APPROVED BLD RESUB 1-BLD2024-0288+Structural_CALCS .14.2024_2.41.22_PM+4324260P.O. Box 13423 Mill Creel, WA 98082 G52 �NGIN�Fi�✓ Civil d Structural Challenge d Success BLD2024-0288 TEL: (425) 408-2748 info@cs2engineers.com REVIEWED BY CITY OF EDMONDS Structural Calculations For Installation of Restaurant Type 1 Hood For Gyro Maker at Edmonds 10016 Edmonds Way #A Redmond, WA 98020 G✓2 LNG INEFi�✓ Prepared By: Sung U. Cho, P.E. Prepared Date: June 4, 2024 CS2 No.: 2425 RESUB Jun 14 2024 .� 6/O6/2024 G52 LNG/N��RS Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 Civil S Structural gy. S. Cho Date: 6/4/2024 Challenge � 5ucce5a Subject: Design Calculations Page: SCOPE OF WORK The scope of work includes the installation design for a Type I Hood system, including the Exhaust Fan (EF) and Make-up Air Unit (MAU) as shown in the mechanical drawings by Great Sun Corp, and an analysis of the existing roof structure. The existing roof structure consists of two different types of roof construction. It appears the roof was modified when the building was remodeled. The original roof structure was constructed with 4x6 T&G decking (actual size), and a portion of the roof has been modified with 2x8 wood joist members at 24" o.c., spanning between the 5-1/8"x16"glulam beams. The glulam beams are supported by steel columns at middle of the building. The existing roof structure information is shown in the structural drawing for reference. The existing roof is structurally adequate to handle the proposed new loading conditions. The type 1 hood will be laterally secured to the wall structure and gravitation loading will be tranferred to roof strucure and bearing wall in between the hoods. If the roof or floor has any other equipment installed other than this report shows, this report is invalid and the additional structural analysis needs to be performed. General contractor shall verify all existing dimensions, member sizes and conditions prior to commencing any work. All dimensions of existing condition shown on the reference are intended as guidelines only and must be verified infield. Any discrepancies shall be called to the attention of the architect or engineer and shall be resolved before proceeding with the work. Contractor shall provide temporary bracing for the structure and structural components until all final connections have been completed in accordance with the plans. Weight of Equipment (per GREAT SUN CORP.) Type I Hood: 10-ft = 651 Ibs (Eton -Aire "5424 EX-2-PSP-F") E.F.: EADU85H = 99 Ibs (Eton -Aire) for Kitchen Hood M.A.U.: EA-Al-G10 = 245 Ibs (Eton -Aire) for Kitchen Hood P.O. Box 13423 Page 1 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com Project: Gyro Maker Restaurant Hood Date: June 4, 2024 Location: Edmonds, WA Prepared By: S. Cho CS2 No: 2425 Page Design Calculation for Type 1 Kitchen Hood Installation P.O. Box 13423 Page 2 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com G52 �NGIN��RS Civil & Structural Challenge & 5uccea5 Type 1 Hood Loading ntt�— ALL AAOIaq MRLSD M OA GALYAIIQ[ OU�" ALL AwDLwG COMtIMlOU6 UOIr� 1'1011T 111RLD KTIIIC011 p1CT AhD t0000 srsTntn ®��� s N VtpLL /11AMt x- TYrt -�- ►wc tuTcc— SNC[t RIX�� ST4111 [SS ST[[. Y�71LL r 1►CJ(U. _ Ara t- ►ttt: rrc T Aw ssA� _ nocw Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 By: S. Cho Date: 6/4/2024 Subject: Desian Calculations Paae: 1� a VNt/� ><� STQL � 7t1 a QIIIYMI�l g111� w A/1 OYCT �� v AIA yCNtf Ta Stt t t 1�G STAtIlLS6 STS=1 TY1L I GR[A3[t000 W "I �� � .. ;ae•:r�� �U �1.E YT 1 3[CT10N ELEYAiION YEYr ��� acaiE:.K• = r P =Loading on hanger rods (minimum 2 rods) D =Loading on wall structure Wt =Weight of Type 1 Hood = 651 Ibs (for 10-ft Hood) P = 4t = 162.8 Ibs zo• --�- +o' -�- ao' to o•r+on.ilo 000-on. P.O. Box 13423 Page 3 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com SCE AMERICAN SOCIETY OF CIVIL ENGINEERS Address: 10016 Edmonds Way Edmonds, Washington 98020 L 1���t S' S;y Rcb�� �y� v !, - n tbtllrghim RA I'• I 1 HO �.n Rti z - - �i � �S� C I. ... Wind c,�..,,t \ I.V ��..