REVIEWED RESUB 1-BLD2024-0288+Manufacturer_Specifications_and_Installation_Instructions+6.14.2024_2.41.22_PM+4324256REVIEWED MorganBY CITY OF EDMONDS CAdvanced Materials FireMaster° FastWrap° XL Product Data and Installation Guidelines Product Description Thermal Ceramics FireMaster FastWrap XL is a flexible blanket composed of high temperature fibers classified for applications to 2192°F (1200°C) and fully encapsulated in a durable glass fiber reinforced foil facing for easy handling and installation. BLD2024-0288 RFSl1R Thermal Ceramics FastWrap XL is UL and ULC Listed for 1 and 2 hour fire resistive enclosure protection, zero clearance for kitchen exhaust ducts, electrical circuit protection, and as a component in UL firestop designs for fire resistance rated floors, ceilings, and walls. The core fibers in FastWrap XL are manufactured using Thermal Ceramics patented Superwoolo fiber which is an alkaline -earth silicate wool with low biopersistence and therefore increased safety for installers. FastWrap XL is under UL's Follow -Up Service Program to ensure the consistent quality essential to this life -safety application. Features or Benefits • Thin and Lightweight at 1-1/2" (38mm) thick, 6 pcf (96 kg/m3) density • Contours easily to complex duct designs • Grease duct installation UL and ULC Listed with butt joints at all seams on both layers • Fully foil encapsulated for fast and clean installation • Contains 2192°F (1200°C) rated fibers • Microbial Resistance validated by UL Environment • Good sound absorption • Compliant to IMC, NFPA 96, UMC, CIVIC, CNBC Applications G�pSSIFjeo EUL UDC LISTED \\ anal INTERNATIONAL CODE COUNCIL! • 2 hour enclosure and firestop system for kitchen ex- haust duct • Zero clearance to combustibles • 1, 2 and 3 hour enclosure and firestop system for hazardous exhaust ducts, pressurization ducts, clothes dryer exhaust ducts, trash and linen chutes, and other fire rated HVAC ducts • 1 hour electrical circuit integrity protection • Engineered and tested solutions for fire protection of structural steel and storage vessels per ASTM E119, ISO 834, and UL1709 f/R"SlER` FireMaster° FastWrap° XL Product Data and Installation Guidelines Specifications - Division 23 07 00 (or 15080) CSI Spec and AutoCAD available online, www.arcat.com/sd/clients/thermcer.html. Thermal Ceramics FireMaster FastWrap XL is a flexible high temperature insulation rated to 2192°F (1200°C) that is fully encapsulated in FSP facing. The duct enclosure system shall be listed by UL and /or ULC per ASTM E 2336, CAN/ULC S144 and ISO 6944 for 1-, 2- and 3-hour rating and zero clearance to combustibles, and tested per ASTM E84 for a flame/smoke rating less than 25/50. Insulation shall have a nominal thickness of 1-1/2 inches (38 mm) and density of 6 pcf (96 kg/m). Insulation shall have an R-Value of 7.3 at 75°F. Installation shall be in strict accordance to manufacturers published installation instructions, UL or ULC Listings, and shop drawings. Physical Properties Product Unit Size Units/ Weight/ FastWrap 1.5in x 24in x 25ft 1 37.5 Roll 1.5in x 48in x 25ft 1 75 XL Listing and Code Reports Listed Uses Agency Listing Layers Grease Duct Enclosure per ASTM E2336 UL G18 ESR 2213 and AC101 (2012, 2015 IMC, NFPA 96, 2 UMC, CMC) UL ER14229-01 ULC Grease Duct Test Protocol and CAN/ ULC FRD 4, 7* 2 ULC S144* Through Penetration FireStop System per UL ASTM E814, UL 1479 See Figure 2 1 or 2 ULC UL HNLJ.V1, 19, 1- or 2-hour Ventilation Duct Enclosure 29 1 ULC FRD 3, 5, 6, per ISO 6944 18 3-hour Ventilation Duct Enclosure per UL HNLJ.V2 2 ISO 6944 Electrical Circuit Protective System UL FHIT.5 2 Morgan CAdvanced Materials Performance Specifications Reference Standard Standard No. Performance Grease Duct Enclosure System ASTM E2336 Pass Section 16.1 - Non -Combustibility ASTM E136 Pass Section 16.2-Fire Resistance (wall) ASTM E119 Pass Section 16.3 - Durability Test ASTM C518 Pass Section 16.4 - Internal Fire Test ASTM E2336 Pass ASTM E814/ Section 16.5 - Fire Engulfment (duct) pass E119 ULC Grease Duct Test Pass Protocol Standard Methods of Fire CAN/ULC Resistance Tests - Grease Duct As- Pass S144 semblies Grease Duct Clearances UL 1978 Pass Air Ventilation Duct Enclosure ISO 6944 Pass Surface Burning Characteristics ASTM E84 <25/50 Thermal Resistance, ASTM C518 7.3 per layer R-value @ 75°F Mold Growth ASTM C1338 ULE Validated CA Standard Low VOCs �01350 ULE Validated Storage Thermal Ceramics FastWrap XL must be stored in a dry warehouse environment on pallets. Pallets should not be stacked. FIRi6ffER 0 Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster° FastWrap° XL Product Data and Installation Guidelines Installation FireMaster FastWrap XL shall be installed by a qualified contractor in accordance with manufacturer's instructions and laboratory design listings. Materials and Equipment • FireMaster FastWrap XL blanket • Aluminum foil tape • Glass filament reinforced tape (optional) • Carbon steel or stainless steel banding material, Minimum 1/2" (13mm) wide, minimum 0.015" (0.4mm) thick, with steel banding clips • Hand banding tensioner and crimping tool • Minimum 12 gage (3mm) steel