FIR2024-0008+Fire_Alarm_Equipment_Specification_Sheets+1.29.2024_3.26.19_PM+402662009 SeaCom ;05W CABLING TECHNOLOGY SOLUTIONS 1912 Everett Avenue Suite.120, Everett, WA 98201 Submittals Kuzmas Fish Market Edmonds, WA Fire Alarm System 01 rib SeaCom CABLING TECHNOLOGY SOLUTIONS Fire Alarm System Kuzma's Fish Market Submittals Material Manufacturer Part Number Page Fire Alarm Control Panel Potter IPA-60 1-4 Cellular Communicator Potter INTELLICOM-5GV 5-8 Manual Pull Station Potter PAD100-PSSA 9-10 Heat Detector Potter PAD300-HD 11-12 Detector Base Potter PAD300-6DB 13-14 Single Input Module Potter PAD100-SIM 15-16 Wall Mounted Strobe & Horn/Strobe Potter S-24WW & HS-24WW 17-20 Ceiling Mounted Strobe & Horn/Strobe Potter CS-24W & CHS-24W 21-24 Weatherproof Horn/Strobe Potter HS-24WR-WP 25-28 (E)POTTER A The Symbol of Protection Features • 60 addresses available on this analog addressable system • Additional system capacity achieved via multi -point SLC modules • 99 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built -In • System Operates as Class A or Class B for SLC, P-Link and NACs • 5 Amp Power Supply, Expandable to 310 amps • 2 NACS, Regulated, Rated at 3 Amps each, expandable to 188 • 2 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each, ideal for manual release and abort • Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®, Cooper Wheelock® and System Sensor® strobes • Dedicated Alarm, Supervisory and Trouble Relays • 4,000 Event History Buffer • Cabinet will house up to 18 AH batteries • Optional two line DACT with UD-2000 that can report General, Zone or Point Information • Built in IP Communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status, Reports and Event Information • Product includes 5 year warranty. • UUKL Listed for Smoke Control Description The IPA-60 is an analog/addressable releasing fire alarm system with a total system capacity of 60 addresses. Additional capacity on the system is achieved using multi -point SLC modules. The control panel utilizes the exclusive Potter protocol that includes a complete line of sensors and modules. Each SLC may be comprised of any combination of smoke sensor, heat detectors or modules and allows for a total of 50 ohms of impedance and may use any wire compliant with the National Electrical Code (NEC). The IPA-60 has a 5 Amp power supply with two Notification Appliance Circuits (NACs) and two hiput/Output (FO) circuits. The NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and power limited. In addition, each output is uniquely programmable and may be configured for steady signal, strobe synchronization, constant power, door holder power, or releasing. The strobe synchronization includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. The I/Os are designed for inputs such as manual release stations and abort switches that will not require polling and react nearly instantaneously. The IPA-60 is listed for releasing of fire suppression systems. The software allows cross zones, counting zones, and timers for suppression. The system is capable of multiple release outputs across multiple hazards. In addition, the PSN-1000 may be used to extend releasing capability. The NACs may be expanded using the PSN-1000 series intelligent power supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and the IPA-60 will support up to 31 power supplies. The system will synchronize the strobes system wide. In addition, the PSN- 1000E has space to allow the installation of up to six expansion cards. The cards mount on a stacker bracket that allows access to all SLC circuit connections. IPA-60 Fire Alarm Control Panel FM APPROVED Technical Specifications •"" `$ LISTED Dimensions 16"W x 17"H x 3 7/8"D AC Mains 3.0 Amps @ 120 VAC 50/60 HZ 2.0 Amps @ 240 VAC 50/60 HZ Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window Standby Current-130 mA Alarm Current-200 mA • 5 Amps power for NACs, I/O, and P-Link Battery • 3 Amps per NAC, regulated • 1 Amp per I/O circuit, regulated • Battery Charger range 8-55 Ah • Battery Charger voltage 27.3 VDC • P-Link maximum current of 1 Amp Temperature and 321 to 1201(0°C to 49°C) with a maximum Humidity Range humidity of 93% non -condensing. NFPA 12, 12A, 13, 15, 16, 17, 17A, 70, 72, 750, and 2001 ANSFUL 864 - Local (L), Remote Sta- tion (RS), Central Station (CS), Propriety (PPU), Auxiliary (AUX).Type of Service: Standards Automatic (A), Manual (M), Water flow (WF) Sprinkler Supervisory (SS) Type of Signaling: Digital Alarm Communicator (DAC), March Time (March), Non Coded (NC), Reverse Polarity (Rev Pol), Other Technologies (OT) IBC 2000, 2003, 2006, 2009, 2012 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830101- REV G • 9/19 PAGE 1 OF 4 Page 1 of 28 (E)POTTER IPA-60 The Symbol of Protection Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 60 addressable devices or modules in any combination. The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PAD100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PAD 100-PHD Combination Analog Photo Electric Smoke/Heat Detector — a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135' Fahrenheit heat detector. PAD100-HD Analog Fixed Temperature Heat Detector that is selectable from 135' F to 185°F. PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay. PAD100-DUCT Addressable Duct Smoke Detector. PAD 100-6B 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD 100-4B 4" round base that may be mounted to an electrical box and wired for connection to the above sensors. PAD 100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. PAD100-CD Addressable CO gas detector. PAD 100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. PAD100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local, group and all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W. Modules Device Description PAD 100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD100-PSDA Dual Action Addressable Pull