APPROVED FIR2023-0116+Fire_Alarm_Battery_Calculations+12.4.2023_11.52.30_AM+3931848L
D
4
9
I
0
N
0
0
E
F
i
I
GENERAL SYSTEM NOTES
PANEL:
1. THE SUPPLEMENTAL NOTIFICATION REMOTE POWER SUPPLY (RPS) IS TO
BE MOUNTED SURFACE, BESIDE THE FACP. THE TOP OF THE PANEL SHALL
NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM
CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED.
2. THE RPS IS TO BE POWERED BY THE SAME DEDICATED 120 VAC
CIRCUIT AS THE FACP. TWO CONDUCTORS TO 120 VAC, ONE CONDUCTOR
TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A HOUSE GROUND WILL
NOT BE ACCEPTABLE.
3. THE BOTTOM THE RPS SHALL BE PENETRATED.
DEVICES:
1. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE
PLACED AT 80 INCHES ABOVE FINISHED FLOOR WITHIN THE SPACE, OR THE
TOP OF THE DEVICE 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER.
2. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL
SETTING.
r�21111IIIIIlIIIIIIIIIIIIIIIIIIII•»•i1y:��r•>• 3��•zy�ra.»a ;ira�•�:n���m�e��l
4. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE
EXISTENCE AND LOCATION OF ALL MOTORIZED SMOKE DAMPERS. THESE ARE
TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE. THESE DEVICE
CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING
RELAY.
5. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS
OF THE SPRINKLER WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES
AND PIV OR 0, S, & Y VALVES.
6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE
OF SPRINKLER HEAT TAPE. THIS HEAT TAPE SHALL BE MONITORED BY THE
FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT WILL PROVIDE
SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY
POWER.
7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL
APPLICABLE INTERSTITIAL CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED
WITH SPRINKLER HEADS.
WIRING:
1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO
TRANSMITTER.
2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER
OR PLENUM RATED WIRE WHERE REQUIRED PER NEC).
3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR
(ELR) AS APPROPRIATE WITH THE FACP / RPS.
4. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND
APPROPRIATELY MARKED.
5. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE
SAME CONDUIT OR RISER AS THE LOW VOLTAGE FIRE ALARM SYSTEM WIRING.
6. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING
AS PART OF THE CABLE.
7. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE
WITHOUT "SHIELDED" AS PART OF THE DESCRIPTION.
GENERAL:
1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED.
2. ALL END OF LINE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER
AT THE E.O.L. LOCATION.
3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC
DEVICE ON ANY GIVEN JUNCTION BOX SHALL BE LEFT OPEN FOR
TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL PASS
THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX.
0110115101 1
ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO SOLUTIONS, INC. HAS
A WARRANTY OF ONE YEAR FROM DATE OF INVOICE. THIS WARRANTY
EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES, AND IS GIVEN IN
LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF
FITNESS, HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER
THE LAWS OF WASHINGTON. ANY WARRANTY WORK PERFORMED BY ABSCO
SOLUTIONS, INC. DOES NOT EXTEND THE WARRANTY OF ONE YEAR FROM
THE DATE OF THE INVOICE.
THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN
ABSCO SOLUTIONS, INC. OR THE CONTRACTOR AUTHORIZED BY ABSCO
SOLUTIONS, INC. PERFORMS OR RE —PERFORMS ANY WORK IDENTIFIED WITHIN
THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO
SOLUTIONS, INC.
LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART
OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS,
INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND
ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO
SOLUTIONS, INC.
TYPICAL
MOUNTING
HEIGHTS
FINISHED
CEILING
CEILING MOUNT
CEILING MOUNT
—STROBE
—SMOKE DETECTOR
—SPEAKER STROBE
—HEAT DETECTOR
CONTROL
MANUAL
PANEL
PULL
STATION
r FF]
60"
48"
FINISHED
FLOOR
Approved
DFM ak6s Burt
South County Fire
Date: 12/13/2023
12-13-2023
PLAN REVIEW
NOTES: APPROVED WITH
CONDITIONS:
1. INSTALL ANNUNCIATOR PANEL
TO RISER ROOM (SHEET FZ101)
2. KNOX BOX REQUIRED AT RISER
ROOM DOOR. (SHEET FZ101)
3. FACP/RISER ROOM AND NO
STORAGE SIGNAGE REQUIRED ON
EXTERIOR DOOR. (SHEET FZ101)
4. INSTALL ONE EXTERIOR STROBE
NEAR EXTERIOR FACP/RISER ROOM
EXTERIOR DOOR. (SHEET FZ101)
5. INSTALL PROTECTIVE COVERS
ON ALL PULL STATIONS PER IFC
907.4.2.5.
DFM BURT
Symbol Legend
SYMBOL
DESCRIPTION
MANUFACTURER
PART NUMBER
BACKBOX REQUIREMENTS
QUANTITY
FI N_X Iij
AM-50 TRANSPONDER 50 WATT, 25 VRMS AUDIO AMPLIFIER
GAMEWELL FCI
1100-0460
1100-0460 - B SIZE, BLACK
1
RPS1
12 AMP AND 24 VOLT POWER SUPPLY
GAMEWELL FCI
HPFF12
PROVIDED
1
DOC
DOCUMENT STORAGE BOX, 12 IN. X 13 IN. X 2.25 IN. W/4GB FLASH DRIVE
SPACEAGE
SS000685
PROVIDED
1
Sp
PHOTO, SMOKE, DETECTOR, IVORY
GAMEWELL FCI
ASD-PL3-IV
B300-6-IV / 4SQR W / 3-0 RING
21
OS
TAMPER SWITCH
GENERIC
GTS
PROVIDED
3
WF
GEN WATERFLOW
GENERIC
GWF
PROVIDED
2
❑F
PULL STATION, DOUBLE ACTION, ADDRESSABLE
GAMEWELL FCI
MS-7AF
DEEP 4-SQR
4
AIM 1
MONITOR MODULE, ADDRESSABLE, CLASS B
GAMEWELL FCI
AMM-21F
DEEP 4-SQR
6
i0
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
SYSTEM SENSOR
SCWL
DEEP 4-SQR
6
L-SERIES SPEAKER/STROBE, WHITE, CEILING
SYSTEM SENSOR
SPSCWL
4-11/16" J-BOX W/4" MUD RING
23
EOL Re
EOL-4.7K
GAMEWELL FCI
EOL-4.7
PROVIDED
4
FACP
E
EXISTING FACP, ANALOG ADDRESSABLE, BILK
GAMEWELL FCI
EXISTING SLP-BLK
EXISTING
1
OS E
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
GAMEWELL FCI
EXISTING ASD-PL3-IV
EXISTING
13
0135'
E
EXISTING THERMAL HEAT DETECTOR 135F, BRIGHT WHITE
GAMEWELL FCI
EXISTING ATD-L3
EXISTING
1
E
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
GAMEWELL FCI
EXISTING MS-7AF
EXISTING
9
\o
\E
EXISTING L-SERIES STROBE 2 WIRE M-C WHITE CEILING
f f f f
SYSTEM SENSOR
EXISTING SCWL
EXISTING
10
Fire Alarm Device Numbering
Circuit
F_ Unique ID
Circuit
Unique ID
F
NACl-001
SLC1•S:001
ADDRESSABLE DEVICE NUMBERING
ADDRESSABLE NAC NUMBERING
Wire Path Label Legend
Chr. Position
Character Purpose
#1
Quantity of the same circuit
#2
Circuit name
14/2-oas = 14AWG 2 CONDUCTOR - SHIELDED CABLE
14/2-ns = 14AWG 2 CONDUCTOR - NON -SHIELDED CABLE
16/2-ns = 16AWG 2 CONDUCTOR - NON -SHIELDED CABLE
PROJECT NOTES
• ALL EXISTING HORN STROBE DEVICES ARE BEING REPLACED WITH SPEAKER STROBES
• TECHNICIAN TO AS —BUILD DEVICE ADDRESSES
• AMBIENT TEMPERATURE 70°F IN ALL SPACES
• AMBIENT SOUND LEVEL >40DB IN ALL SPACES
PROJECT SCOPE OF WORK
• PROVIDE FIRE ALARM UPGRADE TO ACCOMMODATE A REVISED FLOOR PLAN. OCCUPANCY TOTAL WILL NOW REQUIRE THE BUILDING TO BE
CHANGED FROM A FIRE ALARM SYSTEM TO A FIRE ALARM VOICE EVACUATION SYSTEM, PER CODE AND AHJ.
