APPROVED FIR2024-0034+Drawings+4.16.2024_10.44.26_AM+4199081GENERAL NOTES: 1. SYSTEM SHALL BE PRE-ENGINEERED 2. SYSTEM SHALL BE MANUFACTURED BY BADGER FIRE PROTECTION 3. RANGE GUARD SYSTEMS HAVE THE FOLLOWING LISTINGS AND APPROVALS: UNDERWRITERS LABORATORIES INC, UL 300 - UL EX 3559 4. SYSTEM TEMPERATURE LIMITATIONS 32F MIN / 120F MAX 5. INSTALLATION REQUIREMENTS, NOZZLE LIMITATIONS AND DESIGN CRITERIA SHALL COMPLY WITH THE RANGE GUARD TECHNICAL MANUAL AND ALL ADDENDUMS AS PUBLISHED BY BADGER FIRE PROTECTION 6. PIPE AND FITTINGS SHALL BE SCHEDULE 40 BLACK, CHROME PLATED OR STAINLESS. GALVANIZED PIPE SHALL NOT BE USED. 7. ALL REQUIRED ELECTRICAL WORK SHALL BE PERFORMED BY OTHERS AND IS NOT INCLUDED ON THIS SHOP DRAWING. 8. ALL REQUIRED PLUMBING WORK BE PERFORMED BY OTHERS AND IS NOT INCLUDED ON THIS SHOP DRAWING PIPING REQUIREMENTS RANGE GUARD SYSTEMS DO NOT REQUIRE BALANCED PIPING TO ACHIEVE PROPER DISTRIBUTION OF WET CHEMICAL TO ALL NOZZLES. BALANCED PIPING IS NOT NECESSARY BECAUSE A LIQUID HAS NO DIFFICULTY IN TURNING CORNERS OR CHANGING DIRECTIONS. RANGE GUARD NOZZLES COME EQUIPPED WITH PERMANENT PREDETERMINED ORIFICES. THIS MEANS THAT THE LIQUID WILL BE DELIVERED IN THE EXACT QUANTITIES NECESSARY TO THE DUCT, PLENUM AND APPLIANCE HAZARDS AS REQUIRED. ALL PIPE SHALL BE SCHEDULE 40 (STANDARD WEIGHT) BLACK STEEL. PIPE MAY BE CHROME PLATED. GALVANIZED PIPE SHALL NOT BE USED. ALL PIPE AND FITTINGS MUST BE MADE TIGHT WITHOUT PIPE DOPE OR THREAD SEALANT. PIPE FITTINGS SHALL BE STANDARD WEIGHT STEEL, CAST IRON, MALLEABLE IRON OR DUCTILE IRON. GALVANIZED FITTINGS SHALL NOT BE USED. BRANCH LINE CONNECTION AND INDIVIDUAL NOZZLE CONNECTIONS MAY BE MADE BY USING EITHER THE OUTLET OR THE RUN OF A TEE. GENERAL RULES • A MAXIMUM OF 100 EQUIVALENT FT. (30.5 M) BUT NOT MORE THAN 40 LINEAR FT. (12.2 M) OF 1/4-IN. PIPE MAY BE USED FROM EACH BRANCH LINE. • THE HIGHEST POINT OF THE SYSTEM SHALL NOT EXCEED 12 FT. (3.7 M) ABOVE THE CYLINDER OUTLET. • THE VERTICAL RISE OF A BRANCH LINE ABOVE THE SUPPLY LINE SHALL NOT EXCEED MAXIMUM OF 4 FT. (1.2 M). • MAXIMUM DISCHARGE PIPE VOLUME LIMITATIONS SHALL NOT BE EXCEEDED. • MAXIMUM EQUIVALENT LENGTH LIMITATIONS SHALL NOT BE EXCEEDED. • MAXIMUM FLOW POINTS FOR A GIVEN PIPE SHALL NOT BE EXCEEDED. • THERE ARE TO BE NO LOW POINTS OR "TRAPS" PRESENT IN DISCHARGE PIPING. Approved DFM c, Ks Burt South County Fire Date: 05/02/2024 F I R2024-0034 2-3.11 1/2-inch Vent Plug, P/N 9196984 A 1/2-inch Vent Plug is used in the discharge piping near a Range Guard cylinder to prevent pressure build-up in the discharge pipe system, caused by heat, from rupturing the foil seals on each nozzle. The 1/2-inch Vent Plug is to be installed in the discharge piping so that it faces the ceiling or the wall. CAUATION NEVER INSTALL IT FACING DOWN OR AT THE FLOOR. 112 in. (13 mm) NPT� 1-18 in. (29 mm) 1 Figure 2-49. 