REVIEWED RESUB 1-BLD2023-1489+Mechanical_System_Calculations+4.8.2024_6.03.06_PM+4184068RESUB Arby's #769
Apr 09 2024
CITY OF Unit # 12 6 3 49
DEVELOPMENT SERVICES
DEPARTMENT
RTTMENT
Edmonds, Washington
BLD2024-1489
Structural Design Calculations
REVIEWED
BY
CITY OF EDMONDS
04/01/2024
Prepared For:
ICS / Everidge
Andover, KS
PEC Project No.:
248001-019
Prepared by:
Tyler Brown
Reviewed by:
Zachary Bowden, P.E.
License Number: 22007998
Date:
March 28`h, 2024
303 SOUTH TOPEKA WICHITA, KS 67202 316-262-2691 www.pecl.com
INDEX
DESCRIPTION PAGE
Project Overview 1- 1
Parameters 1 - 1
Design Criteria 1 - 1
Structural Calculations 2 - 18
Drawings 19 - 19
Appendix 20 - 26
These calculations, prepared by Professional Engineering Consultants, P.A. for this project, are the
exclusive property of Professional Engineering Consultants, P.A. Their use or publication shall be
restricted for use solely with respect to the specific project noted above. These calculations are
provided for the project noted above for reference only. The civil engineer or structural engineer of
record for each specific project shall prepare, sign, and seal their own set of calculations. These
calculations are not to be used unless signed and sealed by a structural engineer in the employment
of Professional Engineering Consultants, P.A. Professional Engineering Consultants, P.A. shall be
deemed the author of these documents and shall retain all common law, statutory and other reserved
rights including copyright. These calculations shall not be used in part or in whole by the owner or
others for other projects, additions to this project, or for completion of this project by others except
by agreement in writing and with appropriate compensation to Professional Engineering
Consultants, P.A.
PEC Design Calculations
PROJECT OVERVIEW:
The following calculations will analyze International Cold Storage (ICS) unit 126349 for Arby's
#769. Units are comprised of premanufactured UL rated wall assemblies tested and certified by
ICS. The allowable capacities of the unit's members and connections are from the tested report
PFS Corporation No. 09-92. The respective sheets from this report are attached in the appendix.
Calculations were performed to determine the general global loads on the unit and adequacy of
the members and connections.
PARAMETERS:
The dimensions for unit 126349 were given at 10'-0" by 19'-0" with a peak height of 9'-2" per
drawings provided by ICS. The location of the project has been given as 8425 244t" St. SW
Edmonds, Washington 98026. Wall and roof assemblies consist of urethane foam insulation
with .040 aluminum or 26 GA. G90 steel finish with the addition of wood interior stud framing.
The foundations are to be designed by others.
DESIGN CRITERIA:
Applicable Codes/Criteria:
- ASCE 7-16: Minimum Design Loads for Buildings and Other Structures
- International Building Code 2018
- Risk Category: II
Wind Loads:
- Exposure Category: C
- Ultimate Wind Speed: 110 MPH (PER LOCAL JURISDICTION)
- Internal Pressure Coefficient = ± 0.18
Snow Loads:
- Ground Snow Loads: 25 PSF (PER LOCAL JURISDICTION)
- Flat Roof Snow Load:25 PSF (PER LOCAL JURISDICTION)
- Snow Importance Factor, I = 1.0
- Snow Thermal Factor, Ct = 1.3
- Snow Exposure Factor, Ce = 0.9
Seismic Loads:
- Site Class: D (Default)
- Seismic Design Category: D
- Seismic Importance Factor: 1.0
- SS = 1.277, S1= 0.447 , Sps = 1.022
- Reference Seismic Analysis in calculations
Connection and Member Allowable Capacities:
- PFS Corporation Test Report No. 09-92
►SCE
AMERICAN SOCIETY OF CIVIL ENGINEERS
Address:
8425 244th St SW
Edmonds, Washington
98026
ASCE Hazards Report
Standard: ASCE/SE17-16 Latitude: 47.778034
Risk Category: II Longitude:-122.347194
Soil Class: D - Default (see Elevation: 428.92247168483624 ft
Section 11.4.3) (NAVD 88)
c TJ
o� IiaRx
2491h 51 S'J,
a'
u a
vy.
3
11 2{rn Ih Sl
Z
Z
N 19,'llSt
G
EN198th5
z
Wind
2J8h1 St 55V S
Lti ,
24)th St SW _
79 m`
242nr1 St SW a :�
L
Edm°nys•w �
Aurora R
Auora Vibgr
Vdkq�
Aurora
Vrlk.pe
T.— '
C—W, N 2^Gth St
Etho
1 N tJith 51
N 1981h St
yak-
N 1951h St
Fmt aimbk
I I I _ .
[dmonds
\
' E.4�Mrx�
Mr. i.rlbkr
%
�lu�
lip
r�ll ii�
InJnr[b
i
'
hart
Y.li u•.J�I�
Green
Kirkland R"11
"-
talo
HainM l9e
_•-- ..
't��. cap
ISIJrvY
Results:
Ultimate Wind Speed = 110 mph (Per
V
Speed 98 Vmph Local Jurisdiction)
ar mp
25-year MRI 74 Vmph
50-year MRI 78 Vmph
100-year MRI 83 Vmph
Data Source: ASCE/SEI 7-16, Fig. 26.5-1 B and Figs. CC.2-1—CC.2-4, and Section 26.5.2
Date Accessed: Thu Feb 15 2024
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear
interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds
correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability =
0.00143, MRI = 700 years).
