RESPONSE 1 FIRE-FIR2024-0034+4.30.2024_11.39.21_AM+4227319RESUB
Apr 30 2024
HOOD SUPPRESSION SYSTEM
CORRECTION LETTER RESPONSE
City of Edmonds
RE: Ivars, 9910 Edmonds Way
FIR2024-0034
30 Apr 2024
Attn: Fire Marshal office/DFM Burt
In response to plan review corrections dated 24 Apr 2024
1. Provide Proper ICC Certification
PSI Response - ICC Certification 10087093 for Matthew Neilson attached.
2. Provide authorization certificate to work on suppression manufacturer equipment
PSI Response - system manufacturer is Range Guard (Badger). Badger Range
Guard certification of Thea Ray attached
3. Describe the reason for 500°F Degree Links
PSI Response - Attached photo should help - this is a 'low proximity" hood. The
temperature of the exhaust from deep fryers has caused system activation in a
similar system within South County Fire's response area (131 A ve Pub in Martha
Lake) installed with links rated for lower temperatures. (Note: the wood topped
table adjacent to the equipment, circled, will be replaced with stainless steel) -
System responsible party.- Max (Matthew) Neilson is available for discussion on
thismatter 206.503.5251 or max. neilsonPpsintegrated.com
4. Response letter Required
5. Confirm that all components of the suppression system are either Range Guard
or Badger
We confirm that all components listed as part of the "Badger Range Guard Wet
Chemical System "
Prepared By:
PERFORMANCE
SYSTEMS INTEGRATION
Pacific Northwest
Puget Sound Portland Inland
301 Porter Way 7324 SW Durham Rd 4004 E Trent Ave
Milton, WA 98354 Portland, OR 97224 Spokane, WA 99202
Licenses: 675521 (CA), CLE569 (OR), PERFOSI81250 (WA), PERFOSIS1850 (WA)
Job Ivars, Edmonds: Rev1 - April 30, 2024
INTERNATIONAL
CODE
COUNCIL°
INTERNATIONAL CODE COUNCIL
MATTHEW NIELSON
The International Code Council attests that the individual named on this certificate has satisfactorily
demonstrated knowledge as required by the International Code Council by successfully completing the prescribed
written examination based on codes and standards then in effect, and is hereby issued this certification as:
Pre-engineered Kitchen Fire Extinguishing Systems Technician
Greg , eler, CBOT
Given this day September 17, 2021
Certificate No. 1 ON 93
OF FIRE FQ
O
This certificate is the property of ICC and must be returned to ICC in the event of suspension or revocation of the certificate.
4/29/24, 7:44 PM
Training Certificate
eatficAe of �01#jo/e#0)7
This is to certify that
Thea Ray
an employee of
PERFORMANCE SYSTEMS INTEGRATION, LLC
on behalf of KIDDE SAFETY
an Authorized Badger Fire Protection Distributor
has successfully completed a certification training session covering design, installation,
operation and maintenance and has demonstrated a practical knowledge of following
Michael Kraus
Training Manager
Badger products:
Range Guard Wet Chemical
BADGER
19M
Issue Date: 4/30/2024
Expiration Date: 4/30/2027
This certificate is not transferrable. Certificate is only valid as long as the above named company employs the training participant. Acceptance of this certificate
implies that the parties agree to abide by the terms of the distributor agreement or absent an agreement Kidde Fire Systems Terms and Conditions of Sale. Any
violation or alteration of this certificate will result in the immediate voiding of this certificate and possible revocation of access to the Kidde Fire Systems product line
hftps://www.kidde-fenwal.com/Training/Certificate?id=51712 1 /1