SEQUENCE OF OPERATIONS
Output Activated
Alarm Device
General
Notification -
Alarm Strobe +
Speaker
Transmit
Alarm
Signals
Transmit
Trouble
Signals at
FACP
Transmit
Supervisory
Signals at
FACP
Enable
Speakers for
Announcement
Keypad
Annunciator
Smoke Detector
X
X
X
Heat Detector
X
X
X
Manual Pull Station
X
X
X
EA. FACP Alarm
X
X
X
EA. FACP Trouble
X
X
Ext. FACP Supervisory
X
X
Water Flow Alarm
X
X
X
Water Flow Supervisory
X
X
Key Microphone
X
F I R2023-0116
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Firm Name and Address
AQ
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM
NICET: IV # 97083
Q5-
1-08/09/23
Submittal Set
AP
Rev.# —Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
FIRE
ALAR M
Sheet Name
LEGENDS,
DETAILS,
FIRE ALARM
PLANS
1
01
0
III
FOR
L
I
l7
I
Firm Name and Address
N
0
E
F
G
101
Appliance List
Job number: 24495 Job name: The Trike Stop - FA
Panel Card
Circuit
Address
Device
Part Number
Description
User Label
INX1
SPK1
END OF LINE
EOL-4.7
EOL-4.7K
INX1
SPK2
END OF LINE
EOL-4.7
EOL-4.7K
RPX
NAC1
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKERISTROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC1
END OF LINE
EOL-4.7
EOL-4.7K
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
STROBE
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
SPEAKER/STROBE
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
EXISTING STROBE
EXISTING SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING
RPX
NAC2
END OF LINE
EOL-4.7
EOL-4.7K
ZN1
[SLC1•M:010]
VALVE TAMPER SWITCH
GTS
TAMPER SWITCH
ZN1
[SLC1•M:011]
VALVE TAMPER SWITCH
GTS
TAMPER SWITCH
ZN1
[SLC1•M:012]
VALVE TAMPER SWITCH
GTS
TAMPER SWITCH
ZN1
[SLC1•M:013]
WATERFLOW SWITCH
GWF
GEN WATERFLOW
ZN1
[SLC1•M:014]
WATERFLOW SWITCH
GWF
GEN WATERFLOW
SLC-PM
SLC1
S:001
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:001
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:002
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:002
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
M:003
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:003
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:004
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:004
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:005
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:005
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
M:006
ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:006
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:007
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:007
ADDRESSABLE PULL STATION
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:008
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:008
ADDRESSABLE PULL STATION
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:009
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:009
ADDRESSABLE PULL STATION
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:010
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:010
MONITOR MODULE
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
M:011
MONITOR MODULE
AMM-217
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
S:011
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:012
MONITOR MODULE
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
S:012
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:013
WALLBOX / ENCLOSURE
SS000685
DOCUMENT STORAGE BOX, W/4GB FLASH DRIVE
SLC-PM
SLC1
M:013
MONITOR MODULE
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
S:013
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:014
MONITOR MODULE
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
S:014
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:015
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:015
MONITOR MODULE
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
SLC-PM
SLC1
M:016
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:016
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:017
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:017
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:018
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
M:018
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
M:019
EXISTING ADDRESSABLE PULL STATION
EXT. MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SLC-PM
SLC1
S:019
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:020
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:021
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:022
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:023
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:024
EXISTING HEAT DETECTOR
EXT. ATD-L3
THERMAL HEAT DETECTOR 135F, BRIGHT WHITE
SLC-PM
SLC1
S:025
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:026
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:027
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:028
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:029
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:030
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:031
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:032
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:033
PHOTOELECTRIC DETECTOR
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:034
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
SLC-PM
SLC1
S:035
EXISTING PHOTOELECTRIC DETECTOR
EXT. ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
Cable/Circuit Report
Job number: 24495 Job name: The Trike Stop - FA
Cable Length Overage: 0%
Source
Circuit
Circuit Type
Wiring Style
Manufacturer
Part No.
