Loading...
REVIEWED RESUB3 BLD2022-0769+Structural_Analysis_or_Calculations+10.19.2022_9.07.53_PM+3175028SE01705E Hardening National 48kW 10/17/22 Rev 1 7151 Columbia Gateway Dr., Suite A deL**%' Columbia, MD 21046 advantage engineers Phone:443.367.0003 RESUB Structural Calculations Oct 20 2022 CITY OF EDMONDS DEVELOPMENT SERVICES -1-111 Structural Design in Accordance with: 2018 International Building Code Design Provisions: ASCE 7-16 Wood Design: National Design Specifications for Wood Construction - 2018 Edition Steel Design: Manual of Steel Construction - 15th Edition Masonry Design: TMS 402/602-16 Concrete: ACI 318-14 For T-Mobile Use Only: STRUCTURAL ASSESSMENT RESULT: PASS Definitions: A PASS indicates the structural investigation has concluded that the modifications to the existing structure will be structurally acceptable provided the provisions of the drawings as determined from this investigation are followed. A FAIL indicates the structural analysis has concluded the proposed modifications to the structure are beyond the proposed scope of the project and must be revised to meet current structural building code standards. . The following documentation shall be available on ' site for the building inspector: COE APPROVED ARCHITECTURAL PLAN SET ' ❑ COE APPROVED STRUCTURAL PLAN SET ; ❑ COE REVIEWED CALCULATION PACKET ! ❑ ENERGY CREDIT WORKSHEET ' ; ❑ SITE PLAN ; ❑ CIVIL PLAN ■ ; ■ ❑ ■ ■ ; ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 ■ SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 DISCLAIMER Structural analysis for a new generator and supporting equipment. Herewith, we are submitting our structural analysis calculations to the immediate structural members that support the proposed (replaced) generator for the subject project. Our calculations are based on the available structural and architectural drawings which do not include the construction documents for the superstructure the equipment is attached to. Please be advised that the evaluation and recommendations made are based on minimum design loads per current building codes without full as -built plans and without on -site intrusive investigation and verification. With this inherent limitation, the design and evaluation was done in accordance with generally accepted engineering principles and practices. The engineer of record shall be notified immediately when discrepancy occurs between the actual on -site condition and this report. We find the immediate existing structural supports to be adequate for the proposed loads. These calculations have been prepared using the degree of care normally exercised by others in the profession under similar circumstances. No other warranty is expressed or implied. SE01705E Hardening National 48kW 10/17/22 advantage engineers Rev 1 Material Specifications (UNO Concrete: 3,000 PSI at 28 days (Foundation Design based on 2,500 PSI) Masonry/Concrete Block: Grade S, Med. Wt. Units Reinforcing Steel: ASTM A615, Grade 60 Structural Steel: Compact Sections per ASTM A992, Pipe Steel per ASTM A501, Tube Steel per ASTM A500 and all other per ASTM A36 Lumber: Grade Marked D.F. #2 per W.C.L.B. GRDG, Rule 17. All Glu-laminated beams shall have minimum Fb = 2,400 PSI, Fv = 155 PSI 7151 Columbia Gateway Dr., Suite A Columbia, MD 21046 Phone: 443.367.0003 SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 Design Criteria 1) Diesel Generator 2) ATS 1) 2) 3) 1) 2) 3) 4) 5) 6) 7) 8) Gravitv Desian Data 4,931 Ibs 39 Ibs Wind Design Data Ultimate Wind Velocity 98 mph Exposure