REVIEWED BLD BLD2024-0979+STRUCTURAL PLANS+7.29.2024_10.00.18_AM+4406413STRUCTURAL NOTES GENERAL REQUIREMENTS BUILDING CODE & REFERENCE STANDARDS: THE "INTERNATIONAL BUILDING CODE" (IBC), 2021 EDITION, AS ADOPTED AND MODIFIED BY THE CITY OF EDMONDS, GOVERNS THE DESIGN AND CONSTRUCTION OF THIS PROJECT. REFERENCE TO A SPECIFIC SECTION IN THE CODE DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE ENTIRE MATERIALS REFERENCE STANDARDS NOTED BELOW. THE LATEST EDITION OF THE MATERIALS REFERENCE STANDARDS SHALL BE USED. SCOPE OF STRUCTURAL WORK: STRUCTURAL DESIGN OF SIGNS FOR A MEDICAL FACILITY. DEFINITIONS: THE FOLLOWING DEFINITIONS APPLY TO THESE GENERAL NOTES: • "STRUCTURAL ENGINEER OF RECORD" (EOR) — THE STRUCTURAL ENGINEER WHO IS LEGALLY RESPONSIBLE FOR STAMPING & SIGNING THE STRUCTURAL DOCUMENTS FOR THE PROJECT. THE FOR IS RESPONSIBLE FOR THE DESIGN OF THE PRIMARY STRUCTURAL SYSTEM. • "SPECIALTY STRUCTURAL ENGINEER" (SSE) — A LICENSED PROFESSIONAL ENGINEER, NOT THE EOR, WHO PERFORMS SPECIALTY STRUCTURAL ENGINEERING SERVICES NECESSARY TO COMPLETE THE STRUCTURE, WHO HAS EXPERIENCE AND TRAINING IN THE SPECIFIC SPECIALTY. THE GENERAL CONTRACTOR, SUBCONTRACTOR, OR SUPPLIER WHO IS RESPONSIBLE FOR THE DESIGN, FABRICATION AND INSTALLATION OF SPECIALTY —ENGINEERED ELEMENTS SHALL RETAIN THE SSE. SUBMITTALS SHALL BE STAMPED AND SIGNED BY THE SSE. DOCUMENTS STAMPED AND SIGNED BY THE SSE SHALL BE COMPLETED BY OR UNDER THE DIRECT SUPERVISION OF THE SSE WITH A PE OR SE LICENSE ISSUED BY THE STATE OF WASHINGTON. • "DEFERRED SUBMITTALS — DEFERRED SUBMITTAL IS ENGINEERING WORK TO BE DESIGNED —BY —OTHERS OR BIDDER —DESIGNED. DESIGN SOIL VALUES: ALLOWABLE SOIL BEARING PRESSURE 1,500 PSF DL + LL 2,000 PSF DL + ILL + SEISMIC/WIND SLABS —ON —GRADE & FOUNDATIONS: ALL SLABS —ON —GRADE AND FOUNDATIONS SHALL BEAR ON STRUCTURAL COMPACTED FILL OR COMPETENT NATIVE SOIL PER THE GEOTECHNICAL REPORT OR AS NOTED IN THESE DOCUMENTS. EXTERIOR PERIMETER FOOTINGS SHALL BEAR NOT LESS THAN 18 INCHES BELOW FINISH GRADE, OR AS REQUIRED BY THE GEOTECHNICAL ENGINEER AND THE BUILDING OFFICIAL. COMPACTION: UNLESS OTHERWISE SPECIFIED BY A GEOTECHNICAL ENGINEER, FOOTINGS SHALL BE PLACED ON COMPACTED MATERIAL AND SHALL BE WELL —GRADED GRANULAR MATERIAL WITH NO MORE THAN 5% PASSING A #200 SIEVE. FILLS PLACED SHALL BE IN MAXIMUM 8" LIFTS AND ALL BEARING SOILS SHALL BE COMPACTED TO 95% MAXIMUM DENSITY AT OPTIMUM MOISTURE CONTENT USING THE MODIFIED PROCTOR TEST. CAST —IN —PLACE CONCRETE REFERENCE STANDARDS: CONFORMS TO THE LATEST EDITIONS OF THE FOLLOWING: (1) ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY". (2) IBC CHAPTER 19. NOTE PRIORITIES: NOTES ON THE INDIVIDUAL DRAWINGS SHALL GOVERN OVER THESE GENERAL NOTES. STRUCTURAL DETAILS: THE STRUCTURAL DRAWINGS ARE INTENDED TO SHOW THE GENERAL CHARACTER AND EXTENT OF THE PROJECT AND ARE NOT INTENDED TO FIELD REFERENCE: THE CONTRACTOR SHALL KEEP A COPY OF ACI FIELD REFERENCE MANUAL, SP-15, "STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI SHOW ALL DETAILS OF THE WORK. 301) WITH SELECTED ACI AND ASTM REFERENCES." ARCHITECTURAL DRAWINGS: REFER TO THE ARCHITECTURAL DRAWINGS FOR INFORMATION INCLUDING, BUT NOT LIMITED TO: DIMENSIONS, ELEVATIONS, SLOPES, DOOR AND WINDOW OPENINGS, NON —BEARING WALLS, CURTAIN WALLS, STAIRS, ELEVATORS, CURBS, DRAINS, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES AND OTHER NONSTRUCTURAL ITEMS. STRUCTURAL RESPONSIBILITIES: THE FOR IS RESPONSIBLE FOR THE STRENGTH AND STABILITY OF THE PRIMARY STRUCTURE IN ITS COMPLETED STATE. CONTRACTOR RESPONSIBILITIES: THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION AND ALL JOB RELATED SAFETY STANDARDS SUCH AS OSHA AND WSHA. THE CONTRACTOR IS RESPONSIBLE FOR THE STRENGTH AND STABILITY OF THE STRUCTURE DURING CONSTRUCTION AND SHALL PROVIDE TEMPORARY SHORING, BRACING AND OTHER ELEMENTS REQUIRED TO MAINTAIN STABILITY UNTIL THE STRUCTURE IS COMPLETED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO BE FAMILIAR WITH THE WORK REQUIRED IN THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS FOR EXECUTING IT PROPERLY. DISCREPANCIES: IN CASE OF DISCREPANCIES BETWEEN THESE GENERAL NOTES, THE CONTRACT DRAWINGS AND SPECIFICATIONS, AND/OR REFERENCE STANDARDS, THE FOR SHALL DETERMINE WHICH SHALL GOVERN. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE FOR BEFORE PROCEEDING WITH THE WORK. ACCORDINGLY, ANY CONFLICT IN OR BETWEEN THE CONTRACT DOCUMENTS SHALL NOT BE A BASIS FOR ADJUSTMENT IN THE CONTRACT PRICE. SITE VERIFICATION: THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE PRIOR TO FABRICATION AND/OR CONSTRUCTION. CONFLICTS BETWEEN THE DRAWINGS AND ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE FOR BEFORE PROCEEDING WITH THE WORK. ALL UNDERGROUND UTILITIES SHALL BE DETERMINED BY THE CONTRACTOR PRIOR TO EXCAVATION OR DRILLING. ADJACENT UTILITIES: THE CONTRACTOR SHALL DETERMINE THE LOCATIONS OF ALL ADJACENT UNDERGROUND UTILITIES PRIOR TO EXCAVATION. ANY UTILITY INFORMATION SHOWN ON THE DRAWINGS AND DETAILS IS APPROXIMATE AND NOT NECESSARILY COMPLETE. DESIGN CRITERIA CONSTRUCTION LOADS: LOADS ON THE STRUCTURE DURING CONSTRUCTION SHALL NOT EXCEED THE DESIGN LOADS OR THE CAPACITY OF THE PARTIALLY COMPLETED CONSTRUCTION. WIND DESIGN: WIND LOAD IS DETERMINED USING CHAPTER 26 OF ASCE 7-16 IN ACCORDANCE WITH IBC SECTION 1609 WITH THE FOLLOWING FACTORS: BASIC WIND SPEED (3—SECOND GUST) V = 109 MPH WIND IMPORTANCE FACTOR IW = 1.0 RISK —CATEGORY = IV EXPOSURE