Loading...
REVIEWED RESUB1 BLD2024-0067+FIRE DAMPER Manufacturer_SpecS+4.29.2024_3.57.40_PM+4225586REVIEWED 4 BY .NIMFI CITY OF EDMOND M-1 Application BLD2024-0067 Model DFDAF-330 is a multi -blade fire damper with airfoil style blades for use in walls, floors, and partitions with fire resistance rating of 3 hours or more. Model DFDAF-330 may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow in either directions. This model has a manual quadrant which allows the DFDAF-330 to function as both a fire damper and a manual balancing damper. Ratings UL 555 Fire Resistance Rating Fire Rating: 3 hours Dynamic Closure Rating: Actual ratings are size dependent Velocity: Up to 4000 fpm (20.3 m/s) on sizes up to 32 in. x 36 in. (813 mm x 914 mm); 2000 fpm (10.2 m/s) on sizes greater than 32 in. x 36 in. (813mm x 914 mm) Pressure: Up to 8 in. wg (2 kPa) Construction Frame Material Galvanized steel - Frame Material Thickness 16 ga. (1.5mm) - 5 in. x 1 in. Frame Type (127mm x 25mm) - hat channel Blade Action Opposed - Blade Material Galvanized steel - Blade Material Thickness 14 ga. (2mm) equivalent - Blade Type Double skin airfoil - Plated steel out of Linkage airstream, concealed in - jamb Axle Bearings 316SS - Axle Material Plated steel - Jamb Seals Stainless Steel - Closure Device Fusible link - Closure 212°F (100°C), Temperature 165°F (74°C) 286°F (141 °C), 350°F (177°C) Actuator Manual quadrant - a RESUB Apr 29 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT • W & H dimensions furnished approximately'/4 in. ( 6 mm) undersize. (Add sleeve thickness for overall sleeved damper dimension) See complete marking on product. US UL 555 Classification R13317 Model DFDAF-330 meets the requirements for fire dampers established by: National Fire Protection Association NFPA Standards 80, 90A & 101 IBC International Building Codes CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:0103) Inches 8 x 6 32x36(V)or 30x48(HorV) mm 203x152 813x914or 762 x 1219 128 x 96 (V) or 144 x 96 (H) 3048 x 2438 or 3658 x 2438 30 x 48 762 x 1219 LN DFDAF-330 January 2024 Options & Pressure Drop Data • Extra Fusible Links • Factory mounted accessories - Quick connect breakaway connections - Access doors • Flanges • Grille Tabs • OCI (Open Closed Indication switches): Units will be supplied with one OCI per row of damper sections • POC retaining angles • Security bars • Sealed transition and sleeves • Sleeves • Smoke Detector • Test Switch (GTS-4) • Transitions (C, O, R) Document Links 0 INSTALLATION ❑� Uil ff! SPECIFICATIONS ❑� WARRANTY 0 F0 %I L r ~ CATALOG 10 ❑� r ❑ tiF IL TOM - SELECTION GUIDE IN, DFDAF-330 January 2024 AMCA Pressure Drop AMCA Figure 5.2 5D -� Figure 5.2 12 in. x 12 in. (305mm x 305mm) Velocity (fpm) ressure Drop (in. wg) 500 0.03 1000 0.12 1500 0.26 2000 0.46 2500 0.72 3000 1.04 3500 1.41 4000 1.84 AMCA Figure 5.3 24 in. x 24 in. (610mm x 610mm) Velocity (fpm) ressure Drop (in. wg) 500 0.01 1000 0.06 1500 0.12 2000 0.22 2500 0.34 3000 0.49 3500 0.67 4000 0.87 5D r 611) Figure 5.3 12 in. x 12 in. (305mm x 305mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 1000 0.06 1500 0.13 2000 0.23 2500 0.37 3000 0.53 3500 0.73 4000 0.95 AMCA Figure 5.5 p 12 in. x 12 in. (305mm x 305mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.04 1000 0.18 1500 0.42 2000 0.75 2500 1.17 3000 1.68 3500 2.29 4000 2.99 24 in. x 24 in. (610mm x 610mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 1000 0.02 1500 0.06 2000 0.10 2500 0.16 3000 0.23 3500 0.32 4000 0.42 24 in. x 24 in. (610mm x 610mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 1000 0.13 1500 0.29 2000 0.52 2500 0.81 3000 1.17 3500 1.60 4000 2.14 36in. x 36 in. (914mm x 914mm) Velocity (fpm) ressure Drop (in. wg) 500 0.01 1000 0.06 1500 0.12 2000 0.22 2500 0.34 3000 0.49 3500 0.67 4000 0.88 36in. x 36 in. (914mm x 914mm) Velocity (fpm) Pressure Drop On. wg) 500 0.01 1000 0.02 1500 0.05 2000 0.09 2500 0.14 3000 0.21 3500 0.29 4000 0.38 36in. x 36 in. (914mm x 914mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 1000 0.12 1500 0.27 2000 0.48 2500 0.75 3000 1.08 3500 1.48 4000 1. 