Loading...
REVIEWED BLD BLD2021-0786+Structural_Analysis_or_Calculations+6.9.2021_3.04.10_PM+22412841 /8 m •7 info@b2eng i neers. com 425-318-7047 (0) 425-318-0031(C) FULLER REMODEL EDMONDS 10631 229TH PL SW, EDMONDS, WA 98020 STRUCTURAL CALCULATIONS PROJECT NO: 20202 DATE:06-01-21 PREPARED BY: BASRI BASRI PE, SE Design Criteria International Building Code (IBC) 2015 American Society of Civil Engineers (ASCE) 7-10 REMOVAL OF EXISTING INTERIOR LOAD -BEARING WALLS. INSTALLATION OF NEW BEAMS, POSTS AND FOOTINGS. PLEASE SEE ATTACHED CALCULATIONS. I_21I WINKill P of wary, S� • �� 2 A 'P 43789 �0, crURA L ENGNG\� SS/0NAL Fibj E RECEIVED 6.9.2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 2 /8 3 /8 FULLER REMODEL CALCULATIONS g D IMPORTANT NOTE: z CONTRACTOR SHALL PROVIDE w TEMPORARY SHORING AS a EXISTING FLOOR - REQUIRED PRIOR ANY WORK C7 BEAMS TO REMAIN z l x z 1 o 3 II II II II II II II II II II II II I TII1 II NEW 4A II I I II BEAM (Bi 21, II II II II II II II II II II II II II II II II II II II I II II II II II I II u � it II II II II II II II II II II II II II I_ II II II B1-2 11 II II II II II II II II II II II NEW 3.5X9.25 II �I II II P g II II 1I II II II II 1I 11 1I 11 PSL BEAM_ B�f-1 I! I - r II II II II II II II II II II 11 11 1 S-2 II I II II II ExsT. II II II II II II II n II II II II 11 011 1 I 1 II II II z> I I I I I I I PORTION OF EXISTING O II II II II II II II II II II II II III III II II II x w l & II II WALL TO BE REMOVED W ¢ 11 II 11 11 11 II 11 P o m I �12 ANEW II II II II II U 11 1 1I 11 1 1I 1I 11 1 1I 1 0 o 1 1 1BEAru II II 11 1 1 II II 11 1 II HI 11 1 II 1I 11 1 1I �2)2X4 II 11 1 EXST. 1 o Q 1 11 11 11 II II II II II II II II II II II 1 0 'mil I I Q II 11 �tI I I Ir IlL�-f II �I""VIA - I II II II II II II II II II II II II II I ' II II II II II II II II o II II II II� II II II II II II QIj O11 II 11 vv X WI II II II II II II II II II II II II II II II II II II II w II II II II II II II II II II II II II II II II II I�I 0 Lmu II II II II III II II II II II II II Ij 1 °II II II II II II II ii i a II II II II 1-o all EXISTING FLOOR a� II II II II II II FRAMING TO REMAIN 1I II II II II II �II II II II II II II II II II II II II II II II II II II I II I II ` II II vII II I II II II II II II II II II II II II II II II II II II II II II II II I�I II II II IP II I II II II II II B1-T BEAMS TO REMAIN FIRST FLOOR JI I I I I(P) I I B1-1 AND B1-2 ARE DENOTES BEAMS �EXST FULLER REMODEL CALCULATIONS 4 /8 - - - - - - - - - - - - - PROVIDE 4X8 HEADER (BELOW)_(RB-1) - - - - - - - - - - - - - - - ------- - - - - -- - FRB-1 -------- --- --- - ----------------- II II II II II II II II II II II -----�-�--- - - - -- - -- - -- - II II 1 1 1 II II 1 1 II II II 1 1 II II 1 II II 1 1 II II 1 1 II II II 1 1 II II — — — — — — — — — II 1 1 1 II II I I II II II I I II II I I II II I II II