CATEGORY = B GCPI = f0.18 DESIGN BASE SHEAR: DESIGN BASE SHEAR (WINDVERNED), V = 0.437K DEFERRED SUBMITTAL LOADS: ALL PRE—ENGINEERED, PRE —FABRICATED, PRE —MANUFACTURED, OR OTHER PRODUCTS DESIGNED BY OTHERS SHALL BE DESIGNED FOR THE TRIBUTARY DEAD AND LIVE LOADS PLUS WIND, EARTHQUAKE, AND COMPONENT, AND CLADDING LOADS WHEN APPLICABLE. DESIGN SHALL CONFORM TO THE PROJECT DRAWINGS AND SPECIFICATIONS, REFERENCE STANDARDS, AND GOVERNING CODE. SUBMITTALS SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT/EOR PRIOR TO ANY FABRICATION OR CONSTRUCTION FOR ALL STRUCTURAL ITEMS AS NOTED BELOW. THE CONTRACTOR SHALL REVIEW AND PLACE A SHOP DRAWINGS STAMP ON THE SUBMITTAL BEFORE FORWARDING TO THE EOR. SUBMITTALS SHALL BE MADE IN TIME TO PROVIDE A MINIMUM OF ONE WEEK FOR REVIEW BY THE EOR. ADDITIONAL SUBMITTALS REQUIRED FOR THIS PROJECT ARE SPECIFIED IN THE SPECIFIC SECTIONS BELOW. REFERENCE THE INDIVIDUAL MATERIAL SECTION FOR SPECIFIC INFORMATION TO BE INCLUDED IN THE SUBMITTAL. . IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEY SHALL BEAR THE SEAL AND SIGNATURE OF THE WASHINGTON STATE REGISTERED PROFESSIONAL ENGINEER WHO IS RESPONSIBLE FOR THE DESIGN.. CONCRETE REINFORCING GLULAM BEAMS PSL/LSLS TJI FRAMING ALTERNATES: PRODUCT OR MANUFACTURER COMPONENTS SPECIFIED IN THESE DRAWINGS ARE USED AS THE BASIS OF DESIGN FOR THIS PROJECT. ALTERNATES FOR SPECIFIED ITEMS MAY BE SUBMITTED TO THE FOR FOR REVIEW. HOWEVER, CONTRACTOR SHALL SUBMIT A CURRENT ICC—ESR/IAPMO—ER REPORT IDENTIFYING THAT AN ALTERNATIVE COMPONENT HAS THE SAME OR GREATER LOAD CAPACITY THAN THE SPECIFIED ITEM. SHOP DRAWING REVIEW: REVIEW BY THE ARCHITECT/EOR IS FOR GENERAL COMPLIANCE WITH THE DESIGN CONCEPT AND THE CONTRACT DOCUMENTS. DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE EOR, AND THEREFORE, MUST BE VERIFIED BY THE GENERAL CONTRACTOR. MARKINGS OR COMMENTS SHALL NOT BE CONSTRUED AS RELIEVING THE CONTRACTOR FROM COMPLIANCE WITH THE PROJECT PLANS AND SPECIFICATIONS, NOR DEPARTURES THEREFROM. THE CONTRACTOR REMAINS RESPONSIBLE FOR DETAILS AND ACCURACY; FOR CONFIRMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS; FOR SELECTING FABRICATION PROCESSES; FOR TECHNIQUES OF ASSEMBLY; AND FOR PERFORMING WORK IN A SECURE MANNER. WHEN SHOP DRAWINGS (COMPONENT DESIGN DRAWINGS) DIFFER FROM OR ADD TO THE REQUIREMENTS OF THE STRUCTURAL DRAWINGS THEY SHALL BE DESIGNED AND STAMPED BY THE RESPONSIBLE SSE. ALLOW ONE WEEK FOR FOR REVIEW TIME. NON—STRUCTURAL COMPONENTS: DESIGN, DETAILING AND ANCHORAGE OF ALL NONSTRUCTURAL COMPONENTS SHALL BE IN ACCORDANCE WITH ASCE 7-16, CHAPTER 13 AND THE PROJECT SPECIFICATIONS. NONSTRUCTURAL COMPONENTS DESIGNED BY OTHERS SHALL NOT INDUCE TORSIONAL LOADING INTO SUPPORTING STEEL STRUCTURAL MEMBERS WITHOUT ADDITIONAL BRACING OF THOSE MEMBERS TO ELIMINATE TORSIONAL FORCES. TORSIONAL BRACING SHALL BE DESIGNED BY THE NONSTRUCTURAL COMPONENT DESIGNER AND APPROVED BY THE EOR. ANCHORAGE TO THE PRIMARY STRUCTURE IS PER THE BIDDER —DESIGN CONTRACTOR OR SUPPLIER. TESTS & INSPECTIONS INSPECTIONS: ALL CONSTRUCTION IS SUBJECT TO INSPECTION BY THE BUILDING OFFICIAL IN ACCORDANCE WITH IBC SEC 110. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED INSPECTIONS WITH THE BUILDING OFFICIAL. SUBMIT COPIES OF ALL INSPECTION REPORTS TO THE ARCHITECT/EOR FOR REVIEW. THE BUILDING OFFICIAL MAY ACCEPT INSPECTION OF AND REPORTS BY APPROVED INSPECTION AGENCIES IN LIEU OF BUILDING OFFICIAL'S INSPECTIONS. THE CONTRACTOR SHALL OBTAIN APPROVAL OF BUILDING OFFICIAL TO USE THE THIRD —PARTY INSPECTION AGENCY AND CONTRACTOR SHALL ALERT THE ARCHITECT/EOR AS SUCH. SPECIAL INSPECTIONS: IN ADDITION TO THE INSPECTIONS REQUIRED BY IBC SEC 110, A SPECIAL INSPECTOR SHALL BE HIRED BY THE OWNER AS AN INDEPENDENT THIRD —PARTY INSPECTOR TO PERFORM THE SPECIAL INSPECTIONS PER IBC CH. 17. SPECIAL INSPECTIONS SHALL BE PERFORMED BY AN APPROVED TESTING AGENCY AS OUTLINED IN THE SPECIAL INSPECTION SCHEDULE, THE CONTRACT DOCUMENTS, AND/OR THE PROJECT SPECIFICATION. SPECIAL INSPECTIONS SHALL MEET THE REQUIREMENTS OUTLINES IN THE SPECIFIC MATERIALS SECTIONS OF IBC SEC 1705. THE CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE INSPECTIONS, PER THE CITY/BUILDING OFFICIAL REQUIREMENTS. STRUCTURAL OBSERVATIONS: WHEN REQUIRED BY THE PROVISIONS OF SECTION 1704.6.1 OR 1704.6.2, THE OWNER OR THE OWNER'S AUTHORIZED AGENT SHALL EMPLOY THE FOR TO PERFORM STRUCTURAL OBSERVATIONS. STRUCTURAL OBSERVATIONS DO NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS IN SECTION 110 OR THE SPECIAL INSPECTIONS IN SECTION 1705 OR OTHER SECTIONS IN THE CODE. CONCRETE MIXTURES: CONFORM TO ACI 318 CHAPTER 19 "CONCRETE: DESIGN AND DURABILITY REQUIREMENTS." MATERIALS: CONFORM TO ACI 318 CHAPTERS 19 & 20. SUBMITTALS: PROVIDE ALL SUBMITTALS REQUIRED BY ACI 301 SEC 4.1.2. SUBMIT MIX DESIGNS FOR EACH MIX IN THE TABLE BELOW. TABLE OF MIX DESIGN REQUIREMENTS MEMBER STRENGTH TEST AGE MAXIMUM EXPOSURE MAX MINIMUM TYPE/LOCATION (PSI) (DAYS) AGGREGATE CLASSIFICATION W/C RATIO AIR CONTENT FDN — RESIDENTIAL FIG 3500 28 F1, CO 0.45 4.5% MIX DESIGN NOTES: (1) W/C RATIO: WATER—CEMENTITIOUS MATERIAL RATIOS SHALL BE BASED ON THE TOTAL WEIGHT OF CEMENTITIOUS MATERIALS. RATIOS NOT SHOWN IN THE TABLE ABOVE ARE CONTROLLED BY STRENGTH REQUIREMENTS. (2) CEMENTITIOUS CONTENT: A. THE USE OF FLY ASH, OTHER POZZOLANS, SILICA FUME, OR SLAG SHALL CONFORM TO ACI 301 SEC 4.2.2 9B. MAXIMUM AMOUNT OF FLY ASH SHALL BE 20% OF TOTAL CEMENTITIOUS CONTENT UNLESS REVIEWED