�ai cnwbl Y 138th 11 S•N c ASCE Hazards Report Standard: ASCE/SE17-16 Latitude: 47.790308 Risk Category: II Longitude:-122.367385 Soil Class: D -Default (see Elevation: 318.28435779992856 ft Section 11.4.3) (NAND 88) Am on tls•`�'t �Y/ E . 1.'r.t �I ��� - y � - < D > L s 3 n Results: Wind Speed 98 Vmph 10-year MRI 67 Vmph 25-year MRI 74 Vmph 50-year MRI 78 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1 B and Figs. CC.2-1—CC.2-4, and Section 26.5.2 Date Accessed: Wed Jun 05 2024 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years). Site is not in a hurricane -prone region as defined in ASCE/SEI 7-16 Section 26.2. https://ascehazardtool.org/ Page 1 of 3 Wed Jun 05 2024 Page 4 of 16 E® AMERICAN SOCIETY OF CNIL ENGINEERS Seismic Site Soil Class: D -Default (see Section 11.4.3) Results: Ss 1.28 Sp, N/A S, 0.449 T L 6 Fa 1.2 PGA : 0.543 F„ N/A PGA nn : 0.652 S nns 1.536 F PGA 1.2 Snn, N/A le 1 Sos � 1.024 C� 1.356 Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Data Accessed: Wed Jun 05 2024 Date Source: USGS Seismic Design Maps https://ascehazardtool.org/ Page 2 of 3 Wed Jun 05 2024 Page 5 of 16 ''ASCE® AMERICAN SOCIEN OF CIVIL ENGINEERS Snow Results: z Ground Snow Load, p9 : 20 Ib/ft Mapped Elevation: 318.3 ft Data Source: Date Accessed: Wed Jun 05 2024 Statutory requirements of the Authority Having Jurisdiction are not included. Snow load values are mapped to a 0.5 mile resolution. This resolution can create a mismatch between the mapped elevation and the site -specific elevation in topographically complex areas. Engineers should consult the local authority having jurisdiction in locations where the reported `elevation' and `mapped elevation' differ significantly from each other. The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided "as is" and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third -party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third -party content by or from ASCE. ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate fields) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard. In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool. https://ascehazardtool.org/ Page 3 of 3 Wed Jun 05 2024 Page 6 of 16 G52 LNG/N��RS Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 Civil S Structural gy. S. Cho Date: 6/4/2024 Challenge � 5ucce5a Subject: Design Calculations Page: Wind Load Calculation for Other Structure (Reference: IBC 2021, Chapter 1609 & ASCE 7-16, Chapter 29) Design Wind Load (Open Buildings &Other Structure) „,„.� Mean Roof Height, h, (ft) = 10 Building Width, B, (ft) = 50 Building Length L, (ft) = 120 RTU Top Elevation, H, (ft) = 13 Equipment Vertical Size, E, (ft) = See Af � Equipment Width, D, (ft) = See Af I I Gust effect factor, G = 0.85 �� t� Net force coefficient, Cf = N/A �� pX�VOM iRK[N Projected area normal to the wind, Af, (ft2) = Af 1' `� ��* RIS[R a WDD NRD fNl Ov OI.CRS�- 1 )? Basic Wind Speed, Vas, (mph) @Risk Category II = 98 Exposure Category = B �_ r Y. Risk Category= Standard -Occupancy Buildings = II I I Wind Load Importance Factor, IW = 1.00 I I Velocit ressure ex osure coefficient, K = 0.57 I I YP p Z I I Topographic Factor, KZt = 1.00 I I Wind Directionality Factor, Kd = 0.95 - - - - - mn vltx Velocity Pressure, qZ, (Ib/ft2) = 0.00256KZKZtKdV2 = 13.31 Horiz. GCS=Max {min[2-Af / (B�h), 1.9], 1.0}. = 1.9 Ar, EF = 8.9 ftZ (Horiz.) Vert. GCI =Max {min[2-Af / (B'L), 1.5], 1.0} = 1.5 At, eF = 5.6 ftZ (Vert.) Design Lateral Wind Force, Fh= gZGC�Af, (Ib/ft) = 224.9 Ibs, (Horiz.) Design Uplift Wind Force Fv = gZGC�Af, (Ib/ft) = 111.8 Ibs, (Vert.) Exposure B C D Height h, (ft) KZ KZ KZ 0-15 20 25 30 35 40 45 50 55 60 0.57 0.62 0.67 0.70 0.73 0.76 0.79 0.81 0.85 1.03 0.90 1.08 0.95 1.13 0.98 1.01 1.04 1.07 1.16 1.19 1.22 1.25 1.09 1.27 0.83 1.12 1.29 0.85 1.14 1.31 P.O. Box 13423 Page 