Type
Description
Gauge
Length
Color
INX1
IMP1
Power
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
2'-7
Red
INX1
SPK1
Notification
Class B
WINDY CITY
767920
Fire Alarm
14 AWG 2 CONDUCTOR, SHIELDED FPLP
#14
392'-8 1/2
Red
INX1
SPK2
Notification
Class B
WINDY CITY
767920
Fire Alarm
14 AWG 2 CONDUCTOR, SHIELDED FPLP
#14
341'-5
Red
RPS1
AUX1
Power
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
X-4
Red
RPS1
NAC1
Notification
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
384'-10 1/2
Red
RPS1
NAC2
Notification
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
333'-8 1/2
Red
EXT. FACP
SLC1
Signaling line
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
855'-11
Red
Device[SLC1:M:010]
ZN1
Initiating
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
1'-10
Red
Device[SLC1:M:011]
ZN1
Initiating
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
1'-11
Red
Device[SLC1:M:012]
ZN1
Initiating
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
1'-11
Red
Device[SLC1:M:013]
ZN1
Initiating
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
2'-2
Red
Device[SLC1:M:014]
ZN1
Initiating
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
2'-3 1/2
Red
Appliance List by Circuit
Notification/Speaker Devices
Circuit
Device
INX1:SPK1.001
SPEAKER/STROBE
INX1:SPK1.002
SPEAKER/STROBE
INX1:SPK1.003
SPEAKER/STROBE
INX1:SPK1.004
SPEAKER/STROBE
INX1:SPK1.005
SPEAKER/STROBE
INX1:SPK1.006
SPEAKER/STROBE
INX1:SPK1.007
SPEAKER/STROBE
INX1:SPK1.008
SPEAKER/STROBE
INX1:SPK1.009
SPEAKER/STROBE
INX1:SPK1.010
SPEAKER/STROBE
INX1:SPK1.011
SPEAKER/STROBE
INX1:SPK1.012
SPEAKER/STROBE
INX1:SPK2.001
SPEAKER/STROBE
INX1:SPK2.002
SPEAKER/STROBE
INX1:SPK2.003
SPEAKER/STROBE
INX1:SPK2.004
SPEAKER/STROBE
INX1:SPK2.005
SPEAKER/STROBE
INX1:SPK2.006
SPEAKER/STROBE
INX1:SPK2.007
SPEAKER/STROBE
INX1:SPK2.008
SPEAKER/STROBE
INX1:SPK2.009
SPEAKER/STROBE
INX1:SPK2.010
SPEAKER/STROBE
INX1:SPK2.011
SPEAKER/STROBE
RPS1: NAC1.001
SPEAKER/STROBE
RPS1: NAC1.002
SPEAKER/STROBE
RPS1:NAC1.003
SPEAKER/STROBE
RPS1: NAC1.004
SPEAKER/STROBE
RPS1:NAC1.005
SPEAKER/STROBE
RPS1: NAC1.009
SPEAKER/STROBE
RPS1:NAC1.010
SPEAKER/STROBE
RPS1:NAC1.013
SPEAKER/STROBE
RPS1:NAC1.015
SPEAKER/STROBE
RPS1: NAC1.016
SPEAKER/STROBE
RPS1:NAC1.017
SPEAKER/STROBE
RPS1:NAC1.020
SPEAKER/STROBE
RPS1:NAC2.001
SPEAKER/STROBE
RPS1: NAC2.003
SPEAKER/STROBE
RPS1:NAC2.004
SPEAKER/STROBE
RPS1:NAC2.008
SPEAKER/STROBE
RPS1:NAC2.009
SPEAKER/STROBE
RPS1:NAC2.011
SPEAKER/STROBE
RPS1:NAC2.012
SPEAKER/STROBE
RPS1: NAC2.013
SPEAKER/STROBE
RPS1:NAC2.015
SPEAKER/STROBE
RPS1:NAC2.016
SPEAKER/STROBE
RPS1: NAC2.019
SPEAKER/STROBE
RPX:AUX1.001
EXISTING FACP
RPX:NAC1.006
EXISTING STROBE
RPX:NAC1.007
EXISTING STROBE
RPX:NAC1.008
EXISTING STROBE
RPX:NAC1.011
STROBE
RPX:NAC1.012
STROBE
RPX: NAC1.014
STROBE
RPX: NAC1.018
STROBE
RPX:NAC1.019
STROBE
RPX:NAC2.002
EXISTING STROBE
RPX:NAC2.005
EXISTING STROBE
RPX:NAC2.006
EXISTING STROBE
RPX:NAC2.007
EXISTING STROBE
RPX: NAC2.010
STROBE
RPX:NAC2.014
EXISTING STROBE
RPX:NAC2.017
EXISTING STROBE
RPX:NAC2.018
EXISTING STROBE
Appliance List by Circuit
Initiating Devices
Circuit
Device
[SLC1•M:010]:ZN1-001
VALVE TAMPER SWITCH
[SLC1•M:011]:ZN1-001
VALVE TAMPER SWITCH
[SLC1•M:012]:ZN1-001
VALVE TAMPER SWITCH
[SLC1•M:013]:ZN1-001
WATERFLOW SWITCH
[SLC1•M:014]:ZN1-001
WATERFLOW SWITCH
SLC-PM:SLC1-M:001
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:002
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:003
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:004
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:005
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:006
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:007
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:008
ADDRESSABLE PULL STATION
SLC-PM:SLC1-M:009
ADDRESSABLE PULL STATION
SLC-PM:SLC1-M:010
MONITOR MODULE
SLC-PM:SLC1-M:011
MONITOR MODULE
SLC-PM:SLC1-M:012
MONITOR MODULE
SLC-PM:SLC1-M:013
MONITOR MODULE
SLC-PM:SLC1-M:014
MONITOR MODULE
SLC-PM:SLC1-M:015
MONITOR MODULE
SLC-PM:SLC1-M:016
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:017
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:018
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-M:019
EXISTING ADDR. PULL STATION
SLC-PM:SLC1-S:001
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:002
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:003
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:004
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:005
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:006
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:007
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:008
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:009
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:010
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:011
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:012
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:013
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:014
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:015
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:016
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:017
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:018
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:019
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:020
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:021
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:022
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:023
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:024
EXISTING HEAT DETECTOR
SLC-PM:SLC1-S:025
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:026
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:027
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:028
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:029
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:030
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:031
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:032
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:033
PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:034
EXISTING PHOTOELECTRIC DETECTOR
SLC-PM:SLC1-S:035
EXISTING PHOTOELECTRIC DETECTOR
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
sehlrdom
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM
NICET: IV # 97083
05-
1-08/09/23
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
FIRE
ALARM
Sheet Name
APPLIANCE
LISTS &
CABLE/CIRCUIT
REPORT
1
11
0
n
L 1 1 4 1 1 b I / 1 0
A
B
D
E
F
G
H
Battery Calculations for Panel: EXT. FACP