AND APPROVED OTHERWISE BY EOR. B. FOR CONCRETE USED IN ELEVATED FLOORS, PORTLAND CEMENT CONTENT SHALL CONFORM TO ACI 301 SEC 4.2.2.1. ACCEPTANCE OF LOWER CEMENT CONTENT IS CONTINGENT ON PROVIDING SUPPORTING DATA TO THE FOR FOR REVIEW AND ACCEPTANCE. (1) AIR CONTENT: CONFORM TO ACI 301 SEC 4.2.2.4. HORIZONTAL EXTERIOR SURFACES IN CONTACT WITH THE SOIL REQUIRE ENTRAINED AIR. USE EXPOSURE CATEGORY FO, SO, WO, AND CO UNLESS NOTED OTHERWISE. TOLERANCE IS +/— 1.5%. AIR CONTENT SHALL BE MEASURED AT POINT OF PLACEMENT. (2) EXPOSURE CLASSIFICATION: THE MIX DESIGN PROVIDED SHALL MEET THE REQUIREMENTS OF ACI 318 CHAPTER 19, BASED ON THE EXPOSURE CLASSIFICATION INDICATED IN THE TABLE ABOVE. (3) SLUMP: UNLESS OTHERWISE SPECIFIED OR PERMITTED, CONCRETE SHALL HAVE AT THE POINT OF DELIVERY, A SLUMP OF 4" +/— 1". FOR ADDITIONAL CRITERIA, REFERENCE ACI 301 SEC 4.2.2.2. (4) NON —CHLORIDE ACCELERATOR: NON —CHLORIDE ACCELERATING ADMIXTURE MAY BE USED IN CONCRETE SLABS PLACED AT AMBIENT TEMPERATURES BELOW 50F AT THE CONTRACTOR'S OPTION. FORMWORK: CONFORM TO ACI 301 SEC 2 "FORMWORK AND FORM ACCESSORIES." REMOVAL OF FORMS SHALL CONFORM TO SEC 2.3.2 EXCEPT STRENGTH INDICATED IN SEC 2.3.2.5 SHALL BE 0.75 F'C. MEASURING, MIXING, AND DELIVERY: CONFORM TO ACI 301 SEC 4.3. HANDLING, PLACING, CONSTRUCTING, AND CURING: CONFORM TO ACI 301 SEC 5. EMBEDDED ITEMS: POSITION AND SECURE IN PLACE EXPANSION JOINT MATERIAL, ANCHORS AND OTHER STRUCTURAL AND NON—STRUCTURAL EMBEDDED ITEMS BEFORE PLACING CONCRETE. CONTRACTOR SHALL REFER TO MECHANICAL, ELECTRICAL, PLUMBING, AND ARCHITECTURAL DRAWINGS AND COORDINATE ALL OTHER EMBEDDED ITEMS. GROUTED REBAR AND ANCHOR BOLTS: FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS: DRILL HOLES IN EXISTING CONCRETE TO DEPTH NOTED ON PLANS OR TO DEPTH AS NECESSARY TO DEVELOP THE STRENGTH OF THE REBAR LISTED IN THE MANUFACTURER'S ICC—ESR/IAPMO—ER REPORT. DRILL THE HOLE DIAMETER PER MANUFACTURER'S INSTRUCTIONS. ROUGHEN SIDES OF HOLES BY PERCUSSIVE DRILLING METHODS. HOLES SHALL BE BRUSHED AND BLOWN FREE OF DEBRIS AND SURFACE RESIDUE BEFORE GROUTING OPERATION. SPECIAL INSPECTION IS REQUIRED. CONCRETE REINFORCEMENT REFERENCE STANDARDS: CONFORM TO: (1) ACI 301 "STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE."SEC 3" REINFORCEMENT, AND REINFORCEMENT SUPPORTS." (2) IBC CHAPTER 19, CONCRETE. (3) ACI 318 AND ACI 318R. (4) ACI SP-66 "ACI DETAILING MANUAL" INCLUDING ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT." (5) CRSI MSP-2 "MANUAL OF STANDARD PRACTICE." (6) ANSI/AWS D1.4 "STRUCTURAL WELDING CODE — REINFORCING STEEL." SUBMITTALS: CONFORM TO ACI 301 SEC 3.1.1 "SUBMITTALS, DATA, AND DRAWINGS." SUBMIT PLACING DRAWINGS SHOWING FABRICATION DIMENSIONS AND LOCATIONS FOR PLACEMENT OF REINFORCEMENT AND REINFORCEMENT SUPPORTS. MATERIALS: REINFORCING BARS WELDABLE REINFORCING BARS SMOOTH WELDED WIRE FABRIC DEFORMED WELDED WIRE FABRIC BAR SUPPORTS TIE WIRE ASTM A615, GRADE 60, DEFORMED BARS. ASTM A706, GRADE 60, DEFORMED BARS. ASTM A185 ASTM A497 CRSI MSP-2, CHAPTER 3 "BAR SUPPORTS." 16.5 GAGE OR HEAVIER, BLACK ANNEALED. FABRICATION: CONFORM TO ACI 301, SEC 3.2.2 "FABRICATION," AND ACI SP-66 "ACI DETAILING MANUAL." WELDING: BARS SHALL NOT BE WELDED UNLESS AUTHORIZED. WHEN AUTHORIZED, CONFORM TO ACI 301, SEC 3.2.2.2. "WELDING" AND PROVIDE ASTM A706, GRADE 60 REINFORCEMENT. PLACING: CONFORM TO ACI 301, SEC 3.3.2 "PLACEMENT." PLACING TOLERANCES SHALL CONFORM TO SEC 3.3.2.1 "TOLERANCES." CONCRETE COVER: CONFORM TO THE FOLLOWING COVER REQUIREMENTS FROM ACI 301, TABLE 3.3.2.3. CONCRETE CAST AGAINST EARTH 3" CONCRETE EXPOSED TO EARTH OR WEATHER (#5 & SMALLER) 1-1/2" CONCRETE EXPOSED TO EARTH OR WEATHER (#6 & LARGER) 2" BARS IN SLABS AND WALLS 3/4" THE FOLLOWING STRUCTURAL OBSERVATIONS ARE REQUIRED TO BE COMPLETED BY THE FOR DURING CONSTRUCTION. THE FOR IS TO BE NOTIFIED WHEN ELEMENTS LISTED BELOW ARE SUBSTANTIALLY COMPLETE AND READY FOR OBSERVATION. CONTACT THE FOR A MINIMUM OF (2) BUSINESS DAYS PRIOR TO COVERING THE WORK SPLICES & DEVELOPMENT LENGTH: CONFORM TO ACI 301, SEC 3.3.2.7. REFER TO "LAP SPLICE & DEVELOPMENT SCHEDULE" ON PLANS FOR TYPICAL SPLICES. THE SPLICES AND DEVELOPMENT LENGTHS INDICATED ON INDIVIDUAL SHEETS CONTROL OVER THE SCHEDULE. USE CLASS B SPLICES UNLESS OTHERWISE NOTED. SOILS AND FOUNDATIONS MECHANICAL CONNECTIONS MAY BE USED WHEN APPROVED BY THE EOR. REFERENCE STANDARDS: CONFORM TO IBC CHAPTER 18 "SOILS AND FOUNDATIONS." GEOTECHNICAL REPORT: RECOMMENDATIONS CONTAINED IN "UPDATED GEOTECHNICAL ENGINEERING STUDY RAINIER CREST DIVISION II (LOTS 1-7) PROPOSED RESIDENTIAL DEVELOPMENT" BY EARTH SOLUTIONS NW LLC, DATED FEBRUARY 2, 2015 & UPDATED MARCH 17, 2017 WAS USED FOR DESIGN. GEOTECHNICAL INSPECTION: THE GEOTECHNICAL ENGINEER OR THIRD —PARTY INSPECTOR SHALL INSPECT ALL PREPARED SOIL BEARING SURFACES PRIOR TO PLACEMENT OF CONCRETE AND REINFORCING STEEL AND PROVIDE A LETTER TO THE OWNER STATING THAT SOILS ARE ADEQUATE TO SUPPORT THE "ALLOWABLE FOUNDATION PRESSURE" SHOWN BELOW. SOIL COMPACTION SHALL BE SUPERVISED BY AN APPROVED TESTING AGENCY OR GEOTECHNICAL ENGINEER. SITE SOIL CONDITIONS, FILL PLACEMENT, AND LOAD —BEARING REQUIREMENTS SHALL BE AS REQUIRED BY SECTION 1705.6 AND TABLE 1705.6. ASSUMED VALUES SHALL BE FIELD VERIFIED BY THE BUILDING OFFICIAL OR THE GEOTECHNICAL ENGINEER PRIOR TO PLACING CONCRETE. THE BUILDING OFFICIAL SHALL BE PERMITTED TO WAIVE THE REQUIREMENT FOR A GEOTECHNICAL INVESTIGATION WHERE SATISFACTORY DATA FROM ADJACENT AREA IS AVAILABLE THAT DEMONSTRATES AN INVESTIGATION IS NOT NECESSARY FOR ANY OF THE CONDITIONS IN SECTIONS 1803.5.1 — 1803.5.6 AND SECTIONS 1803.5.10 — 1803.5.11. REINFORCING BAR CHART BAR SIZE TOP BARS OTHER BARS DEVELOPMENT LENGTH, Ld #4 33" 25" 19" #5 41 " 31 " 24" #6 48" 37„ 29„ #7 70" 54" 41" #8 80" 62" 47" #9 90" 70" 53" #10 100" 78" 59" #11 110" 85" 65" SCHEDULE NOTES: 1. ALL LENGTHS ARE IN INCHES AND FOR f'c= 4,000 PSI. 2. "TOP BARS" ARE HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 12" OF CONIC IS CAST IN THE MEMBER BELOW THE BAR. 3. FOR f'c = 5,000 PSI USE 90% OF LENGTH. 