Site is not in a hurricane -prone region as defined in ASCE/SEI 7-16 Section 26.2.
hftps:Hascehazardtool.org/ Page 1 of 3 Thu Feb 15 2024
2
gsi�E*
AMERICAN SOCIETY OF CIVIL ENGINEERS
Seismic
Site Soil Class: D - Default (see Section 11.4.3)
Results:
Ss :
1.277
Sp, :
N/A
S,
0.447
T L :
6
Fa
1.2
PGA:
0.542
Fv
N/A
PGA M :
0.65
SMs :
1.532
FPGA
1.2
SM,
N/A
le
1
SIDS :
1.021
C,
1.355
Ground motion hazard analysis may be required. See ASCE/SEI
7-16 Section 11.4.8.
Data Accessed:
Thu Feb 15 2024
Date Source:
USGS Seismic Design
Maps
hftps:Hascehazardtool.org/ Page 2 of 3 Thu Feb 15 2024
3
ASCE®
AMERICAN SOCIETY OF CIVIL ENGINEERS
Snow
. . . . . . 2
Grun So Lad,pg 01/ft
Mapped levatlon: 428.9 ft
Data Source:
Date Accessed: Thu Feb 15 2024
Ground Snow Load = 25 PSF (Per Local
Jurisdiction)
Statutory requirements of the Authority Having Jurisdiction are not included.
Snow load values are mapped to a 0.5 mile resolution. This resolution can
create a mismatch between the mapped elevation and the site -specific
elevation in topographically complex areas. Engineers should consult the local
authority having jurisdiction in locations where the reported `elevation' and
`mapped elevation' differ significantly from each other.
The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided "as is" and without warranties of any
kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or
has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable
sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or
quality of any data provided herein. Any third -party links provided by this Tool should not be construed as an endorsement, affiliation,
relationship, or sponsorship of such third -party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent
professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such
professionals in interpreting and applying the contents of this Tool or the ASCE standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors,
employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential
damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by
law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data
provided by the ASCE Hazard Tool.
https://ascehazardtool.org/ Page 3 of 3 Thu Feb 15 2024
4
BUILDING CODES & DESIGN INFO
Building Codes adopted by the City of Edmonds as of 2/1/2021 as amended by the State of
Washington Building Code Council (SBCC).
Adoption of the 2021 Codes and Amendments has been delayed by the state until March 15,
2024.
See link below for amendments specific to the Edmonds Community Development Code (ECDC).
2018 International Building Code
2018 International Residential Code
2018 International Mechanical Code
2018 International Fuel Gas Code
2018 International Fire Code
2018 International Existing Building
Code
2018 International Property
Maintenance Code
2018 ICC Performance Code
2018 Washington State Energy Code
• Residential
• Commercial
2018 Uniform Plumbing Code
Edmonds Community Development
Code Title 19
WA State Amendments to ICC Codes
as applicable
Electrical permits are administered
by WA State Dept. of L&I. The edition
of the National Electrical Code in
effect is that which is currently
adopted by the State.
The International Code Council promulgates
the International Codes that form the basis for
• building codes in Washington State and the City
of Edmonds. Visit their site to explore the
national code development process.
In Washington the State Building Code Council
is charged with the adoption and amendment of
• the International Codes. The council was
created by the State Legislature in 1974 and
given authority from RCW 19.27.
A good source of code books and other code
related publications is the Washington
Association of Building Officials Bookstore. You
• can also check the WABO website to check for
training opportunities, resources and to see
what is happening within the state building code
world.
The State Energy Codes. A very good source of
information on energy codes with some very
• useful publications is the WSU Energy
Extension.
5
DESIGN CRITERIA FOR EDMONDS
Min. Roof Snow Load 25 psf (non -reducible)
Ground Snow Load 25 psf (non -reducible)
Seismic Design Category D1(Residential) / Category D (Commercial)
Wind Speed 85 mph (Basic), 110mph (Ultimate)
Wind Exposure B,C & D (varies with location contact plan review staff)
Winter Design Temp 27 degrees F (-3 degree C)
Mean Annual Temp 50 degrees F (10 degree C)
O
6
❑®PEC
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.
CS2018 Ver 2018.03.17
JOB TITLE ICS - Edmonds, WA
126349
JOB No. 248001-019 SHEET NO.
CALCULATED BY TJB
CHECKED BY EMP
STRUCTURAL CALCULATIONS
FOR
ICS - Edmonds, WA
126349
248001-019
DATE 2/23/24
DATE
www.struware.com
7
Professional Engineering Consultants
303 S. Topeka
Wichita, Kansas
(316)262-2691
www.pecl.com
Code Search
Code: International Building Code 2018
Occupancy:
Occupancy Group = S Storage
Risk Category & Importance Factors:
Risk Category = II
Wind factor = 1.00
Snow factor = 1.00
Seismic factor = 1.00
Type of Construction:
Fire Rating:
Roof = 0.0 hr
Floor = 0.0 hr
Building Geometry:
Roof angle (0)
0.25 / 12 1.2 deg
Building length (L)
19.0 ft
Least width (B)
10.0 ft
Mean Roof Ht (h)
9.2 ft
Parapet ht above grd
0.0 ft
Minimum parapet ht
0.0 ft
JOB TITLE ICS - Edmonds. WA
126349
JOB NO. 24bUU"I-UI
CALCULATED By TJB
CHECKED By EMP
Live Loads:
Roof 0 to 200 sf: 20 psf
200 to 600 sf: 24 - 0.02Area, but not less than 12 psf
over 600 sf: 12 psf
SHEET NO.