7 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com G52 �NGINF�RS Civil & Structural Challenge & 5uccea5 Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 By: S. Cho Date: 6/4/2024 Subject: Desian Calculations Paae: Wind Load Calculation for Other Structure (Reference: IBC 2021, Chapter 1609 & ASCE 7-16, Chapter 29) n Wind Load (Open Buildings &Other Structure) Mean Roof Height, h, (ft) = 10 Building Width, B, (ft) = 50 Building Length L, (ft) = 120 RTU Top Elevation, H, (ft) = 13 Equipment Vertical Size, E, (ft) = See Af Equipment Width, D, (ft) = See Af Gust effect factor, G = 0.85 Net force coefficient, Cf = N/A Projected area normal to the wind, Af, (ft2) = Af Basic Wind Speed, Vas, (mph) @Risk Category II = 98 Exposure Category = B Risk Category= Standard -Occupancy Buildings = II Wind Load Importance Factor, IW = 1.00 Velocity pressure exposure coefficient, KZ = 0.57 Topographic Factor, KZt = 1.00 Wind Directionality Factor, Kd = 0.95 Velocity Pressure, qZ, (Ib/ftZ) = 0.00256KZKZiKdV2 = 13.31 Horiz. GCS =Max {min[2-Af / (B"h), 1.9], 1.0}. = 1.9 Af, MAU - Vert. GCr=Max {min[2-Af / (B*L), 1.5], 1.0} = 1.5 Af, MAU Design Lateral Wind Force, Fh= gZGCrAf, (Ib/ft) = 317.7 Ibs, (Horiz.) Design Uplift Wind Force Fv = gZGC�Af, (Ib/ft) = 286.4 Ibs, (Vert.) Exposure B C D Height KZ KZ KZ h, (ft) 0-15 0.57 0.85 1.03 20 0.62 0.90 1.08 25 0.67 0.95 1.13 30 0.70 0.98 1.16 35 0.73 1.01 1.19 40 0.76 1.04 1.22 45 0.79 1.07 1.25 50 0.81 1.09 1.27 55 0.83 1.12 1.29 60 0.85 1.14 1.31 12.6 ftZ (side) 14.3 ft2 (plan) P.O. Box 13423 Page 8 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com G52 LNG/N��RS Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 Civil S 5tru�tural gy. S. Cho Date: 6/4/2024 Challenge � 5ucce5a Subject: Desian Calculations Paae: Per USGS Seismic Data SS = 1.280 g SMS = 1.536 g Site Class = D (Per USGS) S� = 0.449 g SM� = N/A g ulate Seismic Desian Base Shear Structure Height, hh, (ft) = 10 Attachment level Sos = 2/3 SMS = 1.024 (per USGS) Soy = 2/3 SM� = N/A (per USGS) Risk Category= Standard -Occupancy Buildings = II Seismic Design Category per Sps = D Component amplification factor, ap Component Importance factor, IP Component operating weight, Wp Component response modification factor, RP Height of attachment /Mean roof height, z/h Seismic Design Force, Fp = (0.4a„S„�Wo) (1+2xz/h) RP/IP Max. seismic design force, Fpmax — 1.6SosIpWP Min. seismic design force, Fpm;,, = 0.3SosIPWP = 2.5 (ASCE 7, Table 13.5.1 & 13.6.1) = 1 (ASCE 7, Section 13.3) = Wp (Ib) = 6.0 (ASCE 7, Table 13.5.1 & 13.6.1) = 1 (z/h need not exceed 1.0) = 0.512 Wp (Eq. 13.3-1) = 1.638 WP (Eq. 13.3-2) = 0.307 Wp (Eq. 13.3-3) II Seismic Design Force, Fp = 0.512 �Np II Weight of E.F. = 99 Ibs Weight of MAU = 245 Ibs Seismic Design Force, FpE.F. = 50.7 Ibs Seismic Design Force, FpMA� 125.4 Ibs F.) P.O. Box 13423 Mill Creek, WA 98082 Page 9 of 16 TEL: (425) 408-2748 info@cs2engineers.com G52 LNG/N��RS Project: Edmond Gyro Maker Type 1 Hood Installation Client: Owner Job No.: 2425 Civil B Structural gy. S. Cho Date: 6/4/2024 Challenge & 5u�ce55 Subject: Design Calculations Seismic Load Calculation for Components and System uesign rarame[er D = WP = Equipment Weight E = pQE = pFP , (Ib/ft) W = Fh= gZGC,Ar, (Ib/ft) p = 1.0 EEF = 50.7 Ibs EMAU W EF = 224.9 Ibs W MAU - Exhaust Fan D = WP = 99 Ibs EEF = 50.7 Ibs WEF = 224.9 Ibs h = 30 in b = 24 in LC Load Combination a OTM 5a) D+W 6746 5b) (1.0+0.14Sos)D+0.7pQE 1064 6a) D +0.75 W 5060 6b) (1.0+0.105Sps)D+0.525pQE 798 7) 0.6D+W 6746 8) (0.6-0.14Sps)D+0.7pQE 1064 Make-up Air Unit D = WP = 245 Ibs EMau = 125.4 Ibs W Mau = 317.7 ft2 h = 30 in b = 27 in LC Load Combination a OTM 1) D N/A 5a) D+W 9531 5b) (1.0+0.14Sos)D+0.7pQE 2634 6a) D +0.75 W 7149 6b) (1.0+0.105Sps)D+0.525pQE 1976 7) 0.6D+W 9531 8) (0.6-0.14Sos)D+0.7pQE 2634 (a) ASCE 7-16, Section 2.4 &Section 12.4 (b) Overturning Moment in (Ibs-in) (c) Resisting Moment in (Ibs-in) (d) Compressive force (C) _ (OTM+RM)/b in (Ibs) (e) Uplift force (T) _ (OTM-RM)/b in (Ibs) 125.4 Ibs 317.7 Ibs N C � T RM`°' Comp. `°' Uplift (T) `c' (uplift force govern) 1188 50 -50 1188 331 232 1188 94 -5 1188 260 161 1188 83 -16 712.8 311 251 713 74 15 ,.