4. FOR f'c = 3,000 PSI USE 115% OF LENGTH. FIELD BENDING: CONFORM TO ACI 301 SEC 3.3.2.8. "FIELD BENDING OR STRAIGHTENING." BAR SIZES #3 THROUGH #5 MAY BE FIELD BENT COLD THE FIRST TIME. OTHER BARS REQUIRE PREHEATING. DO NOT TWIST BARS. STRUCTURAL STEEL DESIGN STANDARDS: STRUCTURAL STEEL FOR THIS PROJECT IS DESIGNED IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC STEEL CONSTRUCTION MANUAL. REFERENCE STANDARDS: CONFORM TO: (1) AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS & BRIDGES." (2) RCSC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS." (3) AWS D1.1 "STRUCTURAL WELDING CODE — STEEL." (4) AWS D1.3 "STRUCTURAL WELDING CODE — SHEET STEEL." (5) AWS D1.8 "STRUCTURAL WELDING CODE — SEISMIC SUPPLEMENT." (6) AISC 341 "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS." (7) ASCE 3 "STANDARD FOR THE STRUCTURAL DESIGN OF COMPOSITE SLABS." WELDING: CONFORM TO AWS D1.1, D1.3 & D1.8. WELDERS SHALL BE CERTIFIED IN ACCORDANCE WITH AWS AND WABO REQUIREMENTS. USE E70 ELECTRODES OF TYPE REQUIRED FOR MATERIALS TO BE WELDED. SHOP PAINTING: CONFORM TO AISC 360, AISC SPECIFICATION SEC M3, AND AISC CODE SEC 6.5. DO NOT PAINT STEEL TO BE EMBEDDED IN CONCRETE. DO NOT PAINT SURFACES TO BE FIELD WELDED OR WHERE SLIP —CRITICAL BOLTS ARE SPECIFIED. ALL OTHER INTERIOR STEEL SHALL BE PAINTED WITH ONE COAT OF GREY SHOP PRIMER. ALL EXPOSED EXTERIOR STEEL SHALL BE PAINTED WITH AN EXTERIOR MULTI —COAT SYSTEM AS PER THE ARCHITECT OR PROJECT SPECIFICATIONS. FIELD TOUCH—UP PAINTING SHALL BE WITH PRIMER FOR EXPOSED INTERIOR SURFACES AND AS PER THE ARCHITECT OR PROJECT SPECIFICATIONS FOR EXPOSED EXTERIOR SURFACES. GALVANIZING: ALL EXPOSED STEEL OUTSIDE THE BUILDING ENVELOPE SHALL BE HOT —DIPPED GALVANIZED. APPLY FIELD TOUCH—UPS PER PROJECT SPECIFICATIONS. ERECTION: CONFORM TO AISC SPECIFICATION SEC M4 "ERECTION" AND AISC CODE SEC 7 "ERECTION." STEEL WORK SHALL BE CARRIED UP TRUE AND PLUMB WITHIN THE LIMITS DEFINED IN AISC CODE SEC 7.11. BRACING: THE CONTRACTOR SHALL PROVIDE TEMPORARY BRACING BY AISC SPECIFICATION SEC M4.2 "BRACING" AND AISC CODE SEC 7.10 "TEMPORARY SUPPORT OF STRUCTURAL STEEL FRAMES." LE 000000000000000000000000000000000000000000000 REVIEWED BY CITY OF EDMONDS BUILDING DEPARTMENT RECEIVED Jul 29 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT w Q 0 co /L^ cV W N N LIJLV— z c� � CD W z 0 00a- m Q� o 0 U O7 LLi v i z J D- Q W z J L j > L� z z W z 00 o CD 00 oo w J w � Nz � g D_ m 07/19/2024 L�J (_c) 0 CD N z 0 m < CIL U Z 0 Z U/ 0 Q = 0cr- U� W W 0 _ z W 0—) W M >< 111 C 0 � z Cal L-LJ L-LJ CHK BY: DRW BY: L2E L2E SCALE: AS SHOWN BAR = 1" FULL SIZE DATE: 2024.07.12 III] :RI[16�►ZQ101FA BLD2024-0979 SHEET: 1 OF 2 DWG N0: s l O O 3 8" THICK BASE PLATE (4 5/8" 0 36KSI F1554 ANCHOR BOLTS PER BASE PLATE PIPE 3 X-STRONG d ° e ° .,d ° d r--' ----- Q ---- — e --—' --- d -- ---.dam----A'---------- d. d ° ° d ° 11 5'-0" D SOLETAI L SCALE: 3/4"=1 ISOLATED FTG z 0 U ry cn z 0 U ry 0 W 0 z I w U w U SIGN ABOVE nolE-nlT AS SHOWN EEP CONCRETE FOOTING (7) #5 T&B TRANSVERSE :,,4 (3) #5 T&B LONGITUDINAL S3( GRADE 3" CLR TYP q LENGTH PER 1/S300 2 D ETA L SCALE: 3/4"=1 '-0" ISOLATED FTG - LONGITUDINAL SECTION POST PER 1/S300 BASE PLATE PER 1/S300 HIGH STRENGTH NON SHRINK GROUT PAD, 2" THICK MAX CONCRETE FOUNDATION PER 1/S300 LIJ m d LLJ m w U m oz 4 z �o GRADE 00 1 I1 I II II ° d 4-4 d . c d d e U a ;�, III IIIIIIIII-III f 111 111 111 11- 3" CLR TYP WIDTH PER 1/S300 _,---POST PER 1/S300 BASE PLATE PER 1/S300 HIGH STRENGTH NON SHRINK GROUT PAD, 2" THICK MAX CONCRETE FOUNDATION PER 1/S300 REINFORCING PER 2/S300 =1-1 I-1 1— III U L.L.I d LLJ D AlETL 3 SCALE: 3/4"=1'- 0" ISOLATED FTG - TRANSVERSE SECTION 6" BASE PLATE PER 1/S300 1 1 BOLTS 1/S300 I I I POST PER 1/S300 I I I I FULL PEN SECTION C-C D ETAI L 4 SCALE: 3'1 1 0" BASE PLATE RECEIVED Jul 29 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-0979 z 0 cf) w ry w Q 0 co ^ CV W N N W z U I� � CD L Z 0 U c O7 bi vi z J D- zQLL,Jw z > LU z z z � o W (/� U CV W � Q J m 07/19/2024 1 CAI O 00 Q U� U� z 0 C3 z U� O U i =0 Q �w � w 0 0 w 0-) 3: 0-) U� 0 0 (_o 7- N CHK BY: DRW BY: L2E I L2E SCALE: AS SHOWN BAR = 1" FULL SIZE DATE: 2024.07.12 JOB NO: 24-097 SHEET: 3 OF 2 DWG NO: S300 L2 ENGINEERS, LLC 17848 NE 198th Place Woodinville, WA 98072 Swedish Signs 21600 Highway 99 Edmonds, WA 98026 Division 10 Signs Jordan Weiner 24-097 Structural Calculations 07/19/2024 Iz L2 Engineers, LLC 1 17848 NE 1981b Place, Woodinville, WA 98072 1 206-251-2346 L2 ENGINEERS, LLC 17848 NE 198th Place Woodinville, WA 98072 Table of Contents • Design Basis and Loads • Calculations Iz L2 Engineers, LLC 1 17848 NE 1981b Place, Woodinville, WA 98072 1 206-251-2346 L2 ENGINEERS, LLC 17848 NE 198th Place Woodinville, WA 98072 Design Basis and Loads Location Latitude 47.802861 N Longitude 122.330730 W Elevation 343 ft (NAVD 88) [ASCE Hazards Report] Iz Building