FireMaster° FastWrap° XL
Product Data and Installation Guidelines
Product Description
Thermal Ceramics FireMaster FastWrap XL is a flexible blanket composed
of high temperature fibers classified for applications to 2192°F (1200°C)
and fully encapsulated in a durable glass fiber reinforced foil facing for
easy handling and installation.
Thermal Ceramics FastWrap XL is UL and ULC Listed for 1 and 2 hour fire resistive
enclosure protection, zero clearance for kitchen exhaust ducts, electrical circuit
protection, and as a component in UL firestop designs for fire resistance rated floors,
ceilings, and walls.
The core fibers in FastWrap XL are manufactured using Thermal Ceramics patented
Superwoolo fiber which is an alkaline -earth silicate wool with low biopersistence and
therefore increased safety for installers. FastWrap XL is under UL's Follow -Up Service
Program to ensure the consistent quality essential to this life -safety application.
Features or Benefits
• Thin and Lightweight at 1-1/2" (38mm) thick,
6 pcf (96 kg/m3) density
• Contours easily to complex duct designs
• Grease duct installation UL and ULC Listed with butt
joints at all seams on both layers
• Fully foil encapsulated for fast and clean installation
• Contains 2192°F (1200°C) rated fibers
• Microbial Resistance validated by UL Environment
• Good sound absorption
• Compliant to IMC, NFPA 96, UMC, CMC, CNBC
Applications
��pSSIFj�o
UL
RECEIVED
oJan 25_20245
UDC
LISTED
\\
anal
INTERNATIONAL
CODE COUNCIL!
• 2 hour enclosure and firestop system for kitchen ex-
haust duct
• Zero clearance to combustibles
• 1, 2 and 3 hour enclosure and firestop system for
hazardous exhaust ducts, pressurization ducts, clothes
dryer exhaust ducts, trash and linen chutes, and other
fire rated HVAC ducts
• 1 hour electrical circuit integrity protection
• Engineered and tested solutions for fire protection of
structural steel and storage vessels per ASTM E119,
ISO 834, and UL1709
f/R"SlER
`
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
Specifications - Division 23 07 00 (or 15080)
CSI Spec and AutoCAD available online,
www.arcat.com/sd/clients/thermcer.html.
Thermal Ceramics FireMaster FastWrap XL is a flexible
high temperature insulation rated to 2192°F (1200°C) that is
fully encapsulated in FSP facing. The duct enclosure
system shall be listed by UL and /or ULC per ASTM E 2336,
CAN/ULC S144 and ISO 6944 for 1-, 2- and 3-hour rating
and zero clearance to combustibles, and tested per ASTM
E84 for a flame/smoke rating less than 25/50. Insulation
shall have a nominal thickness of 1-1/2 inches (38 mm) and
density of 6 pcf (96 kg/m). Insulation shall have an R-Value
of 7.3 at 75°F. Installation shall be in strict accordance to
manufacturers published installation instructions, UL or ULC
Listings, and shop drawings.
Physical Properties
Product
Unit
Size
Units/
Weight/
FastWrap
1.5in x 24in x 25ft
1
37.5
Roll
1.5in x 48in x 25ft
1
75
XL
Listing and Code Reports
Listed Uses
Agency
Listing
Layers
Grease Duct Enclosure per ASTM E2336
UL
G18
ESR 2213
and AC101 (2012, 2015 IMC, NFPA 96,
2
UMC, CMC)
UL
ER14229-01
ULC Grease Duct Test Protocol and CAN/
ULC
FRD 4, 7*
2
ULC S144*
Through Penetration FireStop System per
UL
ASTM E814, UL 1479
See Figure 2
1 or 2
ULC
UL
HNLJ.V1, 19,
1- or 2-hour Ventilation Duct Enclosure
29
1
ULC
FRD 3, 5, 6,
per ISO 6944
18
3-hour Ventilation Duct Enclosure per
UL
HNLJ.V2
2
ISO 6944
Electrical Circuit Protective System
UL
FHIT.5
2
U Morg an
CAdvanced Materials
Performance Spec
REVIEWED
BY
CITY OF EDMONDS
cations
Reference Standard
Standard No.
