SEE REV1 approved RESUB1 FIR2022-0032+Fire_Alarm_Plan+6.13.2022_12.41.52_PM+2928432FIRDA LE VILLAGE SHOPPING PLAZA GENERAL NOTES 1. ALL WALL MOUNTED AUDIBLE & VISUAL SIGNALING APPLIANCES SHALL HAVE THEIR HEIGHTS ABOVE THE FINISHED FLOOR AT 80" TO BOTTOM. NFPA 72, 2016 EDITION, ALLOWS 80"-96" FOR VISUAL DEVICES AND REQUIRES A MINIMUM OF 90" TO TOP FOR AUDIBLE DEVICES OR 6" FROM CEILING, WHICHEVER IS LOWER. FOR SLEEPING AREAS GREATER THAN 16' (LINEAR) VISIBLE NOTIFICATION SHALL BE WITHIN 16' OF PILLOW AND GREATER THAN OR EQUAL TO 24'' FROM CEILING TO TOP OF LENS FOR 110CD. 2. ALL EQUIPMENT SHALL BE U.L. LISTED. 3. ELECTRICAL CONTRACTOR SHALL FURNISH ACCESS PANELS TO AREAS THAT REQUIRE SERVICING, TROUBLESHOOTING ETC. 4. DO NOT DEVIATE FROM ANY CONDUIT OR WIRE RUNS SHOWN ON FLOORPLANS WITHOUT PRIOR APPROVAL FROM SYSTEM SUPPLIER. EXCESSIVE VOLTAGE DROP, ADDITIONAL PARTS, ENGINEERING ETC. ARE A RESULT OF DEVIATIONS AND ARE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. 5. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR -FLOW NOR CLOSER THAN 3 FEET FROM AN AIR SUPPLY DIFFUSER. 6. ALL 120VAC POWER REQUIREMENTS FOR THE FIRE ALARM SYSTEM SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR AND SHALL MEET ALL REQUIREMENTS OF THE AHJ. 7. SMOKE DETECTOR TESTING SHALL BE ACCOMPLISHED WITH APPROVED SMOKE. 8. ALL WIRING, INITIATING DEVICES AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION. THE FIRE ALARM CONTROL PANEL SHALL SUPERVISE THE ANNUNCIATOR PANEL, INITIATING AND INDICATING DEVICE CIRCUITS. 9. ALL WIRING SHALL BE CUT FOR IN AND OUT. WIRING SHALL NOT BE LOOPED THROUGH DEVICES. ALL SPLICED WIRE POSSESING SHIELDS SHALL HAVE SHIELDS SPLICED AND TAPED TO PREVENT GROUND FAULTS. 10. THE ALARM SYSTEM SHALL HAVE AN AUDIBILITY OF NOT LESS THAN 15DB ABOVE AMBIENT NOISE LEVELS. TESTING SHALL BE ACCOMPLISHED WITH A DB METER. 11. ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS. 12. INSTALLATION SHALL BE IN COMPLIANCE WITH NFPA, LOCAL, STATE, NEC AND CONTRACT DRAWINGS. VICINITY MAP 234tn Pi- WhirlyBall y II ne technoiogy 2-1, s, W 23e1h s, sw T.J.Ma.q7. / s \ 238tl st sw Hosoonyi Korean s - Madrona K-8 School0 Clerk's Office F p ` 14m111rw bNh PI 01gt/rQ zamn sl sw SW F 26N 0ih PISW q 21PI 5W M � Burlin (n a y e g' 9 gJ 2slsiflSW 4 2llc,l lsw gg f Ip/ P\ a v s s 24md St ya s s 4 s •FlydaleAve, z rr Edmonds, WA 98020 zlsrem W c Denny's I panera Brea 2a4m 3t 3W UW Neighborhood _ -- 5' NNMI, $horelineClinic... Kruckeberg t n NW 2oaa s, B 9 ICI Nw2omas, z Botan ic Garden f = NNo dSt IliheHorne Depot Q Nw 202W N 202 d St NW 201 s, s1 Nw 2o,ct st Costco Wholes le 1P NW 202MA � © H19i,IA ?' - Nw2a9ms Discount Tire "looms Echo E ' Lake Park a Nwwnnfl � A s HILLWOOD N1991ns1 NVZelvinGSyre- O £ NW198Ns1 naems NW 19]A St Elementary School ; King's Elementary School 0 1 Echo OD Elementary Sc 1.MW, NW 195thr N19SNN19SMF' I Spin All �' Einstein Middle School0 Kin s Schools Bowling Center g 0 Dale Turner - F I SHEET # FIRE ALARM SYSTEM EDMONDS, WA SHEET INDEX DESCRIPTION FA-01 SYSTEM INFORMATION FA-02 TYPICAL MOUNTING & WIRING DETAILS FA-03 CALCULATIONS FA-04 BASEMENT FA-05 FIRST FLOOR FA-06 SECOND FLOOR