FIR2024-0008+Fire_Alarm_Equipment_Specification_Sheets+1.29.2024_3.26.19_PM+402662009 SeaCom
;05W CABLING TECHNOLOGY SOLUTIONS
1912 Everett Avenue Suite.120, Everett, WA 98201
Submittals
Kuzmas Fish Market
Edmonds, WA
Fire Alarm System
01 rib SeaCom
CABLING TECHNOLOGY SOLUTIONS
Fire Alarm System
Kuzma's Fish Market
Submittals
Material
Manufacturer
Part Number
Page
Fire Alarm Control Panel
Potter
IPA-60
1-4
Cellular Communicator
Potter
INTELLICOM-5GV
5-8
Manual Pull Station
Potter
PAD100-PSSA
9-10
Heat Detector
Potter
PAD300-HD
11-12
Detector Base
Potter
PAD300-6DB
13-14
Single Input Module
Potter
PAD100-SIM
15-16
Wall Mounted Strobe & Horn/Strobe
Potter
S-24WW & HS-24WW
17-20
Ceiling Mounted Strobe & Horn/Strobe
Potter
CS-24W & CHS-24W
21-24
Weatherproof Horn/Strobe
Potter
HS-24WR-WP
25-28
(E)POTTER
A The Symbol of Protection
Features
• 60 addresses available on this analog addressable system
• Additional system capacity achieved via multi -point SLC modules
• 99 software zones
• NFPA 72 Compliant Smoke Sensitivity Test Built -In
• System Operates as Class A or Class B for SLC, P-Link and NACs
• 5 Amp Power Supply, Expandable to 310 amps
• 2 NACS, Regulated, Rated at 3 Amps each, expandable to 188
• 2 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each,
ideal for manual release and abort
• Strobe Synchronization and System Wide Sync for Potter/AMSECO®,
Gentex®, Cooper Wheelock® and System Sensor® strobes
• Dedicated Alarm, Supervisory and Trouble Relays
• 4,000 Event History Buffer
• Cabinet will house up to 18 AH batteries
• Optional two line DACT with UD-2000 that can report General, Zone or
Point Information
• Built in IP Communicator
• Ethernet Port for Programming and Network Connectivity
• E-Mail System Status, Reports and Event Information
• Product includes 5 year warranty.
• UUKL Listed for Smoke Control
Description
The IPA-60 is an analog/addressable releasing fire alarm system with a
total system capacity of 60 addresses. Additional capacity on the system
is achieved using multi -point SLC modules. The control panel utilizes
the exclusive Potter protocol that includes a complete line of sensors and
modules. Each SLC may be comprised of any combination of smoke
sensor, heat detectors or modules and allows for a total of 50 ohms of
impedance and may use any wire compliant with the National Electrical
Code (NEC).
The IPA-60 has a 5 Amp power supply with two Notification Appliance
Circuits (NACs) and two hiput/Output (FO) circuits. The NACs are rated at
3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated
and power limited. In addition, each output is uniquely programmable and
may be configured for steady signal, strobe synchronization, constant
power, door holder power, or releasing. The strobe synchronization
includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock
and with the exclusive Quadrasync each output may have a unique brand
and all strobes will flash together. The I/Os are designed for inputs such as
manual release stations and abort switches that will not require polling and
react nearly instantaneously.
The IPA-60 is listed for releasing of fire suppression systems. The
software allows cross zones, counting zones, and timers for suppression.
The system is capable of multiple release outputs across multiple hazards.
In addition, the PSN-1000 may be used to extend releasing capability.
The NACs may be expanded using the PSN-1000 series intelligent power
supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional
input circuits and the IPA-60 will support up to 31 power supplies. The
system will synchronize the strobes system wide. In addition, the PSN-
1000E has space to allow the installation of up to six expansion cards.
The cards mount on a stacker bracket that allows access to all SLC circuit
connections.
IPA-60
Fire Alarm Control Panel
FM
APPROVED
Technical Specifications
•"" `$ LISTED
Dimensions
16"W x 17"H x 3 7/8"D
AC Mains
3.0 Amps @ 120 VAC 50/60 HZ
2.0 Amps @ 240 VAC 50/60 HZ
Enclosure
16 gauge cold rolled steel with removable
locked door with Lexan viewing window
Standby Current-130 mA
Alarm Current-200 mA
• 5 Amps power for NACs, I/O, and P-Link
Battery
• 3 Amps per NAC, regulated
• 1 Amp per I/O circuit, regulated
• Battery Charger range 8-55 Ah
• Battery Charger voltage 27.3 VDC
• P-Link maximum current of 1 Amp
Temperature and
321 to 1201(0°C to 49°C) with a maximum
Humidity Range
humidity of 93% non -condensing.
NFPA 12, 12A, 13, 15, 16, 17, 17A, 70,
72, 750, and 2001
ANSFUL 864 - Local (L), Remote Sta-
tion (RS), Central Station (CS), Propriety
(PPU), Auxiliary (AUX).Type of Service:
Standards
Automatic (A), Manual (M), Water flow
(WF) Sprinkler Supervisory (SS) Type of
Signaling: Digital Alarm Communicator
(DAC), March Time (March), Non Coded
(NC), Reverse Polarity (Rev Pol), Other
Technologies (OT)
IBC 2000, 2003, 2006, 2009, 2012
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101- REV G • 9/19 PAGE 1 OF 4
Page 1 of 28
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
SLC Loop Accessories
The control panel may be connected with up to 60 addressable devices or modules in any combination. The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Loop Devices
Device
Description
PAD100-PD
Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot.
PAD 100-PHD
Combination Analog Photo Electric Smoke/Heat Detector — a smoke detector with a listed obscuration of 1.02 to 3.83 percent
obscuration and a fixed temperature 135' Fahrenheit heat detector.
PAD100-HD
Analog Fixed Temperature Heat Detector that is selectable from 135' F to 185°F.
PAD 100-DUCTR
Addressable Duct Smoke Detector with Form C Relay.
PAD100-DUCT
Addressable Duct Smoke Detector.
PAD 100-6B
6" round base that is mounted to an electrical box and wired for connection of one of the above sensors.
PAD 100-4B
4" round base that may be mounted to an electrical box and wired for connection to the above sensors.
PAD 100-IB
Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop.
PAD100-RB
Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC.
PAD100-SB
Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call.
PAD100-CD
Addressable CO gas detector.
PAD 100-DD
Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure.
PAD100-LFSB
Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local, group and all
call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz)
PAD100-SPKB
Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W.
Modules
Device
Description
PAD 100-MIM
Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PAD100-PSSA
Single Action Addressable Pull Station.
PAD100-PSDA
Dual Action Addressable Pull Station.
PAD100-SIM
Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box.