� ��„��,- � +""C': R�7 RM ° -� Comp. Uplift (T) e 3308 123 -123 3308 476 231 3308 220 -25 3308 387 142 3308 196 -49 1985 427 280 (uplift force govern) 1985 171 24 Use minimum (4) #12 self -tapping screws at each side for sheet metal connections & use (4) 1/4" lag screws at each sides for roof connection P.O. Box 13423 Page 10 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com Project: Gyro Maker Restaurant Hood Date: June 4, 2024 Location: Edmonds, WA Prepared By: S. Cho CS2 No: 2425 Page Analysis of Existing Structure P.O. Box 13423 Page 11 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com P.O. Box 13423 Project Title: G52 ENG/NPERS Mill creek, wA 9ao82 Engineer: TEL. 425.408.2748 Project ID: cneuenge a ���e55 - c���i a eeruee�rei info@cs2engineers.com Project Descr: Wood Beam Project File: 2425 Edmonds Gyro Maker Hood EnerCalc.xlsx.ec6 LIC# : KW-06013944, BuiId:20.24.06.04 CS2 ENGINEERS (c) ENERCALC INC 1983-2023 DESCRIPTION: Existing 4x6 T&G decking with Exhaust Fan Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set :IBC 2021 Material Properties Analysis Method : Allowable Stress Design Fb + 1,000.0 psi E :Modulus of Elasticity Load Combination :IBC 2021 Fb - 1,000.0 psi Ebend- xx 1,300.Oksi Fc - Prll 1,000.0 psi Eminbend - xx 1,300.Oksi Wood Species Douglas Fir -Larch (North) Fc - Perp 1,000.0 psi Wood Grade No. 1/No. 2 Fv 65.0 psi Ft 65.Opsi Density 34.Opcf Beam Bracing Beam is Fully Braced against lateral -torsional buckling D(O.g495) II D(0.015) S(0.025) 4x6 Span=12.Oft Applied Loads Beam self weight NOT internally calculated and added Uniform Load : D = 0.0150, S = 0.0250 , Tributary Width = 1.0 ft Point Load : D = 0.04950 k @ 2.0 ft, (Exhaust Fan) DESIGN SUMMARY r� Service loads entered. Load Factors will be applied for calculations. Maximum Bending Stress Ratio = 0.551: 1 Maximum Shear Stress Ratio Section used for this span 4x6 Section used for this span (weak orientation) fb: Actual = 823.23psi F'b = 1,495.00psi Load Combination +D+S Location of maximum on span = 5.781 ft Span #where maximum occurs = Span # 1 Maximum Deflection Max Downward Transient Deflection 0.459 in Ratio = Max Upward Transient Deflection 0 in Ratio = Max Downward Total Deflection Q.793 in Ratio = Max Upward Total Deflection 0 in Ratio = Maximum Forces &Stresses for Load Combinations �• • = 0.275 : 1 4x6 (weak orientation) fv: Actual = 20.55 psi F'v = 74.75 psi Load Combination +D+S Location of maximum on span = 0.000 ft Span #where maximum occurs = Span # 1 Q >=240 Span: 1 : S Only 313 <240 n/a 181 >=180 Span: 1 : +D+S Q <180 n/a Load Combination Max Stress Ratios Moment Values Shear Values Segment Length Span # M V CD CM Ct CLx CF Cfu C i C r M fb F'b V fv F'v D Only 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.294 0.166 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.32 343.9 1,170.0 0.12 9.7 58.5 +D+S 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.551 0.275 1.15 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.77 823.2 1,495.0 0.26 20.6 74.8 +D+0.750S 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.470 0.239 1.15 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.66 703.2 1,495.0 0.23 17.8 74.8 +0.60D 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.099 0.056 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.19 206.3 2,080.0 0.07 5.8 104.0 Page 12 of 16 P.O. Box 13423 G52 PNG/NPER5 Mill creek, WA 98082 TEL. 425.408.2748 Challenge a eucce55 — civil a etru�tural info@es2engineers.com Project Title: Engineer: Project ID: Project Descr: Wood Beam Project File: 2425 Edmonds Gyro Maker Hood EnerCalc.xlsx.ec6 LIC# : KW-06013944, BuiId:20.24.06.04 CS2 ENGINEERS DESCRIPTION: Existing 4x6 