FIR2023-0120+Fire_Sprinkler_Equipment_Specification_Sheets+12.14.2023_12.44.09_PM+3953160FIR2023-0120
Bulletin 006 May 2019
Reliably
RECEIVED
Features Dec 14 2023
ONDS
• cULus Listed as Residential Sprinklers CILOPMTY OF E T SERVICES
p DEVELOPMENT SERVICES
• Push -On cover plate installation DEPARTMENT
• Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626. In addition, Model RFCLL Series
sprinklers are cULus Certified for Health Effects to NSF/ANSI
standard 61 Annex G (ILL) and Australian WaterMark Certified
(WMCS).
Model RFC30 sprinklers have a 1650F (74°C) temperature
rated fusible -link operating element. Model RFC43, RFC49,
RFC58, and RFC76 sprinklers are offered with either a 1650F
(74°C) or 212OF (100°C) temperature rated fusible -link oper-
ating element. Sprinklers with a 1650F (74°C) temperature
rating are ordinary temperature classification and are listed
for use with a 1350F (57°C) temperature rated cover plate.
Sprinklers with a 212OF (100°C) temperature rating are inter-
mediate temperature classification and are listed for use with
a 1650F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by ei-
ther pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49 and
RFC49LL sprinklers allow 1/2" (13 mm) of cover plate adjust-
ment. Model RFC58 and RFC76 sprinklers allow 3/4" (19 mm)
of cover plate adjustment. Model RFC cover plates are avail-
able in a variety of finishes as listed in Table H.
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
Model RFC30 & RFC30LL
Model RFC49 & RFC49LL
Model RFC76
cULus Listed
Model RFC43 & RFC43LL
Model RFC58
�ft
i
Model RFC Cover Plate
Sprinkler Model
Nominal K-Factor
gpm/psi (1/min/barl/2 )
Max. Coverage Area
ft x ft (m x m)
Listings &
Approvals
Sprinkler Identification
Number (SIN)
RFC30
3.0(43)
14 x 14 (4.3 x 4.3)
cULus
RA0611
RFC30LL
3.0(43)
14 x 14 (4.3 x 4.3)
cULus, ILL, WMCS
RA3211
RFC43
4.3(62)
20 x 20 (6.1 x 6.1)
cULus
RA0612
RFC43LL
4.3(62)
20 x 20 (6.1 x 6.1)
cULus, ILL, WMCS
RA3212
RFC49
4.9(71)
20 x 20 (6.1 x 6.1)
cULus
RA0616
RFC49LL
4.9(71)
20 x 20 (6.1 x 6.1)
cULus, ILL, WMCS
RA3216
RFC58
5.8(84)
20 x 20 (6.1 x 6.1)
cULus
RA0613
RFC76
7.6(109)
20 x 20 (6.1 x 6.1)
WILLIS
RA0618
WLus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service.
ILL cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC30LL only)
Watermark Certified (RFC30LL only)
Model RFC30 & RFC30LL Sprinkler Components and Dimensions
O [ •1@ V
Bottom View
2-5/16" (58 mm) _
Threads Dia.
Body_-
Cup -
Tower
1-3/4" (44 mm) +/- 1/4" (6 mm)
Fusible Link Nominal face of fitting to ceiling
Deflector (retracted)
Pin (extended) _
Deflector (extended)
Model RFC Cover Plate 3-5/16" (84 mm) Dia
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria
—3/16"(5mm'
Ceiling
Minimum Flow and Residual Pressure
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
12 x 12
9
9.0
(3.6 x 3.6)
(34)
(0.62)
14 x 14
10
11.0
(4.3 x 4.3)
(38)
(0.76)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliably Page 2 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC43LL only)
Watermark Certified (RFC43LL only)
Model RFC43 & RFC43LL Sprinkler Components and Dimensions
a• � N
Bottom View 11
f
2-5/16" (58 mm)
Threads Dia.
Body -
Cup - �=
Tower 1-3/4" (44 mm) +/- 1/4" (6 mm)
Fusible Link Nominal face of fitting to ceiling
Deflector (retracted) I 3/16" (5 mm;
Pin (extended) I I I I
Deflector (extended)1
Model RFC Cover Plate 3-5/16" (84 mm) Dia. — Ceiling
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area
Ordinary Temperature
Intermediate Temperature
Flow
Pressure
Flow
Pressure
ft. x ft.
(m x m)
gpm
psi
gpm
psi
(1/min)
(bar)
(1/min)
(bar)
15 x 15
12
7.8
12
7.8
(4.6 x 4.6)
(45)
(0.54)
(45)
(0.54)
16 x 16
13
9.1
13
9.1
(4.9 x 4.9)
(49)
(0.63)
(49)
(0.63)
18 x 18
18
17.5
(5.5 x 5.5)
(68)
(1.21)
20 x 20
21
23.8
(6.1 x 6.1)
(79)
(1.64)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliably Page 3 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.9 (71 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Sensitivity
Fast -response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
Cover Plate Finishes cULus Listed to UL 1626
(See Table H) cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC49LL only)
Watermark Certified (RFC49LL only)
Model RFC49 & RFC49LL Sprinkler Components and Dimensions
Threads
Body =
Cup
Tower
Fusible Link
Deflector (retracted)
Pin (extended)
Deflector (extended)
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Bottom View
2-5/16" (58 mm)
Dia.