PAD 100-DIM
Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD100-TRTI
Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs.
PAD 100-NAC
Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PAD100-ZM
Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PAD100-IM
Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PAD100-RM
Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.
PAD 100-LED
Module provides a single addressable LED that is controlled by the control panel.
PAD 100-SM
Speaker Module provides switching for two audio channels.
PAD 100-LEDK
Addressable LED and key switch that mounts in a single gang box.
PAD 100-DRTS
DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.
PAD100-OROI
One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101- REV G • 9/19 PAGE 2 OF 4
Page 2 of 28
(E)POTTER
The Symbol of Protection
SLC Features
The Potter protocol is a digital protocol with a proven design for
reliability and noise immunity. The system does not require special
cable or conductors for connection of the Signaling Line Circuit
as long as the cable is compliant with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
"T-Taps", with a max wiring distance of 10,000 Ft.
Sensor Features
The sensors through the fire alarm control panel provide a real
time status as to the condition of the system. The smoke detector
sensitivity, heat detector temperature level and drift compensation
are all programmable options. The system also allows for a day/night
mode where the panel automatically adjusts the sensitivity depending
on the time of day. To assist in the reduction of false alarms, the
smoke detectors also have a maintenance warning that sends a trouble
signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity.
User Interface
The fire alarm control panel has a 2 x 16 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
• AC Power - Green
• Alarm - Red
• Earth Fault - Amber
• Supervisory - Amber
• Silenced - Amber
• Trouble - Amber
• Pre -Release - Amber
• Release - Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
P-Link
The IPA-60 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 64 devices may be connected to a single P-Link connection. The
P-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
RA-6075R — 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
IPA-60
Fire Alarm Control Panel
RA-6500R(F) — 4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) — 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) — 10 amp, remote intelligent power supply with
6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in
conjunction with the IPA-60 as releasing circuits.
CA-6075 — Class A convertor that converts the SLC, NACs and
P-Link connection
UD-2000 — UL listed, Dual line telephone alarm communicator
DRV 50 — LED driver expander, used to connect up to 50 LEDs in a
graphic display
FCB-1000 — Fire communication bridge, provides remote mounting
of the Ethernet connection
FIB-1000 — Fiber interface module, used to extend P-Link to multi -
mode fiber (2 required)
RLY-5 — Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125AC
SPG-1000 — Serial parallel gateway, allows for the connection to a
serial or parallel printer
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi -Connect allows up to sixty-three IPA series panels to
share a single reporting technology.
IDC-6 — Initiating device circuit provides 6 programmable inputs
AE-2 — Two card expansion cabinet
AE-8 — Eight card expansion cabinet
AE-14 — Fourteen card expansion cabinet
Ethernet/I.P. Connection
The IPA-60 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UL
listed Sur -Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101- REV G • 9/19 PAGE 3 OF 4
Page 3 of 28
(E)POTTER
The Symbol of Protection
Dimensions
•
•
• 00
II 0
0
0
0
LEFT SIDE
Ordering Information
IPA-60
Fire Alarm Control Panel
® O
TOP • DEPTH = 3.75 "
0 0
DOOR = 16.07"
BACKBOX = 15.77" a DEPTH = 3.84"
BOTTOM
Model
Description
Stock No.
IPA-60
Fire Alarm Releasing Control Panel
3992714
Replacement Board IPA-60
3992738
II 0
RIGHT SIDE
DWG #593-1
Compatible Releasing Devices
Note: For releasing applications please order the Potter EOLD
(3005012) for circuits connected to a releasing solenoid or actuator.
Brand
Description
Skinner
73218BN4UNLVNOC112CZ
73212BN4TNLVNOC322C2
Victaulic
753-E Series
Mini Max
MX123 & MX200 w/ 8876677 & 889323
Viking
11591, 11601, 11602,13843, & 13844
TLX
PA0036
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101- REV G • 9/19 PAGE 4 OF 4
Page 4 of 28
(E)POTTER
The Symbol of Protection
Features
• 5G LTE-M commercial fire alarm communicator
• Verizon or AT&T models available
• Direct connect to Potter panels with Ethernet (Contact ID)
• UD-2000 DACT not required when using Ethernet on Potter panels
• Interfaces with other panels over a single DACT connection for universal compatibility
• Meets UL 864 requirements for sole, primary, or backup path communications
• 5-minute or 60-minute supervision
• Power from fire panel 24V auxiliary power supply or plug-in transformer (included)
• Red/Locking metal enclosure
• Secure cloud -based account management tools
• Use any local and national central stations with no extra equipment or setup
• IntelliView Compatible — iOS/Android App & Browser access
• IntelliView Cloud Services and Apps included when used on Potter Panels
• Alert: Detailed event status, counters, history, push notifications
• Backup: Panel programming backed up to the cloud
• Test/Inspect: One person walk -test tool
• Program: Remotely Upload & Download panel configurations
Description
Provides sole or dual path 5G LTE-M cellular monitoring
communication for any commercial fire panel. Potter panels using
the Potter IntelliCom Advanced Gateway offer the most advanced
features in the industry without the need for a UD-2000 POTS dialer.
Potter panels enable automatic panel program backups/retrieval,
remote programming, cloud storage, and mobile walk test that creates
an NFPA-72 initiation device report. If the existing panel supports
Contact ID, it's a candidate for upgrading with the Potter IntelliCom
Advanced Gateway.
IntelliComTM
5G LTE Advanced Gateway
0 LISTED
Technical Specifications
Cellular Service
5G LTE - Verizon orAT&T
Dimensions
7.5" H x 11.5" W x 3.5" D
Color
Red
Primary Power
12VAC or 12/24VDC (29VDC max)
Standby Current
68mA @ 24VDC (w/ Link Supervision)
Transmit Current
140mA @24VDC
Compatible Panels
Fire panels with dialer (Contact ID)
Potter Panels — See
IPA-4000(V), IPA-100, IPA-60,
manual for specific
AFC- 1000(V), AFC-100,
services available. UD-
AFC-50, ARC-100, PFC-4064
2000 not required.