T&G decking with Exhaust Fan Overall Maximum Deflections Load Combination Span Max. "" Defl Location in Span Load Combination Max. "+" Defl Location in Span +D+S 1 0.7934 5.956 0.0000 0.000 Vertical Reactions Support notation :Far left is #1 Values in KIPS Load Combination Support 1 Support 2 Max Upward from all Load Conditions 0.281 0.248 Max Upward from Load Combinations 0.281 0.248 Max Upward from Load Cases 0.150 0.150 D Only 0.131 0.098 +D+S 0.281 0.248 +D+0.750S 0.244 0.211 +0.60D 0.079 0.059 S Only 0.150 0.150 Page 13 of 16 P.O. Box 13423 Project Title: G52 ENG/NPERS Mill creek, wA 9ao82 Engineer: TEL. 425.408.2748 Project ID: cneuenge a ���e55 - c���i a eeruee�rei info@cs2engineers.com Project Descr: Wood Beam Project File: 2425 Edmonds Gyro Maker Hood EnerCalc.xlsx.ec6 LIC# : KW-06013944, BuiId:20.24.06.04 CS2 ENGINEERS (c) ENERCALC INC 1983-2023 DESCRIPTION: Existing 2x8 Joists +additional 2x8 Joist Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set :IBC 2021 Material Properties Analysis Method : Allowable Stress Design Fb + 1,000.0 psi E :Modulus of Elasticity Load Combination :IBC 2021 Fb - 1,000.0 psi Ebend- xx 1,300.Oksi Fc - Prll 1,000.0 psi Eminbend - xx 1,300.Oksi Wood Species Douglas Fir -Larch (North) Fc - Perp 1,000.0 psi Wood Grade No. 1/No. 2 Fv 65.0 psi Ft 65.Opsi Density 34.Opcf Beam Bracing Beam is Fully Braced against lateral -torsional buckling Repetitive Member Stress Increase D(0.1628) D 0,0.03 D(0.03) S(0.05) 2-2x8 Span = 12.0 ft Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Uniform Load : D = 0.0150, S = 0.0250 ksf, Tributary Width = 2.0 ft, (Roof loads) Point Load : D = 0.1628 k @ 4.0 ft, (Type 1 Hood) Varying Uniform Load : D= 0.0->0.0150 ksf, Extent = 1.0 --» 4.0 ft, Trib Width = 2.0 ft, (Parapet) DESIGN SUMMARY � - � • Maximum Bending Stress Ratio = 0.535: 1 Maximum Shear Stress Ratio = 0.532 : 1 Section used for this span 2-2x8 Section used for this span 2-2x8 fb: Actual = 849.24psi fv: Actual = 39.77 psi F'b = 1,587.00psi F'v = 74.75 psi Load Combination +D+S Load Combination +D+S Location of maximum on span = 5.168ft Location of maximum on span = 0.000 ft Span #where maximum occurs = Span # 1 Span #where maximum occurs = Span # 1 Maximum Deflection Max Downward Transient Deflection Q.189 in Ratio = Q >=240 Span: 1 : S Only Max Upward Transient Deflection 0 in Ratio = 760 <240 n/a Max Downward Total Deflection 0.3gg in Ratio = 370 >=180 Span: 1 : +D+S Max Upward Total Deflection 0 in Ratio = Q <180 n/a Maximum Forces &Stresses for Load Combinations Load Combination Max Stress Ratios Moment Values Shear Values Segment Length Span # M V CD CM Ct CLx CF Cfu C i C r M fb F'b V fv F'v D Only 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.369 0.360 0.90 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.00 458.4 1,242.0 0.31 21.0 58.5 +D+S 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.535 0.532 1.15 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.86 849.2 1,587.0 0.58 39.8 74.8 +D+0.750S 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = 12.0 ft 1 0.472 0.469 1.15 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.64 748.8 1,587.0 0.51 35.1 74.8 +0.60D 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Page 14 of 16 P.O. Box 13423 Project Title: - G52 PNG/NPERS Mill Creek, wA 98082 Engineer: _TEL.425.408.2748 Project ID: Challenge a eucce55 — civil a etru�tural info@cs2engineers.com Project Descr: Wood Beam Project File: 2425 Edmonds Gyro Maker Hood EnerCalc.xlsx.ec6 LIC# : KW-06013944, BuiId:20.24.06.04 CS2 ENGINEERS (c) ENERCALC INC 1983-2023 DESCRIPTION: Existing 2x8 Joists +additional 2x8 Joist Maximum Forces &Stresses for Load Combinations Load Combination ax ress a ios omen a ues ear a ues Segment Length Span # M V CD CM Ct CLx CF Cfu C i C r M fb F'b V fv F'v Length = 12.0 ft 1 0.125 0.121 1.60 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.60 275.0 2,208.0 0.18 12.6 104.0 Overall