93 12in. X 48 in. (305mm x 1219mm) Velocity (fpm) ressure Drop (in. wg) 500 0.01 1000 0.05 1500 0.12 2000 0.21 2500 0.33 3000 0.48 3500 0.65 4000 0.85 12in. X 48 in. (305mm x 1219mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 1000 0.02 1500 0.06 2000 0.10 2500 0.16 3000 0.24 3500 0.33 4000 0.43 12in. X 48 in. (305mm x 1219mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 1000 0.12 1500 0.27 2000 0.49 2500 0.77 3000 1.11 3500 1.51 4000 1.97 Greenheck Fan Corporation certifies that the model F' •�•9 0E CERTI A MIMI DFDAF-330 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and ;7ti1• procedures AIR performed in accordance with AMCA Publication 511 0, �;�• ! and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only. 48 in. x 12 in. (1219mm x 305mm) velocity (fpm) ressure Drop (in. wg) 500 0.02 1000 0.08 1500 0.18 2000 0.33 2500 0.51 3000 0.74 3500 1.00 4000 1.31 48 in. x 12 in. 0219mm x 305mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 1000 0.04 1500 0.10 2000 0.18 2500 0.29 3000 0.42 3500 0.57 4000 0.74 48 in. x 12 in. 0219mm x 305mm) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 1000 0.14 1500 0.32 2000 0.57 2500 0.89 3000 1.28 3500 1.75 4000 2.29 LH DFDAF-330 January 2024 Sleeve and Sideplate Dimensions The drawings below and corresponding table show the position of the DFDAF-330 damper when mounted in a factory sleeve ("A" dimension). The standard mounting locations provide enough space for the mounting of manual quadrant(s) and allow space for installation of retaining angles and duct connections. The following options may affect the range of available mounting locations: transitions, security bars, grille tabs. The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be positioned at other locations within a range of 7 3/,6 in. (183mm) to 16 in. (406mm) for the "A" dimension. P, EA > 5 -'N n. Sleeve Length Sleeve 0IUU[JldLt! Dampers with no OCI 7 3/16 in. (183) 16 (406) 0116 (157) Height < 12 in. (305) 12 (305) I 16 (406) 12 (305) OCI Height > 12 in. (305) 7 3/,6 in. (183) 16 (406) 12 (305) OCI NOTE: Entire damper frame is not required to be installed within the wall. The damper blades, when closed should be contained within the wall. Transitioned Damper Dimensions When a fire damper is being used in conjunction with round or oval ductwork, the DFDAF-330 can be supplied in a factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show overall damper size. D*+ 2 it D*+ 2 in. (51 mm)+TS (406mm)' '\ Minimum TYPE R W*+2 in. (51mm)+TS —>\ T 2 in. (51mm)+TS (406mm) Minimum TYPE O W* + 2 in. (51 mm)+TS—>\ 7 H*+2 in. (51mm)+Ts t 16 in. (406mm) Minimum TYPE C *These dimensions are furnished approximately v in. (6mm) undersize, except round and oval dimensions which are approximately Ya in.(3mm) undersize. Ts = (2)(Sleeve Thickness) 0. DFDAF-330 January 2024 Multiple Section Dampers DFDAF-330 Multi -blade Fire Damper Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The following figures show maximum damper section size and assembly configurations for multi -section dampers. Larger damper sizes may ship in multiple sections. 48 (1219 F-ju�60 in. (1524 mm) Two Section 96 in. (2438 mm")) 48 in. (1 19 mn 4 sections wide 2 sections high NOTE: Entire damper frame is not required to be installed within the wall. The damper blades, when closed should be contained within the wall. LdGREENHECK Copyright ® 2024 Greenheck Fan Corporation DFDAF-330, R14, January 2024 Greenheck Fan Corporation reserves the right to make product changes without notice P.O. Box 410 • Scho/idd,, W154476-N 10 • 715.359.61 ]1 •g—h-k.com