REVIEWED RESUB 1-BLD2024-0502+Structural_Calculations+5.14.2024_9.20.31_AM+4255100REVIEWED BLD2024-0502 RESUB
BYMay 14 2024
CITY OF E D M O N DS of �EPaR�EM ES
V e e r s Engineer: Trevor Jones
Address: 518 Lake Cleveland Street, Burley, ID
May 08, 2024 83318
Phone: (208) 994-1680
Subject: Proposed Solar Panel Installation
Edmonds United Methodist Church, 828 Caspers Street, Edmonds United Methodist Church, WA
PV Letters Job #006-1574
To Whom it May Concern,
We have reviewed information, provided by our client, related to the proposed solar panel installation at the above -referenced address.
The purpose of the review was to determine if the existing roof is structurally adequate for the proposed installation. Based on our review
and analysis of the given information, and in accordance with governing building codes, it is our professional opinion that the existing
structure is permitted to remain unaltered for the proposed solar installation.
Design Parameter Summary
Governing Building Code: 2021 International Residential Code (IRC)
Risk Category: II
Wind Exposure: C
Design Wind Speed: 110 mph
Ground Snow Load: 25 psf
Roof Information
Roof Structure: 2x4 Manufactured Trusses @ 24" O.C. (assumed)
Roofing Material: Asphalt Shingles
Roof Slope: 14, 18 degrees
Roof Connection Details
Lag Screws: 1 screw, 5/16" dia min., with min. 2.5" embedment into roof truss top chord only, at 72" O.C. max
Stagger attachments to avoid overloading any individual truss top chord.
EnEineerine Analysis
The proposed installation - including weight of panels, racking, and mounts - will be approximately 2.59 psf. Based on information
provided by the client the existing roof is composed of one layer of asphalt shingles. Therefore, according to the International Existing
Building Code, Section 806.2, Exception 2, the structure need not be altered for gravity loading. The relevant provision states "buildings
in which the increased dead load is attributable to the addition of a second layer of roof covering weighing 3 pounds per square foot
(0.1437 Miri2) or less over an existing single layer of roof covering" are excepted from alterations for gravity
loading.
Additionally, the proposed installation complies with the requirements of WAC Section 51-51-03240 R324.4 (Exception) and is
therefore deemed adequate to support the load of the rooftop solar system. See attached calculations.
The proposed installation will be 6" max. above the roof surface (flush mounted) and parallel to the roof surface. Therefore, any
increase in wind loading on the building structure from the solar panel installation is expected to be negligible. Wind is the governing
lateral load case. Because the increase in lateral loading is not increased by more than 10%, per provisions in the adopted building
codes, the structure need not be altered for lateral loading.
Wind uplift on the panels has been calculated in accordance with the relevant provisions of ASCE 7-16. This loading has been used to
verify the adequacy of the connection specified above. Connection locations should be in accordance with design drawings.
IronRidge XR100 rails will support the modules and will fasten to the roof structure with IronRidge F1ashFoot2 along the rail.
Conclusion
The roof structure need not be altered for either gravity loading (including snow) or lateral loading (including wind). Therefore, the
existing structure is permitted to remain unaltered. Connections to the roof must be made per the "Roof Connection Details" section
above. Copies of all relevant calculations are enclosed.
Limitations and Disclaimers
The opinion expressed in this letter is made in reliance on the following assumptions: the existing structure is in good condition; the
existing structure is free from defects in design or workmanship; and the existing structure was code -compliant at the time of its design
and construction. These assumptions have not been independently verified, and we have relied on representations made by our client
with respect to the foregoing. The undersigned has not inspected the structure for defects, although we have reviewed the information
provided by our client, including pictures where applicable.
Electrical design is excluded from this analysis. Waterproofing is the sole responsibility of the installer and is also excluded from this
analysis. Solar panels must be installed per manufacturer specifications. Structural design and analysis of the adequacy of solar panels,
racks, mounts, and other components is performed by each component's respective manufacturer; the undersigned makes no statement
of opinion regarding such components. This letter and the opinions expressed herein are rendered solely for the benefit of the permitting
authority (city or county building department) and your office, and may not be utilized or relied on by any other party.
if you have any questions or concerns, please contact me at (208)-994-1680, or email me directly at Trevor@pvletters.com.
Sincerely,
Trevor A. Jones, P.E.
5/8/2024
Pko
0, 91
#7f
APV Letters
Detailed Loading Comparison (Roof 1)
This calculation justifies the additional solar load by comparing existing vertical reactions to proposed
reactions, thus showing that stresses will not increase by more than 5%, and therefore the proposed
installation is justified.