Maximum Deflections Load Combination Span Max. "" Defl Location in Span Load Combination Max. "+" Defl Location in Span +D+S 1 0.3888 5.912 0.0000 0.000 Vertical Reactions Support notation :Far left is #1 Values in KIPS Load Combination Support 1 Support 2 Max Upward from all Load Conditions 0.622 0.546 Max Upward from Load Combinations 0.622 0.546 Max Upward from Load Cases 0.322 0.300 D Only 0.322 0.246 +D+S 0.622 0.546 +D+0.750S 0.547 0.471 +0.60D 0.193 0.147 S Only 0.300 0.300 Page 15 of 16 Project: Gyro Maker Restaurant Hood Location: Edmonds, WA Date: June 4, 2024 Prepared By: S. Cho CS2 No: 2425 Page Appendix P.O. Box 13423 Page 16 of 16 TEL: (425) 408-2748 Mill Creek, WA 98082 info@cs2engineers.com FOR QUESTIONS, CALL THE Seattle Offlce REGION 85 PHONES C425) 212 - 5996 EMAILi reg65@econalr,coro HOOD INFORMATION HOOD OPTIONS ✓OB Gyro Makers EdMonds o '� eco n air LOCATION Edrlonds, WA, 98020 � DATE 3/1/2024 ✓OB 6654920 i�¢®�l®� ✓, DEG 1 DRAWN BYJDC-85 REY. SCALE 3/8' = 1'-0' MAX EXHAUST PLENUM TOTAL HOOD CDNFIG RISERCS) HOOD TAG MODEL M NUFACTUR RLENGTH COOKING TYPE APPLIANCE DESIGN TOTAL SUPPLY HODD END TO WIDTH LENG HEIGHT DIA CFM VEL SP NO TEMP DUTY CFM/FT EXH CFM CFM CONSTRUCTION END ROW 5424 600 430 SS 1 ECON-AIR 10' 0' I HEAVY 240 2400 4' 14' 2400 2245 -0,768' 2160 ALONE ALONE EX-2-PSP-F DEG WHERE EXPOSED FILTERS) LIGHTCS) UTILITY CABINETCS) HOOD TAG EFFICIENCY @ 7 WIRE FIRE SYSTEM ELECTRICAL SWITCHES FIRE SYSTEM HDOD ANGIN TYPE SIZE MODEL # QUANTITY NO TYPE QTY HEIGHT LENGTH MICRONS QTY TYPE GUARD LOCATION SIZE PIPING T 1 SS BAFFLE WITH 7 16' 16' 30% 3 L55 SERIES E26 NO NO 651 HANDLES LBS HODD TAG OPTION NO INSULATION FOR TOP OF HODD, 1 INSULATION FOR HACK OF HODD, HOOD NO TAG POS LENGTH WIDTH HEIGHT TYPE RISERCS) WIDTH LENG DIA CFM SP 1 Front 120' 20' 6' MUA 12' 26' 720 0,195' MUA 12' 26' 720 0,195' MUA 12' 26' 720 0,195' ® GREASE DUCT & CHIMNEY SPECIFICATI❑NSI PR❑VIDE GREASE DUCT EQUAL T❑ EC❑N-AIR M❑DEL "EDW" R❑UND 20 GAUGE 430 STAINLESS STEEL DUCTW❑RK, M❑DEL "EDW" IS LISTED T❑ UL-1978 AND IS INSTALLED USING "V" CLAMP L❑(KING C❑NNECTIDNS SEALED WITH 3M FIRE BARRIER 2000 PLUS, M❑DEL "EDW" DDES N❑T REQUIRE WELDING PR❑VIDING IT HAS BEEN INSTALLED PER THE MANUFACTURES INSTALLATI❑N GUIDE, PR❑VIDE RATED ACCESS D❑❑RS AT EVERY CHANGE IN DIRECTI❑N AND EVERY 12' ❑N CENTER, PER MANUFACTURES LISTING M❑DEL "EDW" H❑RIZ❑NTAL RUNS LESS THAN 75 FT. CAN BE SL❑PED 1/16" PER 12", H❑RIZ❑NTAL RUNS M❑RE THAN 75 FT. CAN BE SL❑PED 3/16" PER 12", DUCT SH❑ULD BE SL❑PED AS MUCH AS P❑SSIBLE T❑ REDUCE THE CHANCE ❑F GREASE ACCUMULATI❑N IN H❑RIZ❑NTAL RUNS, IF THE DUCT ❑R CHIMNEY IS WITHIN 18 INCHES ❑F C❑MBUSTIBLE MATERIAL, PROVIDE UL-2221 ❑R UL-103 HT LISTED D❑UBLE WALL GREASE DUCT ❑R D❑UBLE WALL CHIMNEY EQUAL T❑ EC❑N-AIR M❑DEL "EDW- 2R, 2R TYPE HT, 3R, ❑R 3Z" R❑UND 20 GAUGE 430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS ❑LITER SHELL, EC❑N-AIR REC❑MMENDS THE USE ❑F LISTED, PRE -FABRICATED R❑UND GREASE EXHAUST DUCT T❑ REDUCE STATIC PRESSURE IN THE SYSTEM, MINIMIZE INSTALLATI❑N AND INSPECTI❑N TIMES, AND ENSURE DUCT IS LIQUID TIGHT VERIFY CEILING HEIGHT HEIGHT REQUIRED TO VERIFY THAT HOOD FTTS SPACE AND TO SIZE THE ENCLOSURE PANELS � HVAC DISTRIBUTION NOTE � HIGH VEL❑CITY DIFFUSERS ❑R HVAC RETURNS SH❑ULD N❑T BE PLACED WITHIN TEN C10) FEET ❑F THE EXHAUST H❑❑D, PERF❑RATED DIFFUSERS ARE REC❑MMENDED, CUSTOMER APPROVAL TO MANUFACTURE: APPROVED AS NOTED ❑ APPROVED WITH NO EXCEPTION TAKEN ❑ REVISE AND RESUBMR ❑ SIGNATURE YOUR TTRE DATE PATENT NUMBERS AC-PSP (UNITED STATES) - US PATENT 7963830 B2. AC-PSP WALL (CANADA) - CA PATENT 2620509. AC-PSP ISLAND (CANADA) - CA PATENT 2520330. 1' LAYER ❑F INSULATION FACTORY INSTALLED IN INTERNAL BACK STANDOFF. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE T❑ COMBUSTIBLE SURFACES. FIELD CUT 14' DIAMETER 54' U.L. LISTED L55 SERIES E26 CANOPY LIGHT FIXTURE — HIGH TEMP ASSEMBLY. 