REVIEWED BLD2024-0544+Manufacturer_Specifications_and_Installation_Instructions+3.13.2024_1.55.48_PM+412810546
UPFLC
4C
5 13.1C
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
PLAN VIEW
11X7J&f11: IX59
PLAN VIEW OF UNIT
25 TON COOLING AND STEAM HEAT UNIT
DIMENSION DRAWING
RECEIVED
Apr 25 2024 BLD2024-0544
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
8"
85
NOTES:
1. VERIFY WEIGHT, CONNECTION,
AND ALL DIMENSION WITH
INSTALLER DOCUMENTS
BEFORE INSTALLATION
2.OVERALL UNIT WIDTH INCREASES
5/8" BEYOND LIFTING LUG
WITH ULTRA LOW LEAK POWER
EXHAUST DAMPERS
3. IF FIELD CONVERTING SUPPLY&
RETURN OPENING(S)TO
HORIZONTAL OR VERTICAL
AIRFLOW, FACTORY MUST VERIFY
IF UNIT OPTIONS WILLALLOW IT.
FACTORY INSTALLATION IS
ALWAYS RECOMMENDED.
/4" �88 112"�
3 7/8"
3/8" DRAIN HOLES
BOTH SIDE) FRONT VIEW
SEE NOTE 3-/
1/8" CONDUIT
C CONTROL CIRCUIT
1/8" CONDUIT
.0 CONTROL CIRCUIT
1/8" CON DU ITAC &
C CONTROL CIRCUIT
1 /8" CONN. THRU
IASE FOR POWER SUPPLY
Created: 1/9/2024 Page: 1 of 8
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
VARIABLE
FREQUENCY OUTDOORAIR [OUTDOORAIR LEVAPCOIL SUPPLYAIRSECTION
DRIVE OPTION SECTION DAMPERS
RETURN AIR
EXHAUST SECTION DAMPERS
ILTER SECTION EXTENDED CASING /
HEAT SECTION
EXHAUST S
I
II •
�I
I
ECTION FILTER / EVAP SECTION SUPPLYAIR SECTION EXTENDED CASING / .• '
HEAT SECTION
20 - 30 TON COOLING EXTENDED CASING TYPICAL LAYOUT
DIMENSION DRAWING
Created: 1/9/2024 Page: 2 of 8
Created: 1/9/2024 Page: 2 of 8
Tag: 25T RTU-2, 25T RTU-2-1
Quantity: 2
Customer:
Project:
Name: Kruger Medical Building Remodel
43
PANEL C
40 11/16"
44
PANEL
T--I F— — — —�
I
I I
4011/16" ' '
� SUPPLY �
I I
I I
25 12"
NOTES:
1. FOR HORIZONTAL DISCHARGE ON SFHM, SLHM AND SSHM UNITS, ONLY THE PANEL B CAN BE REMOVED. PANELACANNOT BE
USED DUE TO THE LOCATION OF THE HEATING
2. ADD AN EXTRA 0.20 - INCHES PRESSURE DROP TO THE SUPPLY EXTERNAL STATIC ACCOUNT FOR THE EXTRATURN
THE AIR IS MAKING.
1 THE OPENINGSALL HAVEA1.25-INCH LIPAROUND THE PERIMETER TO FACILITATE DUCTWORK ATTACHMENT
4_ IF EXHAUSTIRETURN FANS ARE BEING USED, PROVISION SHOULD BE MADE FOR ACCESS TO THE EXHAUST COMPONENTS
,SINCE THE ACCESS DOOR IS NOW BEING USED AS RETURN
5. USE THE DIMENSION PROVIDED AND THE SUPPLY CFM TO CALCULATE THE VELOCITY (FT/MIN) THOUGHT THE OPENINGS
TO BE SURE THEY ARE ACCEPTABLE COILS.
25TON HORIZONTAL DISCHARGE PANEL
DIMENSION DRAWING
Created: 1/9/2024 Page: 3 of 8
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION
WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
25 TON POWER AND CONTROL OPENINGS
DIMENSION DRAWING
Created: 1/9/2024 Page: 4 of 8
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
1"
5/8" 112"
5 8" y
1"
3"
90° 5 5/8"
3 5/8"
111 " �--2 3/4"30'
1 5/8"
5/8" 9/16"
13116" _
5 13/16"
TYPICAL PEDESTAL AND BASE
DIMENSION DRAWING
UNIT BASE
2 1/2" LIFTING LUG
SHIPS WITH CURB �4" LONG
FIELD INSTALLED
GASKET
3"
2 1/2"- LIFTING LUG
4" LONG 3/8"
3" PEDESTAL
2" X 4" NAILER
(FURNISHED WITH KIT)
ROOF CURB
TYPICAL PEDESTALAND BASE PAN DETAIL TYPICAL ROOF CURBAND BASE PAN DETAIL
DETAIL DETAIL
Created: 1/9/2024 Page: 5 of 8
Tag: 25T RTU-2, 25T RTU-2-1
Quantity: 2
Customer:
Project:
Name: Kruger Medical Building Remodel
Center of Gravity X:13.54It
Notes:
Center of Gravity Y. 3.88 ft
1. The actual weight is stamped on the unit
nameplate.