C Assumed Bldg. Height 8.6 ft Seismic Desian Data Site Class Risk Category Importance Factor Design Spectral Responses Seismic Design Category Response Modification Amplification Factor Analysis Procedure 1 Ss = 1.280 S 1 = 0.449 SIDS = 1.024 SD1 = 0.554 D 2.5 1 Equivalent Lateral Force Procedure SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 Wind Load Derivation Wind Design is per ASCE 7-16 Method Exposure Category C Basic Wind Speed = 98 mph Kzt = (1 + K1 * K2 * K3 )12 (26.8.2) Building Height (h) = 8.6 ft Kzt = 1 for flat conditions Building Width (B) = 3.2 ft G, the Gust effect factor (26.9.1-26.9.7) Building Length = 9 ft Directionality Factor kd (26.6-1) Kzt = 1 kd = 0.85 for all applications G = 0.85 except, tanks, chimneys kd = 0.9 and rooftop towers kz = 0.9 Square 0.9 q = 16.9 psf Hexagonal or Round 0.95 q (ASD) = 10.6 psf Velocity Pressure Exposure Coefficient kz (27.3.1) Velocity Pressure q = kzt*kd*kz*V^2 SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 Wind Load Derivation Wind Design is per ASCE 7-16 Method DESIGN WIND LOAD FOR FREE-STANDING WALLS AND SIGNS note: Signs attached to buildings shall be in accordance with CH 30. P = qz*Cf s Wind Pressure on Generator h = 7.7 ft B = 8.6 ft h B/h = 1.1 P = 26 psf P (ASD) = 16 psf Wind Force on Generator = h * B * P (ASD) = 1,086 Ibs Wind Pressure on ATS h= 3ft B = 2 ft B/h = 0.67 P = 27.9 psf P (ASD) = 17.5 psf Wind Force on ATS = h *B * P (ASD) = 105 Ibs Note: Use (2) 2'-0" long P-1000 unistruts at each side of the ATS attached to equipment shelter wall using (4) 3/8" lag screws into wood studs, (2) screws per side SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/2022 advantage engineers Phone:443.367.0003 Rev 1 Seismic Loading Derivation Soil Site Class D (assumed) Latitude: 47.783125 Longitude:-122.366983 Wall Type (light frame, other) other Lateral Resisting system A-ZZ) A.9 Notes: Per USGS, Assume structural components in site class D (conservative) Risk Category = II Importance Factor = 1 Ss = 1.280 S1 = 0.449 Ta = Ct*hn^x where Inn is the height in feet above the base to the highest level of the Sds= 1.024 Sd1 = 0.554 structure Ct = 0.02 Structure Ct x x = 0.75 Stl Moment Frames 0.03 0.80 hn = 8.6 Conc. Moment Frames 0.02 0.90 Eccentric Braced Frames 0.03 0.75 All other Struct. Systems 0.02 0.75 Cs final = 0.41 Cs_min = 0.00 Cs max = 2.21 Cs min = 0.05 Cs = 0.41 Ta = 0.10 R = 2.5 Out of Plane Anchorage Force 0.41 Wp 0 = 2 Collector Element Force 1.64 Wp Cd = 1.75 Steel Collector Element Force 2.29 Wp Seismic Design Category D ASCE AMERICAN SOCIM OF CIVIL ENGINEERS Address: No Address at This Location ASCE 7 Hazards Report Standard: ASCE/SEI 7-16 Elevation: 354.9 ft (NAVD 88) Risk Category: II Latitude: 47.783125 Soil Class: D - Default (see Longitude:-122.366983 Section 11.4.3) / \ E dmonda S��reAn• - Keiini..ie BM^!I� �•• ��J f­ e1 Vat I 1\\1keew+W kil Aland I l�r Are Wind Results: Wind Speed 98 Vmph 10-year MRI 67 Vmph 25-year MRI 74 Vmph 50-year MRI 78 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1 B and Figs. CC.2-1—CC.2-4, and Section 26.5.2 Date Accessed: Mon May 23 2022 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is not in a hurricane -prone region as defined in ASCE/SEI 7-16 Section 26.2. https://asce7hazardtoo1.onIine/ Page 1 of 3 Mon May 23 2022 E® AMERICAN SOCIETY OF CIVIL ENGINEERS Seismic Site Soil Class: D - Default (see Section 11.4.3) Results: Ss 1.28 Sp, N/A S, 0.449 T L 6 Fa 1.2 PGA: 0.543 Fv N/A PGA M : 0.651 S Ms 1.536 F PGA 1.2 SM, N/A le 1 SIDS 