8.3 LOCATION OF SPRINKLERS:
O6-J.1 SprinKlerS snail De InsLallea In all areas
i except where omission is permitted by 8.3.2
through 8.3.8.
2 8.3.2 Sprinklers shall not be required in
bathrooms of 55 ft2 and less.
b..i..i SprmKlers Snail not De regUlrea In cloLnes
<3> closets, linen closets, and pantries that meet all
of the following conditions:
(1) The area of the space does not exceed 24 ft2
(2) The walls and ceilings are surfaced with
noncombustible or limited -combustible materials
as defined in NFPA 220.
4 8.3.4 Sprinklers shall not be required in garages,
open attached porches, carports, and similar
structures.
8.3.5 Sprinklers shall not be required in attics
5
with or without storage, penthouse equipment
rooms, elevator machine rooms, concealed
spaces dedicated exclusively to and containing
only dwelling unit ventilation equipment,
floor/ceiling spaces, elevator shafts, crawl
spaces, and other concealed spaces that are not
used or intended for living purposes.
O8.3.6 Sprinklers shall not be required in covered,
unheated projections of the building at
entrances/exits as long as the dwelling unit has
another means of egress.
l �
--------------------------------------4------+---
1 12
1 12 TYP.
5
10 4
A10 — — A10
v 1 5 I
II 5I 1 1---------
T O PLATEO \ / 4 LEVEL TWC
T.O. PLATE
L—B EL
o
N
cc
(O
�^
J
U
m
Cl)
N
N
CLOSET
�
bo
9
0
U
A10
co
o
CO
U
o
N
w N
LEVEL TWO
a
T.O. SUB FLOOR
----
_91F—
—
— — — — — —
0
T
LEVEL ONE
=
T.O. PLATE
a
Ul
U
co
CM
m
DECK
LIVING
8
A10
LEVEL ONE (
T.O. SUB FLOOR— I
I I
-
—
—
--
------------
AVE
AGE
GRADE = 362.5'
I
I
CRA1
- - - - - - - - -
III —III —III —III —III —III —III —III •
- - - 11-III-III-III-1 11 III-
III —III —I I1—III—I I-111—III III --I
I —
SECTION A 4'
SCALE: 3/ 16" = 1'-0"
SITE PLAN
SCALE: 1/16" = 1'-0"
16'
6'-8" MIN.
GUARDRAIL
HEADROOM
36'
MIN. PER
N
PER IRC
IRC
312.1.2.1
311.7.2, TYP.
HANDRAILS
/
34"-38" PER
IRC311.7.8.1
-
A10
&b MAX. PER
INC 312.1.3.1
4CE 2
PRIMARY CC0
BEDROOM N
3 bo
A10
I — — LEVEL TWO
I 1 T.O. SUB FLOOR
91
rr
Y
��bti��81.5L
GARAGE SEPARATION TO
—
T.O. PLATE
HAVE MIN. 1/2" GWB @
GARAGE SIDE WALL /
MIN. 5/8" TYPE "X" GWB @
2
CEILING PER IRC TABLE R302.6
A10
co
CM
GARAGE 04
0)
UNDER -STAIR PROTECTION
1
TO HAVE MIN. 1/2" GWB
A10
@ WALLS & CEILING PER
IRC TABLE R302.7
GARAGE
T.O. SLAB
---------------------
----
---------+E+E+FTT _
.FTIF-
5
A10
I FIIFI
08-28-2024
PLAN REVIEW
NOTES: APPROVED WITH CONDITIONS:
1. Approved set of plans must be on site at the time of
inspection. Failure to provide the approved plan may result
in a re -inspection fee. System drain(s): SEE CONDITION
NOTED AT RISER. If riser is above lowest grade, 2nd
drain required and signage at riser indicating location is
required. Systems required signage IAW NFPA 13D.
2. Coverage required to the following areas: Clothes
closets, linen closets and pantries exceeding 24 square
feet in area, with the smallest dimension greater than 3'
and having wall and ceiling surfaces of gypsum board.