DATE 2/23/24
DATE
www.struware.com
Professional Engineering Consultants
303 S. Topeka
Wichita, Kansas
(316)262-2691
www.pecl.com
Wind Loads: ASCE 7- 16
Ultimate Wind Speed
110 mph
Nominal Wind Speed
85.2 mph
Risk Category
II
Exposure Category
C
Enclosure Classif.
Enclosed Building
Internal pressure
+/-0.18
Directionality (Kd)
0.85
Kh case 1
0.849
Kh case 2
0.849
Type of roof
Monoslope
Topographic Factor (Kzt)
Topography
Flat
Hill Height (H)
80.0 ft
Half Hill Length (Lh)
100.0 ft
Actual H/Lh =
0.80
Use H/Lh =
0.50
Modified Lh =
160.0 ft
From top of crest: x =
50.0 ft
Bldg up/down wind?
downwind
H/Lh= 0.50
Ki =
0.000
x/Lh = 0.31
K2 =
0.792
z/Lh = 0.09
K3 =
1.000
At Mean Roof Ht:
Kzt = (1+KjK2K3)12
=
1.00
Gust Effect Factor
h = 9.2 ft
B = 10.0 ft
/z (0.6h) = 15.0 ft
Rigid
Structure
e =
0.20
f =
500 ft
Zmin =
15 ft
c =
0.20
90, 9v =
3.4
Lz =
427.1 ft
Q =
0.96
Iz =
0.23
G =
0.90 use G = 0.85
JOB TITLE ICS - Edmonds, WA
126349
JOB NO. 248UU1-U19
CALCULATED BY TJB
CHECKED BY EMP
SHEET NO.
DATE 2/23/24
DATE
I
V(Z)
Speed-up
V(Z) x(up-aind) -= x(downwind)
H!2 rH
' Lh Hl2
V(z)
Z -
Speed-up
V(Z) x(upwind) x(downwind)
�- HJ2
- H
2D RIDGE or 3D AXISYMMETRICAL HILL
Flexible structure if natural frequency < 1 Hz (T > 1 second).
If building h/B>4 then may be flexible and should be investigated.
h/B = 0.92 Rigid structure (low rise bldg)
G = 0.85 Using rigid structure default
Flexible or Dvnamicaliv Sensitive Structure
34icy (n,) =
0.0 Hz
Damping ratio ((3) =
0
/b =
0.65
/a =
0.15
Vz =
92.9
N 1 =
0.00
Kn =
0.000
Rh =
28.282 n = 0.000
RB =
28.282 n = 0.000
RL =
28.282 n = 0.000
9R =
0.000
R =
0.000
Gf =
0.000
h = 9.2 ft
9
Professional Engineering Consultants
303 S. Topeka
Wichita, Kansas
(316)262-2691
www.pecl.com
JOB TITLE ICS - Edmonds, WA
126349
JOB No. 248001-019
CALCULATED BY TJB
CHECKED BY EMP
Wind Loads - MWFRS all h (Except for Open Buildings)
Kh (case 2) = 0.85 h = 9.2 ft GCpi = +/-0.18
Base pressure (qh) = 22.4 psf ridge ht = 9.3 ft G = 0.85
Roof Angle (0) = 1.2 deg L = 19.0 ft qi = qh
Roof tributary area - (h/2)*L: 87 sf B = 10.0 ft
(h/2)*B: 46 sf
Ultimate Wind Surface Pressures (nsf)
SHEET NO.
DATE 2/23/24
DATE
Surface
Wind Normal to Ridge
B/L = 0.53 h/L = 0.92
Wind Parallel to Ridge
L/B = 1.90 h/L = 0.48
Cp ghGCP w/+q;GCP; w/-ghGCpi
Dist.* Cp ghGCP w/ +q;GCP; w/-ghGCpi
Windward Wall (WW)
0.80
15.2
see table below
0.80
15.2
see table below
Leeward Wall (LW)
-0.50
-9.5
-13.5
-5.5
-0.32
-6.1
-10.1 -2.1
Side Wall (SW)
-0.70
-13.3
-17.3
-9.3
-0.70
-13.3
-17.3 -9.3
Leeward Roof (LR)
**
Included in windward
roof
Neg Windward Roof: 0 to h/2*
-1.23
-23.4
-27.5
-19.4
0 to h/2*
-0.90
-17.1
-21.1 -13.1
h/2 to h*
-0.73
-13.9
-18.0
-9.9
h/2 to h*
-0.90
-17.1
-21.1 -13.1
h to 2h*
-0.67
-12.67
-16.69
-8.64
h to 2h*
-0.50
-9.5
-13.5 -5.5
> 2h*
-0.30
-5.7
-9.7 -1.7
Pos/min windward roof press.
-0.18
-3.4
-7.4
0.6
Min press.
-0.18
-3.4
-7.4 0.6
-KooT angle < -iu aegrees. i nereTore, ieewara roof 'horizontai aistance Trom winowara eage
is included in windward roof pressure zones.
For monoslope roofs, entire roof surface is
either windward or leeward surface.
Windward Wall Pressures at 'Y' (psf) Combined WW + LW
Windward Wall Normal I Parallel LR
z Kz Kzt gzGCP w/+q;GCP; w/-qhGCpi to Ridge to Ridge /
h= 0 to 15' 0.85 1.00 15.2 11.2 19.2 24.7 21.3 SWj
_LW
NOTE:
See figure in ASCE7 for the application of full and partial loading
of the above wind pressures. There are 4 different loading cases.