I I II II II I I II II — — — — — — — — — I II I I II II I I II II II I I II II I _ b I I II II II II II II I I II II II I I II II i— — — — — — — — — — — — I 1 II II 1 1 1 II II 1 1 II II II 1 1 'HI-1 II 1 1 I 1 II II 1 1 1 II II 1 1 II II II 1 NEwax81 II 1------- --- --- — 1 11 11 1 1 1 11 11 1 1 11 11 11 1 BEAMJH -Ty 11 1 1 2 I i 11 11 - - S2 - - - EXISTING ROOF II II II II II II II 11 11 1 1 FRAMING TO REMAIN I II II I I I II II I I II II II I II II CONTRACTOR TO FIELD p p 1 II II 1 1 1 II II 1 1 II II III VERIFY EXISTING II = _ _ _ _ _ II II II II II II II HEADERS; 4X8 (MIN)(RB-1 II 1 II II 1 1 1 II 11 1 1 11 11 11 1 1 11 Rh'R-1 II 1------- --- --- — I 1 11 11 1 1 1 11 11 1 1 11 11 11 1 1 11 11 1 EXISTING ROOF - - - - - - - - - - - - FRAMING TO REMAIN 1 11 11 1 1 1 11 11 u u 11 11 11 1 1 11 11 1 1 11 11 1 1 1 11 11 1 1 11 11 11 1 1 11 11 i— — — — — — — — — — 1 11 11 1 1 1 11 II I I II II II I I II II I I II II I I I II II I I II II II I I II II i— — — — — — — — — — — I II II I I I II II I I II II II I I II II I T — — — — — — — — — — — — — I H H I I I H 11 1 1 11 11 11 1 1 11 11 — — — — — — — — — — — — — — — ROOF PLAN RB-1 AND H1-1 ARE DENOTES ROOF BEAMS - - - - - - - - - - - - - - - 5 /8 BeamChek v2020 licensed to: B2 Engineers Reg # 5508-68754 FULLER REMODEL EDMONDS B1-1 Date: 12/08/20 Selection 3-1/2x 9-1/4 2.0E TJ Parallam W.S. PSL Lu = 0.0 Ft Conditions NDS 2015 Min Bearing Area R1= 2.6 in R2= 2.1 in (1.5) DL Defl= 0.22 in Data Attributes Actual Critical Status Ratio Values Adjustments Beam Span 14.6 ft Reaction 1 LL 1040 # Reaction 2 LL 782 # Beam Wt per ft 10.12 # Reaction 1 TL 1633 # Reaction 2 TL 1342 # Bm Wt Included 148 # Maximum V 1633 # Max Moment 4219 '# Max V (Reduced) 1625 # TL Max DefI L / 240 TL Actual Defl L / 390 LL Max Defl L / 360 LL Actual Defl L / 767 Section (W) Shear (in 2) TL Detl (in) LL Defl 49.91 32.38 0.45 0.23 14.75 7.31 0.73 0.49 OK OK OK OK 30% 23% 62% 47% Fb (psi) Fv (psi) E (psi x mil) Fc! (psi) Reference Values 2900 290 2.0 625 Adjusted Values 3433 334 2.0 625 CF Size Factor 1.029 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Point LL Point TL Distance Par Unif LL Par Unif TL Start End 437 B = 639 10.0 100 H = 178 10.0 14.6 925 C = 1369 1.5 H Pt loads: 0 R1 = 1633 R2 = 1342 SPAN =14.6FT Uniform and partial uniform loads are Ibs per lineal ft. FOOTING CALCULATIONS: TOTAL LOAD (TL) = 1,633 LBS SOIL BEARING CAPACITY (SBC) = 1,500 PSF TL/SBC = 1.088 SF (REQUIRED) 1.5'X1.5' = 2.25 SF (PROVIDED) /OK 6 /8 BeamChek v2020 licensed to: B2 Engineers Reg # 5508-68754 FULLER REMODEL EDMONDS B1-2 Date: 12/08/20 Selection 4x 8 DF-L #2 Lu = 0.0 Ft Conditions NDS 2015 Min Bearing Area R1= 5.2 in R2= 0.8 in (1.5) DL Defl= 0.01 in Data Attributes Actual Critical Status Ratio Values Adjustments Beam Span 4.0 ft Reaction 1 LL 2188 # Reaction 2 LL 313 # Beam Wt