Station. PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box. PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs. PAD 100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD 100-LED Module provides a single addressable LED that is controlled by the control panel. PAD 100-SM Speaker Module provides switching for two audio channels. PAD 100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD 100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830101- REV G • 9/19 PAGE 2 OF 4 Page 2 of 28 (E)POTTER The Symbol of Protection SLC Features The Potter protocol is a digital protocol with a proven design for reliability and noise immunity. The system does not require special cable or conductors for connection of the Signaling Line Circuit as long as the cable is compliant with NFPA 70 and NFPA 72. The system allows for Class A or Class B installations as well as "T-Taps", with a max wiring distance of 10,000 Ft. Sensor Features The sensors through the fire alarm control panel provide a real time status as to the condition of the system. The smoke detector sensitivity, heat detector temperature level and drift compensation are all programmable options. The system also allows for a day/night mode where the panel automatically adjusts the sensitivity depending on the time of day. To assist in the reduction of false alarms, the smoke detectors also have a maintenance warning that sends a trouble signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. User Interface The fire alarm control panel has a 2 x 16 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs: • AC Power - Green • Alarm - Red • Earth Fault - Amber • Supervisory - Amber • Silenced - Amber • Trouble - Amber • Pre -Release - Amber • Release - Red The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened. P-Link The IPA-60 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 64 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following: RA-6075R — 2 x 16 LCD annunciator with a key pad in a locked metal enclosure. IPA-60 Fire Alarm Control Panel RA-6500R(F) — 4 x 40 LCD annunciator with a key pad in a locked metal enclosure. Flush mount version available. LED-16(F) — 16 LED annunciator with common indicators in a locked metal enclosure. Flush mount version available. PSN-1000(E) — 10 amp, remote intelligent power supply with 6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in conjunction with the IPA-60 as releasing circuits. CA-6075 — Class A convertor that converts the SLC, NACs and P-Link connection UD-2000 — UL listed, Dual line telephone alarm communicator DRV 50 — LED driver expander, used to connect up to 50 LEDs in a graphic display FCB-1000 — Fire communication bridge, provides remote mounting of the Ethernet connection FIB-1000 — Fiber interface module, used to extend P-Link to multi - mode fiber (2 required) RLY-5 — Relay module, provides 5 form C relay contacts rated at 3.0 amps 24VDC/125AC SPG-1000 — Serial parallel gateway, allows for the connection to a serial or parallel printer The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. MC-1000 Multi -Connect allows up to sixty-three IPA series panels to share a single reporting technology. IDC-6 — Initiating device circuit provides 6 programmable inputs AE-2 — Two card expansion cabinet AE-8 — Eight card expansion cabinet AE-14 — Fourteen card expansion cabinet Ethernet/I.P. Connection The IPA-60 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions. In addition, the Ethernet connection is UL listed as an IP communicator. The IP communicator is listed to report to the UL listed Sur -Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830101- REV G • 9/19 PAGE 3 OF 4 Page 3 of 28 (E)POTTER The Symbol of Protection Dimensions • • • 00 II 0 0 0 0 LEFT SIDE Ordering Information IPA-60 Fire Alarm Control Panel ® O TOP • DEPTH = 3.75 " 0 0 DOOR = 16.07" BACKBOX = 15.77" a DEPTH = 3.84" BOTTOM Model Description Stock No. IPA-60 Fire Alarm Releasing Control Panel 3992714 Replacement Board IPA-60 3992738 II 0 RIGHT SIDE DWG #593-1 Compatible Releasing Devices Note: For releasing applications please order the Potter EOLD (3005012) for circuits connected to a releasing solenoid or actuator. Brand Description Skinner 73218BN4UNLVNOC112CZ 73212BN4TNLVNOC322C2 Victaulic 753-E Series Mini Max MX123 & MX200 w/ 8876677 & 889323 Viking 11591, 11601, 11602,13843, & 13844 TLX PA0036 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830101- REV G • 9/19 PAGE 4 OF 4 Page 4 of 28 (E)POTTER The Symbol of Protection Features • 5G LTE-M commercial fire alarm communicator • Verizon or AT&T models available • Direct connect to Potter panels with Ethernet (Contact ID) • UD-2000 DACT not required when using Ethernet on Potter panels • Interfaces with other panels over a single DACT connection for universal compatibility • Meets UL 864 requirements for sole, primary, or backup path communications • 5-minute or 60-minute supervision • Power from fire panel 24V auxiliary power supply or plug-in transformer (included) • Red/Locking metal enclosure • Secure cloud -based account management tools • Use any local and national central stations with no extra equipment or setup • IntelliView Compatible — iOS/Android App & Browser access • IntelliView Cloud Services and Apps included when used on Potter Panels • Alert: Detailed event status, counters, history, push notifications • Backup: Panel programming backed up to the cloud • Test/Inspect: One person walk -test tool • Program: Remotely Upload & Download panel configurations Description Provides sole or dual path 5G LTE-M cellular monitoring communication for any commercial fire panel. Potter panels using the Potter IntelliCom Advanced Gateway offer the most advanced features in the industry without the need for a UD-2000 POTS dialer. Potter panels enable automatic panel program backups/retrieval, remote programming, cloud storage, and mobile walk test that creates an NFPA-72 initiation device report. If the existing panel supports Contact ID, it's a candidate for upgrading with the Potter