I 1� iiiiiii _[3/16"(5mm'
Model RFC Cover Plate 3-5/16" (84 mm) Dia. \-- Ceiling
Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure M
Max. Coverage Area()
Ordinary Temperature
Intermediate Temperature
Flow
Pressure
Flow
Pressure
ft. x ft.
(m x m)
gpm
psi
gpm
psi
(1/min)
(bar)
(1/min)
(bar)
16 x 16
13
7.0
13
7.0
(4.9 x 4.9)
(49.0)
(0.48)
(49.0)
(0.48)
18 x 18
17
12.0
17
12.0
(5.5 x 5.5)
(64.3)
(0.83)
(64.3)
(0.83)
20 x 20
20
16.7
21
18.4
(6.1 x6.1)
(75.7)
(1.15)
(79.5)
(1.27)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliably Page 4 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed
Model RFC58 Sprinkler Components and Dimensions
Threads —
Body
Cup
Tower
Fusible Link —
Deflector (retracted)
Pin (extended)
Deflector (extended) -
Bottom View
2-5/16" (58 mm)
Dia.
--M-
1-7/8" (48 mm) +/- 3/8" (9 mm)
Nominal face of fitting to ceiling
1 ElJ�3/16"(5mm'
Model RFC Cover Plate � i 3-5/16" (84 mm) Dia. \-- Ceiling
Model RFC58 Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure(')
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
16
7.6
(4.9 x 4.9)
(60.6)
(0.53)
18 x 18
18
9.6
(5.5 x 5.5)
(68.1)
(0.66)
20 x 20
20
11.9
(6.1 x 6.1)
(75.7)
(0.82)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliably Page 5 of 8
May 2019 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-Factor: 7.6 (109 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast -response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC (without wrench -able cap)
Model W3 (with wrench -able cap)
Listings and Approvals
cULus Listed
Model RFC76 Sprinkler Components and Dimensions
Three
Body
Cup
Towei
Fusible Li
Deflector (retra
Pin (extent
Deflector (extend
1-7/8" (48 mm) +/- 3/8" (9 mm)
Nominal face of fitting to ceiling
Model RFC Cover Plate
Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria
Bottom View ° Z
i
2-5/16" (58 mm)
Dia.
3-5/16" (84 mm) Dia.
3/16" (5 mm)
Ceiling
Minimum Flow and Residual Pressure(')
Max. Coverage Area (2)
Flow
Pressure
ft. x ft.
gpm
psi
(m x m)
(1/min)
(bar)
16 x 16
21
7.6
(4.9 x 4.9)
(79.5)
(0.52)
18 x 18
24
9.9
(5.5 x 5.5)
(90.8)
(0.68)
20 x 20
34
20
(6.1 x 6.1)
(128.7)
(1.4)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Reliable Page 6 of 8
May 2019 www.reliablesprinkler.com
Cover Plate Finishes')
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Black Plated
Satin Chrome Stainless Steel Clad(3) Custom Color Paint(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi -gloss, unless specified otherwise.
3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside. Cover plates
are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Installation Dimensions
Recommended
Min. to
Min. to Max.
Sprinkler
Cover
Cover Plate
Hole Diameter
Cover Plate
Max. Face
Dropped Deflector
Cover Plate
Model
Plate
Diameter
in Ceiling
Adjustment
of Fitting to
Distance below
Temperature
Model
inch (mm)
inch (mm)
inch (mm)
Ceilings')
Ceiling
Rating
inch (mm)
inch (mm)
RFC30,
RFC
3-5/16
2-5/8
1/2
1-1/2 to 2
1/2 to 1
1350F
RFC30LL
(84)
(67)
(13)
(38 to 51)
(13 to 25)
(57°C)
RFC43,
1350F(2)
RFC43LL,
RFC
3-5/16
2-5/8
1/2
1-1/2 to 2
1/2 to 1
(57°C)
RFC49,
(84)
(67)
(13)
(38 to 51)
(13 to 25)
or 1650F3>
RFC49LL
(74°C)
1350F(2)
RFC58,
RFC
3-5/16
2-5/8
3/4
1-1/2 to 2-1/4
1/4 to 1
(57°C)
RFC76
(84)
(67)
(19)
(38 to 57)
(6 to 25)
or 1650F3>
(74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method
prior to installation. A 1/2" x 1/2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing
sprinklers.
2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C).
3. For use with 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (66°C).
Installation
Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the
requirements of applicable authorities having jurisdiction. Mod-
el RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a wrench -able protec-
tive cap that should remain on the sprinkler until the sprinkler
system is placed in service following construction.
Model RFC series sprinklers can be installed without removing
the wrench -able protective cap using the Model W3 wrench.
Alternatively, Model RFC series sprinklers can be installed us-
ing the Model FC wrench by temporarily removing the protec-
tive cap during installation of the sprinkler. The use of any other
wrench to installed Model RFC series sprinklers is not permit-
ted and may damage the sprinkler. Fully insert the Model W3
wrench over the cap until it reaches the bottom of the cup, or
the Model FC wrench over the sprinkler until the wrench engag-
es the body. Do not wrench any other part of the sprinkler/cup
assembly. The Model W3 and FC wrenches are designed to be
turned with a standard 1/2" square drive. Tighten the sprinkler
into the fitting after applying a PTFE based thread sealant to the
sprinkler's threads. Recommended installation torque is 8 to 18
ft-Ibs (11 to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-Ibs
(19 to 27 N-m) for 3/4" thread sprinklers.