Parapet
z Kz Kzt qp (psf)
0.0 ft 0.85 1.00 0.0
Windward parapet: 0.0 psf (GCpn = +1.5)
Leeward parapet: 0.0 psf (GCpn = -1.0)
Windward roof overhangs ( add to windward roof pressure) : 15.2 psf (upward)
SW
\W
L �
wuro
G`DMECTION
WRID NORMAL TO RIDGE
WR
WR
fWR LW
W
1--WW
& v
wnaD
DIRECTION
WOJD PARALLEL 70 RIDGE
LW
IVMALwnML kIXMG
10
I
Professional Engineering Consultants JOB TITLE ICS - Edmonds, WA
303 S.Topeka 126349
Wichita, Kansas JOB No. 248001-019 SHEET NO.
(316) 262-2691 CALCULATED BY TJB DATE 2/23/24
www.pecl.com CHECKED BY EMP DATE
Wind Loads - Comaonents & Claddina : h <_ 60'
Kh (case 1) = 0.85
h =
9.2 ft 0.2h = 1.8 ft
Base pressure (qh) = 22.4 psf
0.6h =
5.5 ft
Minimum parapet ht = 0.0 ft
GCpi =
+/-0.18
Roof Angle (0) = 1.2 deg
qi = qh =
22.4 psf
Type of roof = Monoslope
Roof
Area
Negative Zone 1
Negative Zone 1'
Negative Zone 2
Negative Zone 3
Positive All Zones
Overhang Zone 1&1'
Overhang Zone 2
Overhang Zone 3
Parapet
qp = 0.0 psf
Walls
Ultimate Wind Pressures
Surface Pressure (psf)
10 sf
20 sf
50 sf
100 sf
200 sf
350 sf
500 sf
1000 sf
-42
-39.2
-35.6
-32.8
-30.0
-27.8
-26.4
-26.4
-24.1
-24.1
-24.1
-24.1
-20.8
-18.1
-16.3
-16.0
-55.4
-51.9
-47.2
-43.6
-40.0
-37.1
-35.3
-35.3
-75.5
-68.4
-59
-51.9
-44.7
-39.0
-35.3
-35.3
16
16
16
16
16.0
16.0
16.0
16.0
-38
-37.3
-36.4
-35.8
-30.0
-25.3
-22.4
-22.4
-51.4
-46.7
-40.4
-35.6
-30.9
-27.0
-24.6
-24.6
-71.5
-63.2
-52.2
-43.9
-35.6
-28.9
-24.6
-24.6
Uverhang pressures in the table above assume an Internal pressure coettiaent (Vcpl) of 0.0
Overhang soffit pressure equals adj wall pressure (which includes internal pressure of 4 psf)
Solid Parapet Pressure
u ace Pressure (psf)
10 s
20 s
50 s
100 s
200 s
500 s
one
Zone 3 :
0.0
0.0
0.0
0.0
0.0
.
0.0
ASE B : Interior zone :
Corner zone :
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
GCp +/- GCpi
Surface Pressure at h
s
s
s
5 s
s
s
s
5 s
1.44
1.08
1.12
0.92
1.03
0.87
-0.90
0.81
-44.3
24.1
-25.1
20.6
22. 1
19.5
-20.1
18.1
Area 10
Negative Zone 4
Negative Zone 5
Positive Zone 4 & 5
Note: GCp reduced by 10% due to roof angle <= 10 deg
Userinput
16 sf
300 sf
-40.1
-28.4
-24.1
-18.8
-53.0
-37.9
-70.7
-40.6
16.0
16.0
-37.5
-26.6
-48.2
-28.1
65.9
1 -30.7
Userinput
16s
0.0
0.0
0.0
Userinput
74 s
s
-26.0
21.1
-22.9
19.5
11
Professional Engineering Consultants JOB TITLE ICS - Edmonds, WA
303 S.Topeka 126349
Wichita, Kansas JOB No. 248001-019 SHEET NO.