IntelliCom Advanced Gateway. IntelliComTM 5G LTE Advanced Gateway 0 LISTED Technical Specifications Cellular Service 5G LTE - Verizon orAT&T Dimensions 7.5" H x 11.5" W x 3.5" D Color Red Primary Power 12VAC or 12/24VDC (29VDC max) Standby Current 68mA @ 24VDC (w/ Link Supervision) Transmit Current 140mA @24VDC Compatible Panels Fire panels with dialer (Contact ID) Potter Panels — See IPA-4000(V), IPA-100, IPA-60, manual for specific AFC- 1000(V), AFC-100, services available. UD- AFC-50, ARC-100, PFC-4064 2000 not required. Communication Protocols: Ethernet CID over Ethernet DACT CID, SIA, Pulse (4x2, 3xl), Radionics (Ile/3a2,4), DMP Agency ANSI/UL 864 Fire Protective Signaling Systems) Certifications FCC Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830202 - REV B • 9/23 PAGE 1 OF 4 Page 5 of 28 (E)POTTER The Symbol of Protection contact ) Rich Dara IntelliComTM 5G LTE Advanced Gateway Stationentral 1 moll Your Preferred Central Station National Central Stations Local Central Stations Sur -Gard & DMP Receivers Active Signal Alerts Panel Program Cloud Backup Panel Program Cloud Restoral Panel Remote Programming Walk Test Cloud Storage for Programs p Alert p Test & Inspect Signals, Push Notifications, Status Initiation Device Report Generator (ky >>) 5G LTE-M p Program p Backup Remote Programming Tool Automated Cloud Backup & Restoral Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830202 - REV B • 9/23 PAGE 2 OF 4 Page 6 of 28 (E)POTTER The Symbol of Protection (D Test & Inspect initiation Device Report Generator IntelliComTM 5G LTE Advanced Gateway Potter Test & Inspection Initiation Device Report Generator is an automated way to create the NFPA-72 Initiating Device Supplementary Record of Inspection and Testing. This tool eliminates the time-consuming manual process of creating a list of points for the required report. The tool allows a technician to import all the points, mark them as Pass/Fail, document the visual & functional test, and export the results into a file that can be included with the remainder of the user provided NFPA-72 report. This cloud -based tool is complimentary to all customers using a compatible Potter fire alarm control panel with an IntelliCom Advanced Gateway p Backup Automated Cloud Backup & Restoral Potter Automated Cloud Backup & Restoral is an automated way to backup Potter fire alarm control panel databases. This tool ensures that the panels program is always available and secure. Technicians can instantly recover the database from the secure server at any time. Never have to find a specific technician's computer, or thumb drive ever again. This service will save many hours whenever you have that unfortunate event that requires the system to be reprogrammed. This cloud -based tool is complimentary to all customers using a compatible Potter fire alarm control panel with an IntelliCom Advanced Gateway p FPP Remote Programming Tool Web based programming is a reality with the IntelliCom Advanced Gateway and Potter panels. Potter Programming Tool databases can be remotely sent to panels — from anywhere in the world. This is a great tool when commissioning systems, making updates during a T&I session, or simply making label changes. No longer does the technician with the knowledge to reprogram the panel have to be on site.** This cloud -based tool is complimentary to all customers using a compatible Potter fire alarm control panel with an IntelliCom Advanced Gateway. ** NFPA-72 Requires that when changes are made to site -speck software, all functions known to be affected by the change, or identified by a means that indicates changes, must be 100 percent tested. In addition, 10 percent of initiating devices that are not directly affected, up to a maximum of 50 devices, must also be tested and proper operation verified. @ Alert Signals, Push Notifications, Status Panel information is right at your finger tips any time you need it. Receive alerts to any Android or iOS compatible mobile device. Push notifications to the mobile app allow for immediate signal notification. Remote Acknowledge, Silence, Reset, Enable/Disable, and Drill operations are available while a panel is in Walk Test. Prepare for a site visit by retrieving point information and panel history. This cloud -based tool is complimentary too all customers using a compatible Potter fire alarm control panel with an IntelliCom Gateway Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830202 - REV B • 9/23 PAGE 3 OF 4 Page 7 of 28 (E)POTTER The Symbol of Protection Ordering Information IntelliComTM 5G LTE Advanced Gateway Model Description Stock No. IntelliCom-5GV 5G LTE-M Dual path commercial fire alarm communicator (Verizon) 3994000 IntelliCom-5GA 5G LTE-M Dual path commercial fire alarm communicator (AT&T) 3994001 Accessories TG-TAMPER Tamper Switch Assembly compatible with Potter metal enclosures 3994002 ACD-12 12 feet - low loss high performance antenna cable and mounting bracket 3994003 ACD-35 35 feet - low loss high performance antenna cable and mounting bracket 3994004 ACD-50 50 feet - low loss high performance antenna cable and mounting bracket 3994005 ACD-100 100 feet - low loss high performance antenna cable and mounting bracket 3994006 HGDL-0 High Gain Directional Antenna 3994007 EXDL-0 External Omni -Directional Antenna 3994008 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830202 - REV B • 9/23 PAGE 4 OF 4 Page 8 of 28 PAD 100-PSSA/PS DA P POTTER Addressable Pull Station �A The Symbol of Protection Single/Dual Action Features • Single or Dual Action versions • Durable die-cast construction • Reset key matches the fire alarm control panels • Compatible with IPA Series panels • SLC Class A, Class X & Class B • Product includes a 5 year warranty Description The PAD100-PSSA (Single Action) is activated by simply pulling the white "T" bar handle down. The PAD100-PSDA (Dual Action) is activated by lifting the front cover and then pulling the white "T" bar handle down. Once activated, the "T" bar cannot be reset without opening the front cover. Opening the front cover will also activate the pull station. To reset the PAD100-PS Series, use the Potter WS-93 key to unlock and open the front cover. Once the cover is open, push the "T" bar back into the normal position and re -secure the front cover. Application The PAD100-PSSA/PSDA is compatible with Potter's IPA and AFC/ ARC series addressable fire alarm control panels. It is a non -coded addressable pull station available in either a single or dual action model and installs on a single gang box or surface mounts using the P32-BB or P32-DBB (deep) back box. �SBMB<�� •T P Fx .ca C 9 THE US Technical Specifications Operating Voltage 24.0 VDC Max SLC Standby Current 200uA Max SLC Alarm Current 200uA 32°F - 120°F (0° - 49°C) Environmental Limitations Indoor Only Dimensions 4.75" H x 3.25" W x 1.75" D Relative Humidity Range 0 - 93% (non -condensing) Single gang box or Mounting Options Potter P32-BB/DBB APS-SA - 1.22 lbs. Shipping Weight APS-DA - 1.46 lbs. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830097 - REV C • 3/18 PAGE 1 OF 2 Page 9 of 28 PAD 100-PSSA/PSDA (E)POTTER Addressable Pull Station The Symbol of Protection Single/Dual Action Setting the Address The PAD 100-PS Series uses one SLC address assigned to the device. The address is set using the DIP switch located on the back of the PAD 100-PS device. Pull Station Front View Fig I PAD 100-PSDA Pull Station Back View and bring Fig 2 FROM FACP OR PREVIOUS DEVICE TO NEXT DEVICE Ordering Information Model Description Stock No. PAD100-PSSA Addressable Pull Station, Single Action 3992721 PAD100-PSDA Addressable Pull Station, Dual Action 3992720 V PorrEl? PAD 100-PSSA FACTORY WIRED CONTACTS 0 0 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830097 - REV C • 3/18 PAGE 2 OF 2 Page 10 of 28 (BPOTSyrrdWFERThe Features • Selectable Rate of Rise and/or Fixed Heat Detector • Low Profile • Reliable Detection Technology • LED Alarm Indicator • Ambient Temperature Listing of 32°F to 150°F • Simple DIP Switch Address Setting, No Programming Tool Required • Magnetic Test Switch • Product includes 5-year warranty • UUKL Listed for Smoke Control Description The PAD300-HD is a listed analog addressable rate of rise and/or fixed temperature heat detector compatible with any fire alarm control panel that has the Potter Addressable Device (PAD) protocol. The heat sensing portion utilizes a proven thermistor for accurate and reliable heat detection. The detector and base (not included) are made of a durable plastic in an off-white to blend in with the ceiling. The PAD300-HD is UL listed with a selectable fixed temperature point from 135' to 185' Fahrenheit and can be used for rate of rise applications. See detector spacing limitations below. This flexibility allows the installer to cover a wide variety of applications with a single unit. The PAD300-HD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements. The detector is compatible with any of the PAD300 series detector bases and simply twists on. The PAD300-HD is addressed using DIP switches in the rear of the detector and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. PAD300-H D Heat Detector (00 0328-0538 Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 µA Alarm Indicator 1 LED Alarm Set -point Range 135°F to 185°F (57'C to 85'C) Rate of Rise Detection 15'F/min. (8.3'C/min.) (Selectable Option) Installation Temperature Range 32°F to 150'F (0°C to 66°C) Operating Relative Humidity 0% to 93% (Non -condensing) Range Start-up Time Max. 1 sec. Maximum Number of Addresses 127 Per Loop Maximum Number of Lighted 30 Indicators in Alarm Per Loop Color Eggshell White Weight (Without Base) 68 g (2.4 oz) Dimensions (Without Base) Height: 1.5 in (38 mm) Diameter 3.93 in (100mm) Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830210 - REV C • 6/23 PAGE 1 OF 2 Page 11 of 28 (P)POTTER PAD300-H D JI`e4a�"1W tolu.W Heat Detector Operation The PAD300-HD is an analog addressable detector that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LED flashes every time the unit is polled and it will flash at a fast rate if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation. The PAD300-HD with the PAD300-4DB or PAD300-6DB has a low profile to blend into the surrounding environment. The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD300-HD will operate even though the LED will not illuminate. Spacing The ANSI/IJL listed spacing limitations of PAD300-HD smooth ceiling are dependent on alarm set point. Alarm Set -Point Rate of Rise Spacing Fixed Temperature Spacing 135°F to 185°F Max. 70 ft. Max. 70 ft. (57°C to 85°C) Compatible Bases All bases will mount on a single gang, 3-1/2" octagon, 3-1/2" square, double gang, 4" octagon, 4" square, 50mm c/c, 60mm c/c and 70mm c/c boxes. Device Description Stock No. PAD300-4DB 4" Detector Base 3992781 PAD300-6DB 6" Detector Base 3992782 PAD300-IB 6" Base with an Isolator Module Included 3992783 PAD300-RB 6" Base with One Form-C Relay Contact 2A @ 30VDC, 0.5A @ 125VAC 3992784 PAD300-SB 6" Base with sounder module included. Sound pattern is provided from external source 3992785 PAD300-LFSB 6" Base with 520Hz sounder module included. Sound pattern is provided from external source 3992786 Ordering Information Model Description I Stock No. PAD300-HD Heat Detector 13992776 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830210 - REV C • 6/23 PAGE 2 OF 2 Page 12 of 28 (DPOTTER The Symbol of Protection Features • Terminals marked with polarity to assist with installation • Duplicate Terminals for In -and -out SLC Wiring • Terminals accept 22 to 12 AWG wire sizes • Installs on Single Gang, Double Gang, Octagon or 4" Square Box • Locking tab prevents unauthorized detector removal • Product includes 5-year warranty • 6" mounting base comes with trim plate cover Application The Potter PAD300-6DB and PAD300-4DB detector bases are used to install PAD300 series detectors. The PAD300-6DB will mount on a single