Code The applicable design code is the 2021 International Building Code (IBC) as adopted by Washington State. [City of Edmunds Municipal Code] General Load Standard: 2021 IBC Chapter 16 Risk Category: IV Exposure: B Soil Class: D - Default Loads Dead: 20 psf assumption Wind: V = 109 mph [ASCE Design Hazards Report] Geotechnical Presumptive load -bearing values of soils have been assumed to be 1500 psf per IBC Section 1806, Table 1806.2 [Presumptive Load -Bearing Values]. This load -bearing value of soils is for Class 5 materials (CL, ML, MH, and CH). Materials Concrete: Compressive strength, Fc = 3500 psi (28-days) Exposure: F1 SO WO C1 Concrete reinforcement: fs = 60 ksi [ASTM A615, Gr. 60] L2 Engineers, LLC 1 17848 NE 1981b Place, Woodinville, WA 98072 1 206-251-2346 ASCE AMERICAN SOCIM OF CIVIL ENGINEERS Address: 21600 Highway 99 Edmonds, Washington 98026 ASCE Hazards Report Standard: ASCE/SE17-16 Latitude: 47.802942 Risk Category: IV Longitude:-122.33072 Soil Class: D - Default (see Elevation: 342.84387519016377 ft Section 11.4.3) (NAVD 88) II•�iuhr s 212M St SW 17 Cat` F' AM < L I IGIh SI SW SrWIM Ed—J. Ho 1pr1 ; Y F.W. �� 4 JI SN O S r u/,d,Ian I:7m tir• — c Wind I i E nmona� MIY� Ibw� ON i �• CM CllnrF lli � i .. INbmb t 1 Kitkland t Results: Wind Speed 109 Vmph 10-year MRI 67 Vmph 25-year MRI 74 Vmph 50-year MRI 78 Vmph 100-year MRI 83 Vmph Data Source: ASCE/SEI 7-16, Fig. 26.5-1 D and Figs. CC.2-1—CC.2-4, and Section 26.5.2 Date Accessed: Wed Jul 10 2024 Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 1.6% probability of exceedance in 50 years (annual exceedance probability = 0.00033, MRI = 3,000 years). Site is not in a hurricane -prone region as defined in ASCE/SEI 7-16 Section 26.2. https://ascehazardtool.org/ Page 1 of 3 Wed Jul 10 2024 E® AMERICAN SOCIETY OF CIVIL ENGINEERS Seismic Site Soil Class: D - Default (see Section 11.4.3) Results: SS 1.282 Sp, N/A S, 0.451 TL 6 Fa 1.2 PGA: 0.546 Fv N/A PGA M : 0.656 S MS 1.539 F PGA 1.2 SM, N/A le 1.5 SIDS : 1.026 Cv 1.356 Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8. Data Accessed: Wed Jul 10 2024 Date Source: USGS Seismic Design Maps hftps:Hascehazardtool.org/ Page 2 of 3 Wed Jul 10 2024 L2 ENGINEERS, LLC 17848 NE 198th Place Woodinville, WA 98072 Calculations Iz L2 Engineers, LLC 1 17848 NE 1981b Place, Woodinville, WA 98072 1 206-251-2346 5 Vr---OZSH SFsNs 6R4vrrr Lo.+O 14SUMC ZO P.SF DE*o Loon 22.5 Pi-" Z 2. 5 1-20 = Lf-5o 413 DG,fo Loan LAreR,#L La.-o : VrND Lo,4D77AI& COA/MOL-S Jey =A✓S PE.CTrot/. USED 4-5CE 7 -16, CH fPrEIR 2-y Foe. Cf LcoL.*rron/s . RISK 6krEGoay WTvo SpEEO : /01 Ki = 0. gS K,.f = I. oo k� = 1. 00 k2= 0.5 ? 4$CE 7 -16, i. 5 -1 ,,-i p k hSC.E 7 H*E.*RO Tool. k5e-E 7-16, St-CTrav 2.6-L ASCC 7-16, StcTra✓ 2-6. 7 ASGE 746, SEcrzov 2d. IF ASCE 746, 5Ec7roal ZL.I A-SGE 7-14, S1Tso�J ZG.II ASCE 7-16, 0.COZ56[x�1CK�][�][�CE� � Z ISLE 7 l4, E&vaTroA✓ = o.00zsC[d.s�Jri.o]�o.s51G.o31o�2 = 14. 7-Lt Cp Fitcw4 4-SCE 7- l6, FrG 21.3-1 8/6 = 0.1 051 0 5/5 = O- 5 C-f=1.55 F=Y-HGL4:4s = Zz.s \I',+LO._c 6/C -rr's M oR E CAS 0AV' -TZVE k5C- E 606C)T511 SZGNS 24-Oct ? DALAI RH.ULM /gdwC t! i 00C % o OZVO .4SC E 7 - l6, Fie. Zcy. 3 I /I = 437 , 2.7S r4 = 1201,1 A-1{.s L2 ENGINEERS, LLC 17848 NE 198th Place Woodinville, WA 98072 Design Component Key 5/16" THICK BASE PLATE (4) 5/8" 0 36 KSI L-BOLT 0 3XS PIPE POST Fr=7 602420 L2 Engineers, LLC 1 17848 NE 1981b Place, Woodinville, WA 98072 1 206-251-2346 Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: General Footing Project File: 24-097 Swedish Signs.ec6 LIC# : KW-06016908, Build:20.23.10.02 L2 Engineers (c) ENERCALC INC 1983-2023 DESCRIPTION: 602420 Code References Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Material Properties Soil Design Values fc : Concrete 28 day strength = 3.50 ksi Allowable Soil Bearing = 1.50 ksf fy : Rebar Yield = 60.0 ksi Soil Density = 110.0 pcf Ec : Concrete Elastic Modulus = 3,122.0 ksi Increase Bearing By Footing Weight = No Concrete Density = 145.0 pcf Soil Passive Resistance (for Sliding) = 250.0 pcf (P Values Flexure = 0.90 Soil/Concrete Friction Coeff. = 0.30 Shear = 0.750 Increases based on footing Depth Analysis Settings Footing base depth below soil surface = 1.50 ft Min Steel % Bending Reinf. = Allow press. increase per foot of depth = ksf Min Allow % Temp Reinf. = 0.00180 when footing base is below = ft Min. Overturning Safety Factor = 1.0 : 1 Min. Sliding Safety Factor = 1.0 : 1 Increases based on footing plan dimension Add Ftg Wt for Soil Pressure Yes Allowable pressure increase per foot of depth Use ftg wt for stability, moments & shears Yes = ksf Add Pedestal Wt for Soil Pressure No when max. length or width is greater than = ft Use Pedestal wt for stability, mom & shear No Dimensions Width parallel to X-X Axis = 2.0 ft Length parallel to Z-Z Axis = 5.0 ft Z Footing Thickness = 20.0 in Pedestal dimensions... Xo X px : parallel to X-X Axis = in pz : parallel to Z-Z Axis =_ in Height in M Rebar Centerline to Edge of Concrete... at Bottom of footing = 3.0 in 0 Reinforcing 240° Jw Bars parallel to X-X Axis Number of Bars - 7 Reinforcing Bar Size = # 5 Bars parallel to Z-Z Axis Number of Bars = 3 ---_-_-_ Reinforcing Bar Size = # 5 _ _ Bandwidth Distribution Check ACI15.4.4.2 7 - # 5 BarsDirection �HNEN Requiring Closer Separation _ }'=='" Bars along X-X Axis M # Bars required within zone 57.1 % X- --Section Looking -to Z # Bars required on each side of zone 42.9 % Applied