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into
the cup and turning the cover in the clockwise direction until it
is tight against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 13D. The sprinklers are concealed pen-
dent residential sprinklers.
Model RFC 30 and RFC30LL sprinklers are available in ordinary
temperature classification for installation where the Maximum
Ceiling Temperature does not exceed 100°F (38°C). Model
RFC43, RFC43LL, RFC49, RFC49LL, RFC58, and RFC76 sprin-
klers are available in either ordinary or intermediate tempera-
ture classification for installation where the Maximum Ceiling
Temperature does not exceed 100°F (38°C) or 150°F (66°C),
respectively.
Bulletin 006
May 2019
Page 7 of 8
www.reliablesprinkler.com
Model FC
For use with Model RFC Series sprinklers
without wrench -able cap installed
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non -oper-
ation.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada to UL1626, Residential Sprinklers for Fire -protection
Service (cULus).
Certified by Underwriters Laboratories, Inc. and Underwrit-
ers Laboratories of Canada for Health Effects to NSF/ANSI
Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL
only).
Australian WaterMark Certified (RFC30LL, RFC43LL, and
RFC49LL only).
Am
Model W3
For use with Model RFC Series sprinklers
with wrench -able cap installed
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL,
RFC58, and RFC76 sprinklers are covered by U.S. Patent No.
9,248,327 and U.S. Patent No. 7,275,603.
Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are
additionally covered by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model (RFC30, RFC30LL, RFC43, RFC43LL,
RFC49, RFC49LL, RFC58, RFC76)
• Temperature Rating
Cover Plate
• Model RFC
• Temperature Rating
• Finish (See Table H)
Sprinkler Wrench
• Model FC
• Model W3
v
co
co
co
co
0
N
Bulletin 006 Reliable Page 8 of 8
May 2019 www.reliablesprinkler.com
UponorAquaPEX°White, coils
Submittal information
Revision M: Sept. 18, 2018
Project information
Job name:
Location: Part no. ordered:
Uponof
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved by:
Technical data
Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5106
Standard grade hydrostatic ratings (PPI): 200T (93°C) at 80 psi (551 kPa)
180T (82°C) at 100 psi (689 kPa)
73AT (23°C) at 160 psi (1,103 kPa) -
'/2', 3/4", 1", 1'/4", 1'/2" and 2" Uponor AquaPEX° White only: - ---
120T (49°C) at 130 psi (896 kPa) ^
Linear expansion rate: 1.1"MOT/100' (27.94mm/5.56°C/30.48m)
Product information and application use f
Uponor AquaPEX White is used for hot and cold domestic potable water distribution and residential fire safety as well
as radiant heating/cooling and hydronic piping systems containing no ferrous corrodible components or where ferrous
components are isolated from the piping.
✓ Description
Part number
I.D.
O.D.
Weight
'/4' Uponor AquaPEX White, 100-ft. coil
F1040250
0.241"
0.375"
4.0 lbs.
%" Uponor AquaPEX White, 400-ft. coil
F1090375
0.350"
0.500"
20.0 lbs.
%" Uponor AquaPEX White, 1,000-ft. coil
F1120375
0.350"
0.500"
44.0 lbs.
/2' Uponor AquaPEX White, 100-ft. coil
F1040500
0.475"
0.625"
6.0 lbs.
/2" Uponor AquaPEX White, 300-ft. coil
F1060500
0.475"
0.625"
18.0 lbs.
/2" Uponor AquaPEX White, 500-ft. coil
F1100500
0.475"
0.625"
27.6 lbs.
/2" Uponor AquaPEX White, 1,000-ft. coil
F1120500
0.475"
0.625"
54.0 lbs.
%" Uponor AquaPEX White, 300-ft. coil
F1060625
0.574"
0.750"
28.0 lbs.
%" Uponor AquaPEX White, 1000-ft. coil
F1120625
0.574"
0.750"
86.0 lbs.
%" Uponor AquaPEX White, 100-ft. coil
F1040750
0.671"
0.875"
10.0 lbs.
3/4' Uponor AquaPEX White, 300-ft. coil
F1060750
0.671"
0.875"
34.0 lbs.
3/4' Uponor AquaPEX White, 500-ft. coil
F1100750
0.671"
0.875"
54.0 lbs.
1" Uponor AquaPEX White, 100-ft. coil
F1041000
0.862"
1.125"
20.0 lbs.
1" Uponor AquaPEX White, 300-ft. coil
F1061000
0.862"
1.125"
56.0 lbs.
1" Uponor AquaPEX White, 500-ft. coil
F1101000
0.862"
1.125"
93.0 lbs.
1'/4" Uponor AquaPEX White, 100-ft. coil
F1061250
1.054"
1.375"
34.0 lbs.
1'/4' Uponor AquaPEX White, 300-ft. coil
F1021250
1.054"
1.375"
106.0 lbs.
1'/2" Uponor AquaPEX White, 100-ft. coil
F1061500
1.244"
1.625"
44.0 lbs.