Part No:EXISTING SLP-BLK - FACP
Job number: 24495 Job name: The Trike Stop - FA
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
Panel Equipment
SLP MB
1
SLP MAIN ELECTRONICS, BOARD
111.0000 mA
111.0000 mA
243.0000 mA
243.0000 mA
LCD-SLP
1
LCD COLOR TOUCHPAD DISPLAY
30.0000 mA
30.0000 mA
65.0000 mA
65.0000 mA
RPT-E3-UTP
1
REPEATER MODULE - TWISTED PAIR
16.0000 mA
16.0000 mA
17.0000 mA
17.0000 mA
DACT-E3
1
DIGITAL ALARM COMMUNICATOR TRANSMITTER
18.0000 mA
18.0000 mA
18.0000 mA
18.0000 mA
SLC-PM
1
SLC LOOP CARD, VELOCITI OR CLIP MODE
14.0000 mA
14.0000 mA
14.0000 mA
14.0000 mA
PM-9
1
POWER SUPPLY MODULE - 9-AMP
50.0000 mA
50.0000 mA
50.0000 mA
50.0000 mA
Total Panel Stby
239.0000 mA
Total Panel Alarm
407.0000 mA
Peripheral Devices
AMM-2F
6
MONITOR MODULE, ADDRESSABLE, CLASS B
0.3750 mA
2.2500 mA
0.6000 mA
3.6000 mA
ASD-PL3-IV
34
PHOTO, SMOKE, DETECTOR, IVORY
0.2000 mA
6.8000 mA
2.0000 mA
68.0000 mA
MS-7AF
13
PULL STATION, DOUBLE ACTION, ADDRESSABLE
0.3000 mA
3.9000 mA
3.0000 mA
39.0000 mA
ATD-L3
1
THERMAL HEAT DETECTOR 135F, BRIGHT WHITE
0.2000 mA
0.2000 mA
2.0000 mA
2.0000 mA
GTS
3
TAMPER SWITCH (Initiating)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
GWF
2
GEN WATERFLOW (Initiating)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
Total Peripheral Stbyl
13.1500 mA
Total Periph Alarm
112.6000 mA
Total Standby Amps
252.1500 mA
Total Alarm Amps
519.6000 mA
Standby time: 24 Hrs 6.052 Ah
Alarm time: 5 Min 0.043 Ah
Battery requirement: 6.095 Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.314 Ah
Circuit Calculations Panel: EXT. FACP Card: SLC-PM Circuit:SLC1
Circuit Name: SLC1
Circuit Type: Signaling line/FCI - SLC, VELOCITY Terminal Voltage: 20.4 V:DC Amperage: 1.0000 A
Cable: 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP #16
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167 OF Max. operating voltage drop: 18%
Device
Part No
Appliance Desc
Distance
Current
Voltage Voltage Drop
SLP-BLK
Existing Panel
20.4 V
S:001
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
X-0
0.2000 mA
20.3998 V
(0.0002 V)
M:001
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
8'-10
0.3000 mA
20.3989 V
(0.0008 V)
S:002
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
17'-7
0.2000 mA
20.3972 V
(0.0018 V)
S:003
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
19'-2 1/2
0.2000 mA
20.3952 V
(0.0019 V)
M:002
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
27'-2
0.3000 mA
20.3925 V
(0.0027 V)
S:004
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
6'-11
0.2000 mA
20.3919 V
(0.0006 V)
S:005
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
16'-2
0.2000 mA
20.3904 V
(0.0015 V)
M:003
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
26'-5 1/2
0.3000 mA
20.3879 V
(0.0025 V)
S:006
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
8'-9
0.2000 mA
20.3872 V
(0.0007 V)
M:004
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
23'-7 1/2
0.3000 mA
20.3851 V
(0.0021 V)
S:007
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
8'-2
0.2000 mA
20.3844 V
(0.0007 V)
S:008
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
22'-2 1/2
0.2000 mA
20.3825 V
(0.0019 V)
S:009
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
33'-7
0.2000 mA
20.3797 V
(0.0028 V)
M:005
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
8'-2 1/2
0.3000 mA
20.379 V
(0.0007 V)
S:010
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
6'-11 1/2
0.2000 mA
20.3785 V
(0.0005 V)
S:011
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
27'-4
0.2000 mA
20.3764 V
(0.0021 V)
S:012
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
22'-6 1/2
0.2000 mA
20.3747 V
(0.0017 V)
M:006
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
12'-10 1/2
0.3000 mA
20.3738 V
(0.0009 V)
S:013
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
14'-1
0.2000 mA
20.3728 V
(0.001 V)
M:007
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
18'-9 1/2
0.3000 mA
20.3715 V
(0.0013 V)
S:014
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
15'-41/2
0.2000 mA
20.3704 V
(0.001 V)
S:015
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
33'-7
0.2000 mA
20.3682 V
(0.0022 V)
S:016
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
19'-11
0.2000 mA
20.3669 V
(0.0013 V)
S:017
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
19'-4
0.2000 mA
20.3657 V
(0.0012 V)
S:018
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
21'-2 1/2
0.2000 mA
20.3644 V
(0.0013 V)
M:008
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
28'-0
0.3000 mA
20.3628 V
(0.0016 V)
S:019
ASD-PL34V
PHOTO, SMOKE, DETECTOR, IVORY
10'-7
0.2000 mA
20.3622 V
(0.0006 V)
M:009
MS-7AF
PULL STATION, DOUBLE ACTION, ADDRESSABLE
19'-10
0.3000 mA
20.3611 V
(0.0011 V)
S:020
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
20'-8 1/2
0.2000 mA
20.36 V
(0.0011 V)
M:010
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
2'-5 1/2
0.3750 mA
20.3599 V
(0.0001 V)
M:011
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
1'-9
0.3750 mA
20.3598 V
(0 V)
M:012
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
V-9 1/2
0.3750 mA
20.3598 V
(0 V)
M:013
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
6'-0
0.3750 mA
20.3596 V
(0.0002 V)
M:014
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
V-9 1/2
0.3750 mA
20.3595 V
(0 V)
S:021
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
15'-8
0.2000 mA
20.359 V
(0.0006 V)
S:022
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
15'-8
0.2000 mA
20.3584 V
(0.0005 V)
S:023
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
9'-11
0.2000 mA
20.3581 V
(0.0003 V)
S:024
EXT. ATD-L3
EXISTING THERMAL HEAT DETECTOR 135F, BRIGHT WHITE
V-10
0.2000 mA
20.358 V
(0.0002 V)
M:015
AMM-2F
MONITOR MODULE, ADDRESSABLE, CLASS B
20'-6
0.3750 mA
20.3573 V
(0.0006 V)
S:025
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
6'-3 1/2
0.2000 mA
20.3572 V
(0.0002 V)
S:026
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
23'-0 1/2
0.2000 mA
20.3566 V
(0.0006 V)
M:016
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
9'-11 1/2
0.3000 mA
20.3564 V
(0.0002 V)
S:027
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
26'-9 1/2
0.2000 mA
20.3558 V
(0.0006 V)
M:017
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
14'-3
0.3000 mA
20.3555 V
(0.0003 V)
S:028
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
27'-4
0.2000 mA
20.355 V
(0.0005 V)
S:029
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
30'-6 1/2
0.2000 mA
20.3545 V
(0.0005 V)
S:030
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
14'-4 1/2
0.2000 mA
20.3543 V
(0.0002 V)
M:018