insulation pins; steel speed clips, minimum 1-1/2" (38mm) square or 1-1/2" (38mm) diameter, or equivalent sized cup -head pins • Capacitor discharge stud gun • Approved firestop sealant General Cut edges of the blanket shall be taped with aluminum foil tape to prevent exposed edges of the insulation absorbing grease and moisture in the event of a compromised grease duct joint or condensation. Overlaps and/or tightly butted joints are used to block heat transfer in the event of duct deformation resulting from thermal expansion. Filament tape is suggested to hold the blanket in place until steel banding or pinning is installed to permanently secure the blanket. A. Installation on Grease Duct per ASTM E2336 and CAN/ULC S144 (Figure 1) System requires two layers of insulation applied directly to the duct with tight butt joints at all seams on both layers. The first layer of insulation is cut to a length sufficient to wrap around the duct and provide a tight butt joint where the blanket ends meet. Adjacent blankets on the first layer are butted tightly together with longitudinal seams offset minimum 6" (150mm). The second layer of insulation is installed in the same method as the first layer, with seams between layers offset a minimum of 6" (150mm). Banding and/or pinning per Section D is used to permanently secure the insulation to the duct. Morgan CAdvanced Materials B. Installation on HVAC Duct per ISO 6944 (Figure 1) System requires one layer of insulation applied directly to the duct with 3" (75mm) overlaps at all seams. The insulation is cut to a length sufficient to wrap around the duct and provide a 3" (75mm) overlap where the blanket ends meet. Adjacent blankets are installed to provide a minimum overlap of 3" (75mm). Banding and/or pinning per Section D is used to permanently secure the insulation to the duct. C. 2 & 3 Sided Wrap Installation (Figure 4) When space does not allow for a complete wrap applied to the duct on all four sides, the FastWrap XL is approved for 2 or 3 sided installations with mechanical attachment to a rated concrete or CMU assembly. (See Figure 4 for installation details.) D. Mechanical Attachment Methods 1) Banding (Figure 1) - Minimum 1 /2" wide x 0.015" thick (13mm x 0.4mm) carbon steel or stainless steel banding is placed around the entire perimeter of the insulated duct on maximum 10-1/2" (270mm) centers and 1-1/2" (38mm) from each blanket edge or 1-1/2" (38mm) from each collar edge when using the butt joint and collar method. The banding is placed around the blanket and tightened to firmly hold the FastWrap XL in place against the duct, but not cause any cutting or damage to the blanket. 2) Pinning - Pinning on all sides of the duct may be used as an alternative to banding. For ducts wider than 24" (610mm) pinning is required on the bottom of horizontal runs, or on one side of vertical runs (in addition to steel banding). When applicable, 12 Gage (0.4mm) steel pins are installed on 12" (305mm) centers along the width of the duct and 10-1 /2" (270mm) centers along the length of the duct. Pins that extend beyond the outer blanket layer shall be turned down or the excessive length cut off to prevent sharp edges. Shoot through pins (cup head pins) may be used in conjunction with steel banding to prevent blanket sag. FIRIdyffER @ Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster° FastWrap° XL Product Data and Installation Guidelines E. Access Doors Field Fabricated Access Doors - Each access door assembly has four threaded rods 1/4 inch (6mm) in diameter and 5" (127mm) in length, with one welded to each corner of the door opening. Hollow steel tubes, 4-1/2" (114mm) long are installed outside the access cover plate and over the threaded rods. Four 12 gage (3mm) and 4-1/2" (114mm) long steel insulation pins are welded to the access cover plate to allow for installation of the three layers of FastWrap XL. One layer of FastWrap XL is cut to approximately the same size as the access panel, and impaled over the insulation pins on the panel. A second layer of FastWrap XL is cut so as to overlap the first layer a minimum of 1-1/2" (38mm). It is essential that the first and second layer fit tightly against the surrounding wrap with no through openings. The third and outside layer should be cut to overlap the second insulation layer by a minimum of 1-1/2" (38mm). Minimum 1-1/2" (38mm) round or square insulation clips are installed on the insulation pins to secure the three layers of insulation to the access cover plate. All cut edges of the insulation shall be taped with minimum 3" (75mm) wide aluminum foil tape. Wing nuts and washers are installed on the four threaded rods, and tightened against the hollow steel tubes to seal the access cover plate to the duct. F. Through Penetration Firestop assembly (Figure 2) When the duct penetrates a fire rated assembly an approved fire stop system must be employed. Figure 2 provides a list of some of the UL/ULC firestop design listings which can be found in the Certifications Directory at www.ul.com for US systems and www.ulc.ca for Canadian systems. Prior to installing any firestop system the surfaces of all