1'/2" Uponor AquaPEX White, 300-ft. coil
F1021500
1.244"
1.625"
133.0 lbs.
2" Uponor AquaPEX White, 100-ft. coil
F1062000
1.629"
2.125"
68.2 lbs.
2" Uponor AquaPEX White, 200-ft. coil
F1052000
1.629"
2.125"
136.4 lbs.
2" Uponor AquaPEX White, 300-ft. coil
F1022000
1.629"
2.125"
204.6 lbs.
2'/2" Uponor AquaPEX White, 100-ft. coil
F1062500
2.011"
2.625"
88.0 lbs.
2'/2" Uponor AquaPEX White, 300-ft. coil
F1022500
2.011"
2.625"
264.0 lbs.
3" Uponor AquaPEX White, 100-ft. coil
F1063000
2.400"
3.125"
128.0 lbs.
3" Uponor AquaPEX White, 300-ft. coil
F1023000
2.400"
3.125"
384.0 lbs.
Installation
Use ProPEX® fittings for %" through 3" pipe.' Refer to the ProPEX Connections Instructional
Guide, Uponor Piping Pocket Guide, Plumbing Design
Assistance
Manual (PDAM), Complete Design Assistance Manual (CDAM), Hydronic Piping
Design Assistance Manual (HPDAM) or
AquaSAFETm Residential Fire Sprinkler
Installation Guide for more information.
Listings2 Codes
Standards
cNSFus-fs3; cNSFus-pw; cQAlus P321; UL; IAPMO; ICC; IPC; IMC; IRC;
ANSI/NSF 14; ANSI/NSF 61; ASTM
F876; ASTM F877; ASTM F1960; ASTM
CSA; PPI TR-4; ICC-ES; BMEC; CCMC UPC; UMC; NSPC; HUD;
F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101;
UFGS; NPC of Canada;
ASTM E814/ULC S115; CSA
B137.5; CSA B214;
NBC of Canada
UL 18213; ULC/ORD-C199P3; AWWA C9044
Related applications
Contact information
PEX-a plumbing systems
Uponor, Inc.
Uponor Ltd.
AquaSAFETM fire safety systems
5925 148th Street West
6510 Kennedy Road
Radiant heating and cooling systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Hydronic piping systems
Phone: 800.321.4739
Phone: 888.994.7726
Fax: 952.891.2008
Fax: 800.638.9517
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor, Inc. ProPEX'" is a trademark of Uponor Ltd.
2Visit listing agency's website for complete information. 3For'/4", 1" and 1'/4" pipe only.4For
W to 3" pipe.
ProPEX° Ring
Submittal information
Revision I: Nov. 1, 2018
Project information
Job name:
Location: Part no. ordered:
Engineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved by:
Technical data
Material: Engel -method crosslinked polyethylene (PEX-a)
Density: 926 to 940 kg/m3
Degree of crosslinking: 70% to 89%
Product information and application use
Uponor ProPEX® rings are required to make a proper ProPEX connection.' The ProPEX
ring with stop includes a leading edge chamfer and stop edge.
uponof
✓ Description
Part number
Length
I.D.
O.D.
Weight
ProPEX Ring, %"
Q4690302
0.54"
0.49"
0.74"
0.005 lbs.
ProPEX Ring with Stop, ''/2"
Q4690512
0.63"
0.63"
0.87"
0.006 lbs.
ProPEX Ring with Stop, 5/8'
Q4690625
0.79"
0.75"
1.00"
0.008 lbs.
ProPEX Ring with Stop, 3/4'
Q4690756
0.87"
0.88"
1.13"
0.012 lbs.
ProPEX Ring with Stop, 1"
Q4691000
1.10"
1.13"
1.42"
0.020 lbs.
ProPEX Ring with Stop, 1'/4'
Q4691250
1.35"
1.38"
1.66"
0.030 lbs.
ProPEX Ring with Stop, 1'/2"
Q4691500
1.61"
1.63"
1.91"
0.040 lbs.
ProPEX Ring with Stop, 2"
Q4692000
1.97"
2.14"
2.61"
0.133 lbs.
ProPEX Ring with Stop, 2'/z'
Q4692500
2.61"
2.66"
3.25"
0.230 lbs.
ProPEX Ring with Stop, 3"
Q4693000
3.12"
3.16"
3.87"
0.400 lbs.
Installation
Square cut the Uponor PEX tubing. Remove excess material. Slide the ProPEX ring over the end of the tubing (maximum Ihd' over -hang for rings without stop).
When using the ProPEX ring with stop, slide the ring on the tubing with the chamfered edge first until the end of the tubing contacts the stop edge. Expand the
tubing and ring. If using the ProPEX Manual Expander Tool, rotate the tool a quarter turn after each expansion to prevent the formation of grooves. Remove the
expansion tool and fully seat the tubing and ring against the shoulder of the fitting. Make ProPEX connections at temperatures above 5°F/-15°C. For more
information, refer to the Uponor ProPEX Connections Instructional Guide.