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
14'-11
0.3000 mA
20.3541 V
(0.0002 V)
S:031
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
3'-10 1/2
0.2000 mA
20.3541 V
(0 V)
S:032
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
14'-10
0.2000 mA
20.354 V
(0.0001 V)
S:033
ASD-PL3-IV
PHOTO, SMOKE, DETECTOR, IVORY
12'-11 1/2
0.2000 mA
20.3539 V
(0.0001 V)
S:034
EXT. ASD-PL3-IV
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
19'-6
0.2000 mA
20.3538 V
(0.0001 V)
M:019
EXT. MS-7AF
EXISTING PULL STATION, DOUBLE ACTION, ADDRESSABLE
12'-2
0.3000 mA
20.3537 V
(0 V)
S:035
EXT. ASD-PL34V
EXISTING PHOTO, SMOKE, DETECTOR, IVORY
22'-10 1/2
0.2000 mA
20.3537 V
(0 V)
855'-11
13.1500 mA
Total Current: 13.1500 mA
(Total VDrop Percent:0.23%) Total Voltage Drop : 0.0463 V
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Firm Name and Address
(s
sehlrdom
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM
NICET: IV # 97083
1-08/09/23
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
SIRE
ALARM
1 1 ? I I L I I r, 1 '7 1 R
L I 1 1 4 1 1 b I / 1 0
A
B
D
E
F
G
H
Battery Calculations for Panel: RPS1
Part No:HPFF12 - 12 AMP AND 24 VOLT POWER SUPPLY
Job number: 24495 Job name: The Trike Stop - FA
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
Panel Equipment
HPFF12 MB
1
MAIN BOARD FOR HPFF12
75.0000 mA
75.0000 mA
206.0000 mA
206.0000 mA
Total Panel Stby
75.0000 mA
Total Panel Alarm
206.0000 mA
Peripheral Devices
SLP-BLK
1
EXISTING FACP, ANALOG ADDRESSABLE, LCD-SLP (Power)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SCWL
16
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING (Notif.) 15CD
0.0000 mA
0.0000 mA
41.0000 mA
656.0000 mA
EOL-4.7
2
EOL-4.7K (Notif.)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SPSCWL
14
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 15CD
0.0000 mA
0.0000 mA
41.0000 mA
574.0000 mA
SPSCWL
2
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 30CD
0.0000 mA
0.0000 mA
63.0000 mA
126.0000 mA
SPSCWL
7
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 75CD
0.0000 mA
0.0000 mA
111.0000 mA
777.0000 mA
Total Peripheral Stby
0.0000 mA
Total Periph Alarm
2133.0000 mA
Total Standby Amps
75.0000 mA
Total Alarm Amps
2339.0000 mA
Compensation Factors - Standby: 1.2 Alarm: 1.2
Standby time: 24 Hrs 1.8 Ah
Alarm time: 5 Min 0.195 Ah
Battery requirement: 1.995 Ah
Requirement with compensation: 2.394 Ah
Battery Calculations for Panel: INX1
Part No:1100-0460 - INX-CAB, ENCLOSURE, TRANSPONDER, B SIZE, BLACK
Job number: 24495 Job name: The Trike Stop - FA
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
Panel Equipment
INI-VGX
1
INI-VGX COMMAND CENTER VOICE GATEWAY
150.0000 mA
150.0000 mA
150.0000 mA
150.0000 mA
PM-9
1
POWER SUPPLY MODULE - 9-AMP
50.0000 mA
50.0000 mA
50.0000 mA
50.0000 mA
INCC-MIC
1
PAGING MICROPHONE ONLY
20.0000 mA
20.0000 mA
66.0000 mA
66.0000 mA
AM-50-25
1
INX 50 WATT, 25V, AMPLIFIER
86.0000 mA
86.0000 mA
2206.0000 mA
2206.0000 mA
Total Panel Stby
306.0000 mA
Total Panel Alarm
2472.0000 mA
Peripheral Devices
EOL-4.7
2
EOL-4.7K (Notification)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SPSCWL
13
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 77dB 0.25 Watts
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SPSCWL
3
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 80dB 0.5 Watts
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SPSCWL
7
L-SERIES SPEAKER/STROBE, WHITE, CEILING (Notif.) 83dB 1 Watts
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
Total Peripheral Stby
0.0000 mA
Total Periph Alarm
0.0000 mA
Total Standby Amps
306.0000 mA
Total Alarm Amps
2472.0000 mA
Standby time: 24 Hrs 7.344 Ah
Alarm time: 5 Min 0.206 Ah
Battery requirement: 7.55 Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 9.06 Ah
Circuit Calculations Panel: INX1 Card: INX1 Circuit:SPK1
Design
Criteria: Ambient temperature: 167 OF Maximum dB Drop: 3 dB
Circuit
Description
Type
Total Len
SPSCWL
EOL-4.7
Total Watts
Gauge
dB Loss
Max Allowable Len
SPK1
SPEAKER
Notification/Audio 25v
384'-9
12
1
5.50 Watts
#14
-0.22 dB
6072'
Circuit Calculations Panel: INX1 Card: INX1 Circuit:SPK2
Design Criteria: Ambient temperature: 167 OF Maximum dB Drop: 3 dB
Circuit
Description
Type
Total Len
SPSCWL
EOL-4.7
Total Watts
Gauge
dB Loss
Max Allowable Len
SPK2
SPEAKER
Notification/Audio 25v
341'-5
11
1
6.25 Watts
#14
-0.23 dB
5344'
Circuit Calculations Panel: RPS1 Card: RPX Circuit:NAC1
Circuit Name: NAC1
Circuit Type: Notification Terminal Voltage: 20.4 V:DC Amperage: 3.0000 A
Cable: 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP #14
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167 OF Max. operating voltage drop: 18%
Device
Part No
Appliance Desc
Distance
Current
Voltage
Voltage Drop
HPFF12
Panel
20.4 V
001
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
22'-4 1/2
41.0000 mA
20.281 V
(0.119 V)
002
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
24'-11
41.0000 mA
20.1563 V
(0.1247 V)
003
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
15'-4 1/2
41.0000 mA
20.0815 V
(0.0748 V)
004
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
12'-5
41.0000 mA
20.0242 V
(0.0573 V)
005
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
19'-3 1/2
41.0000 mA
19.9375 V
(0.0867 V)
006
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
11'-5
41.0000 mA
19.8896 V
(0.0479 V)
007
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
9'-11
41.0000 mA
19.8523 V
(0.0373 V)
008
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
10'-9
41.0000 mA
19.813 V
(0.0393 V)
009
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 30CD
22'-4 1/2
63.0000 mA
19.7311 V
(0.0819 V)
010
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
26'-2 1/2
41.0000 mA
19.6428 V
(0.0883 V)
011
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
12'-5
41.0000 mA
19.6046 V
(0.0382 V)
012
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
21'-3
41.0000 mA
19.5421 V
(0.0625 V)
013
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
13'-2
41.0000 mA
19.5061 V
(0.0359 V)
014
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
15'-1 1/2
41.0000 mA
19.4678 V
(0.0383 V)
015
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
17'-4 1/2
111.0000 mA
19.428 V
(0.0398 V)
016
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
40'-1
111.0000 mA
19.357 V
(0.0709 V)
017
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
28'-2 1/2
41.0000 mA
19.3233 V
(0.0337 V)
018
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
23'-10
41.0000 mA
19.3005 V
(0.0228 V)
019
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