Performance
Grease Duct Enclosure System
ASTM E2336
Pass
Section 16.1 - Non -Combustibility
ASTM E136
Pass
Section 16.2-Fire Resistance (wall)
ASTM E119
Pass
Section 16.3 - Durability Test
ASTM C518
Pass
Section 16.4 - Internal Fire Test
ASTM E2336
Pass
ASTM E814/
Section 16.5 - Fire Engulfment (duct)
pass
E119
ULC Grease Duct Test
Pass
Protocol
Standard Methods of Fire
CAN/ULC
Resistance Tests - Grease Duct As-
Pass
S144
semblies
Grease Duct Clearances
UL 1978
Pass
Air Ventilation Duct Enclosure
ISO 6944
Pass
Surface Burning Characteristics
ASTM E84
<25/50
Thermal Resistance,
ASTM C518
7.3 per layer
R-value @ 75°F
Mold Growth
ASTM C1338
ULE Validated
CA Standard
Low VOCs
�01350
ULE Validated
Storage
Thermal Ceramics FastWrap XL must be stored in a dry
warehouse environment on pallets. Pallets should not be
stacked.
FIRi6ffER 0
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
Installation
FireMaster FastWrap XL shall be installed by a qualified contractor
in accordance with manufacturer's instructions and laboratory
design listings.
Materials and Equipment
• FireMaster FastWrap XL blanket
• Aluminum foil tape
• Glass filament reinforced tape (optional)
• Carbon steel or stainless steel banding material,
Minimum 1/2" (13mm) wide, minimum 0.015" (0.4mm) thick,
with steel banding clips
• Hand banding tensioner and crimping tool
• Minimum 12 gage (3mm) steel insulation pins; steel speed
clips, minimum 1-1/2" (38mm) square or 1-1/2" (38mm)
diameter, or equivalent sized cup -head pins
• Capacitor discharge stud gun
• Approved firestop sealant
General
Cut edges of the blanket shall be taped with aluminum foil tape to
prevent exposed edges of the insulation absorbing grease and
moisture in the event of a compromised grease duct joint or
condensation. Overlaps and/or tightly butted joints are used to
block heat transfer in the event of duct deformation resulting from
thermal expansion. Filament tape is suggested to hold the blanket
in place until steel banding or pinning is installed to permanently
secure the blanket.
A. Installation on Grease Duct per ASTM
E2336 and CAN/ULC S144 (Figure 1)
System requires two layers of insulation applied directly to the duct
with tight butt joints at all seams on both layers. The first layer of
insulation is cut to a length sufficient to wrap around the duct and
provide a tight butt joint where the blanket ends meet. Adjacent
blankets on the first layer are butted tightly together with
longitudinal seams offset minimum 6" (150mm). The second layer
of insulation is installed in the same method as the first layer, with
seams between layers offset a minimum of 6" (150mm). Banding
and/or pinning per Section D is used to permanently secure the
insulation to the duct.
Morgan
CAdvanced Materials
B. Installation on HVAC Duct per ISO 6944
(Figure 1)
System requires one layer of insulation applied directly to the duct
with 3" (75mm) overlaps at all seams. The insulation is cut to a
length sufficient to wrap around the duct and provide a 3" (75mm)
overlap where the blanket ends meet. Adjacent blankets are
installed to provide a minimum overlap of 3" (75mm). Banding
and/or pinning per Section D is used to permanently secure the
insulation to the duct.
C. 2 & 3 Sided Wrap Installation (Figure 4)
When space does not allow for a complete wrap applied to the
duct on all four sides, the FastWrap XL is approved for 2 or 3 sided
installations with mechanical attachment to a rated concrete or
CMU assembly. (See Figure 4 for installation details.)
D. Mechanical Attachment Methods
1) Banding (Figure 1) - Minimum 1 /2" wide x 0.015" thick
(13mm x 0.4mm) carbon steel or stainless steel banding
is placed around the entire perimeter of the insulated duct
on maximum 10-1/2" (270mm) centers and 1-1/2" (38mm)
from each blanket edge or 1-1/2" (38mm) from each collar
edge when using the butt joint and collar method. The
banding is placed around the blanket and tightened to
firmly hold the FastWrap XL in place against the duct, but
not cause any cutting or damage to the blanket.
2) Pinning - Pinning on all sides of the duct may be used as
an alternative to banding. For ducts wider than
24" (610mm) pinning is required on the bottom of
horizontal runs, or on one side of vertical runs (in addition
to steel banding). When applicable, 12 Gage (0.4mm)
steel pins are installed on 12" (305mm) centers along the
width of the duct and 10-1 /2" (270mm) centers along the
length of the duct. Pins that extend beyond the outer
blanket layer shall be turned down or the excessive length
cut off to prevent sharp edges. Shoot through pins (cup
head pins) may be used in conjunction with steel banding
to prevent blanket sag.
FIRIdyffER @
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
E. Access Doors
Field Fabricated Access Doors - Each access door assembly has
four threaded rods 1/4 inch (6mm) in diameter and 5" (127mm) in
length, with one welded to each corner of the door opening.
Hollow steel tubes, 4-1/2" (114mm) long are installed outside the
access cover plate and over the threaded rods. Four 12 gage
(3mm) and 4-1/2" (114mm) long steel insulation pins are welded to
the access cover plate to allow for installation of the three layers of
FastWrap XL. One layer of FastWrap XL is cut to approximately
the same size as the access panel, and impaled over the insulation
pins on the panel. A second layer of FastWrap XL is cut so as to
overlap the first layer a minimum of 1-1/2" (38mm). It is essential
that the first and second layer fit tightly against the surrounding
wrap with no through openings. The third and outside layer should
be cut to overlap the second insulation layer by a minimum of
1-1/2" (38mm). Minimum 1-1/2" (38mm) round or square insulation
clips are installed on the insulation pins to secure the three layers
of insulation to the access cover plate. All cut edges of the
insulation shall be taped with minimum 3" (75mm) wide aluminum
foil tape. Wing nuts and washers are installed on the four threaded
rods, and tightened against the hollow steel tubes to seal the
access cover plate to the duct.
F. Through Penetration Firestop assembly
(Figure 2)
When the duct penetrates a fire rated assembly an approved fire
stop system must be employed. Figure 2 provides a list of some of
the UL/ULC firestop design listings which can be found in the
Certifications Directory at www.ul.com for US systems and
www.ulc.ca for Canadian systems. Prior to installing any firestop
system the surfaces of all openings and penetrating items must be
clean and dry. The FastWrap XL core blanket (or mineral wool
where allowed by the firestop design listing) must be compressed
into the annular space. The packing material must be recessed a
minimum depth from the surface of the concrete or gypsum
assembly. The recessed opening must be filled with a minimum
thickness of an approved firestop sealant. The packing material
type and compression, minimum recess (typically 1/4" (6mm)), and
approved firestop sealant and thickness (typically 1/4" (6mm)) shall
be as specified in an approved UL / ULC firestop design listing.
When there is not sufficient annular space around the duct to run
the FastWrap XL enclosure system continuous through the fire
rated assembly, the enclosure may terminate above and below the
floor/ceiling assembly or on either side of a wall assembly as
Morgan
CAdvanced Materials
shown in Figure 2. When this method is used, the FastWrap XL
must be mechanically attached on either side of the fire rated as-
sembly using one of the attachment methods described in Section
D, spaced a maximum of 1-1/2" (38mm) from the fire rated
assembly.
G. Support Hanger Systems
1) Grease ducts: Trapeze support hangers shall be spaced on
maximum 60 in. (1500 mm) centers. Hanger rods or straps
shall be anchored with steel drop in or wedge expansion type
masonry anchors. No additional protection is required for
hangers and supports meeting the requirements of the Table
below.