Listings2
cNSFus-fs3; cNSFus-pw; cNSFus-rfh; cQAlus; UL; CSA; PPI TR-4; ICC-ES; IAPMO; BMEC; CCMC; cQAlus P321
Codes
ICC; IPC; IMC; IRC; UPC; UMC; NSPC; HUD; UFGS; NPC of Canada; NBC of Canada
Standards
ANSI/NSF 14; ANSI/NSF 61; ASTM F876; ASTM F877; ASTM F1960; ASTM F2023; ASTM E84; CAN/ULC S102.2; ASTM E119/UL 263; CAN/ULC S101; ASTM
E814/ULC S115; CSA B137.5; CSA B214; UL 18213; ULC/ORD-C199P3
Related applications Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
AquaSAFE fire safety systems
5925 148th Street West
6510 Kennedy Road
Hydronic radiant heating and cooling systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Snow melting systems
Phone: 800.321.4739
Phone: 888.994.7726
Turf conditioning systems
Fax: 952.891.2008
Fax: 800.638.9517
Permafrost prevention systems
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd.
'Visit listing agency's website for complete information; 3For%", 3/<", 1", 1'/4", 1'/" and 2" tubing only
ProPEX° Engineered Polymer (EP) Tee
Submittal information
Revision H: May 23, 2019
Project information
Job name:
Location: Part no. ordered:
Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved bv:
Technical data
Material:
Maximum temperature (no pressure):
Maximum working temperature/pressure:
Engineered polymer (EP)
320°F (160°C)
210'F (99'C) at 150 psi (1,034 kPa)
Product information and application use
ProPEX° engineered polymer (EP) tees make diverting connections for Uponor crosslinked
polyethylene (PEX-a) tubing for use in hot and cold domestic potable water systems,
residential fire sprinkler systems and hydronic radiant heating and cooling systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX° or Wirsbo hePEXTM tubing.'
Note: Branch size is listed last in the part descriptions.
uponof
✓ Description
Part
A
B
Weight
Equivalent
length
Equivalent
length
number
(ft.)
(ft.)
through
branch
through
branch
ProPEX EP Tee, %" PEX x %" PEX x %" PEX
Q4755050
2.50"
1.53"
0.02 Ibs.
1.0
6.3
7.7
3.4
ProPEX EP Tee, '/<" PEX x'/<" PEX x'/" PEX*
Q4757575
3.30"
1.94"
0.05 Ibs.
1.5
15.6
15.7
5.4
ProPEX EP Tee, 1" PEX x 1" PEX x 1" PEX*
Q4751010
4.10"
2.47"
0.07 Ibs.
1.3
12.7
30.5
11.3
ProPEX EP Tee, 1'/" PEX x 1'/" PEX x 1'/" PEX*
Q4751313
4.80"
3.22"
0.15 Ibs.
3.8
8.6
34.0
23.9
ProPEX EP Tee, 1'/z" PEX x 1'/z" PEX x 1'/z" PEX
Q4751515
5.80"
3.82"
0.25 Ibs.
1.8
10.6
63.7
31.0
ProPEX EP Tee, 2" PEX x 2" PEX x 2" PEX
Q4752000
7.45"
4.79"
0.38 Ibs.
0.8
15.5
150.7
52.5
ProPEX EP Tee, 2'/" PEX x 2'/" PEX x 2'/" PEX
Q4752500
10.56"
5.45"
1.14 Ibs.
2.7
22.3
197.2
81.5
ProPEX EP Tee, 3" PEX x 3" PEX x 3" PEX
Q4753000
12.26"
6.37"
1.86 Ibs.
2.8
23.9
286.6
122.8
Installation
Use the appropriate ProPEX Ring for PEX-a tubing. Refer
to the Uponor Professional
Plumbing
Installation Guide, AquaSAFETM Residential
Fire Sprinkler
Installation
Guide or Uponor Radiant Installation Handbook for additional information.
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM F1960; CAN/CSA B137.5; NSF 14;
NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; *cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; *UL 1821; *ULC/ORD-C199P; U.P. Code
Related applications Contact information
PEX-a plumbing systems
Uponor, Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 148'h Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFETM fire safety systems
uponorpro.com
uponorpro.com
'ProPEX®is a registered trademark of Uponor, Inc. ProPEX` is a trademark of Uponor Ltd.
ProPEX° Engineered Polymer (EP) Reducing Tee (up to 11/2") Uporlof
Submittal information
Revision I: Sept. 16, 2019
Project information
Job name:
Location: Part no. ordered:
Engineer:
Date submitted:
Contractor:
Submitted by:
Manufacturer's representative: Approved by:
Technical data
A
Material: Engineered polymer (EP)
Maximum temperature (no pressure): 320°F (160°C)
Max. working temperature/pressure: 210°F (99*C) at
150 psi (1,034
kPa)
Product information and application use
ProPEX® engineered polymer (EP) reducing tees make diverting connections for Uponor PEX-a pipe for use in hot
and cold
e
domestic potable water systems, residential fire sprinkler systems and hydronic radiant heating and cooling
systems. Each
end of the tee is manufactured with an Uponor ProPEX fitting for connections to Uponor
Note: Branch size is listed last in the descriptions.
AquaPEX® or W
irsbo hePEXT"
pipe.' part
✓ Description
Part
A
B
Weight
Equiv. length (ft.)
Equiv. length
Cv
Cv
number
through
(ft.) branch
through
branch
ProPEX EP Reducing Tee, Yi' PEX x Yi' PEX x %" PEX
Q4755575
2.86"
1.76"
0.03 lbs.