9'-1 1/2
41.0000 mA
19.2935 V
(0.007 V)
020
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
18'-4 1/2
111.0000 mA
19.2832 V
(0.0103 V)
EOL-4.7
EOL-4.7K
2'-11 1/2
0.0000 mA
19.2832 V
(0 V)
376'-10 112
1052.0000 mA
Total Current: 1052.0000 mA
(Total VDrop Percent:5.47%) Total Voltage Drop : 1.1168 V
Circuit Calculations Panel: RPS1 Card: RPX Circuit:NAC2
Circuit Name: NAC2
Circuit Type: Notification Terminal Voltage: 20.4 V:DC Amperage: 3.0000 A
Cable: 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP #14
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167 OF Max. operating voltage drop: 18%
Device
Part No
Appliance Desc
Distance
Current
Voltage
Voltage Drop
HPFF12
Panel
20.4 V
001
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
16'-0 1/2
41.0000 mA
20.3111 V
(0.0889 V)
002
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
15'-4 1/2
41.0000 mA
20.2309 V
(0.0802 V)
003
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
17'-10
41.0000 mA
20.1436 V
(0.0873 V)
004
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
14'-9 1/2
41.0000 mA
20.0747 V
(0.0689 V)
005
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
12'-9 1/2
41.0000 mA
20.0181 V
(0.0566 V)
006
SCWL
L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
10'-2 1/2
41.0000 mA
19.9731 V
(0.045 V)
007
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
13'-8
41.0000 mA
19.9173 V
(0.0558 V)
008
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
24'-8
111.0000 mA
19.8194 V
(0.0979 V)
009
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
18'-7 112
41.0000 mA
19.7562 V
(0.0632 V)
010
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
13'-9
41.0000 mA
19.7133 V
(0.0429 V)
011
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
19'-2
111.0000 mA
19.6546 V
(0.0587 V)
012
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
31'-11 1/2
41.0000 mA
19.5765 V
(0.0781 V)
013
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 30CD
37'-9 1/2
63.0000 mA
19.4911 V
(0.0854 V)
014
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
16'-0
41.0000 mA
19.4594 V
(0.0317 V)
015
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 15CD
8'-10 112
41.0000 mA
19.4452 V
(0.0142 V)
016
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
9'-6
111.0000 mA
19.4311 V
(0.0141 V)
017
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
18'-9
41.0000 mA
19.4133 V
(0.0179 V)
018
EXT. SCWL
EXT. L-SERIES STROBE, 2 WIRE, M-C, WHITE, CEILING, 15CD
18'-11 1/2
41.0000 mA
19.3992 V
(0.0141 V)
019
SPSCWL
L-SERIES SPEAKER/STROBE, WHITE, CEILING, 75CD
12'-2
111.0000 mA
19.3923 V
(0.0068 V)
EOL-4.7
EOL-4.7K
2'-10
0.0000 mA
19.3923 V
(0 V)
333'-8 1/21
1081.0000 mA
Total Current: 1081.0000 mA
(Total VDrop Percent:4.94%) Total Voltage Drop : 1.0077 V
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Firm Name and Address
(s
sehlrdom
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM
NICET: IV # 97083
.14 05- -
1-08/09/23
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A. P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
SIRE
ALARM
1 1 ? I I L f '7 1 R
A
B
C
D
E
F
H
L 1 1 4
E
E
E
15CD 0.25W
30CD 0.5W
15CD \ /
15CD 0.25W
75CD 1W
15CD
15CD
75CD 1W EOL 4.71K 0
O
O EOL Re
RPS1:NAC2
�RIPSI.NIAC2.019EORPS1:NAC2.012
RPS1:NAC2.013
RPS1:NAC2.014
RPS1:NAC2.015
RPS1:NAC2.016
RPS1:NAC2.017
S1:NAC2.0L 4.7K 12
INX1:SPK2.007
INX1:SPK2.008
INX1:SPK2.009
INX1:SPK2.010
INX1:SPK2.011
Re
INX1:SPK2
E
E
E
E
75CD 1W
15CD
15CD 0.25W
75CD 1W
15CD
15CD
15CD
15CD 0.5W 15CD 0.25W 15CD
15CD 0.25W
\ /
\ /
\ /
\ /
\ /
RPSI:NAC2.011 RPS1:NAC2.010
RPSI:NAC2.009
RPSI:NAC2.008 RPS1:NAC2.007 RPS1:NAC2.006
RPS1:NAC2.005
RPSI:NAC2.004 RPSI:NAC2.003 RPS1:NAC2.002
RPSI:NAC2.001
INX1:SPK2.006
INX1:SPK2.005
INX1:SPK2.004
INX1:SPK2.003 INX1:SPK2.002
INX1:SPK2.001
15CD
\ /
15CD 0.25W
15CD
\ /
75CD 1W
75CD 1W
15CD 0.25W
15CD
15CD
75CD 1W
EOL 4.71K 0
EOL Re
RPS1:NAC1
RPS1:NAC1.012
RPS1:NAC1.013
RPS1:NAC1.014
RPSI:NAC1.015
RPS1:NAC1.016
RPS1:NAC1.017 RPSI:NAC1.020
RPS1:NAC1.018 RPS1:NAC1.019 EOL 4.7K S2
INX1:SPK1.008
INX1:SPK1.009
INX1:SPK1.010
INX1:SPK1.011
INX1:SPK1 'a
EOL Re
INX1:SPK1
E
E
E
15CD
15CD 0.25W
30CD 0.5W
15CD
15CD
15CD
15CD 0.25W
15CD 0.25W
15CD 0.25W
15CD 0.25W 15CD 0.25W
\ /
RPS1:NAC1.011
RPS1:NAC1.010
RPS1:NAC1.009
RPS1:NAC1.008 RPS1:NAC1.007 RPS1:NAC1.006
RPS1:NAC1.005
RPS1:NAC1.004
RPS1:NAC1.003
RPS1:NAC1.002 RPS1:NAC1.001
INX1:SPK1.007
INX1:SPK1.006
INX1:SPK1.005
INX1:SPK1.004
INX1:SPK1.003
INX1:SPK1.002 INX1:SPK1.001
NAC2
SPK2
NAC1
SPK1
DOC
EXT. FACP
1 AUX1
RPS1
1 SLC1
1
Circuit Legend
Firm Name and Address
uantity
Circuit
Description
J�
Sandions
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
1
AUX1
14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
NAC1
14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
SPK1
14/2-oas = 14 AWG 2 CONDUCTOR, SHIELDED FPLP
1
SLC1
16/2-ns = 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
Project Name and Address
MAIN BUILDING
E
E
E
Op
08Jp
Cp
Op
FE]
Op
SLC1•S:031
SLC1•S:032
SLC1•S:033
SLC1•S:034
SLC1•M:019
SLC1•S:035
E
E
E
E
E
E E E E 135°
08,
OP
OP
FF1
Op FF1 Op Op AIM'
SLCI•M:018
SLC1•S:030
SLC1•S:029
SLC1•S:028
SLC1•M:017
SLC1•S:027 SLC1•M:016 SLC1•S:026 SLC1•S:025 SLC1•M:015 SLC1•S:
1 ZN1 1 ZN1
1 ZN1
1 ZN1
1 ZN1
s
s
s
WF WF
ZNI.001
ZNI.001
ZNI.001
ZN1.001 I ZN1.001
M AIM AIM AIM,~ SP � , , , J, 8 P
SLC1•M:008 SLC1•S:019 SLC1•M:009 SLC1•S:020 SLC1•M:010 SLC1•M:011 SLC1•M:012 SLC1•M:013 SLC1•M:014 SLC1•S:021
S
SLC1•S:018 SLC1•S:017 SLC1•S:016 SLC1•S:015 SLC1•S:014 SLC1•M:007
E
E
OsP
❑F
SLC1•S:001
SLCI•M:001
08 P
SLC1•S:022 SLC1•S:023
E
SLC1•S:013
SLC1•M:006
SLC1•S:012
SLC1•S:011
SLC1•S:010
SLC1•M:005
E
E
E
E
E
E
E
Qp
Op
�
Op
�E`
\v�p
�
Op
�
Op
Op
Op
SLC1•S:002
SLC1•S:003
SLC1•M:002
SLC1•S:004
SLC1•S:005
SLC1•M:003
SLC1•S:006
SLC1•M:004
SLC1•S:007
SLC1•S:008
SLC1•S:009
TO 120VAC (BY OTHERS)
MAIN BUILDING
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM
NICET: IVV## 97083
x 0
1-08/09/23
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
\
A.P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
FIRE
ALARM
1 1 ? I I L I I r, 1 -7 1 R
A
B
C
H
L 4 b / 0
Circuit Legend Firm Name and Address
Quantity Circuit Description
1 AUX1 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP J�
1 NAC1 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP Sehirtions
1 SPK1 14/2-oas = 14 AWG 2 CONDUCTOR, SHIELDED FPLP P.O. BOX 2246
1 SLC1 16/2-ns = 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
NOTE:
Project Name and Address
A E F H Q S u w v Zz ALL EXISTING HORN STROBE DEVICES ARE
BEING REPLACED WITH SPEAKER STROBES.