openings and penetrating items must be clean and dry. The FastWrap XL core blanket (or mineral wool where allowed by the firestop design listing) must be compressed into the annular space. The packing material must be recessed a minimum depth from the surface of the concrete or gypsum assembly. The recessed opening must be filled with a minimum thickness of an approved firestop sealant. The packing material type and compression, minimum recess (typically 1/4" (6mm)), and approved firestop sealant and thickness (typically 1/4" (6mm)) shall be as specified in an approved UL / ULC firestop design listing. When there is not sufficient annular space around the duct to run the FastWrap XL enclosure system continuous through the fire rated assembly, the enclosure may terminate above and below the floor/ceiling assembly or on either side of a wall assembly as Morgan CAdvanced Materials shown in Figure 2. When this method is used, the FastWrap XL must be mechanically attached on either side of the fire rated as- sembly using one of the attachment methods described in Section D, spaced a maximum of 1-1/2" (38mm) from the fire rated assembly. G. Support Hanger Systems 1) Grease ducts: Trapeze support hangers shall be spaced on maximum 60 in. (1500 mm) centers. Hanger rods or straps shall be anchored with steel drop in or wedge expansion type masonry anchors. No additional protection is required for hangers and supports meeting the requirements of the Table below. Hanger Cross Maximum Trapeze Support (or Section Perimeter, in (mm) equivalent Yield Strength) 148 in (3759mm) 2 in x 2 in x A in angle 3B in (10 mm) (51 mm x 51 mm x 3mm) 144 in (3660mm) 2 in x 2 in x 1/4in angle threaded rod (51 mm x 51 mm x 6mm) 2) HVAC ducts: Trapeze support hangers shall be spaced on maximum 60 in. (1500 mm) centers. Hanger rods or straps shall be anchored with steel drop in or wedge expansion type masonry anchors. No additional protection is required for hangers and supports meeting the requirements of the Table below. Hanger Cross Max. Trapeze Support (or Section Perimeter, equivalent Yield in (mm) Strength) 1 in x 16 gage strap 100 (2540) (25mm x 1.5 gage strap) 1/4in (6mm) threaded 1-12 in x 1-12 in x 3/16in rod 50 (1270) angle (38mm x 38mm x 5mm) 38in (10mm) threaded 1-12 in x 1-12 in x 3/16in rod 150 (3810) angle (38mm x 38mm x 5mm) 12in (12.7mm) threaded 218 (5540) 2 in x 2 in x 1/4 in angle rod (51 mm x 51 mm x 6mm) i'lRidySTER @ Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster° FastWrap° XL Product Data and Installation Guidelines Maintenance and Repair Morgan CAdvanced Materials No maintenance is required when installed in accordance with Thermal Ceramics installation instructions. If damage is limited to the foil facing, aluminum foil tape can be used to repair the foil facing. If an area of blanket is found to be damaged, the following procedure must be incorporated. If the damaged area is larger than 8" (203mm) x 8" (203mm) the entire wrap section must be removed and replaced according to Thermal Ceramics installation instructions. If the damaged area is small (less than 8" (203mm) x 8" (203mm)), the damaged area must be cut away and replaced with a new section 1" (25mm) larger in length and width than the cut out, such that the new section can be compressed tightly into the cut-out area. All cut edges of the new section must be taped and sealed with aluminum foil tape. The new section must be held in place with either pinning or banding per Thermal Ceramics installation instructions. 10. Limitations FireMaster FastWrap XL shall be installed in accordance with these installation instructions and appropriate laboratory design listings. The integrity of FastWrap XL systems is limited to the quality of the installation. For personal protective equipment recommendations, please see SDS. Thermal Ceramics, FireMaster, and FastWrap are trademarks of Morgan Advanced Materials. FireMaster products are manufactured by Thermal Ceramics and are distributed by authorised distributors. FIRI&9ER @ Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster® tW Fasrap UMorgan XL Advanced Materials Product Data and Installation Guidelines C Figure 1 Grease and HVAC Duct Enclosure System 1 or 2 Hour Shaft Alternative / Zero Clearance to Combustibles .KKKKKKKK� &�� wn•n•rriarnri intiw TWO LAYER INSTALLATION (Grease Duct perASTM E2336 and CANIULC S144} THe6cope Wrap Option LEGEND t Two Layers of XL Insulation for ASTM E2336 and CANIULC S144 Grease Duct Enclosures One Layer of XL Insulabon for 2-Hour Air Ventilatan Duct Enclosures 2 Stee banding minmtum 112" 13 ride by 0.015' 0.4 thick. 3 T ht butt joints no overlap) at penimeter and lon vtudinal joints. both layers for grease dUM- 4 Min. 3' 5 overlap on perneter and between ad acent blankets Optional 0' XL collar 6 Han - size dependent weight of assembly! see datasheet Secton G 7 Trapeze Supports - size dependent on weight of assembly see datasheet Section G 8 1 Steel Rectangular or Round Duct size a and construct -on dependent per Listed Desi n TM nIW I, a Yu ..- C.--, : --1 -1W 4-. h f 11. —\ — xLooi-to F/Rf({rgSTER° Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster° FastWrap° XL Product Data and Installation Guidelines UMorgan CAdvanced Materials Figure 2 Commercial Kitchen Grease Duct Enclosure System Air Ventilation Duct Enclosure System Through Penetration Firestop Systems F'3( XL rrulatc- zcn7 r,-,s through w assem y XL insulation termnated on both sides of the rated wall assembly f/R"S7fR XL nsu atcn continuous through rated foorloeiling assembly `Factng XL insuation terr-iinatea at the top and botio surface of the flooriceiling assembly Firestop Designs perASTM E814 / UL 1479 - Consult UL / ULC Directories for System Details -L Listing F- 3 T-Railing1 Floori'Vllati 2 Penetrant r3' Enclosure Per 4 Termination 5 Restm Sealant Details C-AJ-7D12 ^--hotr coxwet"U 84xN-. 26 Ga Duct V19 FRD3: 5 18 dvwgh 112 it STI; Tree= C-AJ-7014 3-hour Canctet"Ll 84x24- 26 Ga Duct V2w wW trough 1 Q in: STI: Tremco C-AJ 7019 1 or 2-hour Cortaet"I1 84x24; 26 Ga Duct V19; FRD3. 5, 16 terminate at 114 in; STI; Trerrtco C-AJ 7D21 2-hour ConaelefcMU 4gx24 16 Ga Duct G16 FRC4 7 terminate at 114 in: STL Trem^o C-AJ-7D95 2-tour CanaeleJGAU 3WO 22 Ga Duct V19 FRD3 5 16 *Tap t-rcu h 19' I HittiRectorseaf Tremco C-AJ-7096 2-four ConcrelelCMU 49x24 16 Ga Duct G18 FRD4- 7 wrao t^rcu h 114 in: STI• Hil Rectorseal Tremco F-C-7036 1 or 2-hour Wood*Floor 24xl 16 Ga Duct G18• FRD4 7 Yoap thrcu h 114 in: STI- Ffik Rectorseal- Tremco F-C-7055 1-hour -Wood(GvD Floor 4 Dia 30 Ga Duct V29; FRD28 wrap thrcu h 114 in; STI 2-hour ConcrebXMU Wall 100xl00 26 Ga Duc- V1Q& FRD3:5: 18 termnate at 14 it STI N-L-7121 1 or 2-hour G VYati 30x30. 16 Ga D.ct G16 FRD4: 7 through 114 it STI, Hilt Rectorseal Trenoo 4V-L-7145 1 or 2-hour Gyp Wal1 100x100; 2e Ga Duc. V19 FR03: 5 16 termnate at 518 in STI TYI gttdILprC---du.W cl It. xLOMS Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FireMaster° FastWrap° XL Product Data and Installation Guidelines Figure 3 UMorgan CAdvanced Materials Commercial Kitchen Grease Duct Enclosure System Air Ventilation Duct Enclosure System 1 Or 2 Hour Shaft Alternative / Zero Clearance to Combustibles 2 and 3 Sided Wrap Detail for Attaching to Walls and/or Ceilings XL005-4 Note- Ducts must be independently supported per code LEGEND 1 1 or 2 Hour Rated Concrete floor, ceiling,or wall Two layers of XL Insulabon for Grease Duct Enclosures rinstall per UL G18j One layer of XL Insulation for Air Ventilation Duct Enclosures install peruLvie} Two layers of XL Insulabon for 3-h Air %,entilation Duct Enclosure Install per UL v2) 3 Concrete fasteners stem 4 3116" 5 thick x 2" 50 -3" 75 wide bar stock perforated 12" (305) o.c. 5 8' 203 maximum Air Gap 6 Duct 7 Steel banding min. 112" 13 wide by 0.015' '0.4 thick. 8 Banding clip The Integrr, cr IA cc par—�rtrai Ceram Yi duct ststems h 1IMWC b tie pualtA c-Te rstalfficr AIR"94FRO Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials — Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product's suitability for use with Morgan Advanced Materials - Thermal Ceramics. FOR QUESTIONS, CALL THE Seattle Office REGION 85 PHONE, (425) 212 - 5996 EMAILi reg85@econair.com TTnnn TATFnPUAT7n TT — .Tn R4RR..Ad92n MAX EXHAUST PLENUM TOTAL HOOD CONFIG RISER(S) HOOD TAG MODEL M NUFACTUR RLENGTH COOKING TYPE APPLIANCE DESIGN TOTAL SUPPLY HOOD END TO WIDTH LENG HEIGHT DIA I CFM I VEL I Sp NO TEMP DUTY CFM/FT EXH CFM CFM CONSTRUCTION END ROW 1 5424 ECON-AIR 10, 0' 600 I HEAVY 240 2400 4' 14' 2400 2245 -0.768' 2160 430 SS ALONE ALONE EX-2-PSP-F DEG WHERE EXPOSED 7rnnn TTTFOPAIAT7n AT FILTER(S) LIGHT(S) UTILITY CABINET(S) HOOD TAG EFFICIENCY @ 7 WIRE FIRE SYSTEM I ELECTRICAL I SWITCHES FIRE SYSTEM HOOD ANGIN TYPE SIZE MODEL # QUANTITY NO TYPE QTY HEIGHT LqNGTH MICRONS qTY TYPE GUARD LOCATION SIZE PIPING WEIGHT 1 SS BAFFLE WITH 7 16' 30% 3 L55 SERIES E26 NO NO 651 HANDLES LBS HOOD nPTTONS HOOD NO TAG I OPTION INSULATION FOR TOP OF HOOD. 1 INSULATION FOR BACK OF HOOD. PFRFORATF.n 7TIPPLY PLRArTLlf(S) HOOD NO TAG PUS LENGTH WIDTH HEIGHT TYPE RISER(S) WIDTH LENG DIA CFM SP 1 Front 120' 20, 6' MUA 12' 28' 720 0.195' MUA 12' 28, 720 0.195' MUA 1 12' 28' 720 0.195' ® GREASE DUCT & CHIMNEY SPECIFICATI❑NSI PR❑VIDE GREASE DUCT EQUAL TO EC❑N-AIR MODEL "EDW" ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK. MODEL "EDW" IS LISTED TO UL-1978 AND IS INSTALLED USING "V" CLAMP L❑CKING C❑NNECTI❑NS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL "EDW" DOES NOT REQUIRE WELDING PR❑VIDING IT HAS BEEN INSTALLED PER THE MANUFACTURES INSTALLATI❑N GUIDE. PR❑VIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTI❑N AND EVERY 12' ON CENTER, PER MANUFACTURES LISTING MODEL "EDW" H❑RIZ❑NTAL RUNS LESS THAN 75 FT, CAN BE SLOPED 1/16" PER 12", H❑RIZ❑NTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16" PER 12". DUCT SHOULD BE SLOPED AS MUCH AS P❑SSIBLE TO REDUCE THE CHANCE OF GREASE ACCUMULATI❑N IN H❑RIZ❑NTAL RUNS, IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF C❑MBUSTIBLE MATERIAL, PR❑VIDE UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY EQUAL TO EC❑N-AIR MODEL "EDW- 2R, 2R TYPE HT, 3R, OR 3Z" ROUND 20 GAUGE 430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL. EC❑N-AIR RECOMMENDS THE USE OF LISTED, PRE -FABRICATED ROUND GREASE EXHAUST DUCT TO REDUCE STATIC PRESSURE IN THE SYSTEM, MINIMIZE INSTALLATI❑N AND INSPECTI❑N TIMES, AND ENSURE DUCT IS LIQUID TIGHT VERIFY CEILING HEIGHT HEIGHT REQUIRED TO VERIFY THAT HOOD FITS SPACE AND TO SIZE THE ENCLOSURE PANELS HVAC DISTRIBUTION NOTE HIGH VEL❑CITY DIFFUSERS OR HVAC RETURNS SHOULD NOT BE PLACED WITHIN TEN (10) FEET OF THE EXHAUST HOOD. PERFORATED DIFFUSERS ARE RECOMMENDED. CUSTOMER APPROVAL TO MANUFACTURE: APPROVED AS NOTED ❑ APPROVED WITH NO EXCEPTION TAKEN ❑ REVISE AND RESUBMIT ❑ SIGNATURE YOUR TTDF DATE PATENT NUMBERS AC-PSP (UNITED STATES) - US PATENT 7963830 B2. AC-PSP WALL (CANADA) - CA PATENT 2820509. AC-PSP ISLAND (CANADA) - CA PATENT 2520330. 