1.0
15.6
7.7
5.4
ProPEX EP Reducing Tee, '/;' PEX x Yi' PEX x Yi' PEX
Q4757555
3.10"
1.70"
0.04 lbs.
3.5
6.4
4.6
3.4
ProPEX EP Reducing Tee, '/;' PEX x'/z' PEX x'/;' PEX*
Q4757557
3.10"
1.94"
0.04 lbs.
2.3
16.1
5.4
5.4
ProPEX EP Reducing Tee, '/;' PEX x'/;' PEX x 5/a' PEX
Q4757563
3.30"
1.85"
0.05 lbs.
N/A
N/A
N/A
N/A
ProPEX EP Reducing Tee, '/;' PEX x'/;' PEX x'/z' PEX*
Q4757550
3.30"
1.70"
0.04 lbs.
2.0
7.6
14.2
3.1
ProPEX EP Reducing Tee, '/;' PEX x'/;' PEX x 1" PEX*
Q4757710
3.64"
2.32"
0.08 lbs.
1.5
5.7
15.7
8.7
ProPEX EP Reducing Tee, 1" PEX x'/;' PEX x 1" PEX
Q4751501
3.71"
2.43"
0.09 lbs.
1.98
9.7
12.3
5.7
ProPEX EP Reducing Tee, 1" PEX x'/;' PEX x'/, PEX
Q4751750
3.65"
1.96"
0.07 lbs.
2.27
6.69
3.1
13.2
ProPEX EP Reducing Tee, 1" PEX x'/," PEX x %" PEX*
Q4751775
3.90"
2.24"
0.08 lbs.
2.4
16.7
12.8
5.3
ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x 1" PEX*
Q4751751
3.90"
2.47"
0.08 lbs.
2.4
15.1
12.9
10.5
ProPEX EP Reducing Tee, 1" PEX x'/<" PEX x 1%" PEX
Q4751753
4.15"
2.95"
0.12 lbs.
2.74
19.48
14.7
12.0
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x'/2' PEX*
Q4751150
4.10"
2.00"
0.08 lbs.
1.2
6.5
32.2
3.4
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x %" PEX*
Q4751175
4.10"
2.24"
0.09 lbs.
1.7
6.4
27.8
8.2
ProPEX EP Reducing Tee, 1" PEX x 1" PEX x 1 %" PEX*
Q4751113
4.38"
2.95"
0.13 lbs.
6.52
5.37
15.0
28.0
ProPEX EP Reducing Tee, 1'/;" PEX x'/:' PEX x'/;' PEX*
Q4751377
4.11"
2.38"
0.09 lbs.
2.74
7.41
7.3
12.0
ProPEX EP Reducing Tee, 11/4" PEX x'/;' PEX x 1" PEX*
Q4751371
4.37"
2.62"
0.11 lbs.
2.70
7.59
13.9
12.1
ProPEX EP Reducing Tee, 1 Y;' PEX x 3/;' PEX x 1'/;' PEX*
Q4751373
4.61"
2.88"
0.13 lbs.
2.74
11.91
18.8
12.0
ProPEX EP Reducing Tee, 1 Y;' PEX x 1" PEX x %" PEX*
Q4751317
4.50"
2.73"
0.11 lbs.
3.4
5.2
21.0
9.3
ProPEX EP Reducing Tee, 1'/;' PEX x 1" PEX x 1" PEX*
Q4751311
4.70"
2.97"
0.12 lbs.
11.0
23.0
11.7
8.4
ProPEX EP Reducing Tee, 1%" PEX x 1%" PEX x'/z' PEX*
Q4751350
4.40"
2.15"
0.10 lbs.
1.9
3.9
45.2
4.1
ProPEX EP Reducing Tee, 1%" PEX x 1%" PEX x %" PEX*
Q4751337
4.70"
2.73"
0.13 lbs.
2.3
5.7
43.4
8.9
ProPEX EP Reducing Tee, 1%" PEX x 1%" PEX x 1" PEX*
Q4751331
5.00"
2.97"
0.14 lbs.
4.2
6.3
33.0
15.8
ProPEX EP Reducing Tee, 11/2" PEX x'/;' PEX x %" PEX
Q4751577
4.37"
2.64"
0.13 lbs.
2.88
7.41
7.3
11.7
ProPEX EP Reducing Tee, 11/2" PEX x'/e" PEX x 1'/i' PEX
Q4751575
4.97"
3.39"
0.19 lbs.
2.74
19.10
22.9
12.0
ProPEX EP Reducing Tee, 11/2" PEX x 1" PEX x %" PEX
Q4751517
5.25"
3.06"
0.17 lbs.
4.0
5.1
19.5
9.3
ProPEX EP Reducing Tee, 11/2" PEX x 1" PEX x 1" PEX
Q4751511
5.25"
3.30"
0.18 lbs.
4.3
6.5
18.9
15.6
ProPEX EP Reducing Tee, 1'/z" PEX x 1" PEX x 1'/z' PEX
Q4751505
5.40"
3.45"
0.20 lbs.
4.2
14.9
19.0
26.5
ProPEX EP Reducing Tee, 1'/z" PEX x 1%" PEX x %" PEX
Q4751537
5.50"
2.65"
0.18 lbs.