Dead Load Without Solar With Solar
Asphalt Shingles
Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, CS
Sloped Roof Snow Load
Live Load
5.0
5.0
1.0
1.0
4.0
4.0
1.0
1.0
2.0
2.0
1.5
1.5
0.0
2.6
14.5
17.1
25
1
1.1
1
19
14
No
No
1.00
1.00
19.3
19.3
psf
psf
psf
psf
psf
psf
psf
psf
psf
Eqn. 7.3-1 or jurisdiction min.
degrees
psf
Roof Live Load 1 20 20 psf
NOTE: Analysis assumes there is no live load on solar panels
Load Combination
D + Lr 34.5 37.1 psf
D + S 33.8 36.3 psf
Member Information
Member span
Member spacing
Solar Array start point
Solar Array end point
Solar Array weight
Reaction 1
Reaction 2
Max. Moment
43.0
2.0
--
2.4
--
18.2
--
2.6
1483.5
1527.9
1483.5
1497.5
15947.6
16232.4
ft
ft
ft
ft
psf
%a eg of original
lbs
102.99%
lbs
100.94%
lb*ft
101.79%
Result: Because the reactions and max. moment are not increased by
more than 5%, neither are the stresses in the structural members,
and so per the adopted existing building code, the existing roof
structure is permitted to remain unaltered.
40PV Letters
Lag Screw Calculation (per ASCE 7-16) (Roof 1)
This calculation justifies the connection of the solar panels to existing roof members, by showing the
connection capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail, in
Roof Angle, degrees
Roof Layout
Wind Speed, mph
Exposure Coefficient, K.-
Topographic Factor, Kt
Directionality Factor, Kd
Elevation Factor, Ke
Velocity Pressure qZ, psf
Zones:
Spacing parallel to rail, in
GCp (max)
Exposed Panels? (YE = 1.5)
Effective Wind Area on each con., ft2
Pressure Equalization Factor, ya
Uplift Force, psf
Max. Uplift Force / Connection (0.6 WL), lbs
Solar Dead Load (0.6 DL). Lbs
Max. Uplift Force (0.6 WL - 0.6 DL), lbs
Connection Capacity
Attachment FTG
Attachment location
Fastener Type
Fastener Diameter, in
Embedment Length, in
Lumber Species & Grade
Nominal Withdrawal Capacity W, lbs
# of Screws
Load Duration Factor Cd
Screw Adj. Withdrawal Cap. W', lbs
Attachment FTG Strength with Cd, lbs
Max applied load, lbs
Max allowable load, lbs
14
Gable
110
.5
1.00
0.85
1.00
24.8
2n, 2r, 2e 3r, 3e
72
72
72
2.00
2.67
3.19
No
17.0
17.0
17.0
0.71
0.71
0.71
35.1
46.9
56.0
357.3
477.4
569.5
26.3
26.3
26.3
331.0
451.1
543.2
IronRidge F1ashFoot2
Framing
Lag Screw
0.3125
2.5
DFL #2 (Assumed)
665
1
1.6
1064
1171
543
1064
Compare Adiusted Withdrawal Capacity to ASD Factored Demand
Zones: 1 2n, 2r, 2e 3r, 3e
O.K. O.K. O.K.
40PV Letters
Standard Loading Comparison (Roof 2)
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Dead Load
Asphalt Shingles
1/4" Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, P9
Exposure Factor, Cc
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, Cs
Sloped Roof Snow Load
Live Load
Roof Live Load
Load Combination
D+Lr
D+S
Max. Load
% of original
Result:
Without Solar With Solar
5
5
1
1
4
4
1
1
2
2
1.5
1.5
0
2.59
psf
psf
psf
psf
psf
psf
psf
14.5 1 17.09 psf
25
1.00
1.1
1
19
18
No
No
1.00
1.00
19.3
19.3
psf
ASCE 7 Eqn. 7.3-1 or jurisdiction min.