1' LAYER OF INSULATION FACTORY INSTALLED IN INTERNAL BACK STANDOFF. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. FIELD CUT 14' DIAMETER 54' U,L. LISTED L55 SERIES E26 CANOPY LIGHT FIXTURE — HIGH TEMP ASSEMBLY. 28' 28' 28' I � I 20' 1 ut 0® i i i 20' �I� 40' T 40' �I 10' O'NOM./10' 0.00'OD. PLAN VIEW - HOOD1 10' 0.00" LONG 5424EX-2-PSP-F SUPPLY PLENUM LIE, - 13 TPI HANGING ANGLE STEEL NDD (HARDWARE BY INSTALLER) ORDDD GRADSi DOID m FLAT WASHER L8' - 13 TPI GRADE 3 GINN D STEEL ALL -TREAD. LIE, - 13 TPI GRADE 3 D@JDDDD STEEL HEX WT. SUPPLY PLENUM Ve GRADE 3 HLNRGENG AH3.E (NERM SEARING G DORDRM STEEL FLAT WASTER R(DHDR PMR FIR SUPPLY n.EraDD. Vr GRADE 7 ORSTEELRDD STEEL FLAT WASHER 1/D' - 13 TPI TRADE 3 0@IDRDD STEEL HEX WT. ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR PSP HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT, TORQUE ALL HEX NUTS TO 57 FT-LBS. HOOD CORNER HANGING ANGLE s GRADE (HARDWARE BY INSTALLER) 1/E' GAM 3 aomDDo Sim FLAT vAaER 1/E' - 13 T9 R� s *aND M STEEL ALL-THEAL 1/e - 13 in GRADE 7 RRmDM STEEL HEX WT. 1/e GRADE 3 H® CORNER �' �' A E Odin"" STEEL MT WASHER (VEIOR ' ANEYOt PWR roe HD>�. LIV GRADE 7 GROOM STEEL FLAT VASTER. L8' - 13 TPI GRADE 3 D@IDADD STEEL HEX WM ASSEMBLY INSTRUCTIONS HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATH HOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS. GRADE STEEL Vr - ewDE STEEL 1/E' - fRADE STEEL FULL LENGTH HANGING ANGLE (HARDWARE BY INSTALLER) HANGING ANGLE MUST BE SUPPORTED WITH 1/2' - 13 TPI GRADE 5 (MINIMUM) ALL -THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2' GRADE 5 (MINIMUM) STEEL FLAT WASHERS AND 1/2' - 13 TPI GRADE 5 (MINIMUM) HEX NUTS AS SHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION ABOVE CEILING ANCHORS. SINGLE HEX NUT BENEATH HANGING ANGLE IS ACCEPTABLE FOR FULL LENGTH HANGING ANGLES. MAINTAIN 1/4' OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS. L55 SERIES E26 CANOPY LIGHT FIXTURE - HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL AND SHOCK RESISTANT GLOBE (L55 FIXTURE). FIELD CUT EXHAUST RISER, HANGING ANGLE. 16' SS BAFFLE WITH 1' LAYER OF Ifi�iirlf� INSTALLED IN 3' INTERNAL STANDOFF. MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. IT IS THE RESPONSIBILITY OF THE ARCHITECT/OWNER TO ENSURE THAT THE HOOD CLEARANCE FROM LIMITED -COMBUSTIBLE AND COMBUSTIBLE MATERIALS IS IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. GREASE DRAIN WITH REMOVABLE CUP. 54' HOOD T EQUIPMENT BY OTHERS. 1' LAYER OF INSULATION FACTORY INSTALLED ON TOP OF HOOD, MEETS 0 INCH REQUIREMENTS FOR CLEARANCE TO COMBUSTIBLE SURFACES. ATTACHING PLATES,--- - - �� - 20' 24' NOM, 80' SECTION VIEW - MODEL 5424EX-2-PSP-F HOOD - # 9 FIELD CUT SUPPLY RISER WITH VOLUME DAMPER. 23.5% OPEN STAINLESS STEEL PERFORATED PANEL. A'Yud TTQ7' FAAT TArWf)PUAPT/)AT — Tn PURRFW09n FAN UNIT TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM MOTOR HP BHP PHASE VOLT FLA DISCHARGE WEIGHT SONES NO ENCL VELOCITY (LBS) 1 1 EADU85H ECON-AIR 2400 1 0.850 1524 TEAO-ECM 1.000 0.6360 1 115 1 11.6 1 759 FPM 99 16.6 LfTTA PAAl TATFf)PUATTn AT — .TAA RR.r,QA9n FAN UNIT TAG QTY FAN UNIT MODEL # BLOWER HOUSING MIN DESIGN ESP RPM MOTOR HP BHP PHASE VOLT FLA MCA MOCP WEIGHT SONES NO CFM CFM ENCL (LBS) 2 1 EA-AI-G10 GIOD Al - 2160 0.500 959 TEAO-ECM 1.000 0.6990 1 115 11.6 15.6A 25A 245 VART nOmrn Arc' FAN UNIT NO TAG QTY DESCRIPTION 1 HINGE KIT - SHIPS LOOSE FOR CURB SUPPLIED BY OTHERS 1 ECM WIRING PACKAGE - PWM SIGNAL FROM ECPM03 PREWIRE (TELCO MOTOR), CCW ROTATION 1 1 GREASE BOX 1 FAN BASE CERAMIC SEAL - DU/DR85HFA - SHIP LOOSE - FOR GREASE DUCTS 1 2 YEAR PARTS WARRANTY 1 SIZE 1 UNTEMPERED COMMERCIAL DOWN DISCHARGE FOR BELT DRIVE AHUS 2 1 IMOTORIZED BACKDRAFT DAMPER FOR SIZE I HOUSING - MEETS AMCA CLASS lA RATING 1 ECM WIRING PACKAGE -SUPPLY - PWM SIGNAL FROM ECPM03 PREWIRE (TELCO MOTOR), CW ROTATION 1 12 YEAR PARTS WARRANTY N'AAT d/V'L'Z'Zf)ATF4Z EXHAUST SUPPLY FAN UNIT NO TAG GREASE GRAVITY WALL SIDE GRAVITY MOTORIZED WALL CUP DAMPER MOUNT DISCHARGE DAMPER DAMPER MOUNT 1 YES 2 YES FAN #1 EADU85H - EXHAUST FAN 30 IIL I I 22 1!/2' V /\ DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS). 