1/2-inch Vent Plug, P/N 9196984 ALL PENETRATIONS TO THE HOOD SHALL BE SEALED WITH AN APPROVED QUICK SEAL DEVICE GASKET LOCK WASHER GASKET LOCK COMPRESSION � WASHER NUT NUT ADAPTOR / 0 GASKET /r `., . NUT SEAL � �— ADAPTOR l I I BODY PIPE y. PIPE PIPE DUCT DUCT 05-02-2024 RESUB 1 PLAN REVIEW APPROVED WITH CONDITIONS: 1. HEAT TEST WILL BE REQUIRED AT FINAL. NOTES: CORRECTIONS ON THE ORIGINAL PLANS DID NOT REQUIRE RE-SUMBITING NEW PLANS. SUPPLEMENTAL DOCUMENTATION WAS PROVIDED THAT WAS ACCEPTABLE FOR APPROVAL. DFM BURT AGE GUM WET CHEMICAL SYSTEM RECEIVED Apr 17 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ALL DISCHARGE PIPING TO BE 1/2" BLACK SCHEDULE 40 NPT CONNECTION TO F.A.C.P. ACTIVATES UPON FA SYSTEM DISCHARGE (CONNECTION BY OTHERS) I CONNECTION TO SUPPLY AIR, SHUTS DOWN MU UPON ACTIVATION (CONNECTION BY OTHERS) I CONNECTION TO ALL ELECTRIC UNDER THE I HOOD, SHUTS DOWN UPON ACTIVATION ES (CONNECTION BY OTHERS) 42"-48" REMOTE PULL STATION I UCH I CONTROL HEAD L�, � VENT PLUG 4GAL EXISTING MECHANICAL GAS SHUT OFF VALVE LOCATED BEFORE FIRST APPLIANCE SHALL BE LOCATED IN AN UNOBSTRUCTED LOCATION BETWEEN 42" AND 48" ABOVE THE FINISHED FLOOR (AFF) IN THE PATH OF EGRESS, OR AT A LOCATION ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. CLASS K WET CHEMICAL EXTINGUISHER SHALL BE INSTALLED NO MORE THAN 60" ABOVE THE FINISHED FLOOR WITHIN 30' OF THE HAZARD HAZARD NOZZLE SUMMARY QTY NOZZLE PTS TOTAL DUCT 1 ADP 1 1 PLENUM 1 ADP 1 1 FRYERS 3 F 2 6 CHARBROILER 1 GRW 1 1 TOTAL 9 6'-6" 16"x7" DUCT ('�_,I �ADP� I I I 500 500 500 500 1 IADP I I I I TF F F GRWT 27.5"-45" 24"-48" (3) 14"x24" , 15"x24" FRYERS ' CHAR BROILER - - - - - - - - - - - - - - - - - - - - - - - - SPACING OR BAFFLE BETWEEN FRYERS) AND ADJACENT OPEN FLAME APPLIANCES) - NFPA 96 I12.1.2.4 ALL DEEP -FAT FRYERS SHALL BE INSTALLED WITH AT LEAST A 406 IMM (16 IN.) SPACE BETWEEN THE FRYER AND SURFACE FLAMES FROM ADJACENT COOKING EQUIPMENT. L I12.1.2.5 WHERE A STEEL OR TEMPERED GLASS BAFFLE PLATE IS INSTALLED AT A MINIMUM 203 MM (8 IN.) IN HEIGHT BETWEEN THE FRYER AND SURFACE (FLAMES OF THE ADJACENT APPLIANCE, THE REQUIREMENT FOR A 406 MM (16 IIN.) SPACE SHALL NOT APPLY. I12.1.2.5.1 IF THE FRYER AND THE SURFACE FLAMES ARE AT DIFFERENT HORIZONTAL PLANES, THE MINIMUM HEIGHT OF 203 MM (8 IN.) SHALL BE IMEASURED FROM THE HIGHER OF THE TWO. - - - - - - - - - - - - - - - - - - - - - - - - - RAIffGE'� WET CHEMICAL SYSTEM EXISTING RANGEGUARD 4-GALLON SYSTEM TANK USES 9 of 12 FLOW POINTS PRE-ENGINEERED SYSTEM SHOP DRAWING ONLY - NOT TO SCALE 3-6.1 Plenums Table 3-29. Plenum Protection 1 When no filters are present, the nozzle protecting the plenum is used to discharge the wet chemical on the under- side of the hood. In this case, the hood may not exceed a length of 10 ft. (3 m) or a width of 4ft(1.2m). Longer plenums may be similarly protected with a single ADP nozzle being used for each 10 ft. (3.0 m) of plenum length and each 4 ft. (1.2 m) of plenum width. ADP nozzles may be used in combinations (see Figure 3-28). Multiples may be installed facing in the same direction, and/or at the ends of the plenum pointing in. Each nozzle shall provide a maximum of 10 ft. (3 m) of coverage. ADP nozzles must be centrally located in the plenum with their discharge directed along the length of the plenum and located in relation to the filters as shown in Figure 3-28. Refer to Figure 3-28 for filter height. 