degrees
psf
20 1 0 psf
34.5
17.1
psf
33.8
36.3
psf
34.5
36.3
psf
105.33%
USE OTHER SPREADSHEET
40PV Letters
Lag Screw Calculation (per ASCE 7-16) (Roof 2)
This calculation justifies the connection of the solar panels to existing roof members, by showing the
connection capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail, in
Roof Angle, degrees
Roof Layout
Wind Speed, mph
Exposure Coefficient, K.-
Topographic Factor, Kt
Directionality Factor, Kd
Elevation Factor, Ke
Velocity Pressure qZ, psf
Zones:
Spacing parallel to rail, in
GCp (max)
Exposed Panels? (YE = 1.5)
Effective Wind Area on each con., ft2
Pressure Equalization Factor, ya
Uplift Force, psf
Max. Uplift Force / Connection (0.6 WL), lbs
Solar Dead Load (0.6 DL). Lbs
Max. Uplift Force (0.6 WL - 0.6 DL), lbs
Connection Capacity
Attachment FTG
Attachment location
Fastener Type
Fastener Diameter, in
Embedment Length, in
Lumber Species & Grade
Nominal Withdrawal Capacity W, lbs
# of Screws
Load Duration Factor Cd
Screw Adj. Withdrawal Cap. W', lbs
Attachment FTG Strength with Cd, lbs
Max applied load, lbs
Max allowable load, lbs
18
Gable
110
1.00
0.85
1.00
24.8
2n, 2r, 2e 3r, 3e
72
72
72
2.00
2.67
3.19
No
17.0
17.0
17.0
0.71
0.71
0.71
35.1
46.9
56.0
357.3
477.4
569.5
26.3
26.3
26.3
331.0
451.1
543.2
IronRidge F1ashFoot2
Framing
Lag Screw
0.3125
2.5
DFL #2 (Assumed)
665
1
1.6
1064
1171
543
1064
Compare Adiusted Withdrawal Capacity to ASD Factored Demand
Zones: 1 2n, 2r, 2e 3r, 3e
O.K. O.K. O.K.
PV Letters
Standard Loading Comparison (Roof 3)
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Dead Load
Asphalt Shingles
1/4" Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, Cs
Sloped Roof Snow Load
Live Load
Roof Live Load
Load Combination
D + Lr
D + S
Max. Load
% of original
Result:
Without Solar With Solar
5
5
1
1
4
4
1
1
2
2
1.5
1.5
0
2.59
psf
psf
psf
psf
psf
psf
psf
14.5 1 17.09 Ipsf
25
1.00
1.1
1
19
14
No
Yes
1.00
0.93
19.3
18.0
psf
ASCE 7 Eqn. 7.3-1 or jurisdiction min.
degrees
psf
20 1 0 psf
34.5 17.1 psf
33.8 35.1 psf
34.5 35.1 Ipsf
101.59%
Because the total forces are not increased by more than 5%,
per the relevant code provisions stated in the body of the
letter, the existing roof structure is permitted to remain
unaltered.
40PV Letters
Lag Screw Calculation (per ASCE 7-16) (Roof 3)
This calculation justifies the connection of the solar panels to existing roof members, by showing the
connection capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail, in
Roof Angle, degrees
Roof Layout
Wind Speed, mph
Exposure Coefficient, K.-
Topographic Factor, Kt
Directionality Factor, Kd
Elevation Factor, Ke
Velocity Pressure qZ, psf
Zones:
Spacing parallel to rail, in
GCp (max)
Exposed Panels? (YE = 1.5)
Effective Wind Area on each con., ft2
Pressure Equalization Factor, ya
Uplift Force, psf
Max. Uplift Force / Connection (0.6 WL), lbs
Solar Dead Load (0.6 DL). Lbs
Max. Uplift Force (0.6 WL - 0.6 DL), lbs
Connection Capacity
Attachment FTG
Attachment location
Fastener Type
Fastener Diameter, in
Embedment Length, in
Lumber Species & Grade
Nominal Withdrawal Capacity W, lbs
# of Screws
Load Duration Factor Cd
Screw Adj. Withdrawal Cap. W', lbs
Attachment FTG Strength with Cd, lbs
Max applied load, lbs
Max allowable load, lbs
14
Gable
110
.5
1.00
0.85
1.00
24.8
2n, 2r, 2e 3r, 3e
72
72
72
2.00
2.67
3.19
No
17.0
17.0
17.0
0.71
0.71
0.71
35.1
46.9
56.0
357.3
477.4
569.5
26.3
26.3
26.3
331.0
451.1
543.2
IronRidge F1ashFoot2
Framing
Lag Screw
0.3125
2.5
DFL #2 (Assumed)
665
1
1.6
1064
1171
543
1064
Compare Adiusted Withdrawal Capacity to ASD Factored Demand
Zones: 1 2n, 2r, 2e 3r, 3e
O.K. O.K. O.K.