31 7/8' 24 3/4' FEATURESi - DIRECT DRIVE CONSTRUCTION WO BELTS/PULLEYS). - ROOF MOUNTED FANS. - RESTAURANT MODEL. - UL705 AND UL762 AND ULC-S645 - VARIABLE SPEED CONTROL. - INTERNAL WIRING. - THERMAL OVERLOAD PROTECTION (SINGLE PHASE). - HIGH HEAT OPERATION 300•F (14TC). - GREASE CLASSIFICATION TESTING. - NEMA 3R SAFETY DISCONNECT SWITCH. EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 30VF (149•0 UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. ABNORMAL FLARE-UP TEST EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 60VF (316•0 FOR A PERIOD OF 15 MINUTES WITHOUT THE FAN BECOMING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE CONDITION. OPTIONS - HINGE KIT - SHIPS LOOSE FOR CURB SUPPLIED BY OTHERS. - ECM WIRING PACKAGE - PWM SIGNAL FROM ECPM03 PREWIRE (TELCO MOTOR), CCW ROTATION. - GREASE BOX. - FAN BASE CERAMIC SEAL - DU/DR85HFA - SHIP LOOSE - FOR GREASE DUCTS. - 2 YEAR PARTS WARRANTY. FAN #2 EA-AI-G10D - SUPPLY FAN 1. DIRECT DRIVE UNTEMPERED SUPPLY UNIT WITH 10' BLOWER IN SIZE #1 HOUSING WITH SPEED CONTROL, DISCONNECT SWITCH 2. INTAKE HOOD WITH EZ FILTERS. 3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT. 4. DOWN DISCHARGE CONSTRUCTION FOR SIZE 1 UNTEMPERED BELT DRIVE AHUS. 5. MOTORIZED BACK DRAFT DAMPER 16' X 18' FOR SIZE 1 UNTEMPERED UNITS W/EXTENDED SHAFT, STANDARD GALVANIZED CONSTRUCTION, 3/4' REAR FLANGE, LOW LEAKAGE, TFB120S ACTUATOR INCLUDED. 6. ECM WIRING PACKAGE FOR SUPPLY MOTORS WITH PWM SIGNAL FROM ECPM03 PREWIRE. 7. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER SECTION). B. 2 YEAR PARTS WARRANTY, -NOTE- SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD NOT BE USED. ANY TRANSITIDN AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT. SUGGESTED STRAIGHT DUCT SIZE IS 14' x 14'. r27 3/8' LIFTING LUG. 3 - F BLOWER DISCHARGE. a4m nDcuDx 7 1/a• —I 13 1/4' :IF-- J 6 3/8• FLEX CONDUIT FOR FIELD WIRING 76 1/2' — T 32 1/8— AIRFLOW.SERVICE AIRFLOW. ➢ISC r.' 4M- 29 3/4' BEER/MO T� ACCESS DOOR 24' SERVICE MINIMUM STRAIGHTDUCT \I PER AMCA. 4 �L-JI I- MIN. 14' ® GREASE DUCT & CHIMNEY SPECIFICATIONSI PROVIDE GREASE DUCT EQUAL TO ECON—AIR MODEL 'EDW' ROUND 20 GAUGE 430 STAINLESS STEEL DUCTWORK. MODEL 'EDW' IS LISTED TO UL-1978 AND IS INSTALLED USING 'V' CLAMP LOCKING CONNECTIONS SEALED WITH 3M FIRE BARRIER 2000 PLUS. MODEL 'EDW' DOES NOT REQUIRE WELDING PROVIDING IT HAS BEEN INSTALLED PER THE MANUFACTURES INSTALLATION GUIDE. PROVIDE RATED ACCESS DOORS AT EVERY CHANGE IN DIRECTION AND EVERY 12' ON CENTER. PER MANUFACTURES LISTING MODEL 'EDW' HORIZONTAL RUNS LESS THAN 75 FT, CAN BE SLOPED 1/16' PER 12', HORIZONTAL RUNS MORE THAN 75 FT. CAN BE SLOPED 3/16' PER 12'. DUCT SHOULD BE SLOPED AS MUCH AS POSSIBLE TO REDUCE THE CHANCE OF GREASE ACCUMULATION IN HORIZONTAL RUNS. IF THE DUCT OR CHIMNEY IS WITHIN 18 INCHES OF COMBUSTIBLE MATERIAL, PROVIDE UL-2221 OR UL-103 HT LISTED DOUBLE WALL GREASE DUCT OR DOUBLE WALL CHIMNEY EQUAL TO ECON—AIR MODEL 'EDW— 2R, 2R TYPE HT, 3R, OR 3Z' ROUND 20 GAUGE 430 STAINLESS INNER DUCT INSULATED WITH A 24 GAUGE 430 STAINLESS OUTER SHELL. CUSTOMER APPROVAL TO MANUFACTURE: APPROrID Aa NOTED ❑ APPROrID NTIN NO EXCEPDON TAKEN ❑ REVEE AV RE3UBRC ❑ sNxmRaE TDIIR 'T.E GREASE HO% COVER. GREASE PIPE. GREASE BOX INSTALLATION — CLOSED POSITION GREASE J OPEN POSITION PARTS INCLUDED GREASE BOX GREASE BOX COVER GREASE PIPE GREASE ROX FlELD INSTALLATION SMELT METAL SCREWS 3 - LONG (3/4' LO. STEP 11 ATTACH GREASE DO COVER T13 THE CURB, HOLD 3' DIMENSION AS SHOWN ON PIG 1. SCREW GREASE BOX COVER TO CURB USING C3) LONG (3/V LG.) SCREWS AS SHOWN ON PIG 2. CURL PIC. 1 PIC. 2 CURB. BOX RE GASE COVER. BOX STEP 2) COVER ATTACH GREASE BOX TO CREASE BOX COVER, SLOE AND DROP. AS SHOWN ON PIC 3. CURIL GREASE PIC, 3 H SE BOX. 'Z4CEVER.. STEP 3) P1C'-4 INSTALL GREASE PIPE AS SHOWN W PIG 4. CREASE PIPE. ELECTRICAL PACKAGE - JOB46654920 SWITCHES NO TAG PACKAGE # LOCATION OPTION Ternanl Dlod s Pot sired cannacdon cas»atwn forRodsu r-tory sired M F w V Fkld Conna tksn Rrrkeraips FWd Camaadan to RmA- V d OR Padde •e O CLU— Ruk od se ts unaduk e' CASUnk Monitor and Control Hood control paned to support communi ations to cloud —based Building Management Syste m. — Hood Control Panel to allow cloud —based Building Managemmt System to menitor real time parmreters outlinedoloud—basod as MONITOR in tha points list. — Hood Control Papal to allow Building Management System to control parameters outlined as CONTROL in the points list Hood Control Pant to allow cloud —based Building Management System to romptement SYSTEM ECONOMIZER control strategies for fully integrated Building Management. MONITORING AND CONTROL POINTS LIS T ✓ORG ro Makers Edmonds O LOC.4TION Edmonds, WA, 98020 °s a U econsair DIYG 9/1/2024 DRAIPN �YJDC4850 REM. SCALE 3/8' = 1'-0' FANS CONTROLLED LOCATION QUANTITY TYPE � HP VOLT FLA 1 DCV—Illl WALL MOUNT IN SS BMX SS WALL MOUNT BMX 1 LIGHT 1 FAN SMART CONTROLS DCV EXHAUST 1 1,000 115 11,6 SUPPLY 1 1,000 115 11,6 DCV roseate Aareaen Room Tampanfue YONlTDR Duct Tam) YOL77tIR YW DieMga tYnperaiue YOL77t1R Ritohan R!U Dfeoharpe Twnrarofev YONI7CR Poo, sDaad YON!!CR lap Imrrnya YON1fOR ran reaw YDL�mn Confrowr tooth YON!!OR ran +bow YDLnmn M stoNrs YONTNR PCU /auw YONTNR I+Cr1 Put. Crab !'arroarrfaee YONTNR lks Cenda(en YOL77tIR CORK M. sNtarn YOMTDR Botrmnr Asarwae YONJ7DR Asp fNw Button YOL77tIR !CONTROL ran. Baaon YOLnmR s 1»NrRoa Lkna Button YOLzmN s 1»NrRoa rash Buewn YOLsmR s 1»NrRoa so Araearw llmetlen Room Hmparotwry(+) MONITOR Duet