FIR2024-0006+Calculations+1.26.2024_9.15.38_AM+4022064TOLBraceTM Seismic Bracing Calculations V8.8.124 Contractor: North West Fire Systems Project Address: TRIKE STOP Address: 22645 83rd ave s Kent, WA 98032 . 23107 100TH AVE W Phone: 2067727502 PowenngBusoessWorfdwlde EDMONDS, WA Licence: RECEIVED Jan 26 2024 oPME�TS ER���Es Job # 05392C FIR2024-0006 ESE 0 E RVI Calculations based on 2016 NFPA Pamphlet #13 °ERARTMENT Brace Information TOLCOTM Brace Components TOLCOTM Component Listed Load Adjusted Load Maximum Brace Length TO" (2.134 m) Diameter of Brace 1 Fig. 1001 Clamp 2000 Ibs (907 kg) 1414 Ibs (641 kg) Fig.980 - 1/2" Universal SWIVE 2100 Ibs (953 kg) 1485 Ibs (674 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45' Min. `Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIO.9W UNIVERSAL AVBRACE ATT ACNNENT BRACE PIPE Fastener Information Orientation to Connecting Surface NFPA Type E Fastener Type 1/2in. x 4 1/2in. Lag Screw / Bolt Diameter 1/2in. Length 4 1 /2in. Maximum Load 235 Ibs (107 kg) T�`O PIPE CLAMP FOR 9tlAV gt ACINO Brace Identification on Plans SB-1 Prying Factor N/A Brace Type Lateral[X] Longitudinal 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.602 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 10 ft (3 m) 10 ft (3 m) 7.94 Ib/ft (11.82 kg/m) 79 Ibs (36 kg) 1.5" (40 mm) Sch. 10 77 ft (23.5 m) 77 ft (23.5 m) 3.04 lb/ft (4.52 kg/m) 234 Ibs (106 kg) 1" (25 mm) Sch. 40 4.39 ft (1.3 m) 4.39 ft (1.3 m) 2.05 lb/ft (3.05 kg/m) 9 Ibs (4 kg) Subtotal Weight 322 Ibs (146 kg) Wp (incl. 15%) 370 Ibs (168 kg) Main Size 3^ Type/Sch. Sch. 10 Spacing (ft) 10 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 223 Ibs (101 kg) 966 lb (438 kg) fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations TRIKE STOP 23107 100TH AVE W Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05392C SB-1 NFPA Type E 3" Sch.10 Steel Pipe 10' 0" (3.05 m) Lateral 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2in. x 4 1/2in. Lag Screw or Lag Bolt 4 1/2in. Summary of Pipe within Zone of Influence F.XoN Pawenng Business Worldwide 3" Sch.10 Steel Pipe (76.2 mm) 110 ft (3 m) 1.5" Sch.10 Steel Pipe (38.1 mm) 177 ft (23.5 m) 1" Sch.40 Steel Pipe (25.4 mm) 14.39 ft (1.3 m) G-Factor Used 0.602 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 223 Ibs (101 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 235 Ibs (107 kg) Fig. 1001 Clamp 1414 Ibs (641 kg) Fig.980 - 1/2" Universal Swivel 1485 Ibs (674 kg) Structural Member WOOD TRUSS Calculations prepared by BRYAN FARMER * The description of the Structural Member is for informational purposes only. TOLBraceTI software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace— 8 Visit us at www.tolco.com ■ Ex Iron WASHINGTON STATE ■ DEC 37, 2a CERTIFICATE OF COMPETENCY ■ FIRE SPRINKLER SYSTEMS Byron Richard Moye ; 9419-0815-C Level ; Nort est Fire Systems, LLC ; F��,8CR01/26/2024 i j1 nature Date j r............................a TOLBraceTM Seismic Bracing Calculations V8.8.124 Contractor: North West Fire Systems Project Address: TRIKE STOP Address: 22645 83rd ave s Kent, WA 98032 . 