Application BLD2024-0067
Model DFDAF-330 is a multi -blade fire damper with airfoil style
blades for use in walls, floors, and partitions with fire resistance
rating of 3 hours or more. Model DFDAF-330 may be installed
vertically (with blades running horizontal) or horizontally and is
rated for airflow in either directions.
This model has a manual quadrant which allows the DFDAF-330
to function as both a fire damper and a manual balancing
damper.
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 3 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 4000 fpm (20.3 m/s) on sizes up
to 32 in. x 36 in. (813 mm x 914 mm);
2000 fpm (10.2 m/s) on sizes greater
than 32 in. x 36 in. (813mm x 914 mm)
Pressure: Up to 8 in. wg (2 kPa)
Construction
Frame Material Galvanized steel -
Frame Material
Thickness 16 ga. (1.5mm) -
5 in. x 1 in.
Frame Type (127mm x 25mm) -
hat channel
Blade Action Opposed -
Blade Material Galvanized steel -
Blade Material
Thickness 14 ga. (2mm) equivalent -
Blade Type Double skin airfoil -
Plated steel out of
Linkage airstream, concealed in -
jamb
Axle Bearings 316SS -
Axle Material Plated steel -
Jamb Seals Stainless Steel -
Closure Device Fusible link -
Closure 212°F (100°C),
Temperature 165°F (74°C) 286°F (141 °C),
350°F (177°C)
Actuator Manual quadrant -
a
RESUB
Apr 29 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
•
W & H dimensions furnished approximately'/4 in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
See complete marking on
product.
US UL 555 Classification R13317
Model DFDAF-330 meets the requirements for fire dampers
established by:
National Fire Protection Association
NFPA Standards 80, 90A & 101
IBC International Building Codes
CSFM California State Fire Marshal
Fire Damper Listing (#3225-0981:0103)
Inches 8 x 6
32x36(V)or
30x48(HorV)
mm 203x152 813x914or
762 x 1219
128 x 96 (V)
or
144 x 96 (H)
3048 x 2438
or
3658 x 2438
30 x 48
762 x 1219
LN DFDAF-330 January 2024
Options & Pressure Drop Data
• Extra Fusible Links
• Factory mounted accessories
- Quick connect breakaway connections
- Access doors
• Flanges
• Grille Tabs
• OCI (Open Closed Indication switches): Units will be supplied with one OCI per row of damper sections
• POC retaining angles
• Security bars
• Sealed transition and sleeves
• Sleeves
• Smoke Detector
• Test Switch (GTS-4)
• Transitions (C, O, R)
Document Links
0
INSTALLATION
❑�
Uil
ff!
SPECIFICATIONS
❑�
WARRANTY
0 F0
%I
L
r ~
CATALOG
10
❑�
r
❑ tiF IL TOM -
SELECTION GUIDE
IN, DFDAF-330 January 2024
AMCA Pressure Drop
AMCA Figure 5.2
5D -�
Figure 5.2
12 in. x 12 in. (305mm x 305mm)
Velocity
(fpm)
ressure Drop
(in. wg)
500
0.03
1000
0.12
1500
0.26
2000
0.46
2500
0.72
3000
1.04
3500
1.41
4000
1.84
AMCA Figure 5.3
24 in. x 24 in. (610mm x 610mm)
Velocity
(fpm)
ressure Drop
(in. wg)
500
0.01
1000
0.06
1500
0.12
2000
0.22
2500
0.34
3000
0.49
3500
0.67
4000
0.87
5D r 611)
Figure 5.3
12 in. x 12 in. (305mm x 305mm)
Velocity (fpm)
Pressure Drop
(in. wg)
500
0.01
1000
0.06
1500
0.13
2000
0.23
2500
0.37
3000
0.53
3500
0.73
4000
0.95
AMCA Figure 5.5
p
12 in. x 12 in. (305mm x 305mm)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.04
1000
0.18
1500
0.42
2000
0.75
2500
1.17
3000
1.68
3500
2.29
4000
2.99
24 in. x 24 in. (610mm x 610mm)
Velocity (fpm)
Pressure Drop
(in. wg)
500
0.01
1000
0.02
1500
0.06
2000
0.10
2500
0.16
3000
0.23
3500
0.32
4000
0.42
24 in. x 24 in. (610mm x 610mm)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
1000
0.13
1500
0.29
2000
0.52
2500
0.81
3000
1.17
3500
1.60
4000
2.14
36in. x 36 in. (914mm x 914mm)
Velocity
(fpm)
ressure Drop
(in. wg)
500
0.01
1000
0.06
1500
0.12
2000
0.22
2500
0.34
3000
0.49
3500
0.67
4000
0.88
36in. x 36 in. (914mm x 914mm)
Velocity (fpm)
Pressure Drop
On. wg)
500
0.01
1000
0.02
1500
0.05
2000
0.09
2500
0.14
3000
0.21
3500
0.29
4000
0.38
36in. x 36 in. (914mm x 914mm)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
1000
0.12
1500
0.27
2000
0.48
2500
0.75
3000
1.08
3500
1.48
4000
1. 93
12in. X 48 in. (305mm x 1219mm)
Velocity
(fpm)
ressure Drop
(in. wg)
500
0.01
1000
0.05
1500
0.12
2000
0.21
2500
0.33
3000
0.48
3500
0.65
4000
0.85
12in. X 48 in. (305mm x 1219mm)
Velocity (fpm)
Pressure Drop
(in. wg)
500
0.01
1000
0.02
1500
0.06
2000
0.10
2500
0.16
3000
0.24
3500
0.33
4000
0.43
12in. X 48 in. (305mm x 1219mm)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
1000
0.12
1500
0.27
2000
0.49
2500
0.77
3000
1.11
3500
1.51
4000
1.97
Greenheck Fan Corporation certifies that the model
F' •�•9
0E
CERTI A
MIMI
DFDAF-330 shown herein is licensed to bear the AMCA
Seal. The ratings shown are based on tests and
;7ti1•
procedures
AIR
performed in accordance with AMCA Publication 511
0, �;�• !