Bathrooms more than 55 square feet in area. When fuel
fired equipment is present on covered decks or porches, or
if living space above, at least one quick -response
intermediate temperature sprinkler shall be installed above
equipment or area under living space. All fuel fired
appliances except attics if above all living areas.
DFM Burt
SHEN/FEDERMAN
RESIDENCE
23310 Humber Lane
Edmonds, WA 98020
Main Floor =—363.5'
Approved
D F M aMrLs gust
South County Fire
Date: 08/28/2024
1
1
1
1
1
1
1
�
1
C
1
M
1
J
1
L
1
1
E'
1
�
1
=
1
1
1
1
A
1
-----------------------
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
UNDERGROUND NOTES
All underground to be by others.
Existing 1" copper tap on 8" DI main city
water main along Humber Lane.
B Approx. 36 linear feet of existing 1" copper
line from tap to meter box.
C Newly upgraded 1" combo fire & domestic
water meter by others. Existing 3/4" meter
to be removed.
�Approx. 94 linear feet of new 11/2" CPVC or
D equivalent piping from meter to stub -in
location.
E Stub -in location in mechanical room at lowest
level. See riser detail for continuation.
All underground and supply piping by others
is to be either BlazeMaster CPVC, PE/Poly,
Copper, or PEX subject to acceptability by
governing standards and the plumbing code
where required. Blazemaster CPVC is the
preferred piping material.
If PEX is used the pipe size shown on these
drawings must be increased by two nominal
diameters to be equivalent due to PEX having
thicker walls and smaller internal diameters
than the other materials.
Poly piping may not be acceptable in all areas
except when buried and may not be
acceptable past the slab. It is the
responsibility of the pipe installer to verify
the acceptability of piping with the governing
codes and standards and use one of the
equivalent piping materials listed above as
necessary.
MIN. R-11 BATTED INSULATION OVER
PIPE.
SECURE TO ROOF TRUSS IF BLOWN IN
INSULATION IS USED.
IS A MIN COLD AREA
MINIMUM AND
TO BE MODIFIE1
FOR THE LOCAL
AREA BY THE
INSULATION
CONTRACTOR.
SPRINKLER PIF_...,..
BOTTOM CHORD OF
ROOF TRUSS
VVAKIvI AKtA
TYP. TENTING DETAILS
SCALE: NONE
Maximum Support Spacing for
CPVC Piping
Pipe
Size
Between
Hangers
From
A.S.
Inline
From
End of
Line
3/411
51/2'
3'
6"
1"
6'
4'
9"
11/4"
61/2'
5'
12"
11/2"
7'
7'
12"
2"
81
7'
12"
21/2"
9'
7'
12"
3"
10'
7'
12'
Hanger No. 09W
Pipe Strap
Wood Screw Pipe
# 18 x 11/2"
Pipe Strap
o (Short)
Wood Joist, Beam or Deck
NO INSULATION TO BE
INSTALLED BETWEEN PIPING
AND WARM SPACE
SPRINKLER PIPING TO BE
TIGHT TO WARM FLOOR ABOVE
WARM FLOOR ABOVE
COLD AREA BELOW
Hanger No. 17W
Pipe Strap
Pipe Strap
Wood Screw Pipe
# 12 x 11/4" p
Wood Joist or Beam
Hanger No. 19W
Offset Pipe Hanger
Pipe
Wood Screw
# 18 x 11/2" Offset Pipe
\ , Hanger
TYP. CPVC HANGER DETAILS
SCALE: NONE
Y
oI:
3
LL
W
a
U
U)
a
LL
X
U
>
a
U
rl
z
Tr
� a
LU U
W
U
O a rl
Cal U
RISER SECTION
/ / / / /
Wood Joist, Beam or Deck
O11/2" CPVC or equivalent supply brought in by others.*
11/2" brass combination domestic/fire sprinkler shut off
Ovalve by others. Must be located before the domestic
tee. No monitoring is required.