gang, double gang, octagon, 4" square, 50mm, 60mm, and 70mm electrical box. Description The PAD300-6DB and PAD300-4DB are low -profile, surface -mount bases used with Potter's addressable detectors. The base uses screw clamp terminals that accept wire ranging from 22 to 12 AWG. When installed on recessed electrical boxes, the PAD300-6DB is wide enough to completely cover the back box and the immediate surrounding area. The base is equipped with a locking tab to deter unauthorized removal of the attached detector. PAD300-4DB/6DB 4"/6"Detector Base (001 0328-0539 Technical Specifications Installation Temp Range 320F to 150OF (0°C to 66°C) Operating Humidity Range 0% to 93% (Non -condensing) PAD300-4DB: 3.93 in / 100 mm Dimension PAD300-6DB: 6.3 in / 160 mm PAD300-4DB: 1.34 oz / 38 g Weight PAD300-6DB: 3.03 oz / 86 g Height 0.76 in / 20 mm Acceptable Wire Gauge 22 to 12AWG Single Gang Double Gang 3-1/2" Octagon Box 4" Octagon Box Mounting Options 4" Square with Plaster Ring 50mm c/c Box 60mm c/c Box 70mm c/c Box Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com PRINTED IN USA 8830203 - REV B 2/23 PAGE 1 OF 2 Page 13 of 28 CP, POTTER The Symbol of Protection Locking Feature The PAD300-6DB and PAD300-4DB include a locking feature that prevents removal of the detector without using a tool. 1. To enable this feature, break off the locking tab (See Figure 1), and then install the detector. Fig. I 2. To remove the detector from the base when the locking feature has been enabled, insert a small screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counter -clockwise. Fig. 2 Insert small screwdriver into slot to remove detector from base. Ordering Information PAD300-4DB/6DB 4"/6"Detector Base Wiring Diagrams Fig. 3 1) Class B Wiring: 2) Class A Wiring: 3) Class X Wiring: Model Description I Stock No. PAD300-4DB 4" Detector Base 13992781 PAD300-6DB 6" Detector Base 13992782 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com PRINTED IN USA 8830203- REV B 2/23 PAGE 2 OF 2 Page 14 of 28 (E)POTTER The Symbol of Protection PAD100-SIM Single Input Module Features PgSEMeIFa • One (1) Class B monitoring input • SLC Class A, Class X & Class B • Mounts in a standard 4" or double gang box 2 THE v� • Wiring terminals accessible when mounted in box • All wiring terminals accept 22 to 12 AWG J • Product includes a 5 year warranty p poTTFa NOTE. This addressable module does not support 2-wire smoke 0 ""• detectors. al Description The PAD 100-SIM uses one (1) SLC loop addresses when monitoring one (1) Class B circuit. The module mounts on either a 4" square or double gang box. The module is capable of monitoring one (1) Class B circuit. The PAD100-SIM includes one red LED to indicate the module's status. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate. Application The PAD 100-SIM is compatible with Potter's IPA and AFC/ARC series addressable fire alarm control panels. The PAD100-SIM is an interface module used to monitor dry contact devices such as sprinkler waterflow, valve tamper switches, or conventional pull stations. The module is capable of monitoring one Class B circuit. Setting the Address Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the PAD 100-SIM. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device: 1. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Technical Specifications Operating Voltage 24.OV Max SLC Standby 240µA Current Max SLC Alarm 240µA Current Max Wiring Resistance 100 S2 of IDC Max Wiring I gF Capacitance of IDC EOL Resistor 5.1K 52 Operating Temperature Range 32 to 120OF (0 to 49°C) Operating Humidity Range 0 to 93% (non -condensing) Max no. of Module Per 127 units Loop Dimensions 4.17" (106mm)L X 4.17" (I06mm)W X 1.14" (29mm)D Mounting Options Standard 4" Square or Double Gang Box Shipping Weight 0.6 lbs Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830083 - REV C • 3/18 Page 15 of 28 PAGE 1 OF 2 (E)POTTER The Symbol of Protection Installation Using Compatible Electrical Box Fig 1 Wiring Diagram PADI00-SIM With Class B Circuit Fig 2 FROM FACP PREVIOUS N TO NEXT M( END -OF -LINE RESISTOR 5.1KOHM % W Part #3005013 tE Ordering Information Model Description Stock No. PAD100-SIM Single Input Module 3992704 PAD 100-S I M Single Input Module Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830083 - REV C • 3/18 Page 16 of 28 PAGE 2 OF 2 (E)POTTER The Symbol of Protection Features • 24VDC units have field selectable candela options of 15, 30, 60, 75 & 110 • Super -Slide® Bracket - Ease of Supervision Testing • Checkmate® - Instant Voltage Verification • Synchronize strobe and/or horn with AVSM Control Module • Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Switch selection for high or low dBA • Switch for chime, whoop, mechanical and 2400Hz tone • Tamperproof re-entrant style grill • Switch for continuous or temporal 3 tone (not available on whoop tone) • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) • Faceplate available in red or off-white Description The S-24/HS-24 Series is a low profile strobe and horn/ strobe combination that offers dependable audible and visual alarms and the absolute lowest current available. The S-24 & HS-24 Series 24VDC offers tamperproof field selectable candela options of 15, 30, 60, 75, and 110 candela. The Strobe and Horn/Strobe offers a continuous or sync temporal three in 2400Hz and mechanical tone, a chime and whoop tone. All tones are easy for the professional to change in the field by the use of switches. The S-24 & HS-24 Series has a minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. This Series is shipped with a standard 4" metal mounting plate which incorporates the popular Super -Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The S-24/HS-24 also features the patented Checkmate® - Instant Voltage Verification feature which allows the installer to check the voltage drop draw and match it to the blueprint. The S-24 & HS-24 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use with fire protective