Hanger Cross
Maximum
Trapeze Support (or
Section
Perimeter, in (mm)
equivalent Yield
Strength)
148 in (3759mm)
2 in x 2 in x A in angle
3B in (10 mm)
(51 mm x 51 mm x 3mm)
144 in (3660mm)
2 in x 2 in x 1/4in angle
threaded rod
(51 mm x 51 mm x 6mm)
2) HVAC ducts: Trapeze support hangers shall be spaced on
maximum 60 in. (1500 mm) centers. Hanger rods or straps
shall be anchored with steel drop in or wedge expansion type
masonry anchors. No additional protection is required for
hangers and supports meeting the requirements of the Table
below.
Hanger Cross
Max.
Trapeze Support (or
Section
Perimeter,
equivalent Yield
in (mm)
Strength)
1 in x 16 gage strap
100 (2540)
(25mm x 1.5 gage strap)
1/4in (6mm) threaded
1-12 in x 1-12 in x 3/16in
rod
50 (1270)
angle (38mm x 38mm x
5mm)
38in (10mm) threaded
1-12 in x 1-12 in x 3/16in
rod
150 (3810)
angle (38mm x 38mm x
5mm)
12in (12.7mm) threaded
218 (5540)
2 in x 2 in x 1/4 in angle
rod
(51 mm x 51 mm x 6mm)
i'lRidySTER @
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
Maintenance and Repair
Morgan
CAdvanced Materials
No maintenance is required when installed in accordance with Thermal Ceramics installation instructions. If damage is
limited to the foil facing, aluminum foil tape can be used to repair the foil facing. If an area of blanket is found to be
damaged, the following procedure must be incorporated. If the damaged area is larger than 8" (203mm) x 8" (203mm) the
entire wrap section must be removed and replaced according to Thermal Ceramics installation instructions. If the
damaged area is small (less than 8" (203mm) x 8" (203mm)), the damaged area must be cut away and replaced with a
new section 1" (25mm) larger in length and width than the cut out, such that the new section can be compressed tightly
into the cut-out area. All cut edges of the new section must be taped and sealed with aluminum foil tape. The new section
must be held in place with either pinning or banding per Thermal Ceramics installation instructions.
10. Limitations
FireMaster FastWrap XL shall be installed in accordance with these installation instructions and appropriate laboratory
design listings. The integrity of FastWrap XL systems is limited to the quality of the installation.
For personal protective equipment recommendations, please see SDS.
Thermal Ceramics, FireMaster, and FastWrap are trademarks of Morgan Advanced Materials. FireMaster products are manufactured
by Thermal Ceramics and are distributed by authorised distributors.
FIRI&9ER @
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster® tW
Fasrap UMorgan XL Advanced Materials
Product Data and Installation Guidelines
C
Figure 1 Grease and HVAC Duct Enclosure System
1 or 2 Hour Shaft Alternative / Zero Clearance to Combustibles
.KKKKKKKK� &��
wn•n•rriarnri intiw
TWO LAYER INSTALLATION (Grease Duct perASTM E2336 and CANIULC S144}
THe6cope Wrap Option
LEGEND
t
Two Layers of XL Insulation for ASTM E2336 and CANIULC S144 Grease Duct Enclosures
One Layer of XL Insulabon for 2-Hour Air Ventilatan Duct Enclosures
2
Stee banding minmtum 112" 13 ride by 0.015' 0.4 thick.