(316) 262-2691 CALCULATED BY TJB DATE 2/23/24
www.pecl.com CHECKED BY EMP DATE
Location of C&C Wind Pressure Zones - ASCE 7-16
> O G
^ � I
I > .c I
I I
I I ® I
l 4 I I I
I I I
I t
I I
Roofs w/ 0 <_ 10'
and all walls
h>60'
I I
_ I I
I
O
I I
I
—
I O I
I I
I I
I
Monoslope roofs
10°<0<_30'
h <_ 60' & alt design h<90'
a
Walls h <_ 60'
& alt design h<90'
Multispan Gable &
Gable 7° < 0 <_ 45'
Stepped roofs 0 <_ 3°
h <_ 60' & alt design h<90'
N Mit % Il
C
2
I I I I
I I
2 1 1 1Q' I 2
I I I I
I I
I
L J
Gable, Sawtooth and
Multispan Gable 0 <_ 7 degrees &
Monoslope <_ 3 degrees
h <_ 60' & alt design h<90'
Hip 7° < 0 <_ 27'
Monoslope roofs
3°<0<_10'
h <_ 60' & alt design h<90'
Sawtooth 10' < 0 <_ 45'
h <_ 60' & alt design h<90'
12
1
Professional Engineering Consultants
303 S. Topeka
Wichita, Kansas
(316)262-2691
www.pecl.com
Snow Loads: ASCE 7- 16
Roof slope = 1.2 deg
Horiz. eave to ridge dist (W) = 10.0 ft
Roof length parallel to ridge (L) = 19.0 ft
Type of Roof
Monoslope
Ground Snow Load Pg =
25.0 psf
Risk Category =
II
Importance Factor 1 =
1.0
Thermal Factor Ct =
1.30
Exposure Factor Ce =
0.9
Pf = 0.7*Ce*Ct*I*Pg =
20.5 psf
Unobstructed Slippery Surface
no
Sloped -roof Factor Cs =
1.00
Balanced Snow Load =
20.5 psf
Rain on Snow Surcharge Angle
0.20 deg
Code Maximum Rain Surcharge
5.0 psf
Rain on Snow Surcharge =
0.0 psf
Ps plus rain surcharge =
20.5 psf
Minimum Snow Load Pm =
20.0 psf
Uniform Roof Design Snow Load = 20.5 psf use 25.0
Windward Snow Drifts 1 - Aaainst walls. DaraDets. etc
Upwind fetch
lu =
80.0 ft
Projection height
h =
5.7 ft
Snow density
g =
17.3 pcf
Balanced snow height
hb =
1.19 ft
hd =
2.25 ft
he =
4.51 ft
he/hb >0.2 = 3.8
Therefore, design for drift
Drift height (hd)
=
2.25 ft
Drift width
w =
9.02 ft
Surcharge load:
pd = y*hd =
38.9 psf
Balanced Snow load:
=
20.5 psf
59.4 psf
Windward Snow Drifts 2 - Against walls, parapets, etc
Upwind fetch
lu =
160.0 ft
Projection height
h =
4.0 ft
Snow density
g =
17.3 pcf
Balanced snow height
hb =
1.19 ft
hd =
3.13 ft
he =
2.81 ft
he/hb >0.2 = 2.4
Therefore, design for drift
Drift height (hc)
=
2.81 ft
Drift width
w =
13.96 ft
Surcharge load:
pd = y*hd =
48.5 psf
Balanced Snow load:
=
20.5 psf
69.0 psf
JOB TITLE ICS - Edmonds, WA
126349
JOB NO. 248001-019 SHEET NO.
CALCULATED By TJB DATE 2/23/24
CHECKED By EMP DATE
Nominal Snow Forces
Near ground level surface balanced snow load = 25.0 psf
NOTE: Alternate spans of continuous beams
shall be loaded with half the design roof snow
load so as to produce the greatest possible
effect - see code for loading diagrams and
exceptions for gable roofs..
Lu
Note: If bottom of projection is at least 2 feet
above hb then snow drift is not required.
13
Professional Engineering Consultants JOB TITLE ICS - Edmonds, WA
303 S. Topeka 126349
Wichita, Kansas JOB No. 248001-019 SHEET NO.
(316) 262-2691 CALCULATED BY TJB DATE 2/23/24
www.pecl.com CHECKED BY EMP DATE
Seismic Loads: IBC 2018 Strength Level Forces
Risk Category : 11
Importance Factor (I) : 1.00
Site Class : D
Ss (0.2 sec) = 127.70 %g
S1 (1.0 sec) = 44.70 %g
Fa = 1.000 use 1.20 Sms = 1.532 SDs = 1.022 Design Category = D
Fv = 1.853 Sm1 = 0.828 SD1 = 0.552 Design Category = D
Seismic Design Category = D
Redundancy Coefficient p = 1.30
Number of Stories: 1
Structure Type: All other building system;
Horizontal Struct Irregularities:No plan Irregularity
Vertical Structural Irregularities:No vertical Irregularity
Flexible Diaphragms: Yes
Building System: Bearing Wall Systems
Seismic resisting system: Light frame walls with shear panels - all other materials
System Structural Height Limit: 35 ft
Actual Structural Height (hn) =9.3 ft
See ASCE7 Section 12.2.5 for exceptions and other system limitations
DESIGN COEFFICIENTS AND FACTOR
Response Modification Coefficient (R) = 2
Over -Strength Factor (Do) = 2
Deflection Amplification Factor (Cd) 2
SDs = 1.022
SD1 = 0.552
Seismic Load Effect (E) = Eh +/-Ev = p CE +/- 0.2SDS D = 1.3Qe +/- 0.204D QE = horizontal seismic force
Special Seismic Load Effect (Em) = Emh +/- Ev = Do GE +/- 0.2SDS D = 2Qe +/- 0.204D D = dead loac
PERMITTED ANALYTICAL PROCEDURE:
Simplified Analysis - Use Equivalent Lateral Force Analysis
Equivalent Lateral -Force Analysis - Permittec
Building period coef. (CT) =
0.020
Approx fundamental period (Ta)
rh
User calculated fundamental period (T) _