Communication
Protocols:
Ethernet
CID over Ethernet
DACT
CID, SIA, Pulse (4x2, 3xl), Radionics
(Ile/3a2,4), DMP
Agency
ANSI/UL 864 Fire Protective Signaling
Systems)
Certifications
FCC
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830202 - REV B • 9/23 PAGE 1 OF 4
Page 5 of 28
(E)POTTER
The Symbol of Protection
contact )
Rich
Dara
IntelliComTM
5G LTE Advanced Gateway
Stationentral
1 moll
Your Preferred Central Station
National Central Stations
Local Central Stations
Sur -Gard & DMP Receivers
Active Signal Alerts
Panel Program Cloud Backup
Panel Program Cloud Restoral
Panel Remote Programming
Walk Test
Cloud Storage for Programs
p Alert p Test & Inspect
Signals, Push Notifications, Status Initiation Device Report Generator
(ky >>)
5G LTE-M
p Program p Backup
Remote Programming Tool Automated Cloud Backup & Restoral
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830202 - REV B • 9/23 PAGE 2 OF 4
Page 6 of 28
(E)POTTER
The Symbol of Protection
(D Test & Inspect
initiation Device Report Generator
IntelliComTM
5G LTE Advanced Gateway
Potter Test & Inspection Initiation Device Report Generator is an automated way to create the NFPA-72 Initiating Device
Supplementary Record of Inspection and Testing. This tool eliminates the time-consuming manual process of creating a list of points
for the required report. The tool allows a technician to import all the points, mark them as Pass/Fail, document the visual & functional
test, and export the results into a file that can be included with the remainder of the user provided NFPA-72 report. This cloud -based
tool is complimentary to all customers using a compatible Potter fire alarm control panel with an IntelliCom Advanced Gateway
p Backup
Automated Cloud Backup & Restoral
Potter Automated Cloud Backup & Restoral is an automated way to backup Potter fire alarm control panel databases. This tool
ensures that the panels program is always available and secure. Technicians can instantly recover the database from the secure server
at any time. Never have to find a specific technician's computer, or thumb drive ever again. This service will save many hours
whenever you have that unfortunate event that requires the system to be reprogrammed. This cloud -based tool is complimentary to all
customers using a compatible Potter fire alarm control panel with an IntelliCom Advanced Gateway
p FPP
Remote Programming Tool
Web based programming is a reality with the IntelliCom Advanced Gateway and Potter panels. Potter Programming Tool databases
can be remotely sent to panels — from anywhere in the world. This is a great tool when commissioning systems, making updates
during a T&I session, or simply making label changes. No longer does the technician with the knowledge to reprogram the panel have
to be on site.** This cloud -based tool is complimentary to all customers using a compatible Potter fire alarm control panel with an
IntelliCom Advanced Gateway.
** NFPA-72 Requires that when changes are made to site -speck software, all functions known to be affected by the change, or
identified by a means that indicates changes, must be 100 percent tested. In addition, 10 percent of initiating devices that are not
directly affected, up to a maximum of 50 devices, must also be tested and proper operation verified.
@ Alert
Signals, Push Notifications, Status
Panel information is right at your finger tips any time you need it. Receive alerts to any Android or iOS compatible mobile device.
Push notifications to the mobile app allow for immediate signal notification. Remote Acknowledge, Silence, Reset, Enable/Disable,
and Drill operations are available while a panel is in Walk Test. Prepare for a site visit by retrieving point information and panel
history. This cloud -based tool is complimentary too all customers using a compatible Potter fire alarm control panel with an IntelliCom
Gateway
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830202 - REV B • 9/23 PAGE 3 OF 4
Page 7 of 28
(E)POTTER
The Symbol of Protection
Ordering Information
IntelliComTM
5G LTE Advanced Gateway
Model
Description
Stock No.
IntelliCom-5GV
5G LTE-M Dual path commercial fire alarm communicator (Verizon)
3994000
IntelliCom-5GA
5G LTE-M Dual path commercial fire alarm communicator (AT&T)
3994001
Accessories
TG-TAMPER
Tamper Switch Assembly compatible with Potter metal enclosures
3994002
ACD-12
12 feet - low loss high performance antenna cable and mounting bracket
3994003
ACD-35
35 feet - low loss high performance antenna cable and mounting bracket
3994004
ACD-50
50 feet - low loss high performance antenna cable and mounting bracket
3994005
ACD-100
100 feet - low loss high performance antenna cable and mounting bracket
3994006
HGDL-0
High Gain Directional Antenna
3994007
EXDL-0
External Omni -Directional Antenna
3994008
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830202 - REV B • 9/23 PAGE 4 OF 4
Page 8 of 28
PAD 100-PSSA/PS DA
P POTTER Addressable Pull Station
�A The Symbol of Protection Single/Dual Action
Features
• Single or Dual Action versions
• Durable die-cast construction
• Reset key matches the fire alarm control panels
• Compatible with IPA Series panels
• SLC Class A, Class X & Class B
• Product includes a 5 year warranty
Description
The PAD100-PSSA (Single Action) is activated by simply pulling
the white "T" bar handle down. The PAD100-PSDA (Dual Action)
is activated by lifting the front cover and then pulling the white "T"
bar handle down. Once activated, the "T" bar cannot be reset without
opening the front cover. Opening the front cover will also activate the
pull station. To reset the PAD100-PS Series, use the Potter WS-93 key
to unlock and open the front cover. Once the cover is open, push the
"T" bar back into the normal position and re -secure the front cover.
Application
The PAD100-PSSA/PSDA is compatible with Potter's IPA and AFC/
ARC series addressable fire alarm control panels. It is a non -coded
addressable pull station available in either a single or dual action
model and installs on a single gang box or surface mounts using the
P32-BB or P32-DBB (deep) back box.
�SBMB<�� •T
P
Fx .ca C
9 THE US
Technical Specifications
Operating Voltage
24.0 VDC
Max SLC Standby Current
200uA
Max SLC Alarm Current
200uA
32°F - 120°F (0° - 49°C)
Environmental Limitations
Indoor Only
Dimensions
4.75" H x 3.25" W x 1.75" D
Relative Humidity Range
0 - 93% (non -condensing)
Single gang box or
Mounting Options
Potter P32-BB/DBB
APS-SA - 1.22 lbs.
Shipping Weight
APS-DA - 1.46 lbs.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830097 - REV C • 3/18 PAGE 1 OF 2
Page 9 of 28
PAD 100-PSSA/PSDA
(E)POTTER Addressable Pull Station
The Symbol of Protection Single/Dual Action
Setting the Address
The PAD 100-PS Series uses one SLC address assigned to the device. The address is set using the DIP switch located on the back of the PAD 100-PS
device.
Pull Station Front View
Fig I
PAD 100-PSDA
Pull Station Back View and bring
Fig 2
FROM FACP OR
PREVIOUS DEVICE
TO NEXT DEVICE
Ordering Information
Model
Description
Stock No.
PAD100-PSSA
Addressable Pull Station, Single Action
3992721
PAD100-PSDA
Addressable Pull Station, Dual Action
3992720
V PorrEl?