FA-07 RISER DIAGRAM WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE - ADDRESSABLE LOOP 2 CONDUCTOR #16 FPLP S STROBE CIRCUIT 2 CONDUCTOR #14 FPLP I INITIATION CIRCUIT 2 CONDUCTOR #18 FPLP T POWER SUPPLY TRIGGER 2 CONDUCTOR #14 FPLP B SBUS / ANNUNCIATOR 4 CONDUCTOR #18 FPLP CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA 2 CONDUCTOR 600V #12 AWG THHN/THWN .244 O.D. .0467 2 CONDUCTOR 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 2 CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL: CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/211 .12 SQUARE INCH 3/411 .21 SQUARE INCH 1" .34 SQUARE INCH 1 1/4" .60 SQUARE INCH 1 1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH Approved by Fire 06/14/2022 Subject to field inspection SYMBOLS LEGEND QUANTITY SYMBOL DESCRIPTION MODEL MFG. BACKBOX MOUNTING HEIGHT 1 FACP FIRE ALARM CONTROL 6700 SILENT KNIGHT PROVIDED 66" A.F.F. TO TOP PANEL 1 BPS REMOTE BOOSTER 5496 6A SILENT KNIGHT PROVIDED 66" A.F.F. TO TOP POWER SUPPLY 1 ANN CD UNCIATOR REMOTE 5860R SILENT KNIGHT PROVIDED 66" A.F.F. TO TOP 1 AES AES RADIO AES 7707P AES PROVIDED 66" A.F.F. TO TOP COMMUNICATOR SMOKE DETECTOR 4S BOX W/1 G 1 O (ADDRESSABLE -PHOTO) SK-PHOTO-W SILENT KNIGHT MUD RING CEILING HEAT DETECTOR 4S BOX W/1 G 25 O (ADDRESSABLE -HEAT) SK-HEAT-W SILENT KNIGHT MUD RING CEILING MANUAL PULL STATION 4S BOX W/1 G 1 F (ADDRESSABLE) SKPULL SILENT KNIGHT MUD RING 48" A.F.F. TO CENTER CONTROL MODULE VERIFY LOCATION IN ___ G (ADDRESSABLE) SK-CONTROL SILENT KNIGHT 4S BOX FIELD MONITOR MODULE VERIFY LOCATION IN ___ AIM (ADDRESSABLE) SK-MONITOR SILENT KNIGHT 4S BOX FIELD 110 HORN STROBE OUTDOOR VERIFY LOCATION IN 1 8WP (WALL MOUNT) P2RK SYSTEM SENSOR PROVIDED FIELD 5 HORN STROBE 17 O (CEILING MOUNT) PC2RL SYSTEM SENSOR 4S BOX CEILING 15 STROBE 28 ♦ ♦ (CEILING MOUNT) SCRL SYSTEM SENSOR 4S BOX CEILING ___ -VVA/- END OF LINE RESISTOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A ___ EX EXISTING DEVICE N/A N/A N/A N/A ___ N/A NOT APPLICABLE N/A N/A N/A N/A ___ N/A NOT APPLICABLE N/A N/A N/A N/A ___ N/A NOT APPLICABLE N/A N/A N/A N/A ___ N/A NOT APPLICABLE N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A SCOPE OF WORK BUILDING DESCRIPTION NEW FIRE ALARM SYSTEM - INSTALL SILENT KNIGHT 6700 ADDRESSABLE FIRE BUILDING DESCRIPTION- EXISTING STRUCTURE, MULTIPLE TENANT OFFICES & ALARM CONTROL PANEL, AES RADIO COMMUNICATOR, 1 SMOKE DETECTOR, 25 RETAIL HEAT DETECTORS, 46 AUDIBLE AND VISUAL NOTIFICATION DEVICES IN SUITES AND RESTROOMS PER PLAN. OCCUPANCY CLASSIFICATION- B SPRINKLERED- NO � � M O � � O E •Fr � � LL y OOP as z 0 b N Q w(D o � Z W o �D_Q� C)O JQ U) Q W U) < LL Z QJ 00 Q �1 Li i J w LL Q � ]C LL [� PREPARER: ALAN HETLAND NICET CERTIFICATION: # 146032 FIRE ALARM SYSTEMS LEVEL fV EXPIRATION DATE: 11/01/2023 FIRa022-0032 PROJECT MANAGER: Todd Hetland SCALE: As Noted NO. REVISION DATE - SHOP DRAWINGS 12/20/2021 1 FLOORPLAN 3/28/2022 CORRECTION 2 DELETE PULLS, ADD 6/10/2022 HEATS 3 4 PAGE: SYSTEM INFORMATION DATE: 12/20/2021 SHEET: FA-01 RESUB Jun 13 2022 Cl-Y OF EDMONDS =VE OPMENT SERVICES 22 )s VICES 22 )s VICES 22 )s VICES 22 )s VICES 22 )s VICES 22 )s VICES