Tangara0urs(s+) MONITOR lrOl DleMrye Twnraroaaa MONITOR SUM- AM DkehaVa Tnnparagas YOMTOR Confrowr tooth YOMTOR ran roars MONTM lap status YDNmeR DEMAND CONTROL VENTILATI❑N HOOD CONTROL PANEL SPECIFICATI❑NS, - CONTROLS SHALL BE LISTED BY ETL (UL 508A) AND SHALL COMPLY WITH DEMAND VENTILATION SYSTEM TURNDOWN REQUIREMENTS OUTLINED IN IECC 403.7.5 (2021). - THE CONTROL ENCLOSURE SHALL BE NEMA 1 RATED AND LISTED FOR INSTALLATION INSIDE OF THE EXHAUST HOOD UTILITY CABINET. THE CONTROL ENCLOSURE MAY BE CONSTRUCTED OF STAINLESS STEEL OR PAINTED STEEL. - TEMPERATURE PROBE(S) LOCATED IN THE EXHAUST DUCT RISERS) SHALL BE CONSTRUCTED OF STAINLESS STEEL. - A DIGITAL CONTROLLER SHALL BE PROVIDED TO ACTIVATE THE HOOD EXHAUST FANS DYNAMICALLY BASED ON A FIXED DIFFERENTIAL BETWEEN THE AMBIENT AND DUCT TEMPERATURES SENSORS. THIS FUNCTION SHALL MEET THE REQUIREMENTS OF IMC 507.1.1. - A DIGITAL CONTROLLER SHALL PROVIDE ADJUSTABLE HYSTERESIS SETTINGS TO PREVENT CYCLING OF THE FANS AFTER THE COOKING APPLIANCES HAVE BEEN TURNED OFF AND/OR THE HEAT IN THE EXHAUST SYSTEM IS REDUCED, - A DIGITAL CONTROLLER SHALL PROVIDE AN ADJUSTABLE MINIMUM FAN RUN-TIME SETTING TO PREVENT FAN CYCLING. - VARIABLE FREQUENCY DRIVES (VFDS) SHALL BE PROVIDED FOR FANS AS REQUIRED. THE DIGITAL CONTROLLER SHALL MODULATE THE VFDS BETWEEN A MINIMUM SETPOINT AND A MAXIMUM SETPOINT ON DEMAND, THE DUCT TEMPERATURE SENSOR INPUT(S) TO THE DIGITAL CONTROLLER SHALL BE USED TO CALCULATE THE SPEED REFERENCE SIGNAL. - THE VFD SPEED RANGE OF OPERATION SHALL BE FROM 0% TO 100% FOR THE SYSTEM, WITH THE ACTUAL MINIMUM SPEED SET AS REQUIRED TO MEET MINIMUM VENTILATION REQUIREMENTS. - AN INTERNAL ALGORITHM TO THE DIGITAL CONTROLLER SHALL MODULATE SUPPLY FAN VFD SPEED PROPORTIONAL TO ALL EXHAUST FANS THAT ARE LOCATED IN THE SAME FAN GROUP AS THE SUPPLY FAN. - THE SYSTEM SHALL OPERATE IN PREP MODE DURING LIGHT COOKING LOAD OR COOL DOWN MODE WHEN SUFFICIENT HEAT REMAINS UNDERNEATH THE HOOD SYSTEM AFTER COOKING OPERATIONS HAVE COMPLETED, OPERATION DURING EITHER OF THESE PERIODS WILL DISABLE THE SUPPLY FANS AND PROVIDE AN EXHAUST FAN SPEED THAT IS EQUAL TO THE MINIMUM VENTILATION REQUIREMENT. - A DIGITAL CONTROLLER SHALL DISABLE THE SUPPLY FAN(S), ACTIVATE THE EXHAUST FAN(S), ACTIVATE THE APPLIANCE SHUNT TRIP, AND DISABLE AN ELECTRIC GAS VALVE AUTOMATICALLY WHEN FIRE CONDITION IS DETECTED ON A COVERED HOOD. - A DIGITAL CONTROLLER SHALL ALLOW FOR EXTERNAL BMS FAN CONTROL VIA DRY CONTACT (EXTERNAL CONTROL SHALL NOT OVERRIDE FAN OPERATION LOGIC AS REQUIRED BY CODE). - AN LCD INTERFACE SHALL BE PROVIDED WITH THE FOLLOWING FEATURES, A. ON/OFF PUSH BUTTON FAN & LIGHT SWITCH ACTIVATION. B. INTEGRATED GAS VALVE RESET FOR ELECTRONIC GAS VALVES (NO RESET RELAY REQUIRED). C. VFD FAULT DISPLAY WITH AUDIBLE & VISUAL ALARM NOTIFICATION. D. DUCT TEMPERATURE SENSOR FAILURE DETECTION WITH AUDIBLE & VISUAL ALARM NOTIFICATION. E. MIS -WIRED DUCT TEMPERATURE SENSOR DETECTION WITH AUDIBLE & VISUAL ALARM NOTIFICATION. F. A SINGLE LOW VOLTAGE CAT-5 RJ45 WIRING CONNECTION. G. AN ENERGY SAVINGS INDICATOR THAT UTILIZES MEASURED KWH FROM THE VFDS. DUCT / / ,IJIV ` ROOM TEMPERATU SENSOR. SEQUENCE OF ❑PERATI❑NS, THE HOOD CONTROL PANEL IS CAPABLE OF OPERATING IN ONE OR MORE OF THE FOLLOWING STATES AT ANY GIVEN TIMEi - AUTOMATICi THE SYSTEM OPERATES BASED ON THE DIFFERENTIAL BETWEEN ROOM TEMPERATURE AND THE TEMPERATURE AT THE HOOD CAVITY OR EXHAUST DUCT COLLAR. FANS ACTIVATE AT A CONFIGURABLE TEMPERATURE DIFFERENTIAL THRESHOLD. DEPENDING ON THE JOB CONFIGURATION EACH FAN ZONE CAN BE CONFIGURED AS STATIC OR DYNAMIC. THESE TERMS REFER TO WHETHER A VARIABLE MOTOR (SUCH AS EC MOTORS OR VFD DRIVEN MOTORS) MODULATE WITH TEMPERATURE. IF THE PANEL IS EQUIPPED WITH VARIABLE SPEED FANS AND THE ZONE IS DEFINED AS 'DYNAMIC', THESE WILL MODULATE WITHIN A USER -DEFINED RANGE BASED ON THE TEMPERATURE DIFFERENTIAL. PANELS EQUIPPED WITH VARIABLE SPEED FANS AND A FAN ZONE DEFINED AS 'STATIC', FANS WILL RUN AT A SET SPEED CALCULATED FOR THE DRIVE. DEMAND CONTROL VENTILATION SYSTEMS ARE CAPABLE OF MODULATING EXHAUST AND MAKE UP AIR FAN SPEEDS PER THE REQUIREMENTS OUTLINED IN IECC 403.7.5 (2021). - MANUAL, THE SYSTEM OPERATES BASED ON HUMAN INPUT FROM AN HMI. - SCHEDULE,A WEEKLY SCHEDULE CAN BE SET TO RUN FANS FOR A SPECIFIED PERIOD THROUGHOUT THE DAY, THERE ARE THREE OCCUPIED TIMES PER DAY TO ALLOW FOR THE USER TO SET UP A TIME THAT IS SUITABLE TO THEIR NEEDS. ANY TIME THAT IS WITHIN THE DEFINED OCCUPIED TIME, THE SYSTEM WILL RUN AT MODULATION MODE AND FOLLOW THE FAN PROCEDURE ALGORITHM BASED ON TEMPERATURE DURING THIS TIME. DURING UNOCCUPIED TIME, THE SYSTEM WILL HAVE AN EXTRA OFFSET TO PREVENT UNINTENDED ACTIVATION OF THE SYSTEM DURING A TIME WHERE THE SYSTEM IS NOT BEING OCCUPIED. - OTHERi THE SYSTEM OPERATES BASED ON THE INPUT FROM AN EXTERNAL SOURCE (DDC, BMS OR HARD -WIRED INTERLOCK). - FIRE, UPON ACTIVATION OF THE HOOD FIRE SUPPRESSION SYSTEM, THE EXHAUST FAN WILL COME ON OR CONTINUE TO TO RUN, THE HOOD MAKEUP AIR WILL SHUTDOWN, AND A SIGNAL WILL BE SENT FOR ACTIVATING THE SHUNT TRIP BREAKER PROVIDED BY THE ELECTRICIAN. FUEL GAS WILL SHUT OFF VIA A MECHANICAL/ELECTRICAL GAS VALVE ACTUATED