11/2" brass tee continues to domestic by others. Any
domestic pressure -reducing valves, water softeners, leak
Odetectors, or other devices that will deter water flow are
to be on the domestic -only side of the tee. Brass tee top
outlet to be female -threaded to accommodate male
threaded CPVC adapter connection.
OPiping to domestic by others.
O11/2" CPVC adapter with 11/2x1 CPVC reducing bushing.
MFP scope of work to begin here.
O1" x 1" x 1/2" tee with 1/2" x 1/4" bushing for pressure
gauge. Three way valve included for pressure gauge.
Lowest hose bib on the domestic side of the tee to be
used as the system drain per NFPA 13D.
2'
SCALE: 1/2" = 1'-0"
CONDITION: INSTALL A
PLARCARD NEAR
DRAIN VALVE
INDICATING THAT
HOSE BIB IS THE
DRAIN.
STUB IN:
*Builder to Provide 1" annular clearance to protect piping.
FLUSH TEST:
*Underground installer will be required to have a flush test completed and witnessed
before Moore Fire will hook up to the incoming supply. Underground installer to provide a
CMTC proving this test was done.
PASSIVE PURGE SYSTEM SPECIAL NOTES:
This is a flow -through ("passive purge") system. A 1/2" female adapter will be left at the
remote toilet location. Plumber is to connect from adapter to toilet.
WARNING SIGN:
6.3.4 A warning sign, with minimum 1/4 in. letters, shall be affixed adjacent to the main
shutoff valve and shall state the following:
WARNING: The water system for this home supplies fire sprinklers that require certain
flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure
or automatically shut off the water to the fire sprinkler system, such as water softeners,
filtration systems, and automatic shutoff valves, shall not be added to this system without
a review of the fire sprinkler system by a fire protection specialist.
Do not remove this sign.
Shen -Federman Residence
SITE SPECIFICATIONS
AHJ: City of Edmonds OWNER/LESSEE:
RELATED PERMIT: BLD2023-0401 BERNARD SHEN &
OCCUPANCY TYPE: Residential CATHERINE FEDERMAN
CONST. TYPE: V-B 23310 HUMBER LANE
STORIES: 2 EDMONDS, WA 98020
PARCEL: 00571300101000
GENERAL DESCRIPTION:
New sprinkler system to be installed for a new single family residence.
LEGAL DESCRIPTION:
SHERWOOD VILLAGE BLK 001 D-00 - TR 10
FIRE FLOW
NFPA
13D
Hydrant static pressure of 74 psi received from Olympic View Water & Sewer District on
7/23/24. Water main was noted as a 8-inch ductile iron pipe. 20 psi @ 250 gpm used as
conservative values to complete the supply curve. 71 psi is used at the base of riser as a
conservative value.
SYSTEM SPECIFICATIONS I C
BUILDING CODE: 2021 IRC, IFC, and IBC with WA State Amendments
SYSTEM TYPE: NFPA 13D 2019 Wet Sprinkler System
�
Passive purge system without backflow preventer
GG
SPRINKLER COVERAGE:
256 ft2 per sprinkler listing for rooms with more than one sprinkler and 400 ft2 per
sprinkler listing for a single sprinkler in a room.
SPRINKLER SPACING:
Q
More than one sprinkler in a room: Only one sprinkler in a room:
—
c
c
16-0" max. between heads. 10'-0" max. from any wall.
8'-0" max. from any wall.
CL
8'-0" min. between heads.
u.
u.
O
O
SPRINKLER DETAILS:
N
N
t;d
Residential fast response pendent sprinklers used throughout.
L
HAZARD CLASSIFICATION:
u.
3
3
c
Residential use throughout.
0)
4%
v,
to
PIPING DETAILS:
ai
ai
N
Blazemaster CPVC: Aboveground wet sprinkler system throughout except as noted on the
riser detail.