and comply with the requirements of the AMCA Certified
Ratings Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
48 in. x 12 in. (1219mm x 305mm)
velocity
(fpm)
ressure Drop
(in. wg)
500
0.02
1000
0.08
1500
0.18
2000
0.33
2500
0.51
3000
0.74
3500
1.00
4000
1.31
48 in. x 12 in. 0219mm x 305mm)
Velocity (fpm)
Pressure Drop
(in. wg)
500
0.01
1000
0.04
1500
0.10
2000
0.18
2500
0.29
3000
0.42
3500
0.57
4000
0.74
48 in. x 12 in. 0219mm x 305mm)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
1000
0.14
1500
0.32
2000
0.57
2500
0.89
3000
1.28
3500
1.75
4000
2.29
LH DFDAF-330
January 2024
Sleeve and Sideplate Dimensions
The drawings below and corresponding table show the position of the DFDAF-330 damper when mounted in a factory sleeve ("A"
dimension). The standard mounting locations provide enough space for the mounting of manual quadrant(s) and allow space for
installation of retaining angles and duct connections. The following options may affect the range of available mounting locations:
transitions, security bars, grille tabs.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be positioned at
other locations within a range of 7 3/,6 in. (183mm) to 16 in. (406mm) for the "A" dimension.
P,
EA
> 5 -'N
n.
Sleeve Length
Sleeve
0IUU[JldLt!
Dampers with no OCI 7 3/16 in. (183) 16 (406) 0116 (157)
Height < 12 in. (305) 12 (305) I 16 (406) 12 (305)
OCI
Height > 12 in. (305) 7 3/,6 in. (183) 16 (406) 12 (305)
OCI
NOTE: Entire damper frame is not required to be installed within the wall. The damper
blades, when closed should be contained within the wall.
Transitioned Damper Dimensions
When a fire damper is being used in conjunction with round or oval ductwork, the DFDAF-330 can be supplied in a factory sleeve
with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show
overall damper size.
D*+ 2 it
D*+ 2 in. (51 mm)+TS
(406mm)' '\
Minimum
TYPE R
W*+2 in. (51mm)+TS —>\
T
2 in. (51mm)+TS
(406mm)
Minimum
TYPE O
W* + 2 in. (51 mm)+TS—>\
7
H*+2 in. (51mm)+Ts
t
16 in.
(406mm)
Minimum
TYPE C
*These dimensions are furnished approximately v in. (6mm) undersize, except round and oval dimensions which are approximately Ya in.(3mm) undersize.
Ts = (2)(Sleeve Thickness)
0. DFDAF-330 January 2024
Multiple Section Dampers
DFDAF-330
Multi -blade Fire Damper
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The
following figures show maximum damper section size and assembly configurations for multi -section dampers. Larger damper sizes
may ship in multiple sections.
48
(1219
F-ju�60 in. (1524 mm)
Two Section
96 in.
(2438 mm"))
48 in.
(1 19 mn
4 sections wide
2 sections high
NOTE: Entire damper frame is not required to be installed within the wall. The damper blades, when closed should be contained within the wall.
LdGREENHECK
Copyright ® 2024 Greenheck Fan Corporation
DFDAF-330, R14, January 2024
Greenheck Fan Corporation reserves the right to make
product changes without notice
P.O. Box 410 • Scho/idd,, W154476-N 10 • 715.359.61 ]1 •g—h-k.com