Long Period Transition Period (TL) =
ASCE7 map =
Seismic response coef. (Cs) =
SDSI/R =
need not exceed Cs =
Shc I /RT =
but not less than Cs =
0.044Sdsl =
USE Cs =
Cu = 1.40
0.107 sec x= 0.75 Tmax = CuTa = 0.149
sec Use T = 0.107
6
0.511
2.592
0.045
0.511
Design Base Shear V = 0.511 W
Model & Seismic Response Analysis - Permitted (see code for procedure)
ALLOWABLE STORY DRIFT
Structure Type: All other structures
Allowable story drift Aa = 0.020hsx where hsx is the story height below level x
14
0 PROJECT: International Cold Storage DATE: 2/23/2024
Prrfe tonal Engr'neen)) q Consult oas, ed- JOB # : 248001-019 DESIGNER: TJ13
303 S. IOPLKA • W'1(HI IA, KS 6/202. 316-262-2691 - FAX 3I6-262-3003 DESCRIPTION: 10'X19'-0"X9'-2" CHECKER: EMP
wwa-.pec Lcom • desicgners(Ope: Lmnr Edmonds, WA
LOADS:
Note: Reference attached struware for values and coefficients
UNIT PARAMETERS:
Width: 10 Feet
Length: 19 Feet
leak Height: 9 Feet
0_Inches 10.00 Feet
0_Inches 19.00 Feet
2 Inches 1 9.17 Feet
LATERAL ANAYLSIS:
Seismic Analysis: (Equivalent Lateral Force Procedure)
Seismic Base Shear(s):
V=CSW
_ SoS * 4 = 0,511 W = Weight of Structure = 1222.7 #
CS R
SUs = 1.022 DLRoof= 760.00 #
le 1.0 DLWa11= 212.67 #
R= 2.0 DLRTU= 250 #
p = 1.3
Eh=pV=pCSW=1 812.22 1#
E = 0.2SoSD =1 249.91 #
Wind Load Analysis: (Idealized as Flexible Diaphragm/Single Span)
Wind Load Base Shear(s):
WL= 110 MPH (Ultimate) WW+LW= 24.7 PSF
VWL = (WL + LW) (Height)(Length/Width)
VWL1= 2264.17 # VWL1Roof= 1132.08 # (Governs)
VWL2= 4301.92 # VWL2Roof= 2150.96 # (Governs)
Load Map 0) Roof:
- Ri (Vi)
ViRoof (WO 1 R2 (V2) ICS Unit 1 R2 (V2)
Rl (Vl)
Roof Reactions:
V2Roof#
V2Roof= #
RlRoof= 566.04 #
R2Roof= 1 1075.48 #
T V2Roof (W2)
w1Roof2TJ
plf
wzRoof= plf
V1 Roof= 29.79 plf
V2Roof= 107.55 plf
15
0 PROJECT: International Cold Storage DATE: 2/23/24
Profear¢onal Engineering Consultants, e.�. JOB # : 248001-019 DESIGNER: TJB
303 S. TOPEKA • WICHITA, KS 67202. 316262-2691 • FAX 316-262-3003 DESCRIPTION: 10'X19'-0"X9'-2" CHECKER: EMP
wmv.peclxom • doi0nersQpetl.cem Edmonds, WA
LOADS:
Reference attached struware for values and coefficients
UNIT PARAMETERS:
Width: 10.00 Feet
Length: 19.00 Feet
leak Height: 9.17 Feet
MEMBER CHECKS:
Note: Allowable capacities are per PFS Corporation Test Report No. 09-92
Roof Chord: (Idealized as Simple Span)
Tension/Compression Check
Wl 12
Mi1 8 5.1 k-ft
Mu1
w212 ft = 1.4 k-
Mug = 8 0
T2/C2=M.2*0.6= 44.7 #
Allowable Tension Capacity: Ta = 5387 # > T1 & T2:. Adequate
Roof to Wall Connection:
Shear Check
V1 Roof= 17.9 plf (Factored)
V1 Roof= 64.5 plf (Factored)
Allowable Shear Capacity: ve = 471 plf > v1 & V2 :. Adequate
Roof Joists:
Check roof joist with reinforcing @ 24" on center, reference ICS drawing for construction details.
Additionally check worst case joist with roof mounted unit @ mid -span, per ICS layout.
Roof Joist Idealized:
Roof Joist Span= 24 in.
P W2
W1
L/ 2 ,
�L
P= 100 # (Roof Mounted Unit)
w1= DL =
5 psf
= 10.00 plf
LL =
20 psf
= 40.00 plf
WL =
16 psf
= 32.00 plf
SLb=
25 psf
= 50.00 plf
w2= SLd=
Reference attached snow drift loads
Note: Governing load combination per ASCE-7, DL + LL + W L for the loads noted above.
Maximum Shear = Vmax= 623 #
Maximum Moment = Mmaz 7=#-ft
Allowable roof loads per ICS Drawing/Report with roof reinforced at 24" on center.
wa= 212 psf x 24"/12" = 424 plf
V. _ 2120 # > VMAx :• Adequate
MQ = 5300 k-ft > Mm. :. Adequate
16
0
Profeacaonal Engineering Consultants, e.�.
M3 S. TOPEKA • WICHITA, KS 67202. 316 262-2691 • FAX 316-262-3003
wwn.pecl.com • doi0nersQpetl.cem
LOADS:
Reference attached struware for values and coefficients
UNIT PARAMETERS:
Width: 10.00 1 Feet
Length: 19.00 Feet
leak Height: 9.17 Feet
MEMBER CHECKS:
PROJECT: International Cold Storage
JOB # : 248001-019
DESCRIPTION: 10'X19'-0"X9'-2"
Edmonds. WA
Note: Allowable capacities are per PFS Corporation Test Report No. 09-92
Wall Panels:
Compression Check (Joist Reaction)
4 x 12 12.98 psi
Allowable Compression Capacity: Ca = 28.7 psi > C�
Lateral Pressure (Components and Cladding)
WC&C = 20.4 psf (factored)
Allowable ate pacity: A. = 69.1 psf > we :. Adequate
Shear Walls:
Reference attached shear wall calculations.
DATE: 2/23/24
DESIGNER: TJB
CHECKER: EMP
17
PROJECT 249001 -00: _TL9 - fa me&�, WA DATE ZI2-S ZON
PE
®ITEM S OC- . &LO3AL CA LCS By 71$
` SH F AZ WALL MPS?