PAD 100-PSSA
FACTORY WIRED CONTACTS
0
0
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830097 - REV C • 3/18 PAGE 2 OF 2
Page 10 of 28
(BPOTSyrrdWFERThe
Features
• Selectable Rate of Rise and/or Fixed Heat Detector
• Low Profile
• Reliable Detection Technology
• LED Alarm Indicator
• Ambient Temperature Listing of 32°F to 150°F
• Simple DIP Switch Address Setting, No Programming Tool
Required
• Magnetic Test Switch
• Product includes 5-year warranty
• UUKL Listed for Smoke Control
Description
The PAD300-HD is a listed analog addressable rate of rise and/or
fixed temperature heat detector compatible with any fire alarm control
panel that has the Potter Addressable Device (PAD) protocol. The heat
sensing portion utilizes a proven thermistor for accurate and reliable
heat detection. The detector and base (not included) are made of a
durable plastic in an off-white to blend in with the ceiling.
The PAD300-HD is UL listed with a selectable fixed temperature
point from 135' to 185' Fahrenheit and can be used for rate of rise
applications. See detector spacing limitations below. This flexibility
allows the installer to cover a wide variety of applications with a single
unit.
The PAD300-HD and the control panel communicate over a proven
and robust digital communication path and the system analyzes the
information at the particular device. The total polling speed is less than
five (5) seconds, well under the UL requirements.
The detector is compatible with any of the PAD300 series detector
bases and simply twists on. The PAD300-HD is addressed using DIP
switches in the rear of the detector and can be easily programmed in
the field without special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
PAD300-H D
Heat Detector
(00
0328-0538
Technical Specifications
Operating Voltage
24 VDC
Detector Current Draw
300 µA
Alarm Indicator
1 LED
Alarm Set -point Range
135°F to 185°F (57'C to 85'C)
Rate of Rise Detection
15'F/min. (8.3'C/min.)
(Selectable Option)
Installation Temperature Range
32°F to 150'F (0°C to 66°C)
Operating Relative Humidity
0% to 93% (Non -condensing)
Range
Start-up Time
Max. 1 sec.
Maximum Number of Addresses
127
Per Loop
Maximum Number of Lighted
30
Indicators in Alarm Per Loop
Color
Eggshell White
Weight (Without Base)
68 g (2.4 oz)
Dimensions (Without Base)
Height: 1.5 in (38 mm)
Diameter 3.93 in (100mm)
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830210 - REV C • 6/23 PAGE 1 OF 2
Page 11 of 28
(P)POTTER PAD300-H D
JI`e4a�"1W tolu.W Heat Detector
Operation
The PAD300-HD is an analog addressable detector that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LED flashes every time the unit is polled and it will flash at a fast rate if the unit is in
an active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD300-HD with the PAD300-4DB or PAD300-6DB has a low profile to blend into the surrounding environment. The system has a maximum
of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD300-HD will operate even though the LED will not
illuminate.
Spacing
The ANSI/IJL listed spacing limitations of PAD300-HD smooth ceiling are dependent on alarm set point.
Alarm Set -Point
Rate of Rise Spacing
Fixed Temperature Spacing
135°F to 185°F
Max. 70 ft.
Max. 70 ft.
(57°C to 85°C)
Compatible Bases
All bases will mount on a single gang, 3-1/2" octagon, 3-1/2" square, double gang, 4" octagon, 4" square, 50mm c/c, 60mm c/c and 70mm c/c boxes.
Device
Description
Stock No.
PAD300-4DB
4" Detector Base
3992781
PAD300-6DB
6" Detector Base
3992782
PAD300-IB
6" Base with an Isolator Module Included
3992783
PAD300-RB
6" Base with One Form-C Relay Contact 2A @ 30VDC, 0.5A @ 125VAC
3992784
PAD300-SB
6" Base with sounder module included. Sound pattern is provided from external source
3992785
PAD300-LFSB
6" Base with 520Hz sounder module included. Sound pattern is provided from external source
3992786
Ordering Information
Model
Description
I Stock No.
PAD300-HD
Heat Detector
13992776
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830210 - REV C • 6/23 PAGE 2 OF 2
Page 12 of 28
(DPOTTER
The Symbol of Protection
Features
• Terminals marked with polarity to assist with installation
• Duplicate Terminals for In -and -out SLC Wiring
• Terminals accept 22 to 12 AWG wire sizes
• Installs on Single Gang, Double Gang, Octagon or 4" Square
Box
• Locking tab prevents unauthorized detector removal
• Product includes 5-year warranty
• 6" mounting base comes with trim plate cover
Application
The Potter PAD300-6DB and PAD300-4DB detector bases are used
to install PAD300 series detectors. The PAD300-6DB will mount on
a single gang, double gang, octagon, 4" square, 50mm, 60mm, and
70mm electrical box.
Description
The PAD300-6DB and PAD300-4DB are low -profile, surface -mount
bases used with Potter's addressable detectors. The base uses screw
clamp terminals that accept wire ranging from 22 to 12 AWG.
When installed on recessed electrical boxes, the PAD300-6DB is
wide enough to completely cover the back box and the immediate
surrounding area. The base is equipped with a locking tab to deter
unauthorized removal of the attached detector.
PAD300-4DB/6DB
4"/6"Detector Base
(001
0328-0539
Technical Specifications
Installation Temp Range
320F to 150OF (0°C to 66°C)
Operating Humidity Range
0% to 93% (Non -condensing)
PAD300-4DB: 3.93 in / 100 mm
Dimension
PAD300-6DB: 6.3 in / 160 mm
PAD300-4DB: 1.34 oz / 38 g
Weight
PAD300-6DB: 3.03 oz / 86 g
Height
0.76 in / 20 mm
Acceptable Wire Gauge
22 to 12AWG
Single Gang
Double Gang
3-1/2" Octagon Box
4" Octagon Box
Mounting Options
4" Square with Plaster Ring
50mm c/c Box
60mm c/c Box
70mm c/c Box
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PRINTED IN USA 8830203 - REV B 2/23 PAGE 1 OF 2
Page 13 of 28
CP, POTTER
The Symbol of Protection
Locking Feature
The PAD300-6DB and PAD300-4DB include a locking feature that
prevents removal of the detector without using a tool.
1. To enable this feature, break off the locking tab (See Figure 1), and
then install the detector.
Fig. I
2. To remove the detector from the base when the locking feature has
been enabled, insert a small screwdriver into the slot on the base to
push the plastic tab while simultaneously turning the detector head
counter -clockwise.
Fig. 2
Insert small
screwdriver into
slot to remove
detector from base.
Ordering Information
PAD300-4DB/6DB
4"/6"Detector Base
Wiring Diagrams
Fig. 3
1) Class B Wiring:
2) Class A Wiring:
3) Class X Wiring:
Model
Description
I Stock No.