4 ft (1.2 m) DUCT o; -�� 4 ft. > e e e (1.2 m) 4 e O O+ oaL eae O6.*'. e� ✓Od' .a6e.! Oe6'rPs. e NS a �y o� �0 10 ft. (3 m) SINGLE FILTER BANK COVERAGE 10 ft. (3 m) PLENUM Items Parameters ADP Nozzle 3-6.1.1.1 Protection of Ducts 0 to 50 inches in Perimeter One ADP nozzle, P/N B120011, is required for protection of a duct with a perimeter up to 50-inches (refer to Figure 3-29). Length of duct is unlimited. The nozzle is located at the geometric center of the cross -sectional area that it is protecting, and is located in the duct within six inches of the entrance. Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or off when the system is discharged. DUCT PERIMETER UP TO AND INCLUDING 50 in. (1270 mm) 11.78 in. (300 mm) 15.91 in. MAX. DIAGONAL (404 mm) ,g„ MAX. ♦ I♦— 12.5 in. 11.78 in. (300 mm) (318 mm) — I — MAX. DIAGONAL MAX. + —o SQUARE DUCT I RECTANGULAR DUCT 2 "A" + 2 "B" = 65 in. (1651 mm) ROUND DUCT DUCTENTRANCE I � ADP NOZZLE I I I - 152 mm) OF VERTICAL DUCT IH I I I I .� VERTICALORIZONTAL DUCT AIM POINT I I I / ADP NOZZLE I / / (l OF HORIZONTAL DUCT 2 to 4 in. (51 to 102 mm) NOZZLE TIP to DUCT HIP Figure 3-29. Duct Protection Using Single ADP Nozzle, P/N B 120011 3-4.4 14 in. x 14 in. (356 mm x 356 mm) Deep Fat Fryer 3-4.15 Gas Radiant/Electric Charbroiler Table 3-5. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 14 in. x 14 in. (356 mm x 356 nim) Maximum Appliance Area (with drip board) 14 in. x 24-1/2 in. (356 nun x 622 nun) Nozzle Aim Midpoint of hazard area Nozzle Location (from top Of appliance at an angle of 450 or more from the horizontal) 27-1/2 in. (686 nun) Min. 45 in. (1143 nun) Max. 45In. (1143 mi MAX AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 45 in. (1143 mm) DIAGONAL FROM MAX AIM POINT 45 in. (1143 mm) MAX z_ `- NOZZLE LOCATION E 45 OR MORE FROM `�� `�" E HORIZONTAL °D �o MIDPOINT OF 27 1/2 in HAZARD AREA (6" mm) MIN AIM POINT: MIDPOINT OF HAZARD AREA 14 in. (3 X mm) MAX 24-1/2 in. HAZARD AREA 1622 mm) MAX DRIP BOARD DRIP BOARD 14 in. (356 mm) MAX. 24-1/2 in. (622 mm) MAX. APPLIANCE AREA �- 14 in. (356 mm) MAX FRONT VIEW SIDE VIEW Figure 3-5. 14 in. x 14 in. (356 rnm x 356 mm) Deep Fat Fryer AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID Table 3-21. GRW Nozzle Coverage Area Items Parameters Maximum Cooking Surface 21 in. x 24 in. (533 nun to 610 mnn) Nozzle Aim Midpoint of the hazard area above cooking surface Nozzle Location (located at an angle of 45' or more from the horizontal) 24 in. (610 mm) Min. 48 in. (1219 nun) Max. 48 in. (1219 mm) MAX. A GRW NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 48 in. (12 mm) DIAGONAL FROM MAX.. AIM POINT 48 in. (1219 mm) MAX. A GRW NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID P}. NOZZLE LOCATION z F� 45'OR MORE FROM \ i 0� HORIZONTAL �\\ E 21 in. (533 mm) t AIM POINT: .c MAX. MIDPOINT OF HAZARD AREA RADIANT LAYER GAS FLAME 21 in. (533 mm) MAX. �I 24 in. (610 mm) 10 APPLIANCE AREA MAX. FRONT