23107 100TH AVE W Phone: 2067727502 PowenngBusoessWorfdwlde EDMONDS, WA Licence: Job # 05392C Calculations based on 2016 NFPA Pamphlet #13 Brace Information TOLCOTM Brace Components TOLCOTM Component Listed Load Adjusted Load Maximum Brace Length TO" (2.134 m) Diameter of Brace 1 Fig. 4L Clamp 2000 Ibs (907 kg) 1414 Ibs (641 kg) Fig.980 - 1/2" Universal SWIVE 2100 Ibs (953 kg) 1485 Ibs (674 kg) Type of Brace Sch.40 See Fastener Information Angle of Brace 45° Min. `Calculation Based on CONCENTRIC Loading 'Please Note: These calculations are for TOLCOTM components only. Use of any other components voids these calculations and the listing of the assembly. Least Rad. of Gyration 0.42" (11 mm) Seismic Brace Assembly Detail L/R Value 200 Max Horizontal Load 1310 Ibs (594 kg) TOLCO FIG. 980 O BRACE PIPE Fastener Information Orientation to Connecting Surface NFPA Type E Fastener Type 1/2in. x 3 1/2in. Lag Screw / Bolt O TOLCO FIG.4L Diameter 1/2in. Length 31/2in. Maximum Load 220 Ibs (100 kg) L Brace Identification on Plans SB-2 Prying Factor N/A Brace Type Lateral [ ] Longitudinal [X] 4-Way [ ] Sprinkler System Load Calculation (Fpw = CpWp) C = 0.602 Diameter Type Length Total Length Weight Per Unit Length Total Weight 3" (80 mm) Sch. 10 40 ft (12.2 m) 40 ft (12.2 m) 7.94 Ib/ft (11.82 kg/m) 318 Ibs (144 kg) Subtotal Weight 318 Ibs (144 kg) Wp (incl. 15%) 366 Ibs (166 kg) Main Size Type/Sch. Spacing (ft) 3^ sch. 10 40 Total (Fpw) Maximum Fpw per 9.3.5.5.2 (if applicable) 220 Ibs (100 kg) N/A fTOLBracelm Version 81 Use of TOLBracelm is subject to terms and conditions per the end user license agreement TOLBraceT"" Seismic Calculations TRIKE STOP 23107 100TH AVE W Brace Identification Brace Type (Per NFPA#13) Braced Pipe (ft) Spacing of Brace Orientation of Brace Bracing Material Maximum Brace Length Slenderness Ratio used for Load Calculation True Angle of Brace for Calculation Type of Fastener Length of Fastener Job # 05392C SB-2 NFPA Type E 3" Sch.10 Steel Pipe 40' 0" (12.19 m) Longitudinal 1" Sch.40 7' 0" (2.13 m) 200 45' 1/2in. x 3 1/2in. Lag Screw or Lag Bolt 3 1/2in. Summary of Pipe within Zone of Influence 3" Sch.10 Steel Pipe (76.2 mm) 40 ft (12.2 m) G-Factor Used 0.602 Allowance for Heads and Fittings 15% Conclusions Total Adjusted Load of Pipe in Zone of Influence 220 Ibs (100 kg) Material Capacity 1310 Ibs (594 kg) Fastener Capacity 220 Ibs (100 kg) Fig. 4L Clamp 1414 Ibs (641 kg) Fig.980 - 1/2" Universal Swivel 1485 Ibs (674 kg) Structural Member WOOD TRUSS Calculations prepared by BRYAN FARMER * The description of the Structural Member is for informational purposes only. TOLBraceTI software calculates the brace assembly only, not the structure it is attached to. Calculated with TOLBrace— 8 Visit us at www.tolco.com F.XoN Pawenng Business Worldwide ............................. Ex Iron WASHINGTON STATE DEC3'I, 24 CERTIFICATE OF COMPETENCY FIRE SPRINKLER SYSTEMS Byron Richard Moye ; 9419-0815-C Level Nort est Fire Systems, LLC ; N 8CR ; i 01/26/2024 i t nature Date .............................i