28' 28' 28' I � I 20' 1 '— -- 112'— - — — 112'— — i -- — FJ ,,� ut --- 0'� 0® i i i 20' �I� 40' j- 40' �I 10' O'NOM./10' 0.00'OD. PLAN VIEW - HOOD �1 10' 0.00" LONG 5424EX-2-PSP-F SUPPLY PLENUM � - to TPI HANGING ANGLE sT� �RD (HARDWARE BY INSTALLER) a�omww°�sim rur vnsrEx, 1/E' - t3 TPI T,xnne s oom�w stm xL-ttgrwa 1/E' - t3 TPI T,xnne s oom�w sTm roc rur. suPPLr PLEMM yr cRnne a x�raaaG nnca.t: aEmrt ec�xa+c oomew sTm rut vesrEx xctot �rt Pot swPLr rLeaaa yr r�nc s oomwro soa PUT v�.srcrt. 1/¢' - 19 TPI cxnne a amm�w srm roc wr. ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' — 13 TPI GRADE 5 (MINIMUM) ALL —THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. HDDD CORNER �. _ 19 Ty HANGING ANGLE s m �w (HARDWARE BY INSTALLER) yr t;� e omm.w sTm FUT v�srot. ve• - Is tPI � s ammnw STFEL N1-THEA0. ve• - Is tPI aasE s ammriw srm roc wr. yr maot: a r® cotrm tvrtrtas nxo.E amm�w stm FUT vAS1ER �°� >r� PmNf roc tom. 1/Y fR/i➢E S Q@JDIIA9 STEtl MT VASIER. 1/Y - >8 TP[ fitROE 3 Q@IDIIRD STEEL lo( MITS. ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' — 13 TPI GRADE 5 (MINIMUM) ALL —THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. STF>:L yr - rxpoe STm yr - sIm FULL LENGTH HANGING ANGLE (HARDWARE BY INSTALLER) HANGING ANGLE MUST HE SUPPORTED WITH 1/2' — 13 TPI GRADE 5 (MINIMUM) ALL —THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' — 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR FULL LENGTH HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT—LBS. L55 SERIES E26 CANOPY LIGHT FIXTURE - HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL AND SHOCK RESISTANT GLOBE CL55 FIXTURE), FIELD CUT EXHAUST RISER, HANGING ANGLE, 16' SS BAFFLE WITH 1' LAYER ❑F If�i�ii�r�lf�� INSTALLED IN 3' INTERNAL STANDOFF, MEETS 0 INCH REQUIREMENTS FOR CLEARANCE T❑ COMBUSTIBLE SURFACES, IT IS THE RESPONSIBILITY ❑F THE ARCHITECT/OWNER T❑ ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS, GREASE DRAIN WITH REMOVABLE CUP, 54' HOOD T EQUIPMENT BY ❑THERS, 1' LAYER OF INSULATION FACTORY INSTALLED ON TOP ❑F HOOD, MEETS 0 INCH REQUIREMENTS FOR CLEARANCE T❑ COMBUSTIBLE SURFACES, ATTACHING PLATESi -- �'� - 20' 24' NOM, 80' SECTION VIEW - MODEL 5424EX-2-PSP-F HOOD - � 9 FIELD CUT SUPPLY RISER WITH VOLUME DAMPER, 23,5% OPEN STAINLESS STEEL PERFORATED PANEL, >,Iruerrcm >'eIv rAr�navemrnAr _ rnauaa��o�n FAN UNIT TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM MOTOR HP BHP PHASE VOLT FLA DISCHARGE WEIGHT SONES NO ENCL VELOCITY CLBS) 1 1 EADUBSH ECON-AIR 2400 0,850 1524 TEAO-ECM 1,000 0,6360 1 115 11,6 759 FPM 99 16,6 1.lTld Fd IJ TAIFn RI.ld TTn IJ — .TAA�RR.r,QA9n FAN UNIT TAG QTY FAN UNIT MODEL # BLOWER HOUSING MIN DESIGN ESP RPM MOTOR HP BHP PHASE VOLT FLA MCA MOCP WEIGHT SONES NO CFM CFM ENCL <LBS) 2 1 EA-AI-G10 GIOD AI - 2160 0,500 959 TEAO-ECM 1,000 0,6990 1 115 11,6 15,6A 25A 245 a+�sr namrnrm FAN UNIT NO TAG QTY DESCRIPTION 1 HINGE KIT - SHIPS LOOSE FOR CURB SUPPLIED BY OTHERS 1 ECM WIRING PACKAGE - PWM SIGNAL FROM ECPMO3 PREWIRE CTELCO MOTOR), CCW ROTATION 1 1 GREASE BOX 1 FAN BASE CERAMIC SEAL - DU/DR85HFA - SHIP LOOSE - FOR GREASE DUCTS 1 2 YEAR PARTS WARRANTY 1 SIZE 1 UNTEMPERED COMMERCIAL DOWN DISCHARGE FOR BELT DRIVE AHUS 2 1 MOTORIZED BACKDRAFT DAMPER FOR SIZE 1 HOUSING - MEETS AMCA CLASS lA RATING 1 ECM WIRING PACKAGE -SUPPLY - PWM SIGNAL FROM ECPMO3 PREWIRE CTELCO MOTOR), CW ROTATION 1 2 YEAR PARTS WARRANTY Fd AT d/'/'F I.Q/)ATTiQ EXHAUST SUPPLY FAN UNIT NO TAG GREASE GRAVITY WALL SIDE GRAVITY MOTORIZED WALL CUP DAMPER MOUNT DISCHARGE DAMPER DAMPER MOUNT 1 YES 2 YES FAN #1 EADU85H - EXHAUST FAN 30 IIL I I 22 1!