EAZ \►Jf LL
h+q,_Z.,
h
Aq
Pc w CULT) L------- 4
- �iO L D DOWN L-tF.�sf try,
-�- _ �'F x 10, x 5' x 2'
U Iq ` %
jTu I,Uq}, + (0c"—+ ►,-�G`J *X.0.To, = 1,OS49
* f Lo DOwN CAPP►CI7y = TALL = 3,892" y `TQ AD�QyATF_
• S lit i; H R CHF C lC =
S.W. C APA C1 Ty = Ycru = �i� j Pt,F y Ya ADEQU AT>-
NXT r . 'S.W. 95 RXS
7ikE S.w• (14?AC1Ty WILL 3iL AD30QTi59 FFjz SFC.-flU%,) 93.3.S
A'D,)u%TMENT AC"Tog = 4.((
="�> YAI.i. ' q-4I PGA x D.(,b = 3l ! �cF ) YA ApF Q0 ATE
18
APRX LOCATION OF
FACTORY ROOF MTD
C❑NDENSING UNIT.
19'-7" ❑D SLAB
HEIGHTS
18'-7" _[�.] .......
36' FLUSH
INTERI❑R
RAMP
_ v
00
o �
O O
TIE DOWNS N.T.S.
AS INDICATED
x
PEC Design Calculations
I:1» NLI1111:1
20
ALLOWABLE STRESSES
DERIVED FROM TEST RESULTS
Per PFS Corporation Test Report No. #09-92
ALLOWABLE STRESSES
ROOF TO WALL STRESSES
P = A x Fy x 0.6
Fy (STEEL) = 35,000psi A = .1912 in2
Fy (ALUM.) = 22,000psi A = .5120 in2
P= .1912 x 35,000 x 0.6 = 4,015 lb
P = .5120 x 22,000 x 0.6 = 6,758 lb
ALLOWABLE TENSILE STRESS
Ptotal = 10,773 lb = 5387 lb
S. F. 2
ALLOWABLE COMPRESSIVE STRESS = 5387 lb
80 in2
WALL TO WALL STRESSES
P = A x Fy x 0.6
Fy (STEEL) = 35,000psi A = .508 in2
Fy (ALUM.) = 22,000psi A = .767 in 2
P = .508 x 35,000 x 0.6 = 10,668 lb
P = .767 x 22,000 x 0.6 = 10,124 lb
ALLOWABLE TENSILE STRESS
Ptotal = 20,792 lb = 10,396 lb
S. F. 2
ALLOWABLE COMPRESSIVE STRESS =
RACKING SHEAR STRESS
RACKING SHEAR STRESS
8°
A=.1912 in2
24 GA. STEEL
ROOF
.032 ALUM.
00 ,`o ¢ N
N A=.128 in
N c
Q p 00 J
• N Q
QC***4
0
4"
= 67 psi
III
A=.2550 in2 A=.508 in2
.032 ALUM 1 16 GA. GALV. STEEL
WALL
00 Q J .032 ALUM.
Lo
N C A=.1 8 in2
Q O O C4
• Q
N "o
N
O
• n
¢ 4"
10396 lb = 130 psi
80 in2
ULTIMATE SHEAR STRENGTH PER 3 TEST PANELS
PANEL #1 = 1152.8
Ib/ft
PANEL #2 = 1222.3
Ib/ft
PANEL #3 = 1314.5
Ib/ft
AVERAGE = 1152.8
+ 1222.3 + 1314.5 = 1230 Ib/ft
3
ALLOWABLE RACKING
SHEAR STRESS
1230 lbft =
615 Ib/ft
S. F. 2
ULTIMATE SHEAR STRENGTH PER 3 TEST PANELS
PANEL #1 = 719.4
Ib/ft
PANEL #2 = 576.9
Ib/ft
PANEL #3 = 767.0
Ib/ft
AVERAGE = 719.4 + 576.9 + 767.0 = 687 Ib/ft
3
ALLOWABLE RACKING
SHEAR STRESS
687 Ib ft =
343 Ib/ft
S. F. 2
22
ALLOWABLE STRESSES
COMPRESSIVE STRESS
4"
48"
0
i
COMPRESSIVE STRESS
4"
48"
BENDING STRESS OF WALL PANEL
AVERAGE TEST VALUE FOR 4'-0" WIDE X
9'-4" TALL WALL PANEL = 115psf
AVERAGE TEST VALUE FOR 4'-0" WIDE X
6'-10" TALL WALL PANEL = 206psf
ALLOWABLE MOMENT AND SHEAR ARE
CALCULATED FOR A 1'-0" STRIP OF PANEL.
w = 8 626 ft• Ib w = 2 352 lb)
LZ L
ULTIMATE LOADS PER 3 TEST PANELS
PANEL #1 = 13,881 lb
PANEL #2 = 10,772 lb
PANEL #3 = 11,838 lb
AVERAGE = 13,881 +10,772+11,838 = 12,164 lb
3
ALLOWABLE COMPRESSIVE STRESS
12,164 lb = 63.4 psi = 31.7 psi
(48")(4") S.F. 2
ULTIMATE LOADS PER 3 TEST PANELS
PANEL #1 = 12,598 lb
PANEL #2 = 10,213 lb
PANEL #3 = 9,999 lb
AVERAGE = 12,598+10,213+9,999 = 10,937 lb
3
ALLOWABLE COMPRESSIVE STRESS
10,937 lb = 57.0 psi = 28.5 psi
(48")(4") S.F. 2
M = w— 115 Ib/ft(9'-4"Z) _ 1252 ft• lb
B 8
ALLOWABLE BENDING MOMENT
M = 1252 ft•lb = 626 ft•Ib
S. F. 2
V = wl = 206 Ib/ft (6'-10") = 704 lb
2 2
ALLOWABLE SHEAR
V
704 lb
_
= — 352 Ib
S.F. 2
23
ALLOWABLE BENDING STRESSES
BENDING STRESS OF ROOF PANEL
AVERAGE TEST VALUE FOR 4'-0" WIDE X
8'-0" LONG ROOF PANEL = 144psf
AVERAGE TEST VALUE FOR 4'-0" WIDE X
14'-0" LONG ROOF PANEL = 53psf
ALLOWABLE MOMENT AND SHEAR ARE
CALCULATED FOR A 1'-0" STRIP OF PANEL.