1.024 Cv 1.356 Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Data Accessed: Mon May 23 2022 Date Source: USGS Seismic Design Maps hftps:Hasce7hazardtool.online/ Page 2 of 3 Mon May 23 2022 E® AMERICAN SOCIETY OF CIVIL ENGINEERS The ASCE 7 Hazard Tool is provided for your convenience, for informational purposes only, and is provided "as is" and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE 7 standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third -party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third -party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE 7 standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE 7 Hazard Tool. https:Hasce7hazardtool.online/ Page 3 of 3 Mon May 23 2022 SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 Non -Structural Anchorage Calculator for Diesel Generator Site Conditions Sds = 1.024 Unit Constraints Component System (Al - B) ap = 1 Rp = 2.5 Unit Geometry Total Height of Structure (h) _ Height of Unit (z) _ Center Mass of Unit (d) _ Least Horizontal Dimension (b) _ Unit Weight (W) _ Fp = 0.4aPS,,'WP(1+2z/h) _ (Rp/lp) Fp_max = 8,079 Fp_min = 1,515 Overturning Moment (Mo) Resisting Moment (Mr) _ A7 Tables 13.5-1, 13.6-1 Pullout at Anchorage = Worst Case Vertical Load = Seismic governs over wind with Pullout per anchor Shear per anchor Ip = 1 8.6 ft 8 ft 4.25 ft, moment arm 3.2 ft, for overturning resistance 4,931 Ibs 2,311 Load Combinations (1 + 0.2Sds)D +/- E (0.9 - 0.2Sds)D +/- E 1.2D + 1.OW 9,822 Ibs-ft vs. 4358.753 Ibs-ft 5,485lbs-ft Low vs. 9,468lbs-ft 9,505lbs-ft High 1,355lbs vs.-1,596lbs 6,040 Ibs vs. 4,321 Ibs 2,311 > 1,0261bs 678lbs vs.-798lbs 578 Ibs 256 Ibs 5/8 in diameter x 3 1/4 in embedment expansion anchor each corner Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Page: 1 Address: Specifier: Phone I Fax: E-Mail: Design: SE01705E Date: 5/23/2022 Fastening point: Specifier's comments: 1 Input data Anchor type and diameter: Item number: Effective embedment depth: Material: Evaluation Service Report: Issued I Valid: Proof: Stand-off installation: Profile: Base material: Installation: Reinforcement: Seismic loads (cat. C, D, E, or F) Geometry [in.] & Loading [lb, in.lb] Kwik Bolt TZ2 - SS 304 5/8 (2 3/4) hnoml 2210277 KB-TZ2 5/8x4 1/4 SS304 hef,act = 2.750 in., hnom = 3.250 in. AISI 304 ESR-4266 12/17/2021 1 12/1/2023 Design Method ACI 318-14 / Mech T INS �--r a cracked concrete, 2500, fc' = 2,500 psi; h = 6.000 in. automatic cleaned drilled hole, Installation condition: Dry tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: > No. 4 bar Tension load: yes (17.2.3.4.3 (b)) Shear load: yes (17.2.3.5.3 (c)) Y X Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan W, G \ NO ii Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Page: 2 Address: Specifier: Phone I Fax: E-Mail: Design: SE01705E Date: 5/23/2022 Fastening point: 1.1 Design results Case Description Forces [lb] / Moments [in.Ib] Seismic Max. Util. Anchor [%] 1 Combination 1 N = 678; Vx = 578; Vy = 0; yes 30 Mx=0;My=0;Mz=0; 2 Load case/Resulting anchor forces Anchor reactions [lb] Tension force: (+Tension, -Compression) Anchor Tension force Shear force Shear force x Shear force 1 678 578 578 0 max. concrete compressive strain: [%o] max. concrete compressive stress: [psi] resulting tension force in (x/y)=(0.000/0.000): 0 [lb] resulting compression force in (x/y)=(0.000/0.000): 0 [lb] 3 Tension load Load Nua [lb] Capacity � N„ [lb] Utilization PN = N A N Status Steel Strength* 678 14,132 5 OK Pullout Strength* N/A N/A