Y
C
E
SUPPLY:
CL
to
Supply to come from a 8" DI water main along Humber Lane. An existing 3/4" water meter
yCLa
a
to be upsized to a new 1" combo meter. The existing 1" tap to existing 3/4" water meter to
c
c
be reused for the new 1" combo meter. After the meter a new 11/2" poly line to be installed
y
a
a
from the meter to the riser location in the mechanical room on the lowest floor.qT
=
Y
N
rl
m
rl
Ln
N
II
CPVC COMPATIBILITY:
'i
a
IC
L
A list of approved products for use with BlazeMaster CPVC pipe is included with the product
specifications booklet. For a complete and up-to-date product search, please go to
o
<http://www.moorefire.com/cpvc> Moore Fire Protection is not liable for damage to CPVCCn
~
piping caused by any products which are not approved for contact with it. Information
Z
M
L
about products approved for contact can be found with the manufacturer.
>
;
$
EQUIVALENT PIPING:
II
aJ
LL:
All underground and supply piping by others
is to be either BlazeMaster CPVC, PE/Poly,
Copper, or PEX subject to acceptability by
governing standards and the plumbing code
where required. Blazemaster CPVC is the
preferred piping material.
If PEX is used the pipe size shown on these
drawings must be increased according to the
Equivalent PEX Sizing Table.
Poly piping may not be acceptable in all areas
except when buried and may not be
acceptable past the slab. It is the
r n ibilit f th i in t II r t v rif th
Equivalent PEX Sizing Table
BlazeMaster CPVC,
Poly, or Copper
Size
Equivalent PEX
Size
Inches
3/4
1 'A
1
11/2
1 'A
2
11/2
2
2
NO EQUIVALENT
c=Cn
Y
C
Y
a
M
E
Cn
U.
U.
741
C41
1 p
Vl••
1
.............&i
1
,
1 °
�
{ii
1 H � >•
�'
1 � »
1
1
Gl
U
'.o°�
�1
i
1
espo s y o e p pe sae o e y
acceptability of piping with the governing �' �; Ora`°
Y O 1
codes and standards and use one of the ; ;oaW ;
equivalent piping materials listed above as W T� 80. ;
a
1 ° 1, CommC1
necessary.`.................�
GENERAL NOTES AND LIABILITY O M
z
Install CPVC piping in accordance with manufacturer's instructions and UL listing including � N `°
but not limited to: hanging, vertical restraint, thermal expansion, chemical compatibility, ,-_1 4-J a
concealment, and protection. Horizontal CPVC pipe shall be concealed with a minimum of a) c LL
3/8" gypsum board. All CPVC pipe shall be concealed. o � U �
y 4_, O
All system piping is to be supported per manufacturer's specifications and is to be secured � L -J O
to prevent lateral movement. Pipe is to be secured to prevent sprinkler head movement. 12L ,--I �' o Lf)Ln
.00 00 0 6
Moore Fire Protection's warranty of work does not cover any damage due to freeze related O a, F o a)
problems. Wet piping shall be protected against temperatures below 50 degrees Q o p ru
Fahrenheit. Insulation installed for this purpose shall be located on the cold side of the ^ a o Lu N
pipe only with no insulation on the warm side of the pipe facing the heated interior. r4 O
Coordinate with general and/or insulation contractor. All insulation to be by others. LLj I i If z \
2J � o U-)o _J
Moore Fire Protection shall not be responsible for the ability of the structure to adequately U
support the fire sprinkler system or any appurtenances thereof. M W U Q � 170 �'
Owner is responsible for the periodic inspection, testing and maintenance of the water .—I (n Ow a- (n 0 w
based fire protection system(s) in accordance with the requirements of NFPA 13D Chapter
12.