PAD300-4DB
4" Detector Base
13992781
PAD300-6DB
6" Detector Base
13992782
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PRINTED IN USA 8830203- REV B 2/23 PAGE 2 OF 2
Page 14 of 28
(E)POTTER
The Symbol of Protection
PAD100-SIM
Single Input Module
Features PgSEMeIFa
• One (1) Class B monitoring input
• SLC Class A, Class X & Class B
• Mounts in a standard 4" or double gang box 2 THE v�
• Wiring terminals accessible when mounted in box
• All wiring terminals accept 22 to 12 AWG J
• Product includes a 5 year warranty p poTTFa
NOTE. This addressable module does not support 2-wire smoke 0 ""•
detectors.
al
Description
The PAD 100-SIM uses one (1) SLC loop addresses when monitoring
one (1) Class B circuit. The module mounts on either a 4" square or
double gang box. The module is capable of monitoring one (1) Class
B circuit. The PAD100-SIM includes one red LED to indicate the
module's status. In normal condition, the LED flashes when the device
is being polled by the control panel. When the input is activated, the
LED will flash at a fast rate.
Application
The PAD 100-SIM is compatible with Potter's IPA and AFC/ARC
series addressable fire alarm control panels. The PAD100-SIM is an
interface module used to monitor dry contact devices such as sprinkler
waterflow, valve tamper switches, or conventional pull stations. The
module is capable of monitoring one Class B circuit.
Setting the Address
Each addressable SLC device must be assigned an address. The address
is set using the DIP switch located on the PAD 100-SIM.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage
24.OV
Max SLC Standby
240µA
Current
Max SLC Alarm
240µA
Current
Max Wiring Resistance
100 S2
of IDC
Max Wiring
I gF
Capacitance of IDC
EOL Resistor
5.1K 52
Operating Temperature
Range
32 to 120OF (0 to 49°C)
Operating Humidity
Range
0 to 93% (non -condensing)
Max no. of Module Per
127 units
Loop
Dimensions
4.17" (106mm)L X 4.17"
(I06mm)W X 1.14" (29mm)D
Mounting Options
Standard 4" Square or
Double Gang Box
Shipping Weight
0.6 lbs
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830083 - REV C • 3/18
Page 15 of 28
PAGE 1 OF 2
(E)POTTER
The Symbol of Protection
Installation Using Compatible Electrical Box
Fig 1
Wiring Diagram
PADI00-SIM With Class B Circuit
Fig 2
FROM FACP
PREVIOUS N
TO NEXT M(
END -OF -LINE RESISTOR
5.1KOHM % W
Part #3005013 tE
Ordering Information
Model
Description
Stock No.
PAD100-SIM
Single Input Module
3992704
PAD 100-S I M
Single Input Module
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830083 - REV C • 3/18
Page 16 of 28
PAGE 2 OF 2
(E)POTTER
The Symbol of Protection
Features
• 24VDC units have field selectable candela options of 15, 30, 60,
75 & 110
• Super -Slide® Bracket - Ease of Supervision Testing
• Checkmate® - Instant Voltage Verification
• Synchronize strobe and/or horn with AVSM Control Module
• Prewire entire system, install mounting bracket, then install
signals
• Documented lower installation and operating costs
• Switch selection for high or low dBA
• Switch for chime, whoop, mechanical and 2400Hz tone
• Tamperproof re-entrant style grill
• Switch for continuous or temporal 3 tone (not available on
whoop tone)
• Silence audible while visual appliance will remain flashing (for
use in accepted jurisdictions)
• Faceplate available in red or off-white
Description
The S-24/HS-24 Series is a low profile strobe and horn/
strobe combination that offers dependable audible and visual
alarms and the absolute lowest current available. The S-24
& HS-24 Series 24VDC offers tamperproof field selectable
candela options of 15, 30, 60, 75, and 110 candela. The
Strobe and Horn/Strobe offers a continuous or sync temporal
three in 2400Hz and mechanical tone, a chime and whoop
tone. All tones are easy for the professional to change in the
field by the use of switches. The S-24 & HS-24 Series has a
minimal operating current and has a minimum flash rate of
1Hz regardless of input voltage.
This Series is shipped with a standard 4" metal mounting
plate which incorporates the popular Super -Slide® feature
that allows the installer to easily test for supervision. The
product also features a locking mechanism which secures the
product to the bracket without any screws showing.
The S-24/HS-24 also features the patented Checkmate® -
Instant Voltage Verification feature which allows the installer
to check the voltage drop draw and match it to the blueprint.
The S-24 & HS-24 Series appliances are ANSI/UL 464 and
ANSI/UL 1971, listed for use with fire protective systems
and are warranted for three years from date of purchase.
S-24 & H S-24
Selectable Candela Strobe & Horn/Strobes
PSEMSI
,r
i2 THE uSP
UL
LISTED
S3247
Technical Specifications
Single or Double gang, 4"
Mounting Options
square box, and AVBB surface
mount back box
Terminals
Screw -Clamp Type
Wire Gauge
18 — 12 AWG
Operating Temp
32°F — 120°F (0° — 49°C)
Height — 5"
Dimensions
Width — 4.5"
Depth — 2.5"
Shipping Weight
1.05 lbs
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
Page 17 of 28 8830054-REV C 6/17 PAGE 1 OF 4
(E)POTTER S-24 & H S-24
The Symbol of Protection Selectable Candela Strobe & Horn/Strobes
Switch Locations
TONE
SWITCH POSITION
3
4
5
Mechanical Temporal 3
ON
ON
ON
Mechanical Continuous
OFF
ON
ON
2400 Hz Temporal 3
ON
OFF
ON
2400 Hz Continuous
OFF
OFF
ON
Chime Temporal 3
ON
ON
OFF
Chime Continuous
OFF
ON
OFF
Whoop
ON
OFF
OFF
Whoop
OFF
OFF
OFF
NOTE:
• Switch Positions 1The and 2 in the OFF position to select
isolated horn and strobe power inputs
• Switch Position 6 ON = HIGH dBA
• Switch Position 6 OFF = LOW dBA
Candela Selection
Super Slide® Mounting Bracket
Allows the installer to pre -wire the system, test for system
supervision, remove the signal head until occupancy, switch
out signals without changing mounting brackets and has
locking edge connector for snap -in -place installation.
�d
To remove bezel,
grip bo
hr
bezel d pull in
downward a
outward motion.