PV Letters
Standard Loading Comparison (Roof 4)
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Dead Load
Asphalt Shingles
1/4" Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, Cs
Sloped Roof Snow Load
Live Load
Roof Live Load
Load Combination
D + Lr
D + S
Max. Load
% of original
Result:
Without Solar With Solar
5
5
1
1
4
4
1
1
2
2
1.5
1.5
0
2.59
psf
psf
psf
psf
psf
psf
psf
14.5 1 17.09 Ipsf
25
1.00
1.1
1
19
18
No
Yes
1.00
0.87
19.3
16.7
psf
ASCE 7 Eqn. 7.3-1 or jurisdiction min.
degrees
psf
20 1 0 psf
34.5 17.1 psf
33.8 33.8 psf
34.5 33.8 Ipsf
97.91 %
Because the total forces are decreased, per the relevant code
provisions stated in the body of the letter, the existing roof
structure is permitted to remain unaltered.
Pko
0, 91
#7f
APV Letters
Detailed Loading Comparison (Roof 4)
This calculation justifies the additional solar load by comparing existing vertical reactions to proposed
reactions, thus showing that stresses will not increase by more than 5%, and therefore the proposed
installation is justified.
Dead Load Without Solar With Solar
Asphalt Shingles
Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, CS
Sloped Roof Snow Load
Live Load
5.0
5.0
1.0
1.0
4.0
4.0
1.0
1.0
2.0
2.0
1.5
1.5
0.0
2.6
14.5
17.1
25
1
1.1
1
18
No
Yes
1.00
0.87
19.3
16.7
psf
psf
psf
psf
psf
psf
psf
psf
psf
Eqn. 7.3-1 or jurisdiction min.
degrees
psf
Roof Live Load 1 20 20 psf
NOTE: Analysis assumes there is no live load on solar panels
Load Combination
D + Lr 34.5 37.1 psf
D + S 33.8 33.8 psf
Member Information
Member span
Member spacing
Solar Array start point
Solar Array end point
Solar Array weight
Reaction 1
Reaction 2
Max. Moment
50.2
2.0
--
31.1
--
46.6
--
2.6
1730.9
1743.8
1730.9
1775.0
21709.4
21976.1
ft
ft
ft
ft
psf
%a eg of original
lbs
100.75%
lbs
102.55%
lb*ft
101.23%
Result: Because the reactions and max. moment are not increased by
more than 5%, neither are the stresses in the structural members,
and so per the adopted existing building code, the existing roof
structure is permitted to remain unaltered.
40PV Letters
Lag Screw Calculation (per ASCE 7-16) (Roof 4)
This calculation justifies the connection of the solar panels to existing roof members, by showing the
connection capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail, in
Roof Angle, degrees
Roof Layout
Wind Speed, mph
Exposure Coefficient, K.-
Topographic Factor, Kt
Directionality Factor, Kd
Elevation Factor, Ke
Velocity Pressure qZ, psf
Zones:
Spacing parallel to rail, in
GCp (max)
Exposed Panels? (YE = 1.5)
Effective Wind Area on each con., ft2
Pressure Equalization Factor, ya
Uplift Force, psf
Max. Uplift Force / Connection (0.6 WL), lbs
Solar Dead Load (0.6 DL). Lbs
Max. Uplift Force (0.6 WL - 0.6 DL), lbs
Connection Capacity
Attachment FTG
Attachment location
Fastener Type
Fastener Diameter, in
Embedment Length, in
Lumber Species & Grade
Nominal Withdrawal Capacity W, lbs
# of Screws
Load Duration Factor Cd
Screw Adj. Withdrawal Cap. W', lbs
Attachment FTG Strength with Cd, lbs
Max applied load, lbs
Max allowable load, lbs
18
Gable
110
1.00
0.85
1.00
24.8
2n, 2r, 2e 3r, 3e
72
72
72
2.00
2.67
3.19
No
17.0
17.0
17.0
0.71
0.71
0.71
35.1
46.9
56.0
357.3
477.4
569.5
26.3
26.3
26.3
331.0
451.1
543.2
IronRidge F1ashFoot2
Framing
Lag Screw
0.3125
2.5
DFL #2 (Assumed)
665
1
1.6
1064
1171
543
1064
Compare Adiusted Withdrawal Capacity to ASD Factored Demand
Zones: 1 2n, 2r, 2e 3r, 3e
O.K. O.K. O.K.
PV Letters
Standard Loading Comparison (Roof 5)
This calculation justifies the additional solar load by comparing existing to proposed gravity loads
in the location of the solar panels.