Point Load 1: 6202 lb
2. The weight shown represents the typical
Point Load 2: 655.9 Ib
unit operating weight for the configuration
Point Load 3: 685.4 Ib
selected. Estimated at +/- 10% of the
Point Load 4: 7212 lb
nameplate weight- .
Point Load 5: 740.9 lb
3. Design Special weights are not displayed.
0,0
Point Load 6: 776.6 lb
Any weight added through COD (Custom
Point Load 7: 762.1 lb
Order Design)
Point Load 8: 797 8 lb
will not be accounted in the +/- 10% estimate
0
4. When 2 or more units are to be placed side by
Total Weight: 5,760.0lb
side, the distance between the units should be
increased to 150% of the recommended single
Point load X location 1: 0.33 ft
unit clearance. The units should also be
Point load X location 2: 10.33 ft
staggered to reduce span deflection & assure
Point load X location 3: 18.83 ft
proper diffusion of exhaust air.
Point load X location 4: 22.08 ft
Point load X location 5: N/A
Point load Y location 1: 0.33 ft
Point load Y location 2: 7.25 ft
PL 2, X1
PI-4 X2
PL 6, X 3 PL 8 X4
PL3.X2 PL5,X3 PL7.X4
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
Created: 1/9/2024 Page: 6 of 8
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
72"
96"
Note:
When 2 or more units are to be placed side by side, the distance between the units
should be increased to 150% of the recommended single unit clearance. The units
should also be staggered to reduce span deflection & assure proper diffusion of
exhaust air.
CLEARANCE
CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS
AIR COOLED DRAWING
96"
96"
CLEARANCE
Created: 1/9/2024 Page: 7 of 8
Tag: 25T RTU-2, 25T RTU-2-1
T/�ANE® CQuantity:
Customer:
Project:
Name: Kruger Medical Building Remodel
CUSTOMER CONNECTION WIRE RANGE
NOTES:
COMPONENT TYPE/SIZE
WIRE OTY
PER PHASE
WIRE RANGE
510ATERMINALBLOCK
2
6AWG-250kemI
TERMINAL BLOCKAND STD SCCR DISCONNECT SWITCH SIZES ARE
760ATERMINAL BLOCK
2
4 AWG -500 kcmil
CALCULATED BY SELECTING THE SIZE GREATER THAN OR EQUAL
TO 1.15 X (SUM OF UNIT LOADS).
150ADISCONNECT SWITCH (STD SCCR)
1
14AWG -30AWG
250A DISCONNECT SWITCH (STD SCCR)
1
3/0AWG - 350 kcmil
SEE UNIT LITERATURE FOR UNIT LOAD VALUES.
400ADISCONNECT SWITCH (STD SCCR)
2
2/0AWG -500 kcmil
600ADISCONNECT SWITCH (STD SCCR)
2
2/0AWG -500 kcmil
HIGH SCCR DISCONNECT SWITCH SIZESARE CALCULATED BY SELECTING
150ADISCONNECT SWITCH (HIGH SCCR)
1
14AWG-3)OAWG
250A DISCONNECT SWITCH (HIGH SCCR)
1
3/0AWG - 350 kcmil
THE SIZE GREATER THAN OR EQUAL TO 1.25 X (SUM OF UNIT LOADS).
400ADISCONNECT SWITCH (HIGH SCCR)
2
2/0AWG -500 kcmil
SEE UNIT LITERATURE FOR UNIT LOAD VALUES.
600ADISCONNECT SWITCH (HIGH SCCR)
2
2/0AWG -500 kcmil
`250A DISCONNECT SWITCHES CAN ACCOMMODATE 4AWG - 4/0AWG IF LUG SCREWS ARE CHANGED TO S1A59551 KIT (PROVIDED WITH UNIT)
Created: 1/9/2024 Page: 8 of 8