I I I I I I I I I I
I I I I I I I I I I
_________________ L ________------ ------------ J_
I I I I
1 - - _ - - - - 1
r
SLC1 M.003
.............::
I F I I F E INX1:SPK2 ILO
SLC1•M:007 I I EOL ReEOL 4.71KO I W
I I I EOL R,RPS1:NAC2 1
(D-1 SLC1 INX1:SPK1 (D-1 SLC1 I I 1 SLC1----C) EOL4.7K.Q 1 SLC1
EOL Re EOL 4.7K S) I I I
TOILET ONES' Q\ I (n
1 �$� EOL ReRPS1:NAC1 ��y I I OILS SLC1•S:006 I CLASSROOM ,
I SLC1•S:014 P EOL 4.7K S2 P I 2 _ _ $ E BI34 RPS`INAC2.019 $ E I
o SLC1 •S:013 I 1 PS1 OP 75CD 1W �P I W
I EXISTING I I NAC2.017 1 NAC2 SLC1•S:005 " 1
I KINDERGARTEN INX1:SPK1.012 I 1 ,1 5CD 1 SPK2 1 NAC2 I Z
RPS1:NAC1.020 SLC1•M:006 \ /
I READINESS 75CD 1W r-F I I ' � 1 SPK2 I W
MODIFIED
1 NAC1 - - TOILET I W
1 SPK1 1 SLC1 I I 1 SLC j BI35 1 SLC1 - - - - - -�
..... .......... ......................... _.. -. _ ....................._......_. LC .M- 4
S 1 04
1 EW .RPS1 rill
I 1 /\; NAC1.018 I F `RAC2 018°UILET sroRa�E 15CD E 1 NA 2 Q
/ I 1 SPK2 D SLC1•M:002
/\ S P I I 7 K M 0 P 1 NA P I
NEW ° ; /\`��.....................................: EXIS SLC1•S:012 1 S�C1 SLC1•S:007. 1 SPK , NAC15CD2.014 U
1 SBOR NAC1R•019,/ sroRAG TOIL i I I I I i INX1:SPK2.009 '\ /M�ILET
SLC1•S:004 1
CD : I RPS1:NAC2.015 / \ 1 SLC1 1 U)
- ---:............................................................................................................... I I 15CD 0.25W 1
r ---_ INX1:SPK2.008
W
I 1 NAC1 I I I I I 1 ' ........MECH.I 1 NAC2 RPS1:NAC2.013 I Y_
1 SPK1
1 SLC1 . , ��� 1 1 SPK2 30CD 0.5W
I I I I R Room i I :.: I
1 SLC1 I-L--J------L--1-, 1
(/��) BI33 I �
INX1:SPK2.010 -' P - J 1
II .........................................................::: _ _ _ _ _ _ 6
1 I 1 ❑® I I 75CD 1WC2.016 SLC • :002-IS LC1 ONE'S F_
1 SLC1•S:016�P INX1:SPK1.011 1 1 1 1 I ONES'
1 RPS1:NAC1.017 I I I I CLASSROOM CLASSROOM
I NEW 15CD 0.25W I :: I I NEW NTRY I 1 BI29 1 SLC1 BI3I _ _ _ _ _ - $
\ PRE-K �� FOYER 0
I SLC1•S:015 - (�) I I
BI25 ;g `- P I j BI01 I `S E Q S 1
P S 1•S:011 SLC1•S• 10 I SLC1• � 1 NAC2 P
I INX1:SPK1.010 I I S 008 Q 1 SPK2 SLC1 S.003
1 RPS1:NAC1.016 NEW 1 SLC1 I NaW I S P I I =
I 75CD 1 W F.A.U. CLST. I 1 I I IJI
IBI2I I I I 1 SLC1
1 I 1 1 SL I ::
_ 1 NAC1 dxll,.-SlpK1.0 2 ::::........ -
9
1 SPK1
I RPS1:NAC1.002 F INX1:SPK1.001 1 NAC1
1 NAC1 SLC1•M:005 E RPS1:NAC1.001 J
15CD 0.25W RPS1 FACP
�- -� "` NEW HALL1 SPK1 15CD 0.25W 1 SPK1 SLC1
M: 01- - - - - - - - - - - -
1 I' l iiii J EXISTIN E HA
L_�l_J BI2e $ q
1 SLC1 P
1 BIe2 E INX1:SPK2.007
-----------J NEW $ P $ E SLC1•S:001 RPS1:NAC2.012 - ------------�
I HALL SLC1•S:017 NA 1 P 15CD 0.25W
_ 1 SLC1 5122 SREA. 1 PK1 SLC1•S:009 - - - 10
........................................................
........................ .