systems and are warranted for three years from date of purchase. S-24 & H S-24 Selectable Candela Strobe & Horn/Strobes PSEMSI ,r i2 THE uSP UL LISTED S3247 Technical Specifications Single or Double gang, 4" Mounting Options square box, and AVBB surface mount back box Terminals Screw -Clamp Type Wire Gauge 18 — 12 AWG Operating Temp 32°F — 120°F (0° — 49°C) Height — 5" Dimensions Width — 4.5" Depth — 2.5" Shipping Weight 1.05 lbs Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com Page 17 of 28 8830054-REV C 6/17 PAGE 1 OF 4 (E)POTTER S-24 & H S-24 The Symbol of Protection Selectable Candela Strobe & Horn/Strobes Switch Locations TONE SWITCH POSITION 3 4 5 Mechanical Temporal 3 ON ON ON Mechanical Continuous OFF ON ON 2400 Hz Temporal 3 ON OFF ON 2400 Hz Continuous OFF OFF ON Chime Temporal 3 ON ON OFF Chime Continuous OFF ON OFF Whoop ON OFF OFF Whoop OFF OFF OFF NOTE: • Switch Positions 1The and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON = HIGH dBA • Switch Position 6 OFF = LOW dBA Candela Selection Super Slide® Mounting Bracket Allows the installer to pre -wire the system, test for system supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap -in -place installation. �d To remove bezel, grip bo hr bezel d pull in downward a outward motion. �11 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830054-REV C 6/17 PAGE 2 OF 4 Page 18 of 28 (E)POTTER S-24 & H S-24 ® The Symbol of Protection Selectable Candela Strobe & Horn/Strobes S-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe Model Nominal Candela (ANSI/UL Part Number Number Voltage 1971) S-24WR 4890010 24 VDC 15, 30, 60, 75, 110 S-24WW 4890011 24 VDC 15, 30, 60, 75, 110 HS-24 24 VDC Selectable Candela, Low Profile Evacuation Strobe Candela (ANSI/ Reverberant dBA at 10 In Anechoic Room at Model Number Part Number Nominal Voltage UL 1971) ft, per ANSI/UL 464 loft HS-24WR 4890030 24 VDC 15, 30, 60, 75, 110 62-82 100 HS-24WW 4890031 24 VDC 15, 30, 60, 75, 110 62-82 100 S-24 & HS 24 Strobe Current Ratings 24 VDC (16 - 33 Volts) Candela 24 VDC UL Max 15 cd 30 mA 42 mA 30 cd 35 mA 58 mA 60 cd 66 mA 97 mA 75 cd 80 mA 116 mA 110 cd 103 mA 161 mA S-24 & HS-24 Horn Ratings Model Designations: W = Wall mount R = Red Faceplate W=White Faceplate All units are available in plain (no lettering) Plain units are non -returnable. "ALERT" bezel available for order. "AGENT" bezel available for order. Horn Mode Horn Decibel Levels Horn Current Ratings Minimum SPL at 10 ft, per ANSI/UL 464 (HIGH) Minimum SPL at 10 ft, per ANSUUL 464 (LOW) Regulated 24 VDC Max Operating @ High Setting (mA) Temp 3 (2400 Hz) 78 dBA 71 * dBA 28 mA Temp 3 (Mechanical) 76 dBA 70* dBA 25 mA Temp 3 (Chime) 70* dBA 66* dBA 15 mA Continuous (2400 Hz) 81 dBA 74* dBA 28 mA Continuous (Mechanical) 80 dBA 72* dBA 25 mA Continuous (Chime) 70* dBA 66* dBA 15 mA Whoop 82 dBA 69* dBA 56 mA NOTES. • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power see installation manual. • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830054-REV C 6/17 PAGE 3 OF 4 Page 19 of 28 (E)POTTER The Symbol of Protection S-24 & HS-24 Series Wiring Diagram UL Listed Control Signal Panel S+ S+ S- H+ H- Supervised 0 0 Signal Circuit r� S-24 & H S-24 Selectable Candela Strobe & Horn/Strobes UL Listed Signal Control Panel Signal S+ S+ S- H+ H- s- H+ H- Supervised 0 0 Signal Circuit END OF LINE RESISTOR \ + r� Signal S+ S+ S- H+ H- END OF LINE RESISTOR END OF LINE RESISTOR Notes: All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn, and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC TECHNICAL SUPPORT AT 1-866-956-1211 Architect & Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 horn/strobe Series or approved equal and shall be listed by Underwriters Laboratories, Inc. per ANSI/UL 1971 and/or ANSI/UL 464. The notification appliance shall also be listed with Factory Mutual Listing Service (FM) and the California State Fire Marshal (CSFM). The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models. The appliance shall be capable of testing supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830054-REV C 6/17 PAGE 4 OF 4 Page 20 of 28 CP� POTTER The Symbol of Protection U� LISTED S3247 Product includes a S year warranty Description The Potter CS/CHS Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The CS/CHS offers tamperproof field selectable candela options of 15, 30, 75, 95, 115 and 150 candela. The CHS horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone. All tones are easy for the professional to change in the field by using switches. The models are shipped from the factory in the temporal three alarm mode. The CS Series has a very minimal operating current and has a minimum flash rate of 1Hz regardless of input voltage. CS/CHS SELECTABLE CANDELA CEILING MOUNT Features • Nominal voltage 24 VDC • Tamperproof field selectable candela options 15, 30, 75, 95, 115, & 150 • Super -Slide" Bracket - Ease of Supervision Testing • Checkmate® - Instant Voltage Verification • Synchronize strobe and/or horn with Gentex AVSM Control Module • Prewire entire system, install mounting bracket, then install signals • Documented lower installation and operating costs • Input Terminals 12 to 18 AWG • Switch Selection for High or Low dBA • Switch Selection for 2400Hz or mechanical Tone • Switch Selection for Continuous or Temporal 3 • Tamperproof re-entrant grill • Surface mount with the CLNGBB (Ceiling Surface Mount Back Box) • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature: • 32°F to 120°F (0°C to 49°C). The CS Series is not listed for outdoor use. Unit Dimensions • 6" (15.24 cm) x 2.6" (6.604 cm) The Ceiling Mount Series comes standard with the 4" mounting plate which incorporates the popular Super -Slide® feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The CS/CHS also features the patented Checkmate® - Instant Voltage Verification feature which allows the installer to check the voltage drop draw without removing the signal. The CS Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use with fire protective systems. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -TechSupport: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 - REV A 06/13 PAGE 1 OF 4 Page 21 of 28 (E)POTTER The Symbol of Protection Mounting Super -Slide® 1. Slide Onto Bracket Checkmate® Instant Voltage Verification J o o O W O DOC 00 0 ®C�fn14f��& The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. NOTICE: CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES. CS/CHS SELECTABLE CANDELA CEILING MOUNT 3. Snap Cover Over Assembly Switch Locations N Switch positions 1 and 2 in the down position to select isolated horn and strobe power inputs. Switch 3 selects between temporal or non - temporal tone. Up is temporal. Switch 4 selects between mechanical or high frequency tone. Up is mechanical. Switch 5 selects between high or low dBA. Up is high dBA. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. 98830051 - REV A 06/13 PAGE 2OF4 Page 22 of 28 CS/CHS CP� POTTER SELECTABLE CANDELA The Symbol of Protection CEILING MOUNT CS Series 24 Volt Ceiling Mount Selectable Strobe Model Number Part Number Nominal Voltage Candela CS-24R 4890020 24 VDC 15, 30, 75, 95, 115, 150 CS-24W 4890021 24 VDC 15, 30, 75, 95, 115, 150 CS-24PR 4890022 24 VDC 15, 30, 75, 95, 115,150 CS-24PW 4890023 1 24 VDC 15, 30, 75, 95, 115, 150 CHS Series 24 Volt Ceiling Mount Selectable Horn/Strobe Model Number Part Number Nominal Voltage Candela Reverberant dBA @ 10 ft. per ANSI/UL 464 In Anechoic Room dBA @ 10 ft. CHS-24R 4890040 24 VDC 15, 30, 75, 95, 115, 150 81-86 90 CHS-24W 4890041 24 VDC 15, 30, 75, 95, 115, 150 81-86 90 CHS-24PR 4890042 24 VDC 1 15, 30, 75, 95, 115, 150 1 81-86 1 90 CHS-24PW 4890043 24 VDC 1 15, 30, 75, 95, 115, 150 1 81-86 1 90 Model Designations: C = Ceiling Mount S = Strobe HS = Horn/Strobe R = Red Faceplate W = White Faceplate All units are available in plain (no lettering). Plain units are non -returnable. CS24 Product Strobe Current Ratings (mA) Candela 15 cd 30 cd 75 cd 95 cd 115 cd 150 cd 24 VDC (16-33 Volts) 24 VDC 72 mA 101 mA 167 mA 200 mA 214 mA 286 mA UL Maxi 120 mA 120 mA 1 200 mA 220 mA 290 mA 1 321 mA CHS24 Product Horn Decibel and Current Ratings (mA) Horn Mode Minimum dBA @ 10 ft. per ANSI/UL 464 (HIGH) Minimum dBA @ 10 ft. per ANSI/UL 464 (LOW) Regulated 24 VDC Max. Operating @ High Setting (mA) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical 81 73* 22 Continuous 2400Hz 86 78 23 Continuous Mechanical 84 76 22 NOTES: • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual. • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. • Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). • RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 • Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. #8830051 - REV A PAGE 3 OF 4 06/13 Page 23 of 28 CS/CHS OF POTTER SELECTABLE CANDELA The Symbol of Protection CEILING MOUNT Architect & Engineering Specifications The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSFUL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification appliance shall also be listed with the California State Fire Marshal (CSFM). The notification appliance (combination audible/visible units and audible units only) shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. Conventional CS/CHS Series Wiring Diagrams UL Listed Control Signal Panel S+ S+ S- H+ H- Supervised 0 0 Signal Circuit UL Listed Control Sig�H+H- Panel s- Supervised Signal Circuit END IS LINE RESISTOR Signal I I Signal END OF LINE RESISTOR END OF LINE RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. PotterElectric Signal Company, LLC • St. Louis, MO 63042 USA- CustService: 866-572-3005 -Tech Support: 866-956-0988 •Canada888-882-1833 •www.pottersignal.com PRINTED IN USA MFG. 98830051 - REV A PAGE 4 OF 4 06/13 Page 24 of 28 (E)POTTER The Symbol of Protection Features • Fixed 75cd strobe • Includes the WPBB surface -mount (standard) or WPLPBB Low Profile (LP) enclosure • WPBB/LP made of clear Lexan® - provides maximum visibility and reliability, allowing full 75cd output • Super -Slide® Bracket — Ease of supervision testing • Checkmate® - Instant voltage verification • Synchronize strobe and/or horn with AVSM module • Switch selection for high/low dBA • Switch for chime, whoop, mechanical, and 2400Hz tone • Input terminals accept 18 to 12 AWG • Switch for continuous or temporal 3 tone (not available on whoop) • Tamperproof re-entrant grill • 5 year warranty Application The S/HS-WP Series Outdoor Signals are wall mount, low profile strobes and horn/strobes that offer dependable audible and visual alarms for warning and emergency notification in outdoor locations. Description The S/HS-WP Series Outdoor Signals are 24VDC strobes and horn/ strobes equipped with a fixed 75 candela strobe. This series of outdoor signals are available in two different versions. The standard version includes a surface -mount back box (WPBB) to install directly on a wall. The Low Profile (LP) versions includes a low profile back box (WPLPBB) designed to be installed on a flush - mounted electrical box. The weatherproof enclosure is made of clear Lexan® which provides maximum visibility and reliability for effective visible signaling, allowing full 75cd output. The S/HS-WP series strobe has a minimal operating current and a minimum flash rate of 1Hz regardless of input voltage. The strobe is synchronized using Gentex sync. protocol or the AVSM Sync. Module. The S/HS-WP Series is equipped with a universal 4" mounting bracket which incorporates the popular Super -Slide® feature that allows the installer to easily pre -wire the system and test for supervision. The product also features a locking mechanism that secures the signal to the bracket without showing any screws and the Checkmate® - Instant Voltage Verification Feature which allows the installer to check the voltage drop, current draw, and match against the blue print. S/HS-WP Series Outdoor Strobes and Horn/Strobes �v 1W LP Version Standard MNAUNs Ul LISTED S3247 Product Listings • ANSI/UL 464 and 1638 • Complies with American with Disabilities Act (ADA) • Complies with IBC / IFC / IRC Technical Specifications Operating Voltage Nominal 24VDC (16-33VDC) Operating -31°F - 150°F (-35° - 66°C) Temperature LP Version - 5.75" H x 4.75" W x 3.25" D Dimensions Standard - 5.75" H x 4.75" W x 4.18"D Wiring Connections Terminals accept 18 - 12 AWG LP Version — Single gang, double gang, or 4" square back box Mounting Standard Version - Surface mount back box included Shipping Weight 2.05 lbs. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com 8830057 - REV B • 3/15 PAGE 1 OF 4 Page 25 of 28 (E)POTTER The Symbol of Protection S-24-WP, 75 Candela, Outdoor Strobe Includes Standard or LP Enclosure Model Number Stock Number Body Color WP Enclosure S-24WR-WP 4890050 Red Standard S-24WW-WP 4890051 Off -White Standard S-24PWR-WP 4890052 Red -Plain Standard S-24PWW-WP 4890053 Off -White -Plain Standard SLP-24WR-WP 4890054 Red Low Profile SLP-24WW-WP 4890055 Off -White Low Profile SLP-24PWR-WP 1 4890056 Red -Plain Low Profile SLP-24PWW-WP 1 4890057 Off -White -Plain Low Profile S/HS-WP Series Outdoor Strobes and Horn/Strobes Model Designations "W "= WallMount "R" = Red Face Plate "W "=Off - White Face Plate "P"= Plain (Note: Plain units are non -returnable) "LP"= Low Profile (WPLPBB Enclosure) Strobe Current Ratings Candela 75 cd 24 VDC 112 mA UL Max 170 mA NOTE: ForunfilteredFWRratings, see installation manual. HS-24-WP Series, 75 Candela, Outdoor Horn /Strobe Includes Standard or LP Enclosure Model Number Stock Number Body Color Reverberant dBA at 10', per ANSI/UL 464 In Anechoic Room dBA at 10' WP Enclosure HS-24WR-WP 4890060 Red 70-82 100 Standard HS-24WW-WP 4890061 Off -White 70-82 100 Standard HS-24PWR-WP 4890062 Red -Plain 70-82 100 Standard HS-24PWW-WP 4890063 Off -White -Plain 70-82 100 Standard HSLP-24WR 4890064 Red 70-82 100 Low Profile HSLP-24WW 4890065 Off -White 70-82 100 Low Profile HSLP-24PWR 4890066 Red -Plain 70-82 100 1 Low Profile HSLP-24PWW 4890067 Off -White -Plain 70-82 100 1 Low Profile Horn Decibel and Current Ratings Horn Setting Minimum dBA at 10', Per UL 464 (HIGH) Minimum dBA at 10', Per UL 464 (LOW) Regulated 24VDC Max. Operating Current, at High Setting (mA) Temporal 3 2400Hz 78 71 * 28 Temporal 3 Mechanical 76 70* 25 Temporal 3 Chime 70* 66* 15 Continuous 2400Hz 81 74* 28 Continuous Mechanical 80 72* 25 Continuous Chime 1 70* 66* 15 Whoop 1 82 1 69* 56 *Operating the horn in this mode at this voltage will result in not meeting the minimumANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode). Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com 8830057 - REV B • 3/15 PAGE 2 OF 4 Page 26 of 28 (E)POTTER The Symbol of Protection Tone Switch Locations Tone Switch Position 3 4 5 Mechanical Temporal 3 ON ON ON Mechanical - Continuous OFF ON ON 2400Hz - Temporal 3 ON OFF ON 2400Hz - Continuous OFF OFF ON Chime - Temporal 3 ON ON OFF Chime - Continuous OFF ON OFF Whoop ON OFF OFF Whoop OFF OFF OFF NOTES. - Switch Positions 1 and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON = HIGH dBA • Switch Position 6 OFF = LOW dBA Super Slide® Mounting Bracket 1 Allows the installer to pre -wire the system, test for system - supervision, remove the signal head until occupancy, switch out signals without changing mounting brackets and has locking edge connector for snap -in -place installation. t( Mounting Outdoor Enclosure Super Slide® Mounting Plate: Mounts to WPBB Outdoor Enclosure S/HS-WP Series Outdoor Strobes and Horn/Strobes Checkmate® Instant Voltage Verification It is often necessary to confirm the voltage drop along the line of devices. The access holes are provided in the back of the terminal block to allow the voltage to be measured directly without removing the device. Typically, this would be done at the end of the line to confirm design criteria. Most measurements will be taken using the S+ and S- locations although access is provided to other locations. NOTE. Care should be taken to not short the test probes. Super Slide® Mounting Plate: Mounts to WLPBB Outdoor Enclosure Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com 8830057 - REV B • 3/15 PAGE 3 OF 4 Page 27 of 28 (E)POTTER The Symbol of Protection UL Listed Control Panel Signal S+ S+ S- H+ H- Supervised 0 0 Signal Circuit n S/HS-WP Series Outdoor Strobes and Horn/Strobes Wiring Diagrams UL Listed Control Signal Panel S- H+ H- Supervised 0 0 Signal Circuit END LINE RESISTOR \ + Signal I I Signal END OF LINE RESISTOR END OF LINE RESISTOR NOTES. - All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. Architect and Engineering Specifications The audible and/or visible signal shall be Potter S/HS-WP Outdoor Series or approved equal and shall be listed by Underwriters Laboratories Inc. perANSF UL 1638 and/or ANSFUL 464. The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 112mA or less for the 75Cd strobe circuit. The appliance shall also be capable of meeting the candela requirements of the ADA (75cd). The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power for 24 volt models. The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. The unit shall also be able to verify voltage at the unit without removing unit. The appliance has extended temperature range of -31' to 150DF (-35° to 66' C). The appliance shall satisfy virtually all outdoor and severe environment applications. The WPBB enclosure includes a gasket that must be inserted between the box and mounting bracket. There are drain holes in the back box to allow for drainage, the seal on the WPBB enclosure is not water tight. The WPLPBB enclosure includes a weather seal for mounting to wall and intended for use with universal electrical box. To allow for drainage, bottom edge of enclosure is not water tight. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com iso soo3:zoos DESIGNING, MANUFACTURING, & DISTRIBUTING QUALITY SYSTEMS 8830057 - REV B • 3/15 PAGE 4 OF 4 Page 28 of 28