�11
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 2 OF 4
Page 18 of 28
(E)POTTER S-24 & H S-24
® The Symbol of Protection Selectable Candela Strobe & Horn/Strobes
S-24 24 VDC Selectable Candela, Low
Profile Evacuation Strobe
Model
Nominal
Candela (ANSI/UL
Part Number
Number
Voltage
1971)
S-24WR
4890010
24 VDC
15, 30, 60, 75, 110
S-24WW
4890011
24 VDC
15, 30, 60, 75, 110
HS-24 24 VDC Selectable Candela,
Low Profile Evacuation Strobe
Candela (ANSI/
Reverberant dBA at 10
In Anechoic Room at
Model Number
Part Number
Nominal Voltage
UL 1971)
ft, per ANSI/UL 464
loft
HS-24WR
4890030
24 VDC
15, 30, 60, 75, 110
62-82
100
HS-24WW
4890031
24 VDC
15, 30, 60, 75, 110
62-82
100
S-24 & HS 24 Strobe Current Ratings
24 VDC (16 - 33 Volts)
Candela
24 VDC
UL Max
15 cd
30 mA
42 mA
30 cd
35 mA
58 mA
60 cd
66 mA
97 mA
75 cd
80 mA
116 mA
110 cd
103 mA
161 mA
S-24 & HS-24 Horn Ratings
Model Designations:
W = Wall mount
R = Red Faceplate W=White Faceplate
All units are available in plain (no lettering)
Plain units are non -returnable.
"ALERT" bezel available for order.
"AGENT" bezel available for order.
Horn Mode
Horn Decibel Levels
Horn Current Ratings
Minimum SPL at 10 ft, per
ANSI/UL 464 (HIGH)
Minimum SPL at 10 ft,
per ANSUUL 464 (LOW)
Regulated 24 VDC Max
Operating @ High Setting (mA)
Temp 3 (2400 Hz)
78 dBA
71 * dBA
28 mA
Temp 3 (Mechanical)
76 dBA
70* dBA
25 mA
Temp 3 (Chime)
70* dBA
66* dBA
15 mA
Continuous (2400 Hz)
81 dBA
74* dBA
28 mA
Continuous (Mechanical)
80 dBA
72* dBA
25 mA
Continuous (Chime)
70* dBA
66* dBA
15 mA
Whoop
82 dBA
69* dBA
56 mA
NOTES.
• For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave
Rectified]) power see installation manual.
• Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While
the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level
required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA
setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 3 OF 4
Page 19 of 28
(E)POTTER
The Symbol of Protection
S-24 & HS-24 Series Wiring Diagram
UL Listed
Control Signal
Panel
S+ S+ S- H+ H-
Supervised 0 0
Signal Circuit
r�
S-24 & H S-24
Selectable Candela Strobe & Horn/Strobes
UL Listed
Signal
Control
Panel
Signal
S+ S+ S- H+ H-
s- H+ H-
Supervised
0 0
Signal Circuit
END OF LINE
RESISTOR
\ +
r�
Signal
S+ S+ S- H+ H-
END OF LINE
RESISTOR
END OF LINE
RESISTOR
Notes:
All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits.
However, use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn, and/or mute the horn.
• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM
CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND
MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC TECHNICAL SUPPORT AT 1-866-956-1211
Architect & Engineering Specifications
The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be
listed by Underwriters Laboratories, Inc. per ANSI/UL 1971 and/or ANSI/UL 464. The notification appliance shall also be listed with
Factory Mutual Listing Service (FM) and the California State Fire Marshal (CSFM).
The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at 24VDC as
measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the
visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or
temporal tone output with the temporal signal having the ability to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at
the fire alarm control panel.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power
input voltage. The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting
bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double
workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full
wave rectified power for 24VDC models.
The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be
capable of mounting to a surface back box.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830054-REV C 6/17 PAGE 4 OF 4
Page 20 of 28
CP� POTTER
The Symbol of Protection
U�
LISTED
S3247 Product includes a S year warranty
Description
The Potter CS/CHS Series is a ceiling mount strobe or horn/strobe
combination that offers dependable audible and visual alarms and the
lowest current consumption.
The CS/CHS offers tamperproof field selectable candela options of 15,
30, 75, 95, 115 and 150 candela.
The CHS horn offers a continuous or synchable temporal three in
2400Hz and mechanical tone. All tones are easy for the professional to
change in the field by using switches. The models are shipped from the
factory in the temporal three alarm mode.
The CS Series has a very minimal operating current and has a minimum
flash rate of 1Hz regardless of input voltage.
CS/CHS
SELECTABLE CANDELA
CEILING MOUNT
Features
• Nominal voltage 24 VDC
• Tamperproof field selectable candela options 15, 30, 75, 95, 115,
& 150
• Super -Slide" Bracket - Ease of Supervision Testing
• Checkmate® - Instant Voltage Verification
• Synchronize strobe and/or horn with Gentex AVSM Control
Module
• Prewire entire system, install mounting bracket, then install
signals
• Documented lower installation and operating costs
• Input Terminals 12 to 18 AWG
• Switch Selection for High or Low dBA
• Switch Selection for 2400Hz or mechanical Tone
• Switch Selection for Continuous or Temporal 3
• Tamperproof re-entrant grill
• Surface mount with the CLNGBB (Ceiling Surface Mount Back
Box)
• Silence audible while visual appliance will remain flashing (for
use in accepted jurisdictions)
• Faceplate available in red or off-white
Operating Temperature:
• 32°F to 120°F (0°C to 49°C). The CS Series is not listed for
outdoor use.
Unit Dimensions
• 6" (15.24 cm) x 2.6" (6.604 cm)
The Ceiling Mount Series comes standard with the 4" mounting plate
which incorporates the popular Super -Slide® feature that allows the
installer to easily test for supervision. The product also features a
locking mechanism which secures the product to the bracket without
any screws showing.
The CS/CHS also features the patented Checkmate® - Instant Voltage
Verification feature which allows the installer to check the voltage drop
draw without removing the signal.
The CS Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed
for use with fire protective systems.
PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -TechSupport: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com
PRINTED IN USA
MFG. #8830051 - REV A
06/13
PAGE 1 OF 4
Page 21 of 28
(E)POTTER
The Symbol of Protection
Mounting Super -Slide®
1. Slide Onto Bracket
Checkmate® Instant Voltage Verification
J
o
o O
W
O
DOC
00
0
®C�fn14f��&
The access holes are provided in the back of the terminal block to
allow the voltage to be measured directly without removing the
device. Typically this would be done at the end of the line to confirm
design criteria. Most measurements will be taken using the S+ and
S- locations although access is provided to other locations. NOTICE:
CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES.
CS/CHS
SELECTABLE CANDELA
CEILING MOUNT
3. Snap Cover Over Assembly
Switch Locations
N
Switch positions 1 and 2 in the down position to select isolated horn
and strobe power inputs. Switch 3 selects between temporal or non -
temporal tone. Up is temporal. Switch 4 selects between mechanical or
high frequency tone. Up is mechanical. Switch 5 selects between high
or low dBA. Up is high dBA.
PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com
PRINTED IN USA
MFG. 98830051 - REV A
06/13
PAGE 2OF4
Page 22 of 28
CS/CHS
CP� POTTER SELECTABLE CANDELA
The Symbol of Protection CEILING MOUNT
CS Series 24 Volt Ceiling Mount Selectable Strobe
Model
Number
Part
Number
Nominal
Voltage
Candela
CS-24R
4890020
24 VDC
15, 30, 75, 95, 115, 150
CS-24W
4890021
24 VDC
15, 30, 75, 95, 115, 150
CS-24PR
4890022
24 VDC
15, 30, 75, 95, 115,150
CS-24PW
4890023
1 24 VDC
15, 30, 75, 95, 115, 150
CHS Series 24 Volt Ceiling Mount Selectable Horn/Strobe
Model
Number
Part
Number
Nominal
Voltage
Candela
Reverberant dBA @
10 ft. per ANSI/UL 464
In Anechoic Room
dBA @ 10 ft.
CHS-24R
4890040
24 VDC
15, 30, 75, 95, 115, 150
81-86
90
CHS-24W
4890041
24 VDC
15, 30, 75, 95, 115, 150
81-86
90
CHS-24PR
4890042
24 VDC
1 15, 30, 75, 95, 115, 150
1 81-86
1 90
CHS-24PW
4890043
24 VDC
1 15, 30, 75, 95, 115, 150
1 81-86
1 90
Model Designations:
C = Ceiling Mount S = Strobe HS = Horn/Strobe
R = Red Faceplate W = White Faceplate
All units are available in plain (no lettering).
Plain units are non -returnable.
CS24 Product Strobe Current Ratings (mA)
Candela
15 cd
30 cd
75 cd
95 cd
115 cd
150 cd
24 VDC
(16-33 Volts)
24 VDC
72 mA
101 mA
167 mA
200 mA
214 mA
286 mA
UL Maxi
120 mA
120 mA
1 200 mA
220 mA
290 mA
1 321 mA
CHS24 Product Horn Decibel and Current Ratings (mA)
Horn
Mode
Minimum dBA @ 10 ft.
per ANSI/UL 464
(HIGH)
Minimum dBA @ 10 ft.
per ANSI/UL 464
(LOW)
Regulated 24 VDC
Max. Operating
@ High Setting (mA)
Temp 3 2400Hz
83
75
23
Temp 3 Mechanical
81
73*
22
Continuous 2400Hz
86
78
23
Continuous Mechanical
84
76
22
NOTES:
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the
horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
• For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power,
see installation manual.
• Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
• Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for
public mode fire protection service.These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public
mode application (not applicable when using the chime tone. The chime tone is always private mode).
• RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range
(16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For
audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com
PRINTED IN USA MFG. #8830051 - REV A PAGE 3 OF 4
06/13
Page 23 of 28
CS/CHS
OF POTTER SELECTABLE CANDELA
The Symbol of Protection CEILING MOUNT
Architect & Engineering Specifications
The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters
Laboratories Inc. per ANSFUL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification appliance shall also be listed with the
California State Fire Marshal (CSFM).
The notification appliance (combination audible/visible units and audible units only) shall produce a peak sound output of 90dBA or
greater as measured at 24VDC in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while
leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or
temporal tone output with the temporal signal having the ability to be synchronized.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power
input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting
bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with
the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power.
The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of
mounting to a surface back box.
Conventional CS/CHS Series Wiring Diagrams
UL Listed
Control
Signal
Panel
S+ S+ S- H+ H-
Supervised 0 0
Signal Circuit
UL Listed
Control
Sig�H+H-
Panel
s-
Supervised
Signal Circuit
END IS LINE
RESISTOR
Signal I I Signal
END OF LINE
RESISTOR
END OF LINE
RESISTOR
NOTES:
• All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling
circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn
and/or mute the horn.
• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050)
AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM
CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.pottersignal.com OR CALL POTTER
ELECTRIC AT 1-800-325-3936.
PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 •Canada888-882-1833 •www.pottersignal.com
PRINTED IN USA MFG. 98830051 - REV A PAGE 4 OF 4
06/13
Page 24 of 28
(E)POTTER
The Symbol of Protection
Features
• Fixed 75cd strobe
• Includes the WPBB surface -mount (standard) or WPLPBB Low Profile
(LP) enclosure
• WPBB/LP made of clear Lexan® - provides maximum visibility and
reliability, allowing full 75cd output
• Super -Slide® Bracket — Ease of supervision testing
• Checkmate® - Instant voltage verification
• Synchronize strobe and/or horn with AVSM module
• Switch selection for high/low dBA
• Switch for chime, whoop, mechanical, and 2400Hz tone
• Input terminals accept 18 to 12 AWG
• Switch for continuous or temporal 3 tone (not available on whoop)
• Tamperproof re-entrant grill
• 5 year warranty
Application
The S/HS-WP Series Outdoor Signals are wall mount, low profile
strobes and horn/strobes that offer dependable audible and visual
alarms for warning and emergency notification in outdoor locations.
Description
The S/HS-WP Series Outdoor Signals are 24VDC strobes and horn/
strobes equipped with a fixed 75 candela strobe.
This series of outdoor signals are available in two different versions.
The standard version includes a surface -mount back box (WPBB) to
install directly on a wall. The Low Profile (LP) versions includes a
low profile back box (WPLPBB) designed to be installed on a flush -
mounted electrical box. The weatherproof enclosure is made of
clear Lexan® which provides maximum visibility and reliability for
effective visible signaling, allowing full 75cd output.
The S/HS-WP series strobe has a minimal operating current and a
minimum flash rate of 1Hz regardless of input voltage. The strobe is
synchronized using Gentex sync. protocol or the AVSM Sync. Module.
The S/HS-WP Series is equipped with a universal 4" mounting bracket
which incorporates the popular Super -Slide® feature that allows the
installer to easily pre -wire the system and test for supervision. The
product also features a locking mechanism that secures the signal to
the bracket without showing any screws and the Checkmate® - Instant
Voltage Verification Feature which allows the installer to check the
voltage drop, current draw, and match against the blue print.