N/A N/A Concrete Breakout Failure** 678 2.334 30 OK * highest loaded anchor **anchor group (anchors in tension) Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 2 Hilti PROFIS Engineering 3.0.77 www.hilti.com Company: Address: Phone I Fax: Design: SE01705E Fastening point: 3.1 Steel Strength Nsa = ESR value refer to ICC-ES ESR-4266 � Nsa > Nua ACI 318-14 Table 17.3.1.1 Variables Ase,N [in.) futa [Psi] 0.16 114,604 Calculations Nsa [lb] 18,843 Results Nsa [lb] 0 steel Onondudile 18,843 0.750 1.000 3.2 Concrete Breakout Failure ANc Ncb = ( `ANcO) w ed,N Wc,N Wcp,N Nb Ncb >! Nua ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) 2 ANco = 9 hef WedN=0.7+0.3(alMhn) <1.0 .5hef W cp,N = MAX(ca=min 1.5hef) < 1.0 �Craac lac 1. Nb = kc "a yfc hefs Variables 0 Nsa [lb] 14,132 Page: Specifier: E-Mail: Date: ua [lb] 678 ACI 318-14 Eq. (17.4.2.1a) ACI 318-14 Table 17.3.1.1 ACI 318-14 Eq. (17.4.2.1c) ACI 318-14 Eq. (17.4.2.5b) ACI 318-14 Eq. (17.4.2.7b) ACI 318-14 Eq. (17.4.2.2a) hef [In.] ca.min [In.] W c,N cac [In.] kc 2.750 6.000 1.000 10.000 21 Calculations ANc [in.'] ANco [in.2] W ed,N Wcp,N Nb [lb] 68.06 68.06 1.000 1.000 4,788 Results Ncb [lb] 0 concrete Oseismic Onondudile Ncb [Ib] 4,788 0.650 0.750 1.000 2,334 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan ka 1.000 ua [lb] 678 fc [psi] 2,500 3 5/23/2022 3 Hilti PROFIS Engineering 3.0.77 www.hilti.com Company: Page: 4 Address: Specifier: Phone I Fax: E-Mail: Design: SEW 705E Date: 5/23/2022 Fastening point: 4 Shear load Load Vua [lb] Steel Strength* 578 Steel failure (with lever arm)* N/A Pryout Strength** 578 Concrete edge failure in direction x+** 578 * highest loaded anchor **anchor group (relevant anchors) 4.1 Steel Strength Vsa,eq = ESR value refer to [CC -ES ESR-4266 � Vsteel >— Vua ACI 318-14 Table 17.3.1.1 Variables b ' `se,y [in.21 f"ta [psi] a'V,seis 0.16 114,604 1.000 Calculations Vsa eg [lb] 12,360 Results Vsaeg [lb] 0 steel Ononductile Vsaeg [lb] 12,360 0.650 1.000 8,034 Capacity 41 Va [lb] Utilization P„ = Vua/$ V„ Status 8,034 8 OK N/A N/A N/A 6,704 9 OK 2,501 24 OK Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan Vua [lb] 578 4 Hilti PROFIS Engineering 3.0.77 www.hilti.com Company: Address: Phone I Fax: Design: SE01705E Cnnii.n�ni. n�,ni• 4.2 Pryout Strength '4Nc 1 —kcp [(ANcO� W ed,N Wc,N Wcp,N Nb J ,AVcp w Vcp > Vua ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b) 2 ANcO = 9 hef W ed,N = 0.7 + 0.3 Ca,min 1 < 1.0 1.5hef W cp,N = MAX(Ca—min 1.5hef) < 1.0 �Cac Cac 1. Ny = kc a, A, hef5 a Variables kcp hef [in.] Ca,min [in.] 2 2.750 6.000 ca, [in.] kc 2' a 10.000 21 1.000 Calculations ANc [in .2] ANcO [in .2] W ed,N 68.06 68.06 1.000 Results Vpp [lb] concrete seismic 9,577 0.700 1.000 Page: Specifier: E-Mail: Date: ACI 318-14 Eq. (17.5.3.1a) ACI 318-14 Table 17.3.1.1 ACI 318-14 Eq. (17.4.2.1c) ACI 318-14 Eq. (17.4.2.5b) ACI 318-14 Eq. (17.4.2.7b) ACI 318-14 Eq. (17.4.2.2a) yl c,N f� [psi] 2,500 Wcp.N Nb [lb] 1.000 4,788 �nonductile Vcp [lb] Vua [II 1.000 6,704 578 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 5 5/23/2022 5 Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Address: Phone I Fax: Design: SE01705E Fastening point: 4.3 Concrete edge failure in direction x+ AVc Vcb — (AV.) W ed,V Wc,V Wh,V wparallel,V Vb Vcb ? Vua Avc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b) 2 Avco = 4.5 Cal Wedv =0.7+0.3(1 .2 <1.0 1.5ca1 _ W h,V — h a > 1.0 Vb 7 1.5 Ada a "c Cal d a Variables Cal [in.] cat [in.] W c,v 4.000 6.000 1.200 a da [in.] fc [psi] 1.000 0.625 2,500 Calculations