OUTDOOR UNIT (a) (b)
A4AC3048D1000A
POWER CONNS. - V/PH/HZ (c)
208/230/1/60
MIN. CIR. AMPACITY
24
MAX. OVERCURRENT PROTECTION
40
COMPRESSOR
SCROLL
NO. USED - NO. STAGES
1 - 1
VOLTS/PH/HZ
208/230/1/60
R.L. AMPS (d) - L.R. AMPS
18.5 - 124
FACTORY INSTALLED
YES/NO
START COMPONENTS (e)
NO
INSULATION/SOUND BLANKET
NO
COMPRESSOR HEAT
NO
OUTDOOR FAN
PROPELLER
DIA. (IN.) - NO. USED
27.5
TYPE DRIVE - NO. SPEEDS
DIRECT- 1
CFM @ 0.0IN. W.G. M
4410
NO. MOTORS - HP
1-1/5
MOTOR SPEED R.P.M.
825
VOLTS/PH/HZ
208/230/1/60
F.L. AMPS
0.93
OUTDOOR COIL - TYPE
ALL ALUMINUM
ROWS-F.P.I.
1-24
FACE AREA (SQ. FF.)
18.03
TUBE SIZE (IN.)
3/8
REFRIGERANT
LBS. - R-410A (O.D. UNIT) (g)
5 LBS., 3 OZ
FACTORY SUPPLIED
YES
LINE SIZE - IN. O.D. GAS (h) (i)
7/8
LINE SIZE - IN. O.D. LIQ.
3/8
CHARGING SPECIFICATIONS
SUBCOOLING
10OF
DIMENSIONS
H X W X D
CRATED (IN.)
31.7 x 35 x 35
WEIGHT
SHIPPING (LBS.)
189
NET (LBS.)
159
BLD2024-0786 RECEIVED
Jun 14 2024
REVIEWED - 11VELOPMENrsa°CES
BY DEPARTMENT
CITY OF EDMONDS
BUILDING DEPARTMENT
(a) Certified in accordance with the Air -Source Unitary Air -conditioner
Equipment certification program, which is based on AHRI standard
210/240.
(b) Rated in accordance with AHRI standard 270.
(c) Calculated in accordance with Natl. Elec. Codes. Use only HACR
circuit breakers or fuses.
(d) This value shown for compressor RLA on the unit nameplate and on
this specification sheet is used to compute minimum branch circuit
ampacity and max. fuse size. The value shown is the branch circuit
selection current.
(e) No means no start components. Yes means quick start kit
components. Optional authorized kits include KIT07689 for RunTru or
BAYKSKT267.
M Standard Air - Dry Coil - Outdoor
(9) This value approximate. For more precise value see unit nameplate.
(h) Reference the outdoor unit ship -with literature for refrigerant piping
length and lift guidelines. Reference the refrigerant piping software
pub # 32-3312-xx or refrigerant piping application guide SS-
APG006-xx for long line sets or specialty applications (xx denotes
latest revision).
(I) The outdoor condensing units are factory charged with the system
charge required for the outdoor condensing unit, ten (10) feet of
tested connecting line, and the smallest rated indoor evaporative coil
match. Always verify proper system charge via subcooling (TXV/EEV)
or superheat (fixed orifice) per the unit nameplate.
AM-PRQ-A4AC3048D-1 A-E N