S/HS-WP Series
Outdoor Strobes and Horn/Strobes
�v 1W
LP Version Standard MNAUNs
Ul
LISTED
S3247
Product Listings
• ANSI/UL 464 and 1638
• Complies with American with Disabilities Act (ADA)
• Complies with IBC / IFC / IRC
Technical Specifications
Operating Voltage
Nominal 24VDC (16-33VDC)
Operating
-31°F - 150°F (-35° - 66°C)
Temperature
LP Version - 5.75" H x 4.75" W x 3.25" D
Dimensions
Standard - 5.75" H x 4.75" W x 4.18"D
Wiring Connections
Terminals accept 18 - 12 AWG
LP Version — Single gang, double gang, or
4" square back box
Mounting
Standard Version - Surface mount back box
included
Shipping Weight
2.05 lbs.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
8830057 - REV B • 3/15 PAGE 1 OF 4
Page 25 of 28
(E)POTTER
The Symbol of Protection
S-24-WP, 75 Candela, Outdoor Strobe
Includes Standard or LP Enclosure
Model Number
Stock
Number
Body Color
WP Enclosure
S-24WR-WP
4890050
Red
Standard
S-24WW-WP
4890051
Off -White
Standard
S-24PWR-WP
4890052
Red -Plain
Standard
S-24PWW-WP
4890053
Off -White -Plain
Standard
SLP-24WR-WP
4890054
Red
Low Profile
SLP-24WW-WP
4890055
Off -White
Low Profile
SLP-24PWR-WP
1 4890056
Red -Plain
Low Profile
SLP-24PWW-WP
1 4890057
Off -White -Plain
Low Profile
S/HS-WP Series
Outdoor Strobes and Horn/Strobes
Model Designations
"W "= WallMount
"R" = Red Face Plate
"W "=Off - White Face Plate
"P"= Plain (Note: Plain units are non -returnable)
"LP"= Low Profile (WPLPBB Enclosure)
Strobe Current Ratings
Candela
75 cd
24 VDC
112 mA
UL Max
170 mA
NOTE: ForunfilteredFWRratings, see installation manual.
HS-24-WP Series, 75 Candela, Outdoor Horn /Strobe
Includes Standard or LP Enclosure
Model Number
Stock
Number
Body Color
Reverberant dBA at 10', per ANSI/UL 464
In Anechoic Room dBA at 10'
WP Enclosure
HS-24WR-WP
4890060
Red
70-82
100
Standard
HS-24WW-WP
4890061
Off -White
70-82
100
Standard
HS-24PWR-WP
4890062
Red -Plain
70-82
100
Standard
HS-24PWW-WP
4890063
Off -White -Plain
70-82
100
Standard
HSLP-24WR
4890064
Red
70-82
100
Low Profile
HSLP-24WW
4890065
Off -White
70-82
100
Low Profile
HSLP-24PWR
4890066
Red -Plain
70-82
100
1 Low Profile
HSLP-24PWW
4890067
Off -White -Plain
70-82
100
1 Low Profile
Horn Decibel and Current Ratings
Horn Setting
Minimum
dBA at 10',
Per UL 464
(HIGH)
Minimum
dBA at 10',
Per UL 464
(LOW)
Regulated 24VDC
Max. Operating
Current, at High
Setting (mA)
Temporal 3 2400Hz
78
71 *
28
Temporal 3 Mechanical
76
70*
25
Temporal 3 Chime
70*
66*
15
Continuous 2400Hz
81
74*
28
Continuous Mechanical
80
72*
25
Continuous Chime
1 70*
66*
15
Whoop
1 82
1 69*
56
*Operating the horn in this mode at this voltage will result in not meeting
the minimumANSI/UL 464 reverberant sound level required for public
mode fire protection service. These settings are acceptable only for
private mode fire alarm use. Use the high dBA setting for public mode
application (not applicable when using the chime tone. The chime tone
is always private mode).
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
8830057 - REV B • 3/15 PAGE 2 OF 4
Page 26 of 28
(E)POTTER
The Symbol of Protection
Tone Switch Locations
Tone
Switch Position
3
4
5
Mechanical Temporal 3
ON
ON
ON
Mechanical - Continuous
OFF
ON
ON
2400Hz - Temporal 3
ON
OFF
ON
2400Hz - Continuous
OFF
OFF
ON
Chime - Temporal 3
ON
ON
OFF
Chime - Continuous
OFF
ON
OFF
Whoop
ON
OFF
OFF
Whoop
OFF
OFF
OFF
NOTES. -
Switch Positions 1 and 2 in the OFF position to select
isolated horn and strobe power inputs
• Switch Position 6 ON = HIGH dBA
• Switch Position 6 OFF = LOW dBA
Super Slide® Mounting Bracket 1
Allows the installer to pre -wire the system, test for system -
supervision, remove the signal head until occupancy, switch
out signals without changing mounting brackets and has
locking edge connector for snap -in -place installation. t(
Mounting Outdoor Enclosure
Super Slide® Mounting Plate:
Mounts to WPBB Outdoor Enclosure
S/HS-WP Series
Outdoor Strobes and Horn/Strobes
Checkmate® Instant Voltage
Verification
It is often necessary to confirm the voltage
drop along the line of devices. The access
holes are provided in the back of the
terminal block to allow the voltage to
be measured directly without removing
the device. Typically, this would be done
at the end of the line to confirm design
criteria. Most measurements will be taken
using the S+ and S- locations although
access is provided to other locations.
NOTE. Care should be taken to not
short the test probes.
Super Slide® Mounting Plate:
Mounts to WLPBB Outdoor Enclosure
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
8830057 - REV B • 3/15 PAGE 3 OF 4
Page 27 of 28
(E)POTTER
The Symbol of Protection
UL Listed
Control
Panel Signal
S+ S+ S- H+ H-
Supervised 0 0
Signal Circuit
n
S/HS-WP Series
Outdoor Strobes and Horn/Strobes
Wiring Diagrams
UL Listed
Control
Signal
Panel
S- H+ H-
Supervised
0 0
Signal Circuit
END LINE
RESISTOR
\ +
Signal I I Signal
END OF LINE
RESISTOR
END OF LINE
RESISTOR
NOTES. -
All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits.
However, use of the AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn.
• FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR
AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE
DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936.
Architect and Engineering Specifications
The audible and/or visible signal shall be Potter S/HS-WP Outdoor Series or approved equal and shall be listed by Underwriters Laboratories Inc. perANSF
UL 1638 and/or ANSFUL 464.
The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber.
The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair
of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be
synchronized.
The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage.
The appliance shall have an operating current of 112mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela
requirements of the ADA (75cd).
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals
with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The
unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models.
The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box.
The unit shall also be able to verify voltage at the unit without removing unit.
The appliance has extended temperature range of -31' to 150DF (-35° to 66' C). The appliance shall satisfy virtually all outdoor and severe environment
applications. The WPBB enclosure includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to
allow for drainage, the seal on the WPBB enclosure is not water tight. The WPLPBB enclosure includes a weather seal for mounting to wall and intended
for use with universal electrical box. To allow for drainage, bottom edge of enclosure is not water tight.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
iso soo3:zoos DESIGNING, MANUFACTURING,
& DISTRIBUTING QUALITY SYSTEMS 8830057 - REV B • 3/15 PAGE 4 OF 4
Page 28 of 28