Avc [in.2] Av. [in.2] W ed,V 72.00 72.00 1.000 Results Vcb [I b] concrete seismic 3,572 0.700 1.000 Page: Specifier: E-Mail: Date: ACI 318-14 Eq. (17.5.2.1a) ACI 318-14 Table 17.3.1.1 ACI 318-14 Eq. (17.5.2.1c) ACI 318-14 Eq. (17.5.2.6b) ACI 318-14 Eq. (17.5.2.8) ACI 318-14 Eq. (17.5.2.2a) ha [in.] le [in.] 6.000 2.750 W parallel,V 1.000 Wh,v Vb [lb] 1.000 2,977 �nonductile Vcb [lb] Vua [I b] 1.000 2.501 578 5 Combined tension and shear loads RN Rv Utilization (3N,V [%] Status r� 0.290 0.231 5/3 22 OK RNV = RN + Rv <= 1 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 6 5/23/2022 6 Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Page: 7 Address: Specifier: Phone I Fax: E-Mail: Design: SE01705E Date: 5/23/2022 Fastening point: 6 Warnings • The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C, EOTA TR029 etc.). This means load re -distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for agreement with the existing conditions and for plausibility! • Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout or pryout strength governs. • Refer to the manufacturer's product literature for cleaning and installation instructions. • For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/ • An anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in ACI 318-14, Chapter 17, Section 17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c). • Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) / Section 17.2.3.5.3 (b) waive the ductility requirements and require the anchors to be designed for the maximum tension / shear that can be transmitted to the anchors by a non -yielding attachment. Section 17.2.3.4.3 (d) / Section 17.2.3.5.3 (c) waive the ductility requirements and require the design strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased by cuo. • Hilti post -installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI 318-14, Section 17.8.1. Fastening meets the design criteria! Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Page: 8 Address: Specifier: Phone I Fax: E-Mail: Design: SE01705E Date: 5/23/2022 Fastening point: 7 Installation data Profile: - Hole diameter in the fixture: - Plate thickness (input): - Drilling method: SafeSet - automatic cleaning Cleaning: Automatically performed while drilling Anchor type and diameter: Kwik Bolt TZ2 - SS 304 5/8 (2 3/4) hnom1 Item number: 2210277 KB-TZ2 5/8x4 1/4 SS304 Maximum installation torque: 722 in.lb Hole diameter in the base material: 0.625 in. Hole depth in the base material: 3.750 in. Minimum thickness of the base material: 5.000 in. Hilti KB-TZ2 stud anchor with 3.25 in embedment, 5/8 (2 3/4) hnom1, Stainless steel, installation per ESR-4266 7.1 Recommended accessories Drilling Cleaning • Suitable Rotary Hammer • Properly sized drill bit for SAFEset - automatic cleaning (TE-CD / TE-YD) • Vacuum cleaner Coordinates Anchor in. Anchor x y C-x 1 0.000 0.000 6.000 • No accessory required c,x c-y c•y 6.000 6.000 6.000 Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan Setting • Torque controlled cordless impact tool • Torque wrench • Hammer 0 Hilti PROMS Engineering 3.0.77 www.hilti.com Company: Page: 9 Address: Specifier: Phone I Fax: E-Mail: Design: SE01705E Date: 5/23/2022 Fastening point: 8 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use -specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you. Input data and results must be checked for conformity with the existing conditions and for plausibility! PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 Non -Structural