BY THE HOOD FIRE SUPPRESSION SYSTEM. MODEL NUMBER ID I SCHEMATIC TYPE 11JEJL;f IiH 11LJN OF UF'EHA 11LJN1 6654920 D C V —1111 INSTALL De and Control Ventllatlon, w/ control for 1 Exhaust Fan, 1 Supply Fan, Exhaust on In Fire, Lights out In Fire, Fans nodulnte based on duct temperature. INVERTER DUTY 3 PHASE MOTOR REQUIRED FOR USE WITH VFD. Room temperature JOB NAME or shipped loose for field Installatlon.Verlfy distance between VFD and Motor) addltionaL cost could apply If Gyro Makers Edmonds 3/1/2024 ECP #1-1 distance exceeds 50 feet. 2 BREAKER PANEL TO PRIMARY CONTROL PANEL Responslbllltyl Electrlclan 3 BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED _ BREAKER PANEL PRIMARY CONTROL 4 — ----Hot — H1 BREAKER IPH — Neutral — N1 120 V _ Ground — 5 15 A CONTROL POWER. DO NOT WIRE TO GFCI OR SHUNT TRIP BREAKER. 6 1ST HOOD LIGHT BREAKER SHARED W/ CONTROL POWER. SWITCH #1 7 8 BREAKER PANEL TO FANS Responslbllltyl Electrlclan BREAKER PANEL FANS 9 ----------------HOT —_ _ BREAKER IPH NEUTRAL —_POWER TO 10 115V -------------------- Ground ECM FANS MCA, 14.5A EXH-1 _ MOCP, 25A 11 HOT — BREAKER IPH -------------------- NEUTRAL POWER TO 12 115V ------- Ground ---------- ECM FANS MCAi 14.5A SUP-2 — MOCP, 25A 13 14 CONTROL PANEL TO FANS 15 Responslbllltyi Electrlclan 15 FEED STP THROUGH INNER RD TO RD COOLING TUBE. ALLOW FOR NIDEC MOTOR PWM ENOUGH SLACK ON STP FOR BK TO GR 17 SPEED SIGNAL PROPER HINGING. (EXHAUST ONLY) MOTOR MU TOR ECM—Ol NOTE, PWM SIGNAL IS POLARITY BK TO W _ 18 CONTROL SENSITIVE. �H�$04G���D EHL MOTOR ZIZI TO BK PANEL P1A SHIE I PAIR _ _ _ _ c+ EXH-1 ECM �� v ��2� ECM_OJ 19 FAN, 01 FEED STP THROUGH INNER RD TO RD _ COOLING TUBE. ALLOW FOR NIDEC MOTOR 20 PWM ENOUGH SLACK ON STP FOR BK TO OR SPEED SIGNAL PROPER HINGING. (EXHAUST ONLY) TELCO MOTOR _ ECM-02 NOTE, PWM SIGNAL IS POLARITY BK TO YW 21 CONTROL SENSITIVE. OUTDOOR RATED ZIEHL MOTOR BK TO BK PANEL TO SHIELDED %ISTED PAIR RE C� ---- SUP-2 ECM = ECM_OJ - P2B FAN- 02 23 CONTROL PANEL — — Azov HOT— — SUP-2 REn o ECM-02 N1 —1. NEUTRAL_ _ WHITE N1 SUPPLY FAN INTERLOCK MUST HAVE ITS OWN METAL CONDUIT, WIRE TO PROVIDED CONDUIT DROP. NOT REQUIRED FOR ALL UNITS. SEE MAKE-UP AIR SCHEMATIC. CONTROL PANEL TO ACCESSORY ITEMS Responslbllltyl Electrlclan CONTROL PANEL COMPONENT I F MICROSWITCH 1 :ONTROL PANEL 41N0 Epp TO -------------- 1�C,,4,NC FIRE SYSTEM MICROSWITCH _ _ WIRE C1 TO COMMON (1) WRE ARI TO NORMALLY CLOSED (2). CI TO ARI SHOULD HAVE MS -I +NO CONTINUITY WHEN ARMED. — — — — 1,C,,4NC IF MORE THAN ONE FIRE SYSTEM, WIRE r — — -2 — — J +NO IN SERIES AS SHOWN n11 L -------------- 1'C�NC ----J :ONTROL PANEL J 4 ALL SWITCHES FACTORY WIRED TIE CAT-5 CONNECTION SWITCHES HOOD LIGHTS I )ONTROL PANEL B1 — — — — — — — — — — — BLACK — T TO Wl ___________ WHITE HOOD LIGHTS — — — — — — — — — — — GREEN _ 1400 W MAX WIRE TO J-BOX ON TOP OF HOOD COMM ROUTER CAT-5 ETHERNET CONNECTION :ONTROL PANEL _ _______________ TO WIRE DIRECTLY TO COMMUNICATION WORLD WIDE MODULE. NET REQUIRES 1) DHCP 2) WEB UDP PORT 1444 & 1445 OPEN FOR OUTBOUND TRAFFIC ONLY. :ONTROL PANEL T1A— — — — — — — — — — — — — — --�/-T TO ----J WIRE TO CONTROL BOARD. INSTALLL ROOM TEMP ROOM TEMP SENSOR IN ROOM AWAY FROM HEAT GROUPSi SENSOR SOURCES. DO NOT INSTALL SENSOR ON THE CEILING GRID, SEE MANUAL. ;ONTROL PANEL — — — — — — — — — — — — — — --- TO T2B WIRE TD CONTROL BOARD. HOOD 1 DUCT SENSOR SENSOR MOUNTED IN EXHAUST DUCT RISER 1 ;ONTROL PANEL — — — — — — — — — — — — — — -- 'LZ TU =Eli WIRE TO CONTROL BOARD. SHIP LOOSE DUCT SENSOR SENSOR MOUNTED IN EXHAUST DUCT DUCT STAT THE FOLLOWING CONNECTIONS MAY OR MAY NOT BE REQUIRED BASED ON JOBSITE SPECIFICATIONS HU S-0N_ OIL CONTROL PANEL — — — — — HOT TO SHUNT COIL — T SIGNAL FOR N1 NEUTRAL FROM SHUNT COIL ----- — — — — _ EXTERNAL ST TERMINAL IS ENERGIZED SHUNT TRIP IN FIRE CONDITION. ONTAC R_COI CONTROL PANEL — — — HOT TO CONTACTOR COIL — T SIGNAL FOR � — NEUTRAL —TO —CONTACTOR —COIL— — — — — EXTERNAL KS TERMINAL IS DE —ENERGIZED CONTACTOR COIL IN FIRE CONDITION. — — — — — — — — — — — COMMON _ _ CONTROL PANEL DRY CONTACT SFO1 — — — — — — — NORMALLY OPEN .-- ON/OFF WITH L= _ _ _ _ _ _ _ _ _ _ _ COMMON SUPPLY FAN H2 _ _ _ _ NORMALLY OPEN _ _ GROUP 1 SPARE CONTACTS WILL MAKE COMMON TO NORMALLY OPEN WHEN SUPPLY FAN IS ON. DCV SPEED 0+— — — — — — — — — — — — — — —+ — TO BMS 0-10V OUTPUT VD— WIRE TO ECPM03 TERMINALS. ON PCB CONFIGURABLE OUTPUT. (TOTAL) SEE ECPM03 OWNERS MANUAL. BINS SWITCH CONTROL PANEL — — — — — — — — — — — — — — —��C�� TO SIGNAL SWITCH 101-------T—HR--- — B— OUGHMS — ----J EXTERNAL WILL ACTIVATE ZONE1 FANS AND SWITCH LIGHTS 24 MOTOR POWER CIRCUITS. SEE INSTALLATI❑N DIAGRAM FOR FIELD WIRING REQUIREMENTS. FACTORY WIRING SCHEMATIC CIRCUIT BOARDS ECPM03 DCV Rev. 2.10.00 HMI Rev. 2.10.00 RA-x RD-x 120 VAC 24 VDC RELAY RELAY NO 4 3 NO 4j NC 2 1 NC 2COIL 8 7 COIL 8COM 6 5 COM 6 COMPONENT LABEL LIST DESCRIPTION ST-X Starter C-X varies Contactor varies IM-X VFD varies IR-X Llne/Load Reactor varies LEGEND FIELD WIRING FACTORY WIRING BI<- BLACK YW- YELLOW F.I.- BLUE GY- GREY BR- BROWN PR- PURPLL LR- IJ'�N�- RD- RED WH- WHITE GR- GREEN UR/BL- OR/BL STRIPE BL/RD- BL/RD STRIPE RD/GN- RE/UN STRIl.- WH/BL- WH/BL STP P