3
T ht butt joints no overlap) at penimeter and lon vtudinal joints. both layers for grease dUM-
4
Min. 3' 5 overlap on perneter and between ad acent blankets
Optional 0' XL collar
6
Han - size dependent weight of assembly! see datasheet Secton G
7
Trapeze Supports - size dependent on weight of assembly see datasheet Section G
8
1 Steel Rectangular or Round Duct size a and construct -on dependent per Listed Desi n
TM nIW I, a Yu ..- C.--, : --1 -1W 4-. h f 11. —\ —
xLooi-to
F/Rf({rgSTER°
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
UMorgan
CAdvanced Materials
Figure 2 Commercial Kitchen Grease Duct Enclosure System
Air Ventilation Duct Enclosure System
Through Penetration Firestop Systems
F'3(
XL rrulatc- zcn7 r,-,s through w assem y
XL insulation termnated on both sides of the
rated wall assembly
f/R"S7fR
XL nsu atcn continuous through rated foorloeiling assembly
`Factng
XL insuation terr-iinatea at the top and botio
surface of the flooriceiling assembly
Firestop Designs perASTM E814 / UL 1479 - Consult UL / ULC Directories for System Details
-L Listing
F- 3 T-Railing1
Floori'Vllati
2 Penetrant
r3' Enclosure Per
4 Termination
5 Restm Sealant Details
C-AJ-7D12
^--hotr
coxwet"U
84xN-. 26 Ga Duct
V19 FRD3: 5 18
dvwgh
112 it STI; Tree=
C-AJ-7014
3-hour
Canctet"Ll
84x24- 26 Ga Duct
V2w
wW trough
1 Q in: STI: Tremco
C-AJ 7019
1 or 2-hour
Cortaet"I1
84x24; 26 Ga Duct
V19; FRD3. 5, 16
terminate at
114 in; STI; Trerrtco
C-AJ 7D21
2-hour
ConaelefcMU
4gx24 16 Ga Duct
G16 FRC4 7
terminate at
114 in: STL Trem^o
C-AJ-7D95
2-tour
CanaeleJGAU
3WO 22 Ga Duct
V19 FRD3 5 16
*Tap t-rcu h
19' I HittiRectorseaf Tremco
C-AJ-7096
2-four
ConcrelelCMU
49x24 16 Ga Duct
G18 FRD4- 7
wrao t^rcu h
114 in: STI• Hil Rectorseal Tremco
F-C-7036
1 or 2-hour
Wood*Floor
24xl 16 Ga Duct
G18• FRD4 7
Yoap thrcu h
114 in: STI- Ffik Rectorseal- Tremco
F-C-7055
1-hour
-Wood(GvD Floor
4 Dia 30 Ga Duct
V29; FRD28
wrap thrcu h
114 in; STI
2-hour
ConcrebXMU Wall
100xl00 26 Ga Duc-
V1Q& FRD3:5: 18
termnate at
14 it STI
N-L-7121
1 or 2-hour
G VYati
30x30. 16 Ga D.ct
G16 FRD4: 7
through
114 it STI, Hilt Rectorseal Trenoo
4V-L-7145
1 or 2-hour
Gyp Wal1
100x100; 29 Ga Duc.
V19 FR03: 5 16
termnate at
518 in STI
TYI gttdILprC---du.W cl It.
xLOMS
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.
FireMaster° FastWrap° XL
Product Data and Installation Guidelines
Figure 3
UMorgan
CAdvanced Materials
Commercial Kitchen Grease Duct Enclosure System
Air Ventilation Duct Enclosure System
1 Or 2 Hour Shaft Alternative / Zero Clearance to Combustibles
2 and 3 Sided Wrap Detail for Attaching to Walls and/or Ceilings
XL005-4
Note- Ducts must be independently supported per code
LEGEND
1
1 or 2 Hour Rated Concrete floor, ceiling,or wall
Two layers of XL Insulabon for Grease Duct Enclosures rinstall per UL G18j
One layer of XL Insulation for Air Ventilation Duct Enclosures install peruLvie}
Two layers of XL Insulabon for 3-h Air %,entilation Duct Enclosure Install per UL v2)
3
Concrete fasteners stem
4
3116" 5 thick x 2" 50 -3" 75 wide bar stock perforated 12" (305) o.c.
5
8' 203 maximum Air Gap
6
Duct
7
Steel banding min. 112" 13 wide by 0.015' '0.4 thick.
8
Banding clip
The Integrr, cr IA cc par—�rtrai Ceram Yi duct ststems h 1IMWC b tie pualtA c-Te rstalfficr
AIR"94FRO
Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information
given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal
Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the
product's suitability for use with Morgan Advanced Materials - Thermal Ceramics.