4.2
11.3
33.1
6.3
ProPEX EP Reducing Tee, 1'/z' PEX x 1%" PEX x 1" PEX
Q4751531
5.50"
2.85"
0.19 lbs.
3.1
13.1
36.4
11.2
ProPEX EP Reducing Tee, 1'/z" PEX x 1%" PEX x 1%" PEX
Q4751533
5.50"
3.15"
0.21 lbs.
2.0
17.7
45.4
17.0
ProPEX EP Reducing Tee, 11/2" PEX x 1'/i' PEX x'/i' PEX
Q4751550
4.95"
2.30"
0.14 lbs.
2.4
6.3
60.5
3.4
ProPEX EP Reducing Tee, 1 Yi' PEX x 1'/z' PEX x %" PEX
Q4751557
5.30"
3.06"
0.20 lbs.
2.9
5.4
56.0
9.0
ProPEX EP Reducing Tee, 11/2" PEX x 1'/z" PEX x 1" PEX
Q4751551
5.75"
3.30"
0.21 lbs.
3.1
6.9
53.8
15.3
ProPEX EP Reducing Tee, 11/2" PEX x 1'/i' PEX x 1%" PEX
Q4751553
5.80"
3.56"
0.22 lbs.
3.2
4.1
54.3
33.7
Installation
Use the appropriate ProPEX ring for PEX-a pipe. Refer to the Uponor Piping Systems Installation
Guide,
the AquaSAFETm Residential Fire
Sprinkler Installation Guide or the Uponor
Radiant Installation Handbook for additional information.
Standards Codes
Listings
ASTM E84; ASTM Ell 19; ASTM E814; IBC; IMC; IPC; IRC;
NPC of Canada;
cNSFus-pw; *cNSFus-pw-fs;
cQAlus P321;
HUD MR 1269; ICC-ES-PMG-1006;
ASTM F877; ASTM F1960; NSPC; UMC; UPC
ICC-ES-PMG-1012;
*UL 1821; *ULC/ORD-C199P; U.P. Code
CAN/CSA B137.5; NSF 14; NSF 61
Related applications
Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 148t' Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley, MN 55124
USA
Mississauga, ON L5T 2X4
CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFETM fire safety systems
uponorpro.com
uponorpro.com
'ProPEX® is a registered trademark of Uponor Inc. ProPEXTM is a trademark of Uponor Ltd.
ProPEX° Engineered Polymer (EP) Elbow
Submittal information
Revision J: June 21, 2019
Project information
Job name:
Location: Part no. ordered:
Enoineer: Date submitted:
Contractor: Submitted by:
Manufacturer's representative: Approved bv:
Technical data
Material:
Maximum temperature (no
pressure):
Engineered polymer (EP)
320°F (160°C)
Maximum working
temperature/pressure: 210°F (99°C) at 150 psi (1,034 kPa)
Product information and application use
ProPEX® engineered polymer (EP) elbows make 90-degree connections for Uponor
crosslinked polyethylene (PEX-a) tubing for use in hot and cold domestic potable water
systems, residential fire safety and hydronic radiant heating and cooling systems. Each end
of the elbow is manufactured with an Uponor ProPEX fitting for connections to Uponor
AquaPEX° or Wirsbo hePEXTM tubing.'
uponof
✓ Description
Part number
A
B
Weight
Equivalent
Cv
length (ft.)
ProPEX EP Elbow, %" PEX x'/z" PEX
Q4760500
1.30"
1.30"
0.02 lbs.
10.4
2.6
ProPEX EP Elbow,'/4" PEX x/" PEX'
Q4760750
1.60"
1.60"
0.03 lbs.
10.8
6.7
ProPEX EP Elbow, 1" PEX x 1" PEX'
Q4761000
2.10"
2.10"
0.07 lbs.
11.5
11.9
ProPEX EP Elbow, 1'/d" PEX x 1'/" PEX'
Q4761250
2.45"
2.45"
0.11 lbs.
10.0
22.2
ProPEX EP Elbow, 1'/z" PEX x 1'/2" PEX
Q4761500
2.77"
2.77"
0.18 lbs.
11.5
29.7
ProPEX EP Elbow, 2" PEX x 2" PEX
Q4762000
3.76"
3.76"
0.30 lbs.
17.1
50.2
ProPEX EP Elbow, 2'/z" PEX x 2'/z" PEX
Q4762500
4.93"
4.93"
0.85 lbs.
20.0
86.0
ProPEX EP Elbow, 3" PEX x 3" PEX
Q4763000
5.88"
5.88"
1.44 lbs.
23.2
125.0
ProPEX EP 45 Elbow, 1'/2" PEX x 1'/2" PEX
Q4761515
2.32"
2.32"
0.13 lbs.
9.3
33.1
ProPEX EP 45 Elbow, 2" PEX x 2" PEX
Q4762020
2.91"
2.91"
0.32 lbs.
8.8
68.9
ProPEX EP 45 Elbow, 2'/2" PEX x 2'/2" PEX
Q4762525
3.83"
3.83"
0.65 lbs.
7.0
136.8
ProPEX EP 45 Elbow, 3" PEX x 3" PEX
Q4763030
4.48"
4.48"
1.07 lbs.
