APPROVED FIR2024-0059+Drawings+7.17.2024_11.24.28_AM+4383483HOSOONYI KOREAN RESTAURANT
23830 HIGHWAY 99 SUITE 114
EDMONDS, WA 98026
ICC CERT # 9917130
APPLIANCES 6"
FROM END OF
HOOD
CLASS K WET CHERCAL EXTINGUISHER
SHALL BE INSTALLED 42'. 48'ABOVE
THE FINISHED FLOOR
42" — 48"
REMOTE PULL STATION
SHALL BE INSTALLED 42"-48" AVOVE THE
FLOOR AT A DISTANCE 110 FT FROM THE
HAZARD BUT NOT MORE THAN 20 FT. IT
SHALL BE INSTALLED IN THE PATH OF
EGRESS AND REQUIRE A MAXIMUM
FORCE OF 40 LBS. AND A MAXIMUM
MOVEMENT OF 14" FOR ACTUATION
INSTALLED BY [information for system operator/owner
ALL - AMERICAN FIRE PROTECTION INC. Contact your system manufacturer/distributor to ensure factory trained and
certified personnel perform repairs, maintenance, or servicing of the suppression
P.O. BOX 393 EVERETT, WA 98206 system. Failure to do so may compromise the UL listing of the hood suppression
PHONE: 360 - 474 - 9773 FAX: 360 - 631 - 5146 system, void the warranty and jeopardize insurance claims resulting from a fire.
(2)XADP DUCT
NOZZLES 24" X 12"
14 FT HOOD
ADP
NOZZLE
LINK TEMPERATURE TO BE DETERMINED AT TIME OF TRIP TEST WITH AHJ
�►
I
F ♦
1GRW
�GRW
NOZZLE
NOZZLE
NO2ZLE
27"- 45"
24"- 48"
24"- 48"
1R NOZZLE
20" - 42"
1
R NOZZLE
20" — 42"
GAS (2) GAS
FRYER STOCKPOT
13"X 21" RANGES
EACH
18" X 18"
PIPING SIZE
3/8" PIPING J
1/2" PIPING
3/4" PIPING
GAS CHARBROILER
36" X 24"
4
BADGER
�
Badger
Fire Protection
ADP .
NOZZLE
R NOZZLE R NOZZLE ♦►
20"-42" 20"-42" RNOZZLE RNOZZLE�
20' — 42" 20" — 42"
APPLIANCES 6"
FROM END OF
HOOD
6 BURNER GAS RANGE 4 BURNER GAS 4 BURNER GAS
36" X 24' RANGE RANGE
24" X 24" 24" X 24"
UL 300 COMPLIANT SYSTEM
SYSTEM MFG: BADGER FIRE PROTECTION UCH CONTROL HEAD
RANGE GUARD 6 - GALLON TANK
CAPABLE FLOW POINTS: 18 ACTUAL FLOW POINTS USED: 14
** SYSTEM HAS BEEN DESIGNED AND INSTALLED AND SHALL BE
SERVICED AND MAINTAINED TO UL300, NFPAI7A, NFPA96 AND
MANUFACTURERS INSTRUCTIONS.
RANGE GUARD 6
GALLON
FIRE SYSTEM
F- FIRE SYSTEM AND APPLIANCE DRAWING WILL BE DISPLAYED AT OR NEAR THE SYSTEM MANUAL PULL STATION
Audible Fire Alarm
& Strobe
Connection
to electrical
Shut down
upon
activation
MECHANICAL
AUTOMATIC
GAS SHUTOFF
Approved
DFM Glavin Burt
South County Fire
Date: 08/01 /2024
08-01-2024
PLAN REVIEW
NOTES: APPROVED - NO
COMMENTS
DFM BURT
• IM, I I I IIIl+001
RECEIVED
Jul 18 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT