FIR2024-0069+Fire_Sprinkler_Equipment_Specification_Sheets+8.14.2024_1.37.30_PM+4440733FIR2024-0069 RECEIVED
Aug 15 2024
PLANNING & DEVELOPMENT
DEPARTMENT
FIREPROTECTION
Shen -Federman Residence
2019NFPA13D
23310 Humber Lane
Edmonds, WA 98020
Material Specifications
113 Cherry St, PMB #41900 (425) 271-5598 State Contractor's License
Seattle, WA 98104 # MOOREFP116NP
THIS PAGE INTENTIONALLY LEFT BLANK
Page 1 of 5
cR; FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Freedom° Residential Concealed Pendent Sprinkler VK494 is a small
thermosensitive, glass -bulb residential sprinkler designed for installation on concealed
pipe systems where the appearance of a smooth ceiling is desired. The orifice design,
with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available
water supplies for the hydraulically designed fire -protection system. The fast
response glass bulb operating element and special deflector characteristics meet
the challenges of residential sprinkler standards.
The sprinkler is pre -assembled with a threaded adapter for installation with a
low -profile small -diameter cover assembly installed flush to the ceiling. The two-
piece design allows installation and testing of the sprinkler prior to installation
of the cover plate. The "push -on", "thread -off' design of the concealed cover
plate assembly allows easy installation of the cover plate after the system has
been tested and the ceiling finish has been applied, while also providing up to
1/2" (13 mm) of vertical adjustment. The cover assembly can be removed and
reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler
system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT)
coating has been investigated for installation in corrosive atmospheres and is C-UL-
US-EU Listed as corrosion resistant as indicated in the Approval Charts. The ENT
finish is only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
�&UL Listed (C-UL-US-EU): Category VKKW
EU Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500
psi (34.5 bar).
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric*)
Glass -bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400
Compression Screw: 18-8 Stainless Steel
Yoke: UNS-S43000 Stainless Steel or Phosphor Bronze UNS-051000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Freedom' Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:
Sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the
temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 200 °F (93 °C) = E
For example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Form No. F_012116 17.04.20 Rev 17.2 Replaces Form No. F_012116 Rev 17.1
(added alt. material for yoke)
Page 2 of 5
cR; FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B
Temperature Suffix: 135 °F/57 °C = A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches**:
A. Heavy Duty Part No. 14047W/B** (available since 2006), or
B. Head Cabinet Wrench Part No. 14031*** (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a ''/z" ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat -sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly.. Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-
sure at the sprinkler to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE
1: AVAILABLE SPRINKLER
TEMPERATURE RATINGS
AND FINISHES
Sprinkler
Sprinkler
Maximum
Temperature Rating Cover
Large
Square
Temperature
Nominal
Ambient
of the Cover Plate
Cover Plate
Cover Plate
Bulb Color
Classification
Temperature
Ceiling
Assembly Base Part
Base Part
Base Part
Rating'
Temperature'
(Required)3 Number'
Number'
Number°
Ordinary
155 °F (68 °C)
100 °F (38 °C)
135 °F (57 °C)
13504
13642
15394
Red
Intermediate
200 °F (93 °C)
150 °F (65 °C)
135 °F (57 °C)
13504
13642
15394
Green
Sprinkler Finishes:
Brass and
ENT
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Corrosion Resistant Coatings5: ENT
Footnotes
The sprinkler temperature rating is stamped on the deflector.
z Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
Maximum ambient temperature for cover assembly is 100 °F (38 °C).
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
e The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring
is exposed.
Form No. F_012116 17.04.20 Rev 17.2
Page 3 of 5
cR; FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart
Viking VK494, 4.9 K-Factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the design criteria. For Ceiling types refer to
current editions of NFPA 13, 13R or 13D
Sprinkler Base
NPT Thread Size
Nominal K-Factor
Maximum Water Wor-
Part Number I
SIN
king Pressure
Inches
mm
U.S.
metric 2
20759
VK494
1/2
15
4.9
70.6
175 psi (12 bar)
Max. Coverage
6
Flow
GPM
Pressure
Listings and
Minimum
Area
(LPM)
PSI(bar)
Deflector to
Installation
Approvals3,s
Spacing
Ceiling
Type
Ft.
155 °F (68 °C), 200 °F (93 °C) Temperature
p 4
`
Ft. X Ft.
(m)
(m X m)
Rated Sprinklers
U
12 X 12
13
7.0
(3.7 X 3.7)
(49.2)
(0.48)
14 X 14
13
7.0
(4.3 X 4.3)
(49.2)
(0.48)
Refer to Figure 2
Concealed with
Cover Plate
See Footnotes 7,10, & 11
8
16 X 16
13
7.0
(4.9 X 4.9)
(49.2)
(0.48)
Assembly.
See Footnote 9.
(2.4)
18 X 18
17
12.0
(5.5 X 5.5)
(64.4)
(0.83)
20 X 20
20
16.7
(6.1 X 6.1)
(75.7)
(1.15)
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
s This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
4 Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union.
5 Meets New York City requirements, effective July 1, 2008.
e For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure' used.
7 Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate).
s Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
0 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 9.
C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
Form No. F_012116 17.04.20 Rev 17.2
Page 4 of 5
cR; FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3.)
UL Listing Requirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
• Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
• Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT. Always refer to Bulletin Form No. F 080415 - Best Practices for Residential Sprinkler Handling and Installation.
Also refer to Form No. F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Having Jurisdiction.
Sprinkler and Adapter Assembly
• Protective cap removed
• Use wrench 14047W/B**
^0W Sprinkler Wrench
Part No. 14047W/B**
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
2-1/4" (57 mm)
neter opening
aired in the
ing.
Step 2: 1 1
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
Sprinkler
wrench flat
Figure 1: Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet is required (Not available from Viking)
Sprinkler
frame arms
Form No. F_012116 17.04.20 Rev 17.2
Page 5 of 5
cR; FREEDOM° RESIDENTIAL
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1/2" (15 mm) NPT
1
E
c
2-9/16" (65 mm)
Maximum
NOTE: Upon sprinkler activation, the deflector descends
to approximately 13116" (21 mm) below the sprinkler body.
2-1/16" (52 mm)
Minimum
Figure 2: Sprinkler Dimensions and Cover Installation
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 3: Identification of Custom Paint for Concealed Covers
2-3/4" (70 mm) or
3-5/16" (84 mm)
- -' ' - \- . ......I
Figure 4: Square Cover Assembly 15394
Form No. F_012116 17.04.20 Rev 17.2
Replaces Form No. F_012116 Rev 17.1
(added alt. material for yoke)
RD13
P POTTER Residential Riser with Capped
A The Symbol of Protection Flowswitch Port
Features
• Pre -assembled and pressure tested
• Available in 1",1 1/4", 1 1/2", & 2" nominal pipe size models
• Female adapter ships loose so riser can be installed in a confined
space
• Fits in standard 2 x 4 construction walls
• Easily removable flowswitch port cap for installation of VSR-
SG Flowswitch (VSR-SG not included)
• Includes 3 way valve to allow for calibration of pressure gauge
Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances.
Description
The RD13 Riser (with NPT connectors) is constructed from Listed
CPVC products suitable for fire sprinkler services subject to the
limitations and installation requirements of Flameguard® CPVC
pipe and Spears® CPVC fittings. The RD13 Riser incorporates a
connection for a VSR-SG flow switch, gauge, and drain/test valve.
The connection for the VSR-SG flowswitch is capped with a union
connection to facilitate the installation and removal of the switch in
confined spaces at a later date.
Installation
1. Using appropriate sealant, thread the female adapter on to the
main water supply. Then glue the riser assembly to the female
adapter. Pipe the drain connection to an adequate drain location
capable of handling the drain discharge. The riser can be mounted
in the horizontal or vertical position. The waterflow switch
connection must be located on the top or on the side of the pipe
when installed in the horizontal position. This will prevent debris
from entering the throat of the waterflow switch which could
interfere with proper operation.
2. Following CPVC manufacturer's instructions for preparation and
gluing of CPVC piping systems, glue the main riser to the main
supply line for the sprinkler heads.
Note: All glued connections must be completed and cured before
the flowswitch is installed.
3. A thread sealant shall be used in making threaded connections.
Teflon® thread tape is the recommended sealant. Some thread
sealants other than Teflon thread tape contain solvents or other
materials that may be damaging to CPVC. For other types of
thread sealants, which have been specifically investigated and
confirmed to be "System Compatible", refer to www.spearsmfg.
com. Attach gauge to riser. Apply Teflon® tape to male fitting of
gauge only. See Fig 1.
Riser Technical Specifications
Dimensions
See Fig 1
Service Pressure
175 PSI (12,07 BAR) - UL
Environmental
Limitations
Temperature range: 40°F-120°F (4.5°C-49°C)-
UL
Specifications subject to change without notice.
Service Use
Automatic Sprinkler NFPA- 13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
British Standard BS9251
A CAUTION
Do not over -tighten the union nut, hand tighten only. Use of a
wrench may cause damage to the union nut.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
5401579 - REV B • 11/18 PAGE 1 OF 2
RD13
@POTTER Residential Riser with Capped
The Symbol of Protection Flowswitch Port
Dimensions (See Chart Below)
Fig I
t
NPT Adaptor (Shipped Loose)
3 1/2" Gauge
(Shipped Loose)
1" NPT
— Drain
Valve
Itch
*RD13 Risers (ASSEMBLED DIMENSIONS)
Size
Model Number
Part
Number
Dimension "A"
Dimension `B"
Dimension "C"
Dimension "D"
Dimension "E"
Dimension "F"
(in)
(mm.)
(in.)
(mm)
(in)
(mm.)
(in)
(mm)
(in)
(mm)
(in)
(mm.)
1"
RD13 Riser w/ Cap 1"
1119068
19
483
15 3/4
400
18
457
14 5/8
371
121/4
311
10 1/2
267
1 1/4"
RD13 Riser w/ Cap 1.25"
1119078
19 5/8
498
16 1/2
419
18 1/2
470
15 3/8
391
12 1/2
318
10 5/8
270
1 1/2"
RD13 Riser w/ Cap 1.5"
1119088
N/A
N/A
16 3/4
425
N/A
N/A
15 5/8
397
12 3/4
324
10 3/4
273
2"
RD13 Riser w/ Cap 2"
1119098
N/A
I N/A
1 18 1/4
464
N/A
I N/A
16 7/8
1 429
113 3/8
1340
1 11 1/8
1 283
Ordering Information
Ordering Information
Nominal Pipe
Size
Model
Part Number
V
RD 13 Riser w/ Cap 1"
1119068
1 1/4"
RD13 Riser w/ Cap 1.25"
1119078
1 1/2"
RD13 Riser w/ Cap 1.5"
1119088
2"
RD 13 Riser w/ Cap 2"
1119098
Optional: VSR-SG, stock no. 1144460
Gauge and NPT Adapter shipped loose in box.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
iso sooi:zoos DESIGNING, MANUFACTURING,
& DISTRIBUTING QUALITY SYSTEMS 5401579 - REV B 11/18 PAGE 2 OF 2
tqC00
BLAZEMASTER
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Description
TYCO CPVC Pipe and Fittings pro-
duced by Johnson Controls are
designed exclusively for use in wet
pipe automatic fire sprinkler systems.
The TYCO CPVC Pipe and Fittings are
produced from BLAZEMASTER CPVC
compound that is a specially developed
thermoplastic compound composed
of post chlorinated polyvinyl chloride
(CPVC) resin and state of the art addi-
tives. TYCO CPVC Pipe and Fittings are
easier to install than traditional steel
pipe systems, and at the same time,
provide superior heat resistance and
strength as compared to traditional
CPVC and PVC piping materials used
in the plumbing trade. Various adapt-
ers are available to connect CPVC
pipe to metallic piping. All female pipe
thread adapters have brass inserts for
durability. Grooved adapters connect
directly to grooved end valves and
metallic pipe, with flexible grooved end
couplings.
NOTICE
The CPVC Pipe and Fittings produced
with BLAZEMASTER CPVC compound
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Technical
Data
Sizes
3/4 Inch to 3 Inch
Maximum Working Pressure
175 psi
Approvals
UL and C-UL Listed
FM Approved
LPCB Approved
NSF Certified
M EA Approved
(Refer to Installation Handbook IH-1900
dated April 2016 for exact listing/approval
information.)
Manufacture Source
U.S.A.
Material
Pipe:
ASTM F442, SDR 13.5
Fittings:
ASTM F438 (Sch. 40)
ASTM F439 (Sch. 80)
ASTM F1970
Color
Orange
Worldwide I Contacts I www tyco-fire.com
Installation
TYCO CPVC Pipe and Fittings are to
be to be installed in accordance with
Installation Handbook IH-1900.
Page 1 of 2 AUGUST 2018 TFP1915
TFP1915
Page 2of2
Care and
Maintenance
TYCO CPVC Pipe and Fittings are to be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
control valve for inspection or main-
tenance work on the fire protection
system that it controls, permission to
shut down the affected fire protection
system must first be obtained from
the proper authorities and all person-
nel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and de -vices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any authority having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
1400 Pennbrook Parkway, Lansdale, PA 19446 l Telephone +1-215-362-0700 Otto
6 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls
BLAZEMASTER is a trademark of The Lubrizol Corporation
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
510
CPVC - COPPER - STEEL
HANGER/RESTRAINER
SIZE - SYSTEM PIPE: 3/4" thru 3"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
D@05 203 - EX 4231, EX 2551
LISTED
ALTERNATIVE FOR
#500 Pipe Strap
510 Fastener
SIZE Dim.
rt. - rt
3/4 2.125
1 2.312
1 1/4 3.170
1 1/2 3.400
F2
2 4.010
1/2 4.0
3 5.320
FUNCTION - Support horizontal piping: CPVC, Copper or Steel.
Hanger for steel pipe at 15' spacing per NFPA 13.
Size 3/4" - 2" Prevents upward movement of pipe from pendent sprinkler discharge.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on horizontal or vertical mounting surface.
ASSEMBLY/ATTACHMENT - See drawings.
SPECIAL D 4D Ds FASTENERS PER NFPA 13 - See table.
LISTED
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
ORDERING - Part # and pipe size.
Han;
uaeo MOUNTING FASTENERS
Pipe
Wood
Wood - Thra 5/8" Gyp
Steel — mi.. is GA.
CPVC
#905 or #10 x1 SMS
#14 x 1 1/2 SMS or 1/4 x 2 LS
#14 or 1/4 Tek
Steel/Copper
#14 x1 1/2 SMS or 1/4 x1 1/2 LS
#14 x 2 SMS or 1/4 x 2 LS
#14 or 1/4 Tek
SMS = Sheet Metal Screw
LS = Lag Screw
TeG— k=Tek GypScrewsum Buard AFCON #905 screw - custom 5/16" hex head.
Restraint
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable order any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
lbilize
1/16
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
CPVC - COPPER
SIDE MOUNT HANGER
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
"OUSTED" 203 - EX 4231, EX 2551
FUNCTION - Support horizontal piping - CPVC or Copper.
Stabilize vertical piping.
INSTALLATION - Per these instructions
including NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Install on vertical mounting surface.
ASSEMBLY/ATTACHMENT - See drawings.
SPECIAL -@-s FASTENERS PER NFPA 13 - See table.
usrso
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
ORDERING - Part # and pipe size.
MOUNTING FASTENERS
Pipe
Wood
Steel — Mfn.la GA.
CPVC
#905 or #10 x1 SMS
#14 or 1/4 Tek
Copper
#905 or #10 x1 SMS
#14 or 1/4 Tek
SMS = Sheet Metal Screw
Tek=Tek Screw
AFCON #905 screw - custom 5/16" hex head.
Side View - For
Drawings Below
Hanger - Wood Stud
Hanger - Metal Stud
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
11 '
1/16
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
OFFSET
HANGER & RESTRAINER
CPVC - COPPER - STEEL
SIZE - SYSTEM PIPE: 3/4" thru 2"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
c 9.
usrro 203 - EX 4231, EX 2551
Size 3/4 - 1 1/4: Fastener
spacing fits on wood 2 x 4
Installation - Backing Nut
Hanger = 1 - at top fastener
Restraint = 2 - on each fastene
PATENT - No. 6,648,278.
FUNCTION - Hanger for support of CPVC or copper pipe.
Hanger for steel pipe at 15' spacing per NFPA 13.
Seismic restraint - Both horizontal and vertical.
Vertical restraint for sprinkler discharge. Hanger/
INSTALLATION - Per these instructions RestrainE
including NFPA 13, 13R, 13D and CPVC manufacturers.
Snap over pipe then squeeze strap back allowing pipe to slide freely.
When fastener threads are exposed through wood, install backing nut - See drawing.
ASSEMBLY/ATTACHMENT - See drawings.
SPECIAL - 41. -s FASTENERS PER NFPA 13 - See table.
LWED
FEATURES
* 1 1/2" Offset
* Common center -line for 3/4" and V
* Offset edge eliminates abrasion.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold separately.
® 4k " MOUNTING FASTENERS
nm�n
Pipe
Wood
Wood - Thru 5/8" Gyp
Steel - Min. 18 GA.
CPVC
#905 or #10 x1 SMS
#14 x 2 SMS or 1/4 x 2 LS
#14 or 1/4 Tek
Steel/Copper
#14 x1 1/2 SMS or 1/4 x1 1/2 LS
#14 x 2 SMS or 1/4 x 2 LS
#14 or 1/4 Tek
SMS = Sheet Metal Screw
LS = Lag Screw
Gyp-- Gypsum Board
Tek=Tek Screw
AFCON#905 screw - custom 5/16" hex head.
1.50
r
Hanger/Restrainer
Hanger/Restrainer
�bilize
Specific AFCON products are exclusively designed to be compatible ONLY with other AMON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
CAD
1/16
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
515
DOUBLE OFFSET
HANGER & RESTRAINER
CPVC
SIZE -SYSTEM PIPE: 3/4" and 1"
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
`@"' 203 - EX 4231
PATENT - No. 6,702,236
FUNCTION - Hanger for support of CPVC pipe.
Seismic restraint - Both horizontal and vertical.
Vertical restraint for sprinkler discharge.
INSTALLATION - Per these instructions
including NPFA 13, 13R, 13D and CPVC manufacturers.
When fastener threads are exposed through wood, install backing nut.
ASSEMBLY/ATTACHMENT - See drawings.
SPECIAL D& FASTENERS PER NFPA 13 - See table.
LSTED
FEATURES
* Double 1 1/2" offset with common pipe center -line.
* Offset edge eliminates abrasion.
* Pipe bore provides robust support for rough job conditions.
* Pipe slides easily through bore.
ORDERING - Part # and pipe size.
Hanger/Restrainer
Hanger/Restrainer
D 41 DD MOUNTING FASTENERS
LISTED
CPVC Pipe
Wood
Hanging/Vertical Restraint
#904 or #14 xl 1/2 SMS
Horizontal Restraint
#904 or #14 xl 1/2 SMS
SMS = Sheet Metal Screw
* AFCON#904 Screw - custom 3/8" hex head.
Specific AFCON products are exclusively designed to be compatible ONLY with other AMON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
1/16
CAD7