/2' V / \,� DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN CBY OTHERS), 31 7/8' 24 3/4' FEATURES - DIRECT DRIVE CONSTRUCTION WO BELTS/PULLEYS). - ROOF MOUNTED FANS - RESTAURANT MODEL. - UL705 AND UL762 AND ULC-5645 - VARIABLE SPEED CONTROL. - INTERNAL WIRING. - THERMAL OVERLOAD PROTECTION (SINGLE PHASE). - HIGH HEAT OPERATION 300•F C149•C). - GREASE CLASSIFICATION TESTING. - NEMA 3R SAFETY DISCONNECT SWITCH. IXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 300•F C149•C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EBUILIHRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN VHICH WOULD CAUSE UNSAFE OPERATION. ABNORMAL FLARE-UP TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY VHILE EXHAUSTING HORNING GREASE VAPORS AT 600•F C316•C) FOR A PERO]D OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TD ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION ❑PTIONS - HINGE KIT - SHIPS LOSE FAR CURB SUPPLIED BY OTHERS, - ECM WIRING PACKAGE - PWM SIGNAL FROM ECPMO3 PREWIRE CTELC� MOTOR), CCW ROTATION, - GREASE BMX, - FAN BASE CERAMIC SEAL - DU/DR85HFA - SHIP LOOSE - FOR GREASE DUCTS, - 2 YEAR PARTS WARRANTY, FAN k2 EA-Al-G10D - SUPPLY FAN 1. DIRECT DRIVE UNTEMPERED SUPPLY UNIT WITH 10' BLOWER IN SIZE kl HOUSING WITH SPEED CONTROL, DISCONNECT SWITCH 2. INTAKE HOOD WITH EZ FILTERS, 3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT. 4. DOWN DISCHARGE CONSTRUCTION FOR SIZE 1 UNTEMPERED BELT DRIVE AHUS. 5. MOTORIZED HACK DRAFT DAMPER 16' X 1H' FOR SIZE 1 UNTEMPERED UNITS W/EXTENDED SHAFT, STANDARD GALVANIZED CONSTRUCTION, 3/4' REAR FLANGE, LOW LEAKAGE, TFB120S ACTUATOR INCLUDED. 6. ECM WIRING PACKAGE FOR SUPPLY MOTORS WITH PWM SIGNAL FROM ECPM03 PREWIRE. 7. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER SECTION). B. 2 YEAR PARTS WARRANTY, HINDTEI SUPPLY DUCT MUST BE INSTALLED TD MEET SMACNA STANDARDS, A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST HE RADIUS THROAT, RADIUS HACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE HACK ELBOWS SHOULD NDT BE USED. ANY TRANSITION AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TD SUPPORT DUCT IN ANY WAY. FAILURE TD PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE DF THE EQUIPMENT. SUGGESTED STRAIGHT DUCT SIZE IS 14' x 14'. 27 3/8' LffTING LUG. 3 3%4' HLOVER DLSCNARGE. '"� "� a{m nncuvn 7 1/a• —I 13 1/4' L J 6 3/8' FLEX CDNDUlT fTR F�LO VppNG 76 1/2' — 1T 32 1/8' AIRFLpV. SERVICE AIRFLOV. DISCpNNECT t� 29 3/4' HLOVER/ N70R' ACCESS 0(OR 24' SERVICE MINIMUM STDUCTMT PER AMCAx �L-J --� MIN. 14' ® GREASE DUCT & CHIMNEY SPECIFICATI�NSI PROVIDE GREASE DUCT EQUAL T❑ EC�N—AIR MODEL 'EDW' ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK, MODEL 'EDW' IS LISTED T❑ UL-1978 AND IS INSTALLED USING 'V' CLAMP LOCKING C�NNECTI�NS SEALED WITH 3M FIRE BARRIER 2000 PLUS, MODEL 'EDW' DOES NOT REQUIRE WELDING PROVIDING IT HAS BEEN INSTALLED PER THE MANUFACTURES INSTALLATION GUIDE, PROVIDE RATED ACCESS ODORS AT EVERY CHANGE IN DIRECTION AND EVERY 12' ❑N CENTER, PER MANUFACTURES LISTING MODEL 'EDW' HORIZONTAL RUNS LESS THAN 75 FT. CAN BE SLOPED 1/16' PER 12', HORIZONTAL RUNS MARE THAN 75 FT. CAN BE SLOPED 3/16' PER 12', DUCT SHOULD BE SLOPED AS MUCH AS PASSIBLE T❑ REDUCE THE CHANCE ❑F GREASE ACCUMULATION IN HORIZONTAL RUNS, IF THE DUCT ❑R CHIMNEY IS WITHIN 18 INCHES ❑F COMBUSTIBLE MATERIAL, PROVIDE UL-2221 ❑R UL-103 HT LISTED DOUBLE WALL GREASE DUCT ❑R DOUBLE WALL CHIMNEY EQUAL T❑ EC�N—AIR MODEL 'EDW— 2R, 2R TYPE HT, 3R, ❑R 3Z' ROUND 20 GAUGE 430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS ❑LITER SHELL, CUSTOMER APPROVAL TO MANUFACTURE: APPROrID AH NOTED ❑ APPROrID MIIN HB E%CFPOON TNON ❑ icwE Arm BEsuBRp ❑ sNxArugE MIIR TIME GREASE HD% COVER. GREASE PIPE. GREASE BOX INSTALLATION e� CLOSED POSITION GREASE J OPEN POSITION PARTS INCLUDED �� Mug GREASE BOX. GREASE Hm( COVER F1tEASE PIPE. GREASE BOX FlELD INSTALLATION SMELT METAL SCREVS 3 - L.pNG q/4' LGJ. $7EP 11 ATTACH GREASE HOX COVER Tp THE CURB, kELD 3. OIMENSDIN AS SF�VN ON PIG 1. SLREY GREASE BO!( COVER Tp CURB USING q) LplG q/V LGJ SCREVS AS SHOVN ON PIG B PIC• 1 CURB 3 i �� PIC. 2 _``J "`"„ CURB. GREASE � `` "` HDX GREASE COVER. BD)( ShP 21 COVER ATTACH GREASE HD1( Tp GREASE HO% COVER, SL[DE AN➢ DROP. AS SHpVN ON PIG 3. CUR& GREASE PIC. 3 epO�ER, SE Bm(. O STEP 3) P1C'-4 DISTN.L GREASE PIPE AS SHDVN W PIC. 4. CitEASE PIPE.