w = 8 649 ft• lb) w = 2 288 lb)
L2 L
M — 8L2— 53 Ib/ft8(14'-0"2) _ 1298 ft• Ib
ALLOWABLE BENDING MOMENT
M = 1298 ft• Ib = 649 ft Ib
S. F. 2
V — wL = 144 Ib/ft (8'--n
2 2
ALLOWABLE SHEAR
V = 576 lb = 288 Ib
S. F. 2
BENDING STRESS OF FLOOR PANEL with SKIDS
= 576 lb
TESTING APPARATUS MAX. LOAD WAS 690 PSF.
NO VISIBLE DEFORMATION WAS WITNESSED.
ALLOWABLE FLOOR LOAD
690 psf
BENDING STRESS OF FLOOR PANEL with out SKIDS
LOADS PER 3 COMPRESSION TESTS
PANEL #1 = 21618 psf
PANEL #2 = 21790 psf
PANEL #3 = 23224 psf
AVERAGE = 21618+21790+23224 = 22,211 psf
3
ALLOWABLE FLOOR LOAD
22211 psf = 5552 psf
S. F. 4
24
ALLOWABLE STRESSES
UPLIFT AND SHEAR STRESS ON L2X2X1 /8 ANGLES
UPLIFT AVERAGE ULTIMATE LOAD = 3747 lb
SHEAR AVERAGE TEST VALUE = 6934 lb
ALLOWABLE UPLIFT LOAD
3747 lb = 1874 lb / 3 screws = 625 lb/screw
S. F. 2
ALLOWABLE SHEAR LOAD
6934 lb = 3467 lb / 3 screws = 1156 lb/screw
S. F. 2
ALLOWABLE SHEAR AND TENSION LOADS BASED ON TAPCON CAPACITY
(REFER TO ICC ES REPORT NO. ESR-1328)
ALLOWABLE SHEAR = 420 Ib/ft (FOR SINGLE ANGLE)
ALLOWABLE TENSION = 405 Ib/ft (FOR SINGLE ANGLE)
UPLIFT AND SHEAR STRESS ON L12 ANGLES
UPLIFT AVERAGE ULTIMATE LOAD = 4370 lb
SHEAR AVERAGE TEST VALUE = 4020 lb
ALLOWABLE UPLIFT LOAD
7784 lb = 3892 lb
S. F. 2
ALLOWABLE SHEAR LOAD
4569 lb = 2285 lb
S. F. 2
ALLOWABLE SHEAR LOADS BASED ON HILTI ANCHOR CAPACITY
(REFER TO ICC ES REPORT NO. ESR-1328)
ALLOWABLE SHEAR = 1596 Ib/ft
25
ALLOWABLE STRESSES
ALLOWABLE ROOF UPLIFT AT WALL CONNECTION
ALLOWABLE VALUES ARE BASED ON ICS—ES LEGACY
REPORT NUMBER ER-4780 FOR DRIL—FLEX AND
KWIK—FLEX SELF DRILLING FASTENERS. REFER TO
ANCHORAGE SECTION FOR LEGACY REPORT.
ALLOWABLE PULLOUT
.032 X 306 LBS = 78.3 LBS PER SCREW
.125
ALLOWABLE SHEAR
.032 X 587 LBS =
.125
150 LBS PER SCREW
SCREWS ARE PLACED AT 6"O.C.
ALLOWABLE PULLOUT
78.3 LBS x 2/FOOT
ALLOWABLE SHEAR
150 LBS x 2/FOOT
= 157 LB/FT
= 300 LB/FT
8°
ROOF
ROOF AND WALL ARE
CONNECTED TOGETHER WITH
#10-16 x % TEK SCREWS
AT 6" ON CENTER AT THESE
TWO LOCATIONS.
ALLOWABLE LOADS FOR STEEL C3X6.0 OPENING REINFORCING
FOR OPENING 6'-0" HIGH
Critical Stress = ip Z E = (pi')(29,000 ksij = 9.555 ksi
(L/r)Z (72"/.41611)2
Critical LOAD = 9.555 ksi (1.76 in 2)
= 16,816 Ibs / S.F. 2 = 8408 Ibs
FOR OPENING 6'-6" HIGH
Critical Stress = ip Z E = (pi2)(29,000 ksi = 8.141 ksi
(L/r)Z (78"/.41611)2
Critical LOAD = 8.141 ksi (1.76 in 2) = 14,328 Ibs / S.F. 2 = 7164 Ibs
FOR OPENING 7'-0" HIGH
Critical Stress = ip Z E _
(L/r)Z
(pi2)(29,000 ksi = 7.02 ksi
(84"/.41611)2
Critical LOAD = 7.02 ksi (1.76 in 2) = 12,355 Ibs / S.F. 2 = 6178 Ibs
26