Loads P : Column Load OB : Overburden M-xx M-zz V-x V-z D 0.450 Lr L S W E H k ksf k-ft 1.205 k-ft 0.4370 k k Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: General Footing Project File: 24-097 Swedish Signs.ec6 LIC# : KW-06016908, Build:20.23.10.02 L2 Engineers (c) ENERCALC INC 1983-2023 DESCRIPTION: 602420 DESIGN SUMMARY Min. Ratio Item Applied Capacity Governing Load Combination PASS 0.4648 Soil Bearing 0.6972 ksf 1.50 ksf +0.60D+0.60W about Z-Z axis PASS n/a Overturning - X-X 0.0 k-ft 0.0 k-ft No Overturning PASS 1.483 Overturning - Z-Z 1.160 k-ft 1.720 k-ft +0.60D+0.60W PASS 7.331 Sliding - X-X 0.2622 k 1.922 k +0.60D+0.60W PASS n/a Sliding - Z-Z 0.0 k 0.0 k No Sliding PASS n/a Uplift 0.0 k 0.0 k No Uplift PASS 0.008552 Z Flexure (+X) 0.2779 k-ft/ft 32.489 k-ft/ft +0.90D+W PASS 0.004336 Z Flexure (-X) 0.1409 k-ft/ft 32.489 k-ft/ft +1.20D+W PASS 0.005665 X Flexure (+Z) 0.1969 k-ft/ft 34.755 k-ft/ft +1.40D PASS 0.005665 X Flexure (-Z) 0.1969 k-ft/ft 34.755 k-ft/ft +1.40D PASS n/a 1-way Shear (+X) 0.0 psi 88.741 psi n/a PASS 0.0 1-way Shear (-X) 0.0 psi 0.0 psi n/a PASS 0.003828 1-way Shear (+Z) 0.3397 psi 88.741 psi +1.40D PASS 0.003828 1-way Shear (-Z) 0.3397 psi 88.741 psi +1.40D PASS n/a 2-way Punching 0.7162 psi 88.741 psi +0.90D+W \ Top reinforcing \ mat required (see 'Bending' tab). ! Hand check required for anchor pullout. Detailed Results Soil Bearing Rotation Axis & Xecc Zecc Actual Soil Bearing Stress @ Location Actual / Allow Load Combination... Gross Allowable (in) Bottom, -Z Top, +Z Left, -X Right, +X Ratio X-X, D Only 1.50 n/a 0.0 0.2867 0.2867 n/a n/a 0.191 X-X, +D+0.60W 1.50 n/a 0.0 0.2867 0.2867 n/a n/a 0.191 X-X, +D+0.450W 1.50 n/a 0.0 0.2867 0.2867 n/a n/a 0.191 X-X, +0.60D+0.60W 1.50 n/a 0.0 0.1720 0.1720 n/a n/a 0.115 X-X, +0.60D 1.50 n/a 0.0 0.1720 0.1720 n/a n/a 0.115 Z-Z, D Only 1.50 0.0 n/a n/a n/a 0.2867 0.2867 0.191 Z-Z, +D+0.60W 1.50 4.856 n/a n/a n/a 0.0 0.6384 0.426 Z-Z, +D+0.450W 1.50 3.642 n/a n/a n/a 0.02828 0.5451 0.363 Z-Z, +0.60D+0.60W 1.50 8.093 n/a n/a n/a 0.0 0.6972 0.465 Z-Z, +0.60D 1.50 0.0 n/a n/a n/a 0.1720 0.1720 0.115 Overturning Stability Rotation Axis & Load Combination... Overturning Moment Resisting Moment Stability Ratio Status X-X, D Only None 0.0 k-ft Infinity OK X-X, +D+0.60W None 0.0 k-ft Infinity OK X-X, +D+0.450W None 0.0 k-ft Infinity OK X-X, +0.60D+0.60W None 0.0 k-ft Infinity OK X-X, +0.60D None 0.0 k-ft Infinity OK Z-Z, D Only None 0.0 k-ft Infinity OK Z-Z, +D+0.60W 1.160 k-ft 2.867 k-ft 2.471 OK Z-Z, +D+0.450W 0.870 k-ft 2.867 k-ft 3.295 OK Z-Z, +0.60D+0.60W 1.160 k-ft 1.720 k-ft 1.483 OK Z-Z, +0.60D None 0.0 k-ft Infinity OK Sliding Stability All units k Force Application Axis Load Combination... Sliding Force Resisting Force Stability Ratio Status X-X, D Only 0.0 k 2.266 k No Sliding OK X-X, +D+0.60W 0.2622 k 2.266 k 8.643 OK X-X, +D+0.450W 0.1967 k 2.266 k 11.524 OK X-X, +0.60D+0.60W 0.2622 k 1.922 k 7.331 OK X-X, +0.60D 0.0 k 1.922 k No Sliding OK Z-Z, D Only 0.0 k 1.423 k No Sliding OK Z-Z, +D+0.60W 0.0 k 1.423 k No Sliding OK Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: General Footing Project File: 24-097 Swedish Signs.ec6 LIC# : KW-06016908, Build:20.23.10.02 L2 Engineers (c) ENERCALC INC 1983-2023 DESCRIPTION: 602420 Sliding Stability All units k Force Application Axis Load Combination... Sliding Force Resisting Force Stability Ratio Status Z-Z, +D+0.450W 0.0 k 1.423 k No Sliding OK Z-Z, +0.60D+0.60W 0.0 k 1.079 k No Sliding OK Z-Z, +0.60D 0.0 k 1.079 k No Sliding OK Footing Flexure Flexure Axis & Load Combination X-X, +1.40D X-X, +1.40D X-X, +1.20D X-X, +1.20D X-X, +1.20D+0.50W X-X, +1.20D+0.50W X-X, +1.20D+W X-X, +1.20D+W X-X, +0.90D+W X-X, +0.90D+W X-X, +0.90D X-X, +0.90D Z-Z, +1.40D Z-Z, +1.40D Z-Z, +1.20D Z-Z, +1.20D Z-Z, +1.20D+0.50W Z-Z, +1.20D+0.50W Z-Z, +1.20D+W Z-Z, +1.20D+W Z-Z, +0.90D+W Z-Z, +0.90D+W Z-Z, +0.90D Z-Z, +0.90D One Way Shear Load Combination... +1.40D +1.20D +1.20D+0.50W +1.20D+W +0.90D+W +0.90D Two -Way "Punching" Shear Load Combination... +1.40D +1.20D +1.20D+0.50W +1.20D+W +0.90D+W +0.90D Mu Side Tension As Req'd Gvrn. As Actual As Phi*Mn k-ft Surface in^2 inA2 inA2 k-ft 0.1969 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1969 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1688 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.1266 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1266 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.1266 +Z Bottom 0.4320 AsMin 0.4650 34.755 0.1266 -Z Bottom 0.4320 AsMin 0.4650 34.755 0.03150 -X Bottom 0.4320 AsMin 0.4340 32.489 0.03150 +X Bottom 0.4320 AsMin 0.4340 32.489 0.0270 -X Bottom 0.4320 AsMin 0.4340 32.489 0.0270 +X Bottom 0.4320 AsMin 0.4340 32.489 0.06966 -X Top 0.4320 AsMin 0.4340 32.489 0.1237 +X Bottom 0.4320 AsMin 0.4340 32.489 0.1409 -X Top 0.4320 AsMin 0.4340 32.489 0.2458 +X Bottom 0.4320 AsMin 0.4340 32.489 0.1088 -X Top 0.4320 AsMin 0.4340 32.489 0.2779 +X Bottom 0.4320 AsMin 0.4340 32.489 0.02025 -X Bottom 0.4320 AsMin 0.4340 32.489 0.02025 +X Bottom 0.4320 AsMin 0.4340 32.489 Vu@-X Vu@+X 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi 0.00 psi Vu @ -Z Vu @ +Z Vu: Max 0.34 psi 0.34 psi 0.34 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.29 psi 0.22 psi 0.22 psi 0.22 psi 0.22 psi 0.22 psi 0.22 psi Vu Phi*Vn Vu / Phi*Vn 0.44 psi 177.48psi 0.002469 0.38 psi 177.48psi 0.002116 0.38 psi 177.48psi 0.002116 0.53 psi 177.48psi 0.003012 0.72 psi 177.48psi 