Dead Load
Asphalt Shingles
1/4" Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, Is
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, Cs
Sloped Roof Snow Load
Live Load
Roof Live Load
Load Combination
D + Lr
D + S
Max. Load
% of original
Result:
Without Solar With Solar
5
5
1
1
4
4
1
1
2
2
1.5
1.5
0
2.59
psf
psf
psf
psf
psf
psf
psf
14.5 1 17.09 Ipsf
25
1.00
1.1
1
19
14
No
Yes
1.00
0.93
19.3
18.0
psf
ASCE 7 Eqn. 7.3-1 or jurisdiction min.
degrees
psf
20 1 0 psf
34.5 17.1 psf
33.8 35.1 psf
34.5 35.1 Ipsf
101.59%
Because the total forces are not increased by more than 5%,
per the relevant code provisions stated in the body of the
letter, the existing roof structure is permitted to remain
unaltered.
Pko
0, 91
#7f
APV Letters
Detailed Loading Comparison (Roof 5)
This calculation justifies the additional solar load by comparing existing vertical reactions to proposed
reactions, thus showing that stresses will not increase by more than 5%, and therefore the proposed
installation is justified.
Dead Load Without Solar With Solar
Asphalt Shingles
Plywood
Framing
Insulation
1/2" Gypsum Ceiling
M,E, & Misc
Solar Panel
Total Dead Load
Snow Load
Ground Snow Load, Pg
Exposure Factor, Ce
Thermal Factor, Ct
Importance Factor, IS
Flat Roof Snow Load
Slope
Unobstructed Slippery Surface?
Slope Factor, CS
Sloped Roof Snow Load
Live Load
5.0
5.0
1.0
1.0
4.0
4.0
1.0
1.0
2.0
2.0
1.5
1.5
0.0
2.6
14.5
17.1
25
1
1.1
1
19
14
No
Yes
1.00
0.93
19.3
18.0
psf
psf
psf
psf
psf
psf
psf
psf
psf
Eqn. 7.3-1 or jurisdiction min.
degrees
psf
Roof Live Load 1 20 20 psf
NOTE: Analysis assumes there is no live load on solar panels
Load Combination
D + Lr 34.5 37.1 psf
D + S 33.8 35.1 psf
Member Information
Member span
Member spacing
Solar Array start point
Solar Array end point
Solar Array weight
Reaction 1
Reaction 2
Max. Moment
26.3
2.0
--
0.7
--
16.6
--
2.6
906.3
945.5
906.3
925.5
5952.2
6182.8
ft
ft
ft
ft
psf
%a eg of original
lbs
104.33%
lbs
102.12%
lb*ft
103.87%
Result: Because the reactions and max. moment are not increased by
more than 5%, neither are the stresses in the structural members,
and so per the adopted existing building code, the existing roof
structure is permitted to remain unaltered.
40PV Letters
Lag Screw Calculation (per ASCE 7-16) (Roof 5)
This calculation justifies the connection of the solar panels to existing roof members, by showing the
connection capacity is equal to or greater than the uplift force demands.
Connection Demand
Spacing perpendicular to rail, in
Roof Angle, degrees
Roof Layout
Wind Speed, mph
Exposure Coefficient, K.-
Topographic Factor, Kt
Directionality Factor, Kd
Elevation Factor, Ke
Velocity Pressure qZ, psf
Zones:
Spacing parallel to rail, in
GCp (max)
Exposed Panels? (YE = 1.5)
Effective Wind Area on each con., ft2
Pressure Equalization Factor, ya
Uplift Force, psf
Max. Uplift Force / Connection (0.6 WL), lbs
Solar Dead Load (0.6 DL). Lbs
Max. Uplift Force (0.6 WL - 0.6 DL), lbs
Connection Capacity
Attachment FTG
Attachment location
Fastener Type
Fastener Diameter, in
Embedment Length, in
Lumber Species & Grade
Nominal Withdrawal Capacity W, lbs
# of Screws
Load Duration Factor Cd
Screw Adj. Withdrawal Cap. W', lbs
Attachment FTG Strength with Cd, lbs
Max applied load, lbs
Max allowable load, lbs
14
Gable
110
.5
1.00
0.85
1.00
24.8
2n, 2r, 2e 3r, 3e
72
72
72
2.00
2.67
3.19
No
17.0
17.0
17.0
0.71
0.71
0.71
35.1
46.9
56.0
357.3
477.4
569.5
26.3
26.3
26.3
331.0
451.1
543.2
IronRidge F1ashFoot2
Framing
Lag Screw
0.3125
2.5
DFL #2 (Assumed)
665
1
1.6
1064
1171
543
1064
Compare Adiusted Withdrawal Capacity to ASD Factored Demand
Zones: 1 2n, 2r, 2e 3r, 3e
O.K. O.K. O.K.