VIEW SIDE VIEW Figure 3-17. Gas Radiant/Electric Charbroiler 24 in. (610 mm) MAX. AIM POINT: MIDPOINT OF HAZARD AREA SYSTEM SHALL UTILIZE GLOBE ML®TM FUSIBLE LINKS FOR AUTOMATIC SYSTEM ACTIVATION. FUSIBLE LINKS ARE DESIGNED TO SEPARATE AT SPECIFIC TEMPERATURES, RELEASING TENSION FROM THE FUSIBLE LINK DETECTION LINE AND CAUSING SYSTEM ACTUATION. CORRECT FUSIBLE LINK SELECTION IS AN ESSENTIAL ELEMENT IN THE DESIGN OF ANY FIRE SUPPRESSION SYSTEM. AFTER PERFORMING A TEMPERATURE STUDY TO DETERMINE THE MAXIMUM AMBIENT TEMPERATURE AT THE FUSIBLE LINK LOCATION, THE CORRECT FUSIBLE LINK SHOULD BE SELECTED FROM THE FOLLOWING CHART: 114. . 66 "N I*-.79"t 2.25" TEMPERATURE RATING MAX AMBIENT TEMPERATURE LOAD RATING OF °C OF °C MIN MAX 1350 570 1000 380 10 LBS 40 LBS 1650 740 1000 380 10 LBS 40 LBS 2120 1000 1500 660 10 LBS 40 LBS 2800 1380 2250 1070 10 LBS 40 LBS 3600 1820 3000 1490 10 LBS 40 LBS 4500 2320 3750 1910 10 LBS 40 LBS 5000 2600 4300 2170 10 LBS 40 LBS • UL LISTED TO UL 33, HEAT RESPONSIVE LINKS FOR FIRE • DATE STAMPED WITH YEAR OF MANUFACTURE • CORROSION RESISTANT CONSTRUCTION • STAINLESS STEEL COMPONENTS • FLEXIBLE EYE HOOK CONNECTION • 21/64" MOUNTING HOLE DIAMETER • LISTED FOR USE IN ALL FIRE PROTECTION SYSTEMS Table 3-34. Maxiinunl Allowable Piping Volume PROTECTION SERVICE Cylinder Size Total Discharge Pipe Total Discharge Tubing Volume Max. per Cylinder Max. per Cylinder Max. Allowable 3, 8-inch Pipe Volume per System RG-125 (4.7 L) 72 in.3 (1180 cm3) 1 51 in.3 (836 cm3) 1 72 in.3 (1180 cm3) RG-250 (9.5 L) 139 in.3 (2278 cm3) 1 99 in.3 (1622 cm3) 1 95 in.3 (1557 cm3) RG-400 (15 L) 400 in.3 (6555 cm3) 282 in.3 (4621 c1113) 1 95 in.3 (1557 cm3) RG-600 (22.7 L) 400 in.3 (6555 cm3) 282 in.3 (4621 cm3) 1 95 in.3 (1557 cm3) -G,4,= MINIMUM PIPE LENGTH The minimum pipe length, to prevent splash, required between cylinder and closest cooking appliance nozzle used to protect a liquid hazard, such as a deep fat fiver, is given in Table 3-33, For pipe sizes larger than 1/2-inch (1.3 cm) use formulas 1 and 2, to find the equivalent length in 1/2-inch (1.3 cm) pipe. Table 3-38. Minimum Allowable Pipe Pipe Size Minimum Allowable Pipe 1/4-inch and 3r3-inc 8-1/2 ,2.6 m, linear feet plus (1) 90° e Dcw (2.6 m 1/2-inch Two (2) 900 Elbows and 7 linear feet (2.1m; 3/4-inch and 1-inch 10 equivalent feet of 1/2-inch (13 mm) pipe (see formula. 1 It 2 and Figure 3-39) Cylinder and Valve Maximum Dimensions AssemblyPart Model Flow NumberNumber A B C B120001 RG-1.25G 4 15-1/4 in. 13-3/4 in. 8 in. (387 nun) (349 mm) (203 nuu) B120002 RG-2.5G 8 21 in. 19-5/8 in. 9 tn. (534 mm) (498 mm) (230 mm) B120003 RG-4GS 12 19 in. 17-1/2 in. 12-1/4 in. (483 mm) (444 mm) (311 mm) B 120006 RG-4GM 12 24-3/8 in. 23 in. 10 in. (619 nun) (584 mm) (254 mm) B120005 RG-6G 18 35-1/8 in. 33-3/4 in. 10 in. (892 mm) (857 mm) (254 mm.) Table 3-31. Flow Number Range and Pipe Type Flow Number Range Minimum Pipe Size .035 Wall Stainless Steel Tubing Size 1 —2 1l4-inch 318-inch 1 —8 3/8-inch N/A 1 — 12 1/2-inch 5/8-inch 13 — 24 3/4-inch 7/8-inch 25 — 48 1-inch 1-inch