0.004035 0.28 psi 177.48psi 0.001587 Status OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK Phi Vn Vu / Phi*Vn Status 88.74 psi 0.00 OK 88.74 psi 0.00 OK 88.74 psi 0.00 OK 88.74 psi 0.00 OK 88.74 psi 0.00 OK 88.74 psi 0.00 OK All units k Status OK OK OK OK OK OK Steel Column LIC# : KW-06016908, Build:20.23.10.0, DESCRIPTION: 3xS Post Code References Calculations per AISC 360-16, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : IBC 2021 General Information Steel Section Name : Pipe3xs Analysis Method : Allowable Strength Steel Stress Grade Fy : Steel Yield 36.0 ksi E : Elastic Bending Modulus 29,000.0 ksi Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: Project File: 24-097 Swedish Signs.ec6 Overall Column Height 5.0 ft Top & Bottom Fixity Top Fixed, Bottom Fixed Brace condition : Unbraced Length for buckling ABOUT X-X Axis = 5.0 ft, K = 1.0 Unbraced Length for buckling ABOUT Y-Y Axis = 5.0 ft, K = 1.0 Applied Loads Service loads entered. Load Factors will be applied for calculations. Column self weight included : 51.50 Ibs * Dead Load Factor AXIAL LOADS ... Weight of Sign: Axial Load at 5.0 ft, D = 0.450 k Wind Force: Axial Load at 2.750 ft, W = 0.4370 k DESIGN SUMMARY Bending & Shear Check Results PASS Max. Axial+Bending Stress Ratio = 0.01448 : 1 Maximum Load Reactions.. Load Combination +D+0.60W Top along X-X 0.0 k Location of max.above base 0.0 ft Bottom along X-X 0.0 k At maximum location values are ... Top along Y-Y 0.0 k Pa: Axial 0.7637 k Bottom along Y-Y 0.0 k Pn / Omega: Allowable 52.756 k Ma-x : Applied 0.0 k-ft Maximum Load Deflections ... Mn-x / Omega: Allowable 5.228 k-ft Along Y-Y 0.0 in at 0.0ft above base for load combination Ma-y : Applied 0.0 k-ft Mn-y / Omega: Allowable 5.228 k-ft Along X-X 0.0 in at 0.0ft above base for load combination PASS Maximum Shear Stress Ratii 0.0 : 1 Load Combination 0.0 Location of max.above base 0.0 ft At maximum location values are ... Va : Applied 0.0 k Vn / Omega: Allowable 0.0 k Load Combination Results Maximum Axial + Bending Stress Ratios Maximum Shear Ratios Load Combination Stress Ratio Status Location Cbx Cby KxLx/Ry KyLy/Rx Stress Ratio Status Location D Only 0.010 PASS 0.00 ft 1.00 1.00 52.63 52.63 0.000 PASS 0.00 ft +D+0.60W 0.014 PASS 0.00 ft 1.00 1.00 52.63 52.63 0.000 PASS 0.00 ft +D+0.450W 0.013 PASS 0.00 ft 1.00 1.00 52.63 52.63 0.000 PASS 0.00 ft +0.60D+0.60W 0.011 PASS 0.00 ft 1.00 1.00 52.63 52.63 0.000 PASS 0.00 ft +0.60D 0.006 PASS 0.00 ft 1.00 1.00 52.63 52.63 0.000 PASS 0.00 ft Maximum Reactions Note: Only non -zero reactions are listed. Load Combination D Only +D+0.60W +D+0.450W +0.60D+0.60W +0.60D W Only Extreme Reactions Axial Reaction @ Base 0.502 0.764 0.698 0.563 0.301 0.437 X-X Axis Reaction k Y-Y Axis Reaction Mx - End Moments k-ft My - End Moments @ Base @ Top @ Base @ Top @ Base @ Top @ Base @ Top Axial Reaction X-X Axis Reaction k Y-Y Axis Reaction Mx - End Moments k-ft My - End Moments Item Extreme Value @ Base @ Base @ Top @ Base @ Top @ Base @ Top @ Base @ Top Axial @ Base Maximum 0.764 Anchor Designer" for Concrete Software Version 3.3.2404.1 0 1.Project information Project description: Location: Fastening description: 2. Input Data & Anchor Parameters General Design method:ACI 318-19 Units: Imperial units Anchor Information: Anchor type: Cast -in -place Material: F1554 Grade 36 Diameter (inch): 0.625 Effective Embedment depth, her (inch): 3.438 Anchor category: - Anchor ductility: Yes hmin (inch): 4.81 Cmin (inch): 3.75 Smin (inch): 3.75 Recommended Anchor Anchor Name: J- or L-Bolt - 5/8" 0 J- or L-Bolt, F1554 Gr. 36 Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 1/6 Project: Swedish Signs Address: Phone: E-mail: Comment: Base Material Concrete: Normal -weight Concrete thickness, h (inch): 20.00 State: Uncracked Compressive strength, F. (psi): 3500 4V.,v: 1.4 Reinforcement condition: Supplementary reinforcement present Supplemental edge reinforcement: No Reinforcement provided at corners: No Ignore concrete breakout in tension: No Ignore concrete breakout in shear: No Ignore 6do requirement: No Build-up grout pad: Yes Base Plate Length x Width x Thickness (inch): 8.00 x 8.00 x 0.38 Yield stress: 36000 psi Profile type/size: 3XS Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com Anchor Designerlm for Concrete Software Version 3.3.2404.1 0 Load and Geometry Load factor source: ACI 318 Section 5.3 Load combination: not set Seismic design: No Anchors subjected to sustained tension: Not applicable Apply entire shear load at front row: No Anchors only resisting wind and/or seismic loads: No Strength level loads: Nua [lb]: -450 Wax [lb]: 0 Way [lb]: 437 Mux [ft-lb]: -1205 May [ft-lb]: 0 M­ [ft-lb]:0 <Figure 1> Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 2/6 Project: Swedish Signs Address: Phone: E-mail: 450 lb 0 ft-lb Z 4 3 WIT11111—La 17 0 IM17 Y 437 lb Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com 0 <Figure 2> Anchor Designerlm for Concrete Software Version 3.3.2404.1 Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 3/6 Project: Swedish Signs Address: Phone: E-mail: 3. Resulting Anchor Forces Anchor Tension load, Shear load x, Shear load y, Shear load combined, Nu. (lb) Vuax (lb) Way (lb) �(Vuax)z+(Vuay)z (Ib) 1 1046.2 0.0 109.3 109.3 2 0.0 0.0 109.3 109.3 3 0.0 0.0 109.3 109.3 4 1046.2 0.0 109.3 109.3 Sum 2092.4 0.0 Maximum concrete compression strain (%o): 0.06 Maximum concrete compression stress (psi): 271 Resultant