O �
U o
W00
0')L _
1
KEYNOTE LEGEND (1) 3:0 1C �
OPart Tag O
n � �
LU
RECEIVED LL Lu
O Hydraulic Node Tag Lu
Aug 15 2024 Iw
FIR2024 0069 CITY OF EDMOz
PLANNING &DEVELOPOPMENT Q
DEPARTMENT # Reference Tag
W L w
❑# Underground Note Tag
�# Remote Area Tag
LEVEL 1
SCALE: 1/4" = 1'-0"
Hydraulic Information
Remote Area RA1
OCCUPANCY CLASSIFICATION
Residential
TOTAL HEADS FLOWING
1
K-FACTOR
4.9
Static pressure at riser gauge: 71 psi.
2 sprinklers in the design area flowing 13 gpm minimum
for 16x16 spacing per NFPA 13D and the sprinkler's listing.
Refer to the sprinkler listing for approval chart.
Static pressure at riser gauge: 71 psi.
sprinklers in the design area flowing 13 gpm minimum
[Refer
r 16x16 spacing per NFPA 13D and the sprinkler's listing.
to the sprinkler listing for approval chart.
4 ' Note Co installer Arm overs INSPECTOR NOTE: LEVEL 2 ' Note to installer Arm overs
cannot be more than 4' total 4 cannot be more than 4' total
u _ _ _ _ length _ _ _ _ � BUCKET TEST SCALE: 1/4" = 1'-0" I _ _ _ _length _ _ _
l� HEADS. L
Flat ceiling area of remote
area RA2 to be used for
bucket test with comparable
remote area to RA3.
RECEIVED
Aug 15 2024
CITY OF EDMONDS
PLANNING & DEVELOPMENT
DEPARTMENT
NFPA 13D CODE QUICK REFERENCES
8.3 LOCATION OF SPRINKLERS:
KEYNOTE LEGEND
l
O
8.3.1 Sprinklers shall be installed in all areas
except where omission is permitted by 8.3.2 O
8.3.3 Sprinklers shall not be required in clothes
closets, linen closets, and pantries that meet all
5
8.3.5 Sprinklers shall not be required in attics
with or without storage, penthouse equipment
O
Part Tag
through 8.3.8.
of the following conditions:
rooms, elevator machine rooms, concealed
O
8.3.2 Sprinklers shall not be required in
(1) The area of the space does not exceed 24 ft2.
(2) The walls and ceilings are surfaced with
spaces dedicated exclusively to and containing
only dwelling unit ventilation equipment,
O#
Hydraulic Node Tag
bathrooms of 55 ft2 and less.
noncombustible or limited -combustible materials
floor/ceiling spaces, elevator shafts, crawl
4
as defined in NFPA 220.
8.3.4 Sprinklers shall not be required in garages,
open attached porches, carports, and similar
structures.
6
spaces, and other concealed spaces that are not
used or intended for living purposes.
8.3.6 Sprinklers shall not be required in covered,
unheated projections of the building at
O#
#
Reference Tag
Underground Note Tag
entrances/exits as long as the dwelling unit has
another means of egress.
#
Remote Area Tag
0
z
z
Q
0
V U
C C
O O
U U
h �n
C C
LL LL
rl (4
666
N
LL
0
N
O
O
LL
LL
O
E
V)
M
.................
1
1 s
i i
1 W p
• 1
1
1
Q%
IOW
W
1
U
ipFY
i
= n
d o
1
a.1
,v
I q�W
1 it LL
UQ.
N O (0
1
1
A
V,
1
1 Tn
0 0
�d U d
1
1
1
rn.�
j �� w
1
1
1 W.
�( 00
1
r.
.■■..•
d
O
x
M
T--1LL
C d
N
O w
U C�,
0
(n
aD O
JOB
/gyp
LL 1� L
O
Ln
-.00
00 0
2
M a,E
o
a�
f6
0
QMU
Lu
LL N
m
rl
O
3
2:
It
LU LU N
J
Ln
o
Ln
cn
00
�
n
= .ten
o
Q
o
U LU J
M Q
LLI P LL Q
U
F0
a--'
61
,—I (n O LU
(n
0
w
C/:
W N
O
00
•� Q
u7
O
r
E0
w
L Lu
� z
_0 Q
LL m
Qr� o
y ('M
V � N