with
20/20 vision at a distance of 3 feet and 600 angle at lighting levels ranging from 100 lux - 25,000 lux.
Also, the display shall operate at temperatures of -400 C to 70" C. Firmware and unit configurations
shall be able to be restored via a USB storage device.
2017-09-18 15:17:53Z Page 9 of 9