tension force (lb): 2092 Resultant compression force (lb): 2542 Eccentricity of resultant tension forces in x-axis, e'Nx (inch): 0.00 Eccentricity of resultant tension forces in y-axis, e'Ny (inch): 0.00 Eccentricity of resultant shear forces in x-axis, e'vx (inch): 0.00 Eccentricity of resultant shear forces in y-axis, e'vy (inch): 0.00 437.0 <Figure 3> 437.0 04 03 I 01 U2 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com Anchor Designer" for Concrete Software Version 3.3.2404.1 0 Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 4/6 Project: Swedish Signs Address: Phone: E-mail: 4. Steel Strength of Anchor in Tension (Sec. 17.6.1) Ma (Ib) 0 ONsa (Ib) 13100 0.75 9825 5. Concrete Breakout Strength of Anchor in Tension (Sec. 17.6.2) Nb = kc)a�fchafl 5 (Eq. 17.6.2.2.1) kc )a fc (psi) hof (in) Nb (Ib) 24.0 1.00 3500 3.438 9049 ONcbg =0(ANcIANco)7ec,NYed,N7'c,N7'cp,NNb (Sec. 17.5.1.2 & Eq. 17.6.2.1a) ANc (in2) ANco (in2) ca,min (In) 7ec,N 7ed,N ye,N 168.22 106.35 - 1.000 1.000 1.25 6. Pullout Strength of Anchor in Tension (Sec. 17.6.3) fNpn = fY ,PNP = fYc,P0.9f'cehda (Sec. 17.5.1.2, Eq. 17.6.3.1 & 17.6.3.2.2b) Yo,a fc (psi) da (in) eb=3da (in) 0 Yep,N Nb (Ib) 0 ONcbg (Ib) 1.000 9049 0.75 13420 ONpn (Ib) 1.4 3500 0.63 1.88 0.70 3618 Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com Anchor Designer" for Concrete Software Version 3.3.2404.1 0 8. Steel Strength of Anchor in Shear (Sec. 17.7.1) Vsa (Ib) rpgrout 0 Ogrwtovsa (lb) Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 5/6 Project: Swedish Signs Address: Phone: E-mail: 7865 0.8 0.65 4090 10. Concrete Pryout Strenath of Anchor in Shear (Sec. 17.7.3) OVcpg = Okc^bg = okcp(A-1 ANco) `lec,N `led,N `l e,N `lcp,NNe (Sec. 17.5.1.2 & Eq. 17.7.3.1 b) kcp ANc (in2) ANco (in2) 'Iec,N yed,N 'IqN ycp,N Nb (Ib) 0 OVcpg (Ib) 2.0 266.10 106.35 1.000 1.000 1.250 1.000 9049 0.70 39624 11. Results Interaction of Tensile and Shear Forces (Sec. 17.8) Tension Factored Load, Nu (lb) Design Strength, oNn (lb) Ratio Status Steel 1046 9825 0.11 Pass Concrete breakout 2092 13420 0.16 Pass Pullout 1046 3618 0.29 Pass (Governs) Shear Factored Load, Vu (lb) Design Strength, OW (lb) Ratio Status Steel 109 4090 0.03 Pass (Governs) Pryout 437 39624 0.01 Pass Interaction check NuaI^ Vua/OVn Combined Ratio Permissible Status Sec. 17.8.1 0.29 0.00 28.9% 1.0 Pass 5/8" 0 J- or L-Bolt, F1554 Gr. 36 with hef = 3.438 inch meets the selected design criteria. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com E-71►��1�z•�►■ Anchor Designer" for Concrete Software Version 3.3.2404.1 Base Plate Thickness Company: L2 Engineers, LLC Date: 7/19/2024 Engineer: Brian J Loshbough Page: 6/6 Project: Swedish Signs Address: Phone: E-mail: Required base plate thickness: 0.383 inch Warning: input base plate thickness does not meet required base plate thickness. Steel Maximum stress Calculated plate thickness Stress distribution 36000 psi 32335 psi 0.383 inch (32335 psi 24251 psi 16167 psi 8083 psi 0 psi For ACI and CSA design methods, maximum base plate stress is limited to 0.9 times yield stress. For ETAG design method, maximum base plate stress is limited to yield stress divide by 1.5. Plate stress is derived using Von Mises theory. F. Of . F 6Lf @ �.n = t + t, (Ca bottom) Of or- = t - t2 () 6M,,. Or,, _ t t' + ,' (2'bottom) of Q� = F,, + 6M,a (@bottom) or r t V. I;. 6,. F, 6M 1Y — t23! (@ top) FA, 6M* or, Oro, Ory as follows: St - or,, +or , + (OA -emu )2 +Q 2 2 2 S3 = 0 _ (S1-S2)2+(S1-SX+(S2—S3)2 QJ'we.lE;c - 2 12. Warnings - Designer must exercise own judgement to determine if this design is suitable. Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility. Simpson Strong -Tie Company Inc. 5956 W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: Steel Column Project File: 24-097 Swedish Signs.ec6 LIC# : KW-06016908, Build:20.23.10.02 L2 Engineers (c) ENERCALC INC 1983-2023 DESCRIPTION: US Post Extreme Reactions Axial Reaction X-X Axis Reaction k Y-Y Axis Reaction Mx - End Moments k-ft My - End Moments Item Extreme Value @ Base @ Base @ Top @ Base @ Top @ Base @ Top @ Base @ Top " Minimum 0.301 Reaction, X-X Axis Base Maximum 0.502 " Minimum 0.502 Reaction, Y-Y Axis Base Maximum 0.502 " Minimum 0.502 Reaction, X-X Axis Top Maximum 0.502 " Minimum 0.502 Reaction, Y-Y Axis Top Maximum 0.502 " Minimum 0.502 Moment, X-X Axis Base Maximum 0.502 " Minimum 0.502 Moment, Y-Y Axis Base Maximum 0.502 " Minimum 0.502 Moment, X-X Axis Top Maximum 0.502 " Minimum 0.502 Moment, Y-Y Axis Top Maximum 0.502 " Minimum 0.502 Maximum Deflections for Load Combinations Load Combination Max. Deflection in X dir Distance Max. Deflection in Y dir Distance D Only 0.0000 in 0.000 ft 0.000 in 0.000 ft +D+0.60W 0.0000 in 0.000 ft 0.000 in 0.000 ft +D+0.450W 0.0000 in 0.000 ft 0.000 in 0.000 ft +0.60D+0.60W 0.0000 in 0.000 ft 0.000 in 0.000 ft +0.60D 0.0000 in 0.000 ft 0.000 in 0.000 ft W Only 0.0000 in 0.000 ft 0.000 in 0.000 ft Steel Section Properties : Pipe3xS Depth = 3.500 in I xx = 3.70 inA4 J S xx = 2.11 inA3 Diameter = 3.500 in R xx = 1.140 in Wall Thick = 0.301 in Zx = 2.910 inA3 Area = 2.830 inA2 Iyy = 3.700 inA4 Weight = 10.300 plf S yy = 2.110 inA3 R yy = 1.140 in Ycg = 0.000 in 7.400 inA4 Project Title: Swedish Signs Engineer: ddp Project ID: 24-097 Project Descr: Steel Column Project File: 24-097 Swedish Signs.ec6 LIC# : KW-06016908, Build:20.23.10.02 L2 Engineers (c) ENERCALC INC 1983-2023 DESCRIPTION: US Post Sketches +y +X 0. SOk 0OSOk