8.3
195.5
Installation
Use the appropriate ProPEX ring for PEX-a tubing. Refer to the Uponor Piping
Pocket Guide,
AquaSAFET"
Residential Fire Sprinkler Installation Guide
or Uponor
Radiant Installation Handbook for additional information.
Standards
ASTM E84; ASTM E119; ASTM E814; ASTM F877; ASTM
F1960; CAN/CSA B137.5; NSF
14; NSF 61
Codes
IBC; IMC; IPC; IRC; NPC of Canada; NSPC; UMC; UPC
Listings
cNSFus-pw; 'cNSFus-pw-fs; cQAlus P321; HUD MR 1269; ICC-ES-PMG-1006; ICC-ES-PMG-1012; 'UL 1821; 'ULC/ORD-C199P; U.P. Code
Related applications Contact information
PEX-a plumbing systems
Uponor Inc.
Uponor Ltd.
Hydronic radiant heating and cooling systems
5925 148'h Street West
6510 Kennedy Road
Snow and ice melting systems
Apple Valley, MN 55124 USA
Mississauga, ON L5T 2X4 CANADA
Turf conditioning systems
Phone: 800.321.4739
Phone: 888.994.7726
Permafrost prevention systems
Fax: 952.891.2008
Fax: 800.638.9517
AquaSAFE fire safety systems
uponorpro.com
uponorpro.com
1 ProPEX® is a registered trademark of Uponor, Inc. ProPEXT" is a trademark of Uponor Ltd.
Bulletin 905
® Fire Sprinkler Adapters
Residential Fire Safety System
inblim Multipurpose Piping System
3/4" (19 mm),1" (25.4 mm)
Features:
1. 300 series stainless construction
1. Integral Mounting Bracket
2. Connection Type — PEX (cross -linked Polyethylene) per
ASTM F1960
3. 112" Sprinkler Connection
4. Rating — 130 psig
5. Provides sufficient stand-off from structural members for in-
stallation of recessed and concealed sprinklers.
Approvals and Listings
1. Underwriters Laboratories Inc. UL Listed in accordance with UL
1821 and Certified for Canada (cULus) in accordance with
ULC/ORD C199P
2. NSF International Standard 61
3. Uniform Plumbing Code (UPC) — IAPMO
4. International Plumbing Code (IPC)
Product Description
The Reliable Fire Sprinkler Adapters are specifically
designed to be hanger attachments by integrating a
mounting bracket as a part of the fitting. There are three (3)
basic fitting configurations (Straight, Tee, and Elbow) that
allow to facilitate its use in "NFPA 13D Multipurpose Piping
Systems (Figure A.6.3 b)". The fitting can be mounted
directly to a stud or beam without the use of a separate
hanger.
W
CD
D
0
0
Cn
Installation
1. Install the fitting by attaching the mounting bracket, using
two (2) #10 x 1-1/4" coarse threaded screws (or similar
fasteners) and washer, to the structure
2. Connect one end of the PEX Tubing (using the proper in-
stallation tool and procedure) to the appropriate "barbed"
end desired.
3. Install the properly design sprinkler head into the threaded
end using potable water - safe thread sealants only (Teflon
tape is recommended).
Technical Data: Allowance for friction loss in fittings Ordering Information:
Note: This table shows the allowance for friction loss for
fitting, expressed as equivalent length of pipe.
T ... T ...--
Filing Type
Slim
Equhrdllerd
_ Straight Adat�tc
�4 x 12' FN r ...
.....
_ 1
Straight Actapter
1"x 12 FNPT i
1
_ ..........
Tee ............
3/4' x 3/4' x 1/2' FNPT !
2
Tee
1" x 1" x 1/2' FNPT
2
RH Elbow (90°)
3/4' x 12' FNPT
6
RH Elbow (90')
1 ° x 12' FNmr j
7
LH Elbow (90')
�14 x 12' FNPT
6.
LH Elbow (90°)
1" x 1/2' FNPT i7
Part No.
6888100134
Type
SUaicj rt
SMjl�t
Tee_____..
Tee
Sim
3/4' PEXx 1/2' FNPT
68BB100100
68000234
6BMlCO20D
VPDCx12TNPT
_' PEX x �4 PD( x 12' FNPr
1" PEX x 1" PEX x 12' FNPT
68000334
BbDN (RH)
�W PEX x 12' FNPT
68881003DD
RboN (RH)
1" PEX x 12' FNPT
6900D434
Bbm (LJ-i)
�W PD( x 12' W
6888100400
EbaN (LH)
1" PE)(x 12' FNm
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York , 10523
Dimension Data:
--- ..
F i
.a. �. �• (( •p•
._..... ......
:
•A•
Elbow Adapter
(Only Right Hand Shown, Left Hand is similar)
Connection Sae i A
B
C
D
E
F
3/4" (19 mm) 2.25 (57)
1.88 (48)
1.87 (48)
1.41(36)
.19 (4.8)
.95(24) j
1" (25.4 mm) 2,63(67)
1.88 (48)
2.17(54)
1.54 (39)
.19 (4.8)
.._._.._ 1.18(6.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and propertyfor over 80 years, and are installed and serviced byte most highly qualified and reputa-
be sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A. 02/08 P/N 9999970361