per ft 6.17 # Reaction 1 TL 3250 # Reaction 2 TL 475 # Bm Wt Included 25 # Maximum V 3250 # Max Moment 1631 '# Max V (Reduced) 2608 # TL Max DefI L / 240 TL Actual DefI L / >1000 LL Max Defl L / 360 LL Actual Defl L / >1000 Section (W) Shear (in 2) TL Detl (in) LL Detl 30.66 25.38 0.02 0.01 14.55 18.90 0.20 0.13 OK OK OK OK 47% 74% 12% 11 % Fb (psi) Fv (psi) E (psi x mil) Fc! (psi) Reference Values 900 180 1.6 625 Adjusted Values 1346 207 1.6 625 CF Size Factor 1.300 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Point LL Point TL Distance 2500 B = 3700 0.5 Pt loads: 0 R1 = 3250 R2 = 475 SPAN = 4 FT Uniform and partial uniform loads are Ibs per lineal ft. 7 /8 BeamChek v2020 licensed to: B2 Engineers Reg # 5508-68754 FULLER REMODEL EDMONDS 1-11-1 Date: 6/01 /21 Selection 4x 8 HF #2 Lu = 0.0 Ft Conditions NDS 2015 Min Bearing Area R1= 1.9 in R2= 1.9 in (1.5) DL Defl= 0.05 in Data Attributes Actual Critical Status Ratio Values Adjustments Loads Beam Span 6.5 ft Reaction 1 LL 382 # Reaction 2 LL 382 # Beam Wt per ft 6.17 # Reaction 1 TL 784 # Reaction 2 TL 784 # Bm Wt Included 40 # Maximum V 784 # Max Moment 1274 '# Max V (Reduced) 638 # TL Max DefI L / 240 TL Actual DefI L / 928 LL Max Defl L / 360 LL Actual Defl L / >1000 Section (W) Shear (in 2) TL Detl (in) LL Detl 30.66 25.38 0.08 0.03 13.83 6.38 0.33 0.22 OK OK OK OK 45% 25% 26% 15% ro (psi) ry (psi) t (psi x mn) rc! (psi Reference Values 850 150 1.3 405 Adjusted Values 1105 150 1.3 405 CF Size Factor 1.300 Cd Duration 1.00 1.00 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Uniform LL: 118 Uniform TL: 235 = A Uniform Load A 0 R1 = 784 R2 = 784 SPAN = 6.5 FT Uniform and partial uniform loads are Ibs per lineal ft. 8 /8 BeamChek v2020 licensed to: B2 Engineers Reg # 5508-68754 FULLER REMODEL EDMONDS RB-1 Date: 12/08/20 Selection 4x 8 HF #2 Lu = 0.0 Ft Conditions NDS 2015 Min Bearing Area R1= 2.3 in R2= 2.3 in (1.5) DL Defl= 0.19 in Data Attributes Actual Critical Status Ratio Values Adjustments Beam Span 9.9 ft Reaction 1 LL 495 # Reaction 2 LL 495 # Beam Wt per ft 6.17 # Reaction 1 TL 912 # Reaction 2 TL 912 # Bm Wt Included 61 # Maximum V 912 # Max Moment 2256 '# Max V (Reduced) 800 # TL Max DefI L / 240 TL Actual Defl L / 348 LL Max Defl L / 360 LL Actual Defl L / 795 Section (W) Shear (in 2) TL Detl (in) LL Detl 30.66 25.38 0.34 0.15 21.31 6.96 0.50 0.33 OK OK OK OK 69% 27% 69% 45% Fb (psi) Fv (psi) E (psi x mil) Fc! (psi) Reference Values 850 150 1.3 405 Adjusted Values 1271 173 1.3 405 CF Size Factor 1.300 Cd Duration 1.15 1.15 Cr Repetitive 1.00 Ch Shear Stress N/A Cm Wet Use 1.00 1.00 1.00 1.00 Cl Stability 1.0000 Rb = 0.00 Le = 0.00 Ft Loads Uniform LL: 100 Uniform TL: 148 = A Par Unif TL Start End H = 30 0 9.9 H Uniform Load A 0 R1 =912 R2=912 SPAN = 9.9 FT Uniform and partial uniform loads are Ibs per lineal ft.