ECE-PRCCECA-DRZB_SUBMITTAL_1Date:
Weights:
Units:
Part Number:
gMicroMet l
8/23/2017
1761bs/79.83kg
ECE-PRCCECA-DRZB
Submitted To:
Job:
Notes:
Economizer - Ultra Low Leak Economizer, Horizontal Orientation, ReliaTel Controller, Differential Enthalpy Sensor, Belimo Actuator. Painted
Rain Hood With Aluminum Filter, Barometric Relief, All Necessary Panels And Hardware Included. A RTVM Ventilation Module Is Required
From Trane Factory When A CO2 Sensor Is Combined With Any Of The Following...
Multi -Speed, VAV, Or Zone Sensor.
External, gear driven Direct coupled
dampers. actuators.
.0"
Return air damper
(external)
18.4"
and sleave.
30.0" 20.375"
Stainless steel blade
side seal on return and
Actuator access.
outside air blades.
R/A
Outside air damper
O/A
and hood.
O
Relief hood.
Mounts on return air duct.
Damper Side View
The Information contained in this drawing is the sole property of Micrometl Corporation. Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited.
Indianapolis_3035 N. Shadeland Ave., Indianapolis, IN 46226_800.MMC.HVAC -- Sparks_905 Southern Way, Sparks, NV 89431_800.884.4MMC -- Longview_201 Kodak Blvd., Longview, TX 75602_903.248.4800
Date:
Weights:
Units:
Part Number:
gMicroMet l
1761bs/79.83kg
8/23/2017
ECE-PRCCECA-DRZB
Submitted To:
Job:
Notes:
Economizer - Ultra Low Leak Economizer, Horizontal Orientation, ReliaTel Controller, Differential Enthalpy Sensor, Belimo Actuator. Painted
Rain Hood With Aluminum Filter, Barometric Relief, All Necessary Panels And Hardware Included. A RTVM Ventilation Module Is Required
From Trane Factory When A CO2 Sensor Is Combined With Any Of The Following... Multi -Speed, VAV, Or Zone Sensor.
Compliant Economizer:
1. Title 24: Economizers meet California Energy Commission Title 24-2013 / 2016 prescriptive section 140.4 (damper leakage etc.), and when used with ReliaTel TM controls and field
supplied TracerTm TD-5 Display Module, meet mandatory section 120.2.i for Fault Detection and Diagnostic requirements.
2. ASHRAE 90.1: Economizers meetASHRAE 90.1-2013/2016 damper leakage requirements as stated in Table 6.4.3.4.3., and meet 2016 Fault Detection and Diagnosis requirements
in section 6.4.3.12 when used with ReliaTel TM control systems.
3. IECC: Economizers meet IECC 2012 section C402.4.5.2 and, IECC 2015 sections C403.2.4.3 and C403.3.3.5 for outside air, return air, and relief damper (when provided) leakage
requirements, and when used with ReliaTel TM controls and field supplied TracerTm TD-5 Display Module control systems meet IECC 2015 section C403.2.4.7 for Fault Detection and
Diagnostic requirements. Note: IECC 2015 section C403.2.4.7.1 requires differential return air sensor, which must be ordered separately.
4. AMCA: Outside air and return air (volume) dampers are AMCA Class 1A rated at 1" w.g. Refer to MicroMetl NS1 catalog sheet on web site for details. Relief air dampers (when
provided) are also AMCA rated. Refer to GR1 series catalog sheet on web site for details.
Features:
• Gear driven design for trouble -free operation, eliminating slippage and binding associated with standard linkage.
• Includes assembled rainhood with aluminum water entrainment filters in the outside air section. AIR
IERNRGF
• Rainhood is sloped for water run-off. AIR
PERfORR1RROE
• Power exhaust options available.
• Logic wiring is field supplied and installed between the commercial 2 stage thermostat and HVAC low voltage terminal board.
MicroMetl Corporation
certifies that the models
GR1 and NS1 shown
herein are licensed to bear
the AMCA Seal.
The ratings shown are
based on tests and
procedures performed in
accordance with AMCA
Publication 511 and
comply with requirements
of the AMCA Certified
Ratings Programs.
The AMCA Certified
Ratings Seal applies
to Air Leakage and Air
Performance ratings.
The Information contained in this drawing is the sole property of Micrometl Corporation. Any reproduction in part or whole without the written permission of Micrometl Corporation is prohibited.
Indianapolis_3035 N. Shadeland Ave., Indianapolis, IN 46226_800.MMC.HVAC -- Sparks_905 Southern Way, Sparks, NV 89431_800.884.4MMC -- Longview_201 Kodak Blvd., Longview, TX 75602_903.248.4800