1 `c� Blea
DISH I I �/ i 1 NAC2 F
1 UP ' \` WASH INX1:SPK1.003 /� 1 SLC1 1 NAC2 1 SPK2 E I
SLC1•S:018 8119 RPS1:NAC1.003_ Z 1 SPK2 OFFICE SLC1•M:019
I NEW 1 NAC1 15CD 0.25W .....:::::. 0 BIe4 r 1 �1 SLC1
NEW 1 PK1 KITCHEN - s..................... a ;r---� 1 I
PRE-K :I I PRESCHOOL
I F�SLC1•M:008 INX1:SPK1.009 STOR. S SLC1•M:015 Blel I : o in F---I F"i 1 SLC1 CLASSROOM , 1
I RPS1:NAC1.015 I HALLWAY 11 ;L___� INX1:SPK2.001 1
8123 w '
SLC1•S:034
1 NAC1 l = AIM , 1 Bles 11 SLC1•S:035 BI26 I W
- - � 1 SLC1 75CD 1W �,::.-::--�.......................................................... ��� 0 RPS1:NAC2 001 E
1 SPK1 1 SLC1 `::::::::....... 1 NAC2 15CD 0.25W 1 $ P �( OP 1
1 $ R II 1 SLC1 OE 1 SPK2 1 TOILET 1 NAC2 INX1:SPK2.006 13
SLC1 S:019 P INX1:SPK11005:::::::::.::::::::::.::::::::::::::::::::.::.::::::::::::::::::::::-..........................................................................................:.
.......................
I II INX1:SPK1.004................-------------------, Blzi - :
_ SLC1 S.025 TOY RPS1.NAC2 011
RPS1:NAC1.005 11 .................... :: 1 NAC2 _T_ RP0 i1 I:. 1 SPK2 75CD 1W 1
I 1 NAC1 15CD 0.25W �� RPS1:NAC1.004 1 SPK2 I NAC2.002. ; / ��`' I �
II 16CD 0.25W- , ---6T-eRA6E----_1 1; ,
1 1 SLC1 1 SPK1 o u.,}11 I ........... ...............................
, 15CD I 1 NAC2 I 1
_ �` W
------------- ---- RPS1 TOR \ BI20 I
I ,; PS1 1 SPK2 1
F 3AFFiREIK= • • �NAC1.006 / I PAN RY/ \A IL ' 1 1 S 1 I I: - S I NAC2 010NEW II:
� / 1 SLC1 INX1:SPK2 005 Z
I I RPS1E . I?
I I I 15CD BIe9
\ �c / \ I �.................. SLC1•S:028 :`... Bna �.......... 5C:C RPS1:NAC2.009
1 i I I I TOILET SLC1•S:022 S P � E T _ _
• .HALLWAY....................................................... I
....................
� ( � os,.. ! NAC1 008 � ........... ......... .. 15CD 0.25W 16
B12a SLC S:023 ,gs / \� RPS1 TOR.: 15CD E \ / ° � U
Blll ILE
I
SL •S:Q24 Ff NACA I O OE ;o;
SLC1•M:009 .. RIPS ,. 6115 BIII S S.......................................................................
- - NAC1.01 _ , NEW ... 1 P / \ BII9 P W 17
HALL NX1:SPK2.002 PS1 SLC •029 �Tr�-�_
I F 1 NAC1 I ic D 1 SLC1 1 NAC1 1 LC1 PS1:NAC2.003 ' r--- o AC2.006 P 1 Q 19
I \ / 8112 1 SLC1 L............................... , \\ B2o�.............................................. `
1 SPK1 0 1 SPK1 15CD 0.25W I B115CD . SLC. S C1•S:030 1 NAC2 1 CU
1 ;g / \ ; YOUNG TWOS' 1 NA ' \ / $ 1 SPK2 $ - - - 20
1 1 SPK1 INX1.SPK2 0031 NAC2 1 P
`�--= CLASSROOM RPS1:NAC2.004 / \ 1.]
P I Q
I INX1:SPK1.008 ---
1 SLC1 r -� RPS1:NAC1.013;: E 15CD 0.5W SPFC2° R $LC1•S:033 I 0
15CD 0.25W NX1:SPK1.007 BIe4 $ d -� ES - ' RPS1 -- �, _-.-_ ,1: ;
1 _ 1 S 1 pS1:NAC1.010 P _. I is I
SLC1•S:026 INX1:SPK1.006 \ / T IL - NAC2.007-�--�``- 1 NAC2
1 NAC1 SLC1•S:021 15CD 0.25W RPS1:NAC1.009 , 1 NAC2 eIn BIz4 15CD 1 SPK2 �'� I
I 1 SPK1 RAMP D . 6" $ 30CD 0.5W 1 SPK2 E STOR. ` ''`I 1 SLC11 I
P NEW HALL $ `,RPS1 r :l I'
1 SLO-S:020 BII3 1 SLC1 YOUNG TWOS' P NAC2.005 CLST. f ] PRESCHOOL 1 I U)
NEW STkFF - - - - - -_ -_ ° ° SLC1 S:027 BI25 1, SLC1 INX1:SPK2 004 I I -
- CLASSROOM 1 D _......_......_..... CLASSROOM RPS1:NAC2.008 L- - - 21
TO� \ / I 1 NAC1 SL�1�M:0�� 1 SLC1 0 SLC1•M:017 8123 75CD 1W,.. 1 Y_
} 1 SPK1- - - Bn6LC1
I --- -- E E - ------ - P. S 1
S. RISER EW / \ RPS1 r F F SLC1•M:018 ,. ;I 1
A NDRY NAC1.011 I I
RP 1 ROOM I $ +.. $ I
--�
s
I NAC1.012 L BIIb ' `�15CD I I 1 SLC1 I P L P I
------------------- ------ -� E C1•S:0 ; SLC1•S:032 1
-----�- S 31
. . . . . . .
-::......................... 11�133 24
I
ZN1.001 S AIM, WF AIM1 ZN1.00 CONDITION: I
CONDITION: I ZN1.001 S AIM WF AIM ZN1.001 I INSTALL FACP
INSTALL EXTERIOR FULLY I I I I I I I I I I I I
STROBE AT ZN1.001 S AIM
SLC1•M:013 FUNCTIONING
FACP/RISER ROOM I SLC1•M:010 SLC1•M:014 ANNUNCIATOR N I I I I I I I I I I I
DOOR. SLC1•M:011 SLC1•M:012 1 SLC1 RISER ROOM.
INSTALL KNOX BOX
AT RISER ROOM I I I
DOOR. TRIKE STOP - PHASE 5 TRIKE STOP DAYCAR ENTER - SUIn
TRIKE STOP AYCARE C NTE - SUITE 1
INSTALL A C D nG nH I P I T Z Z� 9Z4
FACP/RISER ROOM
AND NO STORAGE
PLACARDS TO
RISER ROOM
DOOR.
MIM
MAIN BUILDING - FIRE ALARM PLAN Z�
SCALE: 1 /8"=1 10"
RECEIVED
Dec 04 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
LEGAL NOTICE: THE INFORMATION\
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM
NICET: IV # 97083
05-
1-08/09/23
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A. P.
Checked By
D.H.
Date
08/01 /23
Project Name
THE TRIKE STOP
Project Number
24495
System Type
FIRE
ALARM
Sheet Name
MAIN BUILDING
FIRE ALARM PLAN