Anchorage Calculator into Shelter Wall Site Conditions Sds = 1.024 Unit Constraints Component System (Al - B) ap = 1 Rp = 2.5 Unit Geometry Total Height of Structure (h) _ Height of Unit (z) = Center Mass of Unit (d) _ Least Horizontal Dimension (b) _ Unit Weight (W) = Fp = 0.4aps,,,WR(1+2z/h) = (RP/IP) A7 Tables 13.5-1, 13.6-1 Fp_max = 64 Fp_min = 12 Overturning Moment (Mo) _ Resisting Moment (Mr) _ Pullout at Anchorage = Worst Case Vertical Load = Seismic governs over wind with Pullout Shear Ip = 1 7 ft 3 ft 1.5 ft, moment arm 2 ft, for overturning resistance 39 Ibs 12 Load Combinations (1 + 0.2Sds)D +/- E (0.9 - 0.2Sds)D +/- E 1.2D + 1.OW 18 Ibs-ft vs. 0 Ibs-ft 47 Ibs-ft 9lbs vs. -23lbs 23 Ibs 12 > 0 Ibs 9 Ibs vs. 0 Ibs 51 Ibs 0 Ibs 3/8 in diameter x 1.5" long lag screws ATS located inside equipment shelter - NO wind forces ,I� acivantctge engineers Advantage Engineers, LLC 7151 Columbia Gateway Dr, Suite A Columbia, MD 21046 Diameter, D Screw Length, L Thread Length, T Tapered Tip Length, E Threaded Penetration, p Main Member Thickness Specific Gravity, G Side Member Thickness 3/8 in in in Table L2 in Table L2 in in 2x4 Assumed Hem -Fir in ASTM A36 Plate 1.5 1.25 0.2188 1.0313 3.5 0.43 0.120 Wet Service Factor, CM Temperature Factor, Ct Group Anchor Factor, Cg Geometry Factor, Co End Grain Factor, Ceg Diaphragm Factor, Cd; Toe -Nail Factor, Ctn Conversion Factor, KF Resistance Factor, (� Time Effect Factor, A 1 Table 11.3.3 Table 11.3.4 Equation 11.3-1 Section 12.5.1 Section 12.5.2 Section 12.5.3 Section 12.5.4 Table 11.3.1 Table 11.3.1 Table N.3.3 1 1 1 1 1 1 3.32 0.65 1 LRFD FACTORS ONLY Structural Analysis for T-Mobile SE01705E Hardening National Date: 05/23/2022 Prepared by: NAL Job Number: P-029949 Lateral Loads Z'=Z*CM*Ct*Cg*Co*Ceg*Cd;*Ct„*KF*c�*A Lateral Design Value, Zl Lateral Design Value, ZI I Penetraction Factor, p/8D Adjusted Lateral Design, Z'1 Adjusted Lateral Design, Z'I I Withdrawal Loads 120 Ibf 160 Ibf 0.34375 89.02 Ibf 118.69 Ibf Table 12K Table 12K W'=W*CM*Ct*Ce9*C,*KF*(0*A Withdrawal Design Value, W 243 Ibf/in Table 12.2A Adjusted Withdrawal, W'p 540.78 Ibf Lateral Usage 57.3% Withdrawal Usage 0.0% Combined Usage 57.3% SE01705E 7151 Columbia Gateway Dr., Suite A Hardening National 48kW Z.�Columbia, MD 21046 10/17/22 advantage engineers Phone:443.367.0003 Rev 1 '177 Slab on Grade Footing Design TP 0 CL M Does the slab have a Turndown? Y Y or N Turndown Depth 24 in Turndown Width 12 in Slab Thickness 6 in PaW (longer dimension) 9 ft PaL (shorter dimension) 4 ft Moment from W or S 9,822 Ibs-ft Dead Load On Slab 4,931 Ibs Pad Weight 9,300 Ibs Total Load 14,231 Ibs Eccentricity = M/P = 0.69 Bearing Pressure (Minimum is 0 if it matches Maximum) Maximum Bearing Pressure 805 Minimum Bearing Pressure 805 Outside Middle Third Check Resisting Moment 28,462 Net Moment -9,838 Slab Reinforcing Design OK OK Td W �1" PaL PaL = Pad Length P = Gravity Load PaW = Pad Width M = Moment TdW =Tumdown Width TdD = Tumdown Depth Bearing Pressure = Lateral Bearing = Coefficient of Friction = Seismic OR Wind (S/W) _ Lateral Bearing = Sliding Resistance = Factored Loads OK Moment Resisting Moment Total Load Reinforcing Required = 0.10 #4 at 12" OC 6 inch thick X 9 ft wide X 4 ft long concrete slab with #4 at 12" OC 24 in deep X 12 in wide TURNDOWN FOOTINGS REQUIRED Skin Friction = Skin Friction (MAX) _ Bearing Capacity = Total for Bearing = Total for Uplift = 1,500 psf 150 psf/f 0.1 S 120 psf/f 130 psf 9,822 25,616 12,808 1,